SHURflo RVFRESH WATER PUMP Installation And Operation Manual

SHURflo
RV FRESH
WATER
PUMP
for
use
on
INSTALLATION
AND
OPERATION
MANUAL
www.vwT25camper.info - a useful website for owners and enthusiasts of VW T25 / T3 / Vanagon Campervans
SHURflo
RV
FRESH
WATER
PUMP
Installation
and Operation Manual
Shurflo's
patented
RV Fresh Water
Pumps
for drinking
water
were
developed
to
deliver
smooth,
consistent
flow
at all
ranges
of
operation,
while
drawing
low current. The
balanced
diaphragm
design
incorporates
precision
ball
bearings
for
long
life.
Each
motor
is
equipped
with
an
integral
thermal breaker
and all
units
are CE approved. RV
fresh
water
pumps
are
enclosed
to
prevent
incidental
moisture
from
entering;
however,
they
are not
intended
for
envi-
ronments
where
splashed
water
is
present.
When
installed
correctly,
RV Fresh Water
Pumps
provide
years
of
quiet
operation.
General
Information
Sluirflo
water
pumps
meet
the essential health and
safety
requirements and are in conformity
with
the EU EMC directive 89/S36/FEC as specified in EN 55014 (1993).
Shurflo realizes
that
in
many
instances our
pump
is being installed as a replacement
pump
within an existing
system.
The following guidelines should be considered to
achieve optimum
pump
operation.
Mounting
The
pump can be at the same
level
or below the water tank. It may be positioned
above the water tank if needed, as it is capable or a 6 ft (1.8 m)
vertical
prime.
Horizontal
inlet tubing
will
allow
priming
to 30 ft. (9 m).
Consider
a dry
location
that
allows easy access if maintenance is required. The pump should not be located in an area of less than one cubic foot (0.03 m) unless adequate
ventilation is provided. Excessive
heat
may trigger the integral thermal
breaker and interrupt operation.
When
the temperature drops, the breaker
will
auto-
matically
reset
and
start
the operation. The pump may be mounted in any position
If
mounting the pump
vertically,
the pump head should be in the down position so
that
in the
unlikely
event of a leak, water
will
not enter the motor.
Use
No.8 stainless steel hardware to fasten the pump. Choose a
solid
surface (thic
plywood)
that
will
not
amplify
pump operation. The mounting
feel
are intended to
isolate
the pump
from
the mounting surface; over tightening, flattening, or use of
oversized
screws
will
reduce the
ability
to isolate vibration/noise.
Electrical
The
pump should be on a dedicated
(individual)
circuit
protected by the
specified
fuse as indicated on the motor
label.
A
switch
rated at or above 15 amps is recommended, and must interrupt current
flow
on the positive (+ red) lead.
The
pump must be grounded to an earth (battery). The earth wire must be the same
size
(gauge/mm2) as the positive
wire.
Wire
size (gauge/mm*) is based on the distance
from
the power source to the pum|
The
minimum
recommended size wire is No. 14 gauge (2.5mm1). Lengths of 20-
50ft.
(6-15m) use No. 12 gauge (4mm).
The
total current draw on the
circuit
must not exceed 15 amps. If the pump is used ii
conjunction
with
other components, overload current protection (fuse or
circuit
breal
er) and wire size must be for the total amp requirement of all devices on the
circuit.
Plumbing
Shurflo
recommends at least 1 ft. (0.3m) of 1/2" (13mm) I.D.
flexible
high
pressure
tubing
to both ports. Ideally the pump's ports/strainer
should
not be connected to
plastic
or
rigid
pipe. The pump's normal
oscillation
may transmit through
rigid
plumbing
causing noise, and possibly loosen or crack components.
Installation
of a 50 mesh strainer is recommended to prevent foreign debris
from
entering the pump. The
Shurflo
In-Line
Strainer (1/B and 2/B) has a
twist-lock
feature
allowing
simple
cleaning
when plumbed
with
flexible
tubing.
Shurflo
swivel
barb fittings provide easy removal if maintenance or access is
required.
The fittings are designed
with
a "taper-seal", creating water tight connec-
tion
when hand
tightened.
Always
secure barb tubing connections
with
properly
sized
stainless steel clamps to prevent leaks. Never use
Teflon
tape
or sealing
com-
pounds on threads. Sealer may enter the pump causing a
failure.
Failure
due to foi
eign
debris is not covered
under
warranty.
Rapid
cycling
may be caused by excessive back pressure created by one or more o
the
following
within
a plumbing system:
Water filters and purifiers not on
separate
feed
lines.
Flow
restrictors in
taps
and shower heads.
Small
I.D.
lines.
Pipe/tubing should be at least 1/2" (13mm) I.D. for main
lines.
Restrictive fittings and connections (elbows,
"T's",
feeder lines to laps, etc.)
Switch
Shut-Off
Restrictions
in a plumbing system may cause the pump to rapid
cycle
(ON/OFF
within
2 sec.) during low
flow
demands.
Cycling
should be
minimized
to prevent
pulsating
flow,
and to achieve maximum pump
life.
To
determine if adjustment is necessary, turn tap on to lower than average
flow
of
water. The pump should
cycle,
but its "OFF time" must be 2 sec. or longer. If the
cycling
is correct, leave
well
enough alone. If the pump is
cycling
rapidly
increase
the setting by turning the screw
clockwise
(1 1/2 turn
MAX.)
until
the pump oper-
ates
for 1 sec.
with
at least 2 sec. "OFF time"'. If
cycling
cannot be
minimized
con-
sider
removing plumbing restrictions or
simply
install a Shurflo
Accumulator.
Sanitizing
Fresh
water systems require periodic maintenance to deliver a consistent
flow
of
fresh
water. Depending on the use and the environment the system is subject to, san-
itizing
is recommended prior to storing and before using the water system after a
period
of storage. Systems
with
new components, or ones
that
have been subjected
to contamination, should also be disinfected as
follows:
1. Use one of the
following
methods to determine the amount of common house-
hold
bleach needed to sanitize the lank.
A)
Multiply
"gallons (UK) or lank capacity" by 0.156; the result is ounces of
bleach
needed to sanitize the tank.
B)
Multiply
"litres of lank capacity" by 1; the result is the
millililres
of bleach
needed to sanitize the tank.
2. Mix into solution the proper amount of bleach
within
a container of water.
3. Pour the solution (water/bleach) into the tank and
fill
the tank
with
fresh water.
4.
Open all laps (HOT &
COLD)
allowing
the water to run
until
the distinct odour
of
chlorine is detected. •»
5. The standard solution must have four (4) hours of contact
lime
to disinfect
com-
pletely.
Doubling
the solution concentration allows for contact
lime
of (1) hour.
6.
When
the contact time is completed, drain the tank.
Refill
with
fresh water and
purge the plumbing of all
sanitizing
solution.
NOTE:
The
sanitizing
procedure outlined above is in conformance
with
the
approved
procedures of the
U.S.
Public
Health
Service.
:~'MD
ENGLISH
www.vwT25camper.info - a useful website for owners and enthusiasts of VW T25 / T3 / Vanagon Campervans
Loading...
+ 2 hidden pages