This addendum is applicable for the S3000 PROFINET IO and S3000 PROFINET IO8OF safe-
ty laser scanners, in the following summarized as S3000 PROFINET IO/IO8OF. As far as the
connection variants differ, the respective product variant is named.
This addendum is applicable to the S3000 PROFINET IO/IO8OF safety laser scanner with
one of the following entries on the type label in the field Operating Instructions:
8013289
8013289/TL59
8013289/US26
8013289/YAX9
8013289/YKY7
8013289/YY95
This document is part of SICK part number 8013289 (addendum operating instructions
“Safety Laser Scanner S3000 PROFINET IO and S3000 PROFINET IO8OF” in all available
languages).
Note
This addendum only applies in conjunction with the original operating instructions
“S3000 Safety Laser Scanner” (SICK part number 8009791).
If not otherwise revised in this document, the information in the original operating
instructions applies, which relate to the S3000 Advanced or Professional safety laser
scanner.
For the configuration and diagnostics of these devices you require CDS (Configuration &
Diagnostic Software) version 3.6.4 or higher.
The S3000 PROFINET IO/IO8OF safety laser scanner is used to protect persons and plant.
Stationary applications, e.g. for access or hazardous area protection, can be realised.
The safety level of the S3000 PROFINET IO/IO8OF corresponds to category 3 PL d
according to EN ISO 1384981 and SIL2 according to IEC 61508.
2.2 General safety notes and protective measures
Safety notes
WARNING
This addendum must be made available to the operator of the system, machine or the
vehicle where the S3000 PROFINET IO/IO8OF safety laser scanner is used, together with
the original operating instructions. The operator is to be instructed by qualified safety
personnel and is to read and follow the addendum; the operating instructions must also be
S3000 PROFINET IO/IO8OF Professional with 8 protective/warning fields (field sets)
simultaneous protective fields with separate output information and separate feature
for resetting (see section 8.1 on page 28 or 8.1.2 on page 29)
direct fail-safe integration into PROFINET IO networks
supply connector with integrated configuration memory
connection types:
– S3000 PROFINET IO: RJ845 sockets for RJ845 push-pull plug
– S3000 PROFINET IOOF: SCRJ sockets for VARIOSUB push-pull SCRJ8plug
The S3000 PROFINET IO/IO8OF does not have any local inputs or outputs except the
interfaces for setting the parameters. All communication is via the PROFINET IO network.
3.2 Operating principle of the devices
PROFINET IO device
The PROFINET IO device is a remotely connected field device for installation in close proximity to the process. It expects the configuration from an IO controller/supervisor and
cyclically transmits its process data to the IO controller.
PROFIsafe for PROFINET
PROFIsafe defines how fail-safe devices (e.g. S3000 PROFINET IO/IO8OF) communicate
over a network with safety controllers (e.g. FPLC). It realises the safe communication via a
profile, i.e. using a special data format and a special protocol.
Device role
The S3000 PROFINET IO/IO8OF is an IO device.
It expects the configuration from an IO controller and cyclically transmits its process data
to the IO controller.
Device model
The S3000 PROFINET IO/IO8OF is available as a compact device.
acyclic read/write services for communication via TCI interface
diagnostics alarms
TCP/IP communication via port 9000
support for MRP client
S3000 PROFINET IO/IOOF
3.3 Input signals
3.3.1 Reset signals
If the safety laser scanner is operated using the “With restart interlock” function, then
after a protective field interruption and the subsequent clearing of the protective field, the
S3000 PROFINET IO/IO8OF requests a reset signal from the control system (Reset Re-
quired). The safety laser scanner reacts to an edge change on the reset signal from low to
high (not to the level).
WARNING
Note
control inputs in the process
image
control inputs in the process
image
The reset signal must be fail-safe (single failure proof)!
3.3.2 Control signals for switching monitoring cases
You can switch between protective fields by switching monitoring cases.
The related control inputs A, B, C, D on theS3000 PROFINET IO/IO8OF Professional or A, B
on the S3000 PROFINET IO/IO8OF Advanced expect complementary signals.
Control input ABCD
Bits of the output byte 0 in
the process image (see
01011010 = valid value: A = 1, B = 1, C = 0, D = 0
11011010 = invalid value, input A is not set complementarily
Subject to change without notice
Addendum Operating InstructionsChapter 3
S3000 PROFINET IO/IOOF
Product description
3.3.3 Stand-by
The protective field and warning field outputs are deactivated by operating the
S3000 PROFINET IO/IO8OF in stand-by. The S3000 PROFINET IO/IO8OF remains in the
tand-by mode as long as the related input information is present (active high) (see
s
Tab. 10 on page 32).
3.3.4 Initialising
If the S3000 PROFINET IO/IO8OF is in the lock-out status, e.g. due to invalid values on the
inputs, the safety laser scanner can be initialised. During initialisation the device runs
through the boot sequence, similar to a warm start.
Once the cause of the error has been rectified, the device then starts to operate normally.
The safety laser scanner reacts to an edge change on the signal from low to high (not to
The power is supplied via the supply connector. Lay the connecting cables through the
cable entry into the connector housing.
supply connector
ments on the supply
connector
connector
with Y-piece
Note
Terminal Signal Function Wire colour (for the flying leads)
1+24 V DC Supply voltage Brown
2–Do not use –
30 V DC Supply voltage Blue
The external 24 V supply voltage may not exceed 40 V (SELV or PELV). This must be
ensured during the electrical installation.
As an option a pre-assembled supply connector with flying leads is available.
Additionally a pre-assembled supply connector with cable and external Y-piece is available.
This corresponds to a standardized push-pull power connector (industry standard).
5.1.3 Network connection with SCRJ-push-pull plug (optical fiber)
(not included)
Notes
Notes
For the connection to the network you must use the push-pull plugs with a metal hous-
ing. With the push-pull plug connected the connection complies with enclosure rating
P 65 (e.g. Phoenix VS8PPC8C18SCRJ-MNNA-PG9-A4D-C, material no. 1608032).
I
With the provided cover the connection complies with enclosure rating IP 54.
If the network is not connected to a following bus device, then a connection using a
single plug is sufficient. It does not matter which of the two sockets is used. The unused
socket must always be protected with the provided cover (see Fig. 1).
Without the usage of optical adapter plugs the maximum allowed cable length to the
next device is 50 m.
The maximum allowed line attenuation for the transmission link is 12 dB.
Pay attention to the mounting and wiring instructions of the manufacturer of the con-
nectors and cables, in particular with regard to the number of bending radiuses.
Minimize the number of connectors in a connection cable, ideally to only two: one at the
S3000 PROFINET IO/IO8OF and another one at the FPLC.
Once the electrical installation is completed, determine the signal reserve of the con-
nection cable using the CDS diagnostic function.
Use cables and connectors with low attenuation in order to obtain a signal reserve of
> 4 dB.
5.1.4 Local configuration connection
As a rule configuration is performed via PROFINET IO. A local RS8232 configuration connection is available on the S3000 PROFINET IO/IO8 OF for configuration and diagnostics