Shurflo 2088-712-244 Installation Manual

MARINE POTABLE WATER PUMP
Installation and Operation Manual
SHURflo's Marine Duty Potable Water Pumps were developed to endure the harsh marine environment. The patented Tri-a-fram design delivers smooth, consistent flow at all ranges of operation, while drawing low current. The balanced diaphragm design incorporates precision ball bearings for long life. Each motor is equipped with an integral thermal breaker and all are U/L Marine listed. All Marine duty pumps have sealed switches and are finished with a baked-on polyurethane coating to inhibit corrosion. Marine duty potable water pumps are enclosed to prevent incidental moisture from entering; however, they are not intended for environments where splashed water is present. When installed correctly, Marine Duty Potable Water Pumps provide years of quiet operation.
911-448 Rev. E 1/98
®
GENERAL INFORMATION
SHURflo realizes that in many instances our pump is being installed as a replacement pump within an existing system. The following guidelines should be considered to achieve optimum pump operation.
M
The pump may be mounted in any position. If
mounting the pump vertically, the pump head should
]
be in the down position so that water will not enter the motor.
Use #8 stainless steel hardware to fasten the pump.
Choose a solid surface (thick plywood) that will not amplify pump operation. The mounting feet are intended to isolate the pump from the mounting surface; over tightening, flattening, or use of oversized screws will reduce the ability to isolate vibration/noise.
Electrical
The pump should be on a dedicated (individual)
circuit protected by the specified "slow blow" fuse indicated on the motor label.
A U/L approved marine duty (ignition protected)
switch rated at or above 15 amps is recommended, and must interrupt current flow on the positive (+ red) lead.
The pump must be grounded to a "known ground"
(battery). The ground wire must be the same size (gauge/
M
m2) as the positive wire.
Mounting
The pump can be at the same level or below the
water tank. It may be positioned above the water tank if needed, as it is capable of a 6 ft. [1.8 vertical prime. Horizontal inlet tubing will allow priming to 30 ft. [9
Consider a dry location that allows easy access if
maintenance is required. The pump should not be located in an area of less than one cubic foot unless adequate ventilation is provided. Excessive heat may trigger the integral thermal breaker and interrupt operation. When the temperature drops the breaker will automatically reset and start operation.
M
].
Wire size (gauge/Mm2) is based on the distance from
the power source to the pump. Recommended size wire is 50ft.
The total current draw on the circuit must not
#
14 gauge
[6-15M]
use #12 gauge [4
[2.5Mm2]
. For lengths of 20-
M
m2]
.
exceed 15 amps. If the pump is used in conjunction with other components, overload current protection (fuse or circuit breaker) and wire size must be for the total amp requirement of all devices on the circuit.
Plumbing
SHURflo recommends at least 1ft. [.3M] of
½"[13mm] I.D. flexible high pressure tubing to both ports. Ideally the pump's ports/strainer should not be connected to plastic or rigid pipe. The pump's normal oscillation may transmit through rigid plumbing causing noise, and possibly loosen or crack components.
Installation of a 50 mesh strainer is recommended to
prevent foreign debris from entering the pum p. The SHURflo In-Line Strainer (shown) has a twist-
lock feature allowing simple cleaning when plumbed with flexible tubing.
SHURflo swivel barb fittings provide easy
removal if maintenance or access is required. The fittings are designed with a "taper-seal", creating a water tight connection when hand-tightened. Always secure barb tubing connections with properly sized stainless steel clamps to prevent leaks. Never use Teflon tape or sealing compounds on threads. Sealer may enter the pump causing a failure. Failure due to foreign debris is not covered under warranty.
Rapid cycling may be caused by excessive back
pressure created by one or more of the following within a plumbing system :
Water filters and purifiers not on separate feed lines.
!
Flow restrictors in faucets and shower heads.
!
Small I.D. lines. Pipe/tubing should be at least
!
½"[13mm] I.D. for m ain lines.
Restrictive fittings and connections (elbows,
!
"T's", feeder lines to faucets, etc.)
ADJUSTMENT OF SWITCH SHUT-OFF
Restrictions in a plumbing system may cause the pump to rapid cycle (
ON/OFF
within 2 sec.) during low flow demands. Cycling should be minimized to prevent pulsating flow, and to achieve maxim um pum p life.
To determine if adjustment is necessary, turn a faucet to lower than average flow of water. The pump should cycle, but its "
OFF
time" must be 2 sec. or longer. If the cycling is correct, leave well enough alone. If the pump is cycling rapidly, increase the setting by turning the
MAX
screw clockwise (1½ turn for 1 sec. with at least 2 sec. "
.) until the pump operates
OFF
time". If cycling cannot be minimized consider removing plumbing restrictions or simply install a SHUR flo Accum ulator.
ON
Loading...
+ 2 hidden pages