The Flowrite VF 599 series three-way valves are designed to work with either a
pneumatic or electronic actuator. They are available in both ANSI Class 125 and 250.
• Valve flange face-to-face dimensions meet ISA 75.03 standards
• Direct coupled universal bonnet
• Choice of bronze or stainless steel trim
• ANSI Leakage Class IV (0.01% of Cv)
• Cartridge type packing
• Optional service flange available
A typical application for the Flowrite three-way valve is the mixing of two different
temperatures of water supplies.
The valve can also be used for throttling or bypass coil control applications. A pump is
recommended on the coil circuit to improve the heat transfer characteristics of the coil
and for freeze protection.
Table 1. Product Numbers for Three-Way Valve Assemblies.
Technical Instructions Flowrite VF599 Series Three-Way Valves
Line size 2-1/2 to 6 inches (65 to 150 mm)
4, 5, and 6-inch 1-1/2 inches (40 mm)
Body Cast iron ASTM A 126 Class B
Maximum inlet pressure See Table 5
Miscellaneous
Canadian Registration Numbers 0H7645.5
Document Number 155-160P25 2-1/2 to 6-inch Flanged Iron Body
June 10, 2003
Ordering a Valve
Plus Actuator
Assembly
Specifications
Material
To order a complete valve plus actuator assembly from the factory, combine the actuator
prefix code with the suffix of the valve assembly product number. See 155-304P25 (TB 249)
for selection procedure and ordering codes.
Valve assemblies can be ordered using the numbers in Table 1.
The service flange is ordered separately.
Capacity See Tables 6 and 7, and Figure 2
Body style Flanged
Seat style Metal-to-metal
Action Three-way water mixing
Valve body rating See Table 2
Stem travel (Stroke) 2-1/2 and 3-inch 3/4-inch (20 mm)
Body trim See Table 1
Stem Stainless steel ASTM A582 Type 303
Packing EPDM O-ring
Liquid service to 250°F (120°C)
Controlled medium Water, glycol solutions to 50%
Medium temperature range 20 to 250°F (–7 to 120°C)
Operating
Maximum recommended differential pressure
for modulating service
Bronze trim 25 psi (173 kPa)
Stainless steel trim 50 psi (345 kPa).
Rangeability >100:1
Close-off pressures See Tables 8 and 9, and Figure 3
Close-off ratings According to ANSI/FCI 70-2
Leakage rate Class IV (0.01% of Cv)
Flow characteristics Equal percentage for N.C.
Linear for N.O.
0C0838.9
Mounting location NEMA 1 (interior only)
Dimensions See Tables 10 and 11, and Figure 5
Face-to-face dimensions ANSI/ISA S75.03
Valve weight See Table 12
Page 2 Siemens Industry, Inc.
Page 3
Flowrite VF599 Series Three-Way Valves Technical Instructions
Lower seat tool See Table 10
Trim
Valve Size
Inches (mm)
ANSI Class 125
Valve No.
ANSI Class 250
Valve No.
Kit No.
2-1/2 (65)
599-06160
599-06170
599-10125
3 (85)
599-06161
599-06171
599-10126
4 (100)
599-06162
599-06172
599-10127
5 (125)
599-06163
599-06173
599-10128
6 (150)
599-06164
599-06174
599-10129
2-1/2 (65)
599-06165
599-06175
599-10120
3 (85)
599-06166
599-06176
599-10121
4 (100)
599-06167
599-06177
599-10122
5 (125)
599-06168
599-06178
599-10123
6 (150)
599-06169
599-06179
599-10124
2-1/2 to 6-inch Flanged Iron Body Document Number 155-160P25
June 10, 2003
Accessories
Service Kits
Rebuild/repack kit
599-00418: Packing Heating Element:
Allows the stem to move freely in valves
that control fluids at temperatures below
32°F (0°C). Prevents ice crystal
formation on the stem, which may
damage the packing.
Figure 1. Packing Heating Element for Use
with SKB/C, 8-inch and 12-inch Actuators.
Operating Voltage 24 Vac
Heating Output 20W
Valve packing kit 599-08020
Rebuild/repack kits See Table 2
Service flange See Table 3
Flange gaskets and bolts See Table 4
Stem retainer clip 2-1/2 inch and 3-inch valves 599-00305
4, 5, and 6-inch valves 599-00306
To select the rebuild/repack service kit, know your valve body assembly number. The
valve body assembly number is stamped on the tag on the valve body.
Table 2. Rebuild/Repack Service Kit Part Numbers.
Bronze
Steel
Stainless
Siemens Industry, Inc. Page 3
Page 4
Technical Instructions Flowrite VF599 Series Three-Way Valves
Line Size
Service Flange Part Numbers
Inches (mm)
ANSI Class 125
ANSI Class 250
2-1/2 (65)
599-09236
5/8 – 11 × 1-1/2
3 (80)
599-09237
5/8 – 11 × 1-3/4
4 (100)
599-09238
5/8 – 11 × 2
5 (125)
599-09239
3/4 – 10 × 2
6 (150)
599-09240
3/4 – 10 × 2
2-1/2 (65)
599-09241
3/4 – 10 × 2
3 (80)
599-09242
3/4 – 10 × 2-1/2
4 (100)
599-09243
3/4 – 10 × 2-1/2
5 (125)
599-09244
3/4 – 10 × 2-3/4
6 (150)
599-09245
3/4 – 10 × 3
Document Number 155-160P25 2-1/2 to 6-inch Flanged Iron Body
June 10, 2003
Service Flanges Table 3. Part Numbers for VF 599 Service Flanges.
Flowrite VF599 Series Three-Way Valves Technical Instructions
Operation
2-1/2 to 6-inch Flanged Iron Body Document Number 155-160P25
June 10, 2003
Figure 3. Close-off Pressures.
This Flowrite three-way valve is designed as a mixing
valve.
As the valve stem moves downward, the flow through
the NO port decreases and the flow through the NC
port increases. As the valve stem moves upward, the
flow through the NO port increases and the flow
through the NC port decreases.
In the event of power failure, a spring return actuator
returns the valve to its normal position. Non-spring
return actuators will hold the last commanded
position. See the Technical Instructions of the
various actuators for additional information.
If this valve is used in diverting applications, the
following conditions apply:
Diverting service with modulating control can only
use the electro-hydraulic actuator, SKB/C. The
differential pressure must not exceed 90% of the
maximum differential pressure specified for the
three-way valve in mixing service.
Diverting service with a pneumatic actuator can only
be used with two-position control. To change over
from one port to another, there must be no system
pressure. The pump is turned off.
Figure 4. Three-Way Valve
Operation as a Mixing Valve.
Siemens Industry, Inc. Page 7
Page 8
Technical Instructions Flowrite VF599 Series Three-Way Valves
Document Number 155-160P25 2-1/2 to 6-inch Flanged Iron Body
June 10, 2003
Sizing
Mounting and
Installation
The sizing of a valve is important for correct system operation. An undersized valve will
not have sufficient capacity at maximum load. An oversized valve may initiate cycling
and the seat and throttling plug can be damaged because of the restricted opening.
Correct sizing of the control valve for actual expected conditions is considered essential
for good control.
Some variables which must be determined are:
• The medium to be controlled: water, etc.
• The maximum inlet temperature and pressure of the medium at the valve.
• The pressure differential that will exist across the valve under maximum load
demand.
• The maximum capacity the valve must deliver.
• The maximum line pressure differential the valve actuator must close against.
• See AB-1 Control Valve Selection and Sizing (Document Number 155-285) for
further recommendations.
See Tables 6 and 7 for valve capacities.
• Install the valve so that the flow follows the direction of the arrow indicated on the
valve body identification tag.
• For best performance, install the valve assembly with the actuator above the valve
body. The valve and actuator can be installed in any position between vertical and
horizontal. Siemens Building Technologies does not recommend installing the valve
assembly below horizontal or upside down.
• If installing a service flange, see Table 13 for proper placement.
• For flange dimensions and bolt hole information, see 155-303P25 (TB 248). Allow
sufficient space for servicing the valve and actuator. See Table 12 for valve body
dimensions. See Figure 5 and Table 11 for dimensions of the service envelope
recommended around the actuator.
• A lower seat tool is required for removing a three-way valve. See Table 10 for part
numbers.
NOTE: Instructions for field mounting an actuator, spring adjustments, wiring diagrams,
and start-up are covered in the Technical Instructions and Installation
Instructions for each actuator.