Siemens 5SU1644-7KK82 data sheet

Data sheet 5SU1644-7KK82
RCBO, 10 kA, 4P, type A, 300 mA, C-Char, In: 125 A, Un AC: 400 V
product brand name
SENTRON
product designation
RCBO
design of the product
Instantaneous
number of poles
4
number of poles / note
4P
number of poles / with protection
4
tripping characteristic class
C
mechanical service life (switching cycles) / typical
10 000
overvoltage category
III
surge current resistance / at (8/20) µs
1 kA
type of voltage
AC
operational current / at AC / rated value
125 A
supply voltage
● at AC / rated value
230/400 V
● for testing equipment / minimum
100 V
operating frequency
50 Hz
supply voltage frequency / rated value
50 Hz
protection class IP
IP20, if the distribution board is installed, with connected conductors
breaking capacity short-circuit current (Icn) / according to EN 61009-1 / rated value
10 kA switching capacity current
● acc. to EN 60898 / rated value
10 kA
● acc. to IEC 60947-2 / rated value
10 kA
rated residual switching capacity (IΔm) / according to IEC 61009-1
10 kA energy limitation class
3
tripping fault current / rated value
300 mA
residual current type
A
product function / neutral conductor switching
Yes
5SU16447KK82 Page 1/2
12.21.2020
Subject to change without notice
© Copyright Siemens
product feature / touch protection
Yes
product feature
● halogen-free
Yes
● silicon-free
Yes
connectable conductor cross-section / solid
● minimum
6 mm²
● maximum
50 mm²
connectable conductor cross-section / stranded
● minimum
6 mm²
● maximum
50 mm²
connectable conductor cross-section / finely stranded / with core end processing
● minimum
6 mm²
● maximum
35 mm²
tightening torque / with screw-type terminals
● minimum
3 N·m
● maximum
3.5 N·m
position / of power supply cord
Either top or bottom
height
90 mm
width
198 mm
depth
77 mm
installation depth
70 mm
number of modular width units
11
mounting position
any
net weight
2 029 g
weight / with packaging
2 029 g
influence of the surrounding temperature
Max. 95% humidity
ambient temperature / during operation
● minimum
-25 °C
● maximum
55 °C
ambient temperature / during storage
● minimum
-40 °C
● maximum
75 °C
number of test cycles / for environmental testing / acc. to IEC 60068-2-30
28
reference code
● acc. to DIN EN 61346-2
F
● acc. to IEC 81346-2
F
General Product Approval
Declaration of Conformity
Test Certificates
other
Miscellaneous Miscellaneous Miscellaneous
other
Railway
Dangerous Good
Miscellaneous Vibration and Shock Transport
5SU16447KK82 Page 2/3
Information
12.21.2020
Subject to change without notice
© Copyright Siemens
Loading...