POTABLE WATER PUMP
Installation and Operation Manual
SHURflo has supplied pumps to the manufacturers of RV's for over
30 years. Our patented Tri-a-fram® line of potable water pumps
deliver smooth, consistent flow at all ranges of operation, while
drawing low current. The balanced diaphragm design incorporates
two precision ball bearings for long life. SHURflo pumps are
100% tested for proper operation before they leave the factory. When
installed correctly, SHURflo water pumps will provide years of quiet
operation.
A SHURflo pump in combination with a low back pressure water
system can exceed all expectations. For unmatched reliability and
trouble-free performance request SHURflo's complete line of water
system products.
GENERAL INFORMATION
SHURflo realizes that in many instances our pump is being installed as a replacement pump within an existing system.
The following guidelines should be considered to achieve optimum pump operation
MOUNTING
_ The pump can be at the same level or below the
water tank. It may be positioned above the water
tank if needed, as it is capable of a 6 ft. [1.8M]
vertical prime. Horizontal inlet tubing will allow
priming to 30 ft. [9M].
_ Consider a location that allows easy access if
maintenance is required. The pump should not be
located in an area less than one cubic foot unless
adequate ventilation is provided. Excessive heat
may trigger the integral thermal breaker and
interrupt operation. When the temperature drops
the breaker will automatically reset and start
operation.
_ The pump may be mounted in any position. If mounting
the pump vertically, the pump head should be in the down
position so that in the unlikely event of a leak, water
will not enter the motor.
_ Use
#
8 hardware to fasten the pump. Choose a solid
surface (thick plywood) that will not amplify pump
operation. The mounting feet are intended to isolate
the pump from the mounting surface; overtightening, flattening, or use of oversized screws
will reduce the ability to isolate vibration/noise.
ELECTRICAL
_ The pump should be on a dedicated (individual)
circuit, protected by the specified fuse indicated on
the motor label.
_ A switch rated at or above 15 amps is
recommended, and must interrupt current flow on
the positive (+ red) lead. Marine applications should
use U/L approved marine duty (ignition protected)
switches and pumps.
_ Wire size (gauge/Mm2) is based on the distance
from the power source to the pump. Recommended
size wire is #14 gauge [2.5Mm
2
]. For lengths of 20-
50ft. [6-15M] use #12 gauge [4 Mm
2
].
_ The pump must be grounded to a "known ground"
(frame). The ground wire must be the same size
(gauge/Mm2) as the positive wire.
_ The total current draw on the circuit must not exceed
15 amps. If the pump is used in conjunction with
other components, overload current protection (fuse
or circuit breaker) and wire size must be for the total
amp requirement of all devices on the circuit.
PLUMBING
_ SHURflo recommends at least 1ft. [.3 M] of _"
[13mm] I.D. flexible high pressure tubing to both
ports. Ideally the pumps ports/strainer should not
be connected to plastic or rigid pipe. The pump's
normal oscillation may transmit through rigid
plumbing causing noise, and possibly loosen or
crack components.
_ Installation of a 50 mesh strainer (SHURflo P/N 170)
is recommended to prevent foreign debris from
entering the pump.
_ SHURflo swivel barb fittings provide easy removal
if maintenance or access is required. The fittings are
designed with a "taper-seal", creating a water tight
connection when hand-tightened. Never use Teflon
tape or sealing compounds on threads. Sealer may
enter the pump causing a failure. Failure due to
foreign debris is not covered under warranty.
Always secure barb tubing connections with
properly sized stainless steel clamps to prevent
leaks.
_ Rapid cycling may be caused by excessive back
pressure created by one or more of the following
within a plumbing system:
Water filters not on separate feed lines.
Flow restrictors in faucets and shower heads.
Small I.D. lines. Pipe/tubing should be at least _"
[13mm] I.D. for main lines.
Restrictive fittings and connections (elbows, "T's",
feeder lines to faucets, etc.)
SWITCH SHUT-OFF
Restrictions in a plumbing system may cause the
pump to rapid cycle (ON/OFF within 2 sec.) during low
flow demands. Cycling should be minimized to
prevent pulsating flow, and to achieve maximum
pump life.
To determine if adjustment is necessary, turn a faucet
ON to lower than average flow of water. The pump
should cycle, but its "OFF time" must be 2 sec. or
longer. If the cycling is correct, leave well enough
alone. If the pump is cycling rapidly increase the
setting by turning the screw clockwise (1_ turn MAX.)
until the pump operates for 1 sec. with at least 2 sec.
"OFF time". If cycling cannot be minimized consider
removing plumbing restrictions or simply install a
SHURflo Accumulator.