Siemens 540-716, 540-717, 540-514N Installation Instructions Manual

Installation Instructions
Room Pressuriz ation Controller
Output
CAUTION:
Document No. 540-1032
May 3, 2017
Product Description
These instructions explain how to field install (pages 1 through 3) or replace (pages 3 through 4) a Room Pressurization Controller – Pneumatic Output with or without Autozero Modules.
Product Number
540-716 Room Pressurization Controller –
Pneumatic Output
540-717 Room Pressurization Controller –
Pneumatic Output with Autozero Modules
540-514N Room Pressurization Controller
Board – Pneumatic Output (replacement)
Shipping carton includes a pre-assembled metal enclosure with controller board and cover, pneumatic output modules, Autozero Modules with brackets (optional), and four self-tapp ing/drilling screws.
Installation Conventions
Equipment damage or loss of data may occur if you ds not follow procedures as specified.
Required To ols
Prerequisites
(Optional) Room temperature sensor installed
Air velocity sensors installed in ducts
A source of 24 Vac Class 2 power available
Supply power to the unit is OFF
An air supply line is available at the controller
Expected Installation T ime
New controller installation 10 minutes Replacement (old controller has
removable terminal blocks) Replacement (old controller does
not have removable terminal blocks)
NOTE: You may require additional time for database work at the field panel.
6 minutes
16 minutes
New Installation Instru ctions
NOTE: These steps only refer to new installations.
For replacement instructions, refer to pages 3-4. For Autozero Module installation, refer to instruction 540-199.
The following tasks can be performed by the electrician:
Electro-Static Discharge (ESD) wrist strap
Small flat-blade screwdriver
Medium flat-blade screwdriver
Medium-duty electric drill
1/4 in. (6.35 mm) hex nut bit
Portable Operator’s Terminal with Controller
Interface Software Rev. 2.0 or later (required for controller replacement only)
Additional tools needed if not using self-tapping option:
1/4 in. (6.35 mm) hex nut driver
1/8 in. (3 mm) bit
Item Number: 540-1032, Rev. FA Page 1 of 7
1. Loosen, but do not remove, the cover screws and remove the enclosure cover. Using the rear panel of the enclosure as a template (Figures 1 and 2), mark the location for the four screw holes where you will install the enclosure.
2. Do one of the following:
If using the self-tapping screws: Using
the drill and the hex nut bit, start the screws. (Screws do not require starter holes.)
If not using the sel f-tapping screws: Drill
four 1/8 in. (3 mm) pilot holes for the screws. Using the hex nut driver, start the screws.
Document Number 540-1032
CAUTION:
CAUTION:
Installation Instructions May 3, 2017
Figure 1. Room Pressurization Controller – Pneumatic Output without Autozero Modules.
3. Mount the enclosure on the screws and tighten them down with either the drill or hex nut driver.
4. Remove the appropriate knockouts.
5. Place the ESD wrist strap on your wrist and attach it to a good earth ground.
6. Connect the Local Area Network (LAN) trunk (Figure 4). Run the wiring through knockout.
NOTE: Each DO provides a Normally Open (NO) and a Common (C) terminal. Terminate both connections of a 24 Vac load directly to the controller board.
NOTE: The 24 Vac “H” terminal is switched through a TRIAC to the NO terminations when the associated DO is energized.
8. If using a pressure mode switch, then follow the
Room Pressurization Controller (RPC) Pressue Mode Switch nstallation Instructions (540-719)
Do not connect an earth ground to the Shield (S) terminal.
7. Connect the point wiring for the appropriate application. See Figure 7. See Table 1 for application descriptions. Run the wiring through knockout.
included with the switch.
9. After the pressure mode switch is installed, wire the switch to DO8 and AI3 as described in the instructions.
10. Plug the Room Temperature Sensor cable into the RTS port on the controller board. See Figure 1. Run the cable through knockout.
11. Connect the power trunk as shown in Figure 5.
The Controller’s Digital Outputs (DOs) control 24 Vac loads only. The maximum rating is 12 VA for each DO. For higher VA requirements, 110 or 220 Vac requirements, separate
DO NOT apply power to the controller. Run the wiring through knockout.
12. Replace the enclosure cover and tighten the cover screws.
transformers used to power the load, or DC power requirements, use an interposing 220 V 4-relay module (TEC Relay Module P/N 540-147).
Page 2 of 7 Siemens Industry, Inc.
Document Number 540-1032
CAUTION:
Installation Instructions
May 3, 2017
The following task can be performed by the fitter:
13. Connect the tubing from the air velocity sensor pickups to the HI and LO ports outside of the enclosure. The supply pickup goes to the supply AVS ports, and the exhaust pickup goes t o the exhaust AVS ports on the side of the enclosure. Make sure that the “HI” and the “LO” pressure sides of the sensors are connected to the “HI” and “LO” sensor ports on the controller (Figure 1) or Autozero Modules (Figure 2). Refer to Table 2 for air velocity sensor connections.
The installation is complete.
Replacement Instructions
Replacement of a TEC requires you to record, re-enter, or update the initial point values of the controller you are replacing. These are the points marked with an asterisk (*) on the Controller Interface Software (CIS) display.
NOTE: CIS Rev. 2.0 or later is required for controller replacement.
The following tasks can be performed by the system specialist:
1. Place the ESD wrist strap on your wrist and attach it to a good earth ground.
2. Before disconnecting the old controller, do one of the following:
NOTE: If the new controller has a newer firmware revision than the old controller, then skip to the third bullet.
If the old controller communicates with the field panel, then update the controller init ial values at the field panel.
If the old controller does not communicate with the field panel, but communicates with the CIS, or if the controller is stand-alone, then record the initial values (those marked with an asterisk (*) on the CIS display). Record the values.
If the old controller is not communicating at all, or if the controller you are installing has a newer firmware revision than the old controller, then while at the field panel, follow these steps: a. Obtain a field panel P oint Definition
Report for the LCTLR point. Record the values.
b. View the initial value block. (This
information is valid only since the last update was made). Record the values.
c. Delete the LCTLR point from the field
panel.
3. Replace the old controller as follows:
The following tasks can be performed by the electrician:
a. Remove power from the controller. b. If the old controller has the RTS plug
between the LAN trunk and point terminations, then disconnect the wires from the power trunk terminal block. If the old controller has the RTS plug on the opposite end of the board from the power trunk terminal block, then remove the power trunk terminal block.
c. Remove, in the following order, the
controller’s:
LAN trunk terminal block
DO8, AI3, and DI2 only
room temperature sensor
d. Loosen, but do not remove, the mounting
screws.
e. Lift and remove the old enclosure. f. Mount the new enclosure on the mounting
screws and tighten them down with either the drill or hex nut driver.
g. Remove the appropriate knockouts. h. If the old controller has the RTS plug
between the LAN trunk and point terminations, then remove all terminal blocks (except the power trunk) from the new controller. If the old controller has the RTS plug on the opposite end of the board from the power trunk terminal block, then remove all terminal blocks.
Siemens Industry, Inc. Page 3 of 7
Loading...
+ 4 hidden pages