Siemens 546-00303A Installation Instructions Manual

Fume Hood Monitor
The Fume Hood Monitor (FHM) (Figure 1) provides visual and audible alarms to alert a fume hood user of airflow conditions. The mounting plate is designed for fume hoods with or without existing cutouts. This kit contains:
Fume Hood Monitor with mounting plate
Three removable wire connectors
Four sheet metal screws
Two machine screws
2 ft. (0.6 m) air sensor hose
Plastic sidewall adapter and lock ring
Installation Instructions
Document No. 546-00310
November 15, 2006
Expected Installation Time
27 minutes
Prerequisites
Power cable in place
If using a field panel:
Floor Level Network (FLN) cable from the field panel to the FHM in place
If using an external alarm or auxiliary DI connection:
External alarm or auxiliary DI cable from source to FHM in place
Product Numbers
546-00303A Fume Hood Monitor 546-00303B Fume Hood Monitor mounting plate
Warning/Caution Notations
CAUTION:
Equipment damage or loss of data may occur if the user does not follow procedure as specified.
Required Tools
For a fume hood with an existing cutout:
Medium-duty electric drill
1/2-inch. (13.0 mm) drill bit
Small flat-blade screwdriver
Small Philips screwdriver
Wire strippers
For a fume hood without an existing cutout:
Medium-duty electric drill
1/8-inch (3.0 mm) drill bit
1/2-inch (13.0 mm) drill bit
Metal-cutting saw or 3/ 4 in. and 1 in. drill bits
or hole saws
Small flat-blade screwdriver
Small Philips screwdriver
Wire strippers
Figure 1. Fume Hood Monitor.
Instructions
NOTE: Mount the FHM so that the fume hood
operator can easily read its display and can easily reach its buttons. This height is approximately 4-1/2 ft. to 5 ft. (1.4 to 1.5 m) from the floor.
1. Choose the mounting location for the FHM. The FHM should be mounted directly on the fume hood and can be mounted over a pre-existing cutout on the fume hood. See Figure 2 for installation clearance requirements.
Page 1 of 6
Document No. 546-00310 Installations Instructions November 15, 2006
Mounting Plate Installation with an Existing Cutout
1. See Figure 3. If the fume hood is provided with a 2 inch × 4 inch (5.0 × 10.0 cm) cutout with an electric utility box, then use the provided machine screws to attach the mounting plate to the electric utility and skip to Sidewall Hole Mounting.
If the fume hood has no electric utility box,
make sure that the cutout provides enough clearance for the air sensor hose and to connect the power, FLN, external alarm, and auxiliary DI wires. Then continue to Step 2.
Figure 2. Installation Clearance Requirements.
NOTE: Clearance is needed to prevent the sensor
air hose from bending or kinking, and to insert the Portable Operator’s Terminal Cable.
2. Confirm that an earth ground is connected to the mounting plate. To do this, make sure that the following conditions are met:
a. The conduit junction box is grounded, or b. The fume hood enclosure is grounded, or c. A separate wire is connected between the
earth ground and the mounting plate.
3. Continue with one of the following mounting methods: Mounting Plate Installation with an
Existing Cutout or Mounting Plate Installation without an Existing Cutout.
Figure 3. Installation with an Existing Cutout.
2. Position the bracket over the opening and mark the locations of the two mounting holes.
3. Using the 1/8-inch (3.0 mm) drill bit, drill the two mounting holes.
4. Using the screws provided, attach the mounting plate to the mounting surface.
Page 2 of 6
Siemens Building Technologies, Inc.
5. Proceed to Sidewall Hose Mounting.
Loading...
+ 4 hidden pages