Data sheet |
5SU1154-6KK06 |
RCBO, 10 kA, 1P+N, type A, 10 mA, B char., In: 6 A, Un AC: 230 V
Model
product brand name |
SENTRON |
|
RCBO |
product designation |
|
|
Instantaneous |
design of the product |
|
|
|
General technical data
number of poles |
2 |
|
1P+N |
number of poles / note |
|
|
|
number of poles / with protection |
1 |
|
B |
tripping characteristic class |
|
|
10 000 |
mechanical service life (switching cycles) / typical |
|
|
III |
overvoltage category |
|
|
2 |
degree of pollution |
|
|
|
Voltage
surge current resistance / at (8/20) µs |
1 kA |
|
|
Supply voltage
type of voltage
operational current / at AC / rated value
supply voltage
AC
6 A
5SU1154-6KK06 |
12/10/2020 |
Subject to change without notice |
Page 1/6 |
© Copyright Siemens |
|
|
|
●at AC / rated value
●for testing equipment / minimum operating frequency
supply voltage frequency / rated value
230/240 V
100 V
50 Hz
50 Hz
Protection class
protection class IP |
IP20, if the distribution board is installed, with connected |
|
conductors |
|
|
|
|
Switching capacity |
|
breaking capacity short-circuit current (Icn) / according to EN 61009-1 / rated value
switching capacity current
●acc. to EN 60898 / rated value
●acc. to IEC 60947-2 / rated value
rated residual switching capacity (IΔm) / according to IEC 61009-1
energy limitation class
10 kA
10 kA
35 kA
10 kA
3
Dissipation
power loss [W]
●for rated value of the current / at AC / in hot operating state / per pole
●maximum
2.8 W
5.6 W
Current
tripping fault current / rated value |
10 mA |
|
A |
residual current type |
|
|
|
Product details
product function / neutral conductor switching
product feature / touch protection
product feature
●halogen-free
●silicon-free
Yes
Yes
Yes
Yes
Connections
connectable conductor cross-section / solid
●minimum
●maximum
connectable conductor cross-section / stranded
●minimum
●maximum
connectable conductor cross-section / finely stranded
/with core end processing
●minimum
●maximum
0.75 mm²
35 mm²
0.75 mm²
35 mm²
0.75 mm²
25 mm²
5SU1154-6KK06 |
12/10/2020 |
Subject to change without notice |
Page 2/6 |