Shrink polymer systems Cable 7.2kV to 36kV INSTALLATION INSTRUCTION

Installation Instruction
Heatshrink Termination For Single
Core Polymeric Cables 7.2kV to 36kV
* PLEASE READ INSTRUCTIONS THOROUGHLY BEFORE PROCEEDING *
OUTDOOR
UNITS P1-P3 GROVEMERE COURT BICTON INDUSTRIAL PARK KIMBOLTON CAMBS PE28 OEY TEL: +44 (1480) 861001 FAX: +44 (1480) 861002 E-MAIL: info@shrinkpolymersystems.co.uk
WEBSITE: www.shrinkpolymersystems.co.uk
©
General Fitting Instructions
VOLTAGE
INDOOR
L
OUTDOOR
L
X
7.2kV 150mm 200mm 12kV 190mm 270mm LENGTH OF LUG
17.5kV 250mm 300mm BARREL + 10% 24kV 310mm 360mm 36kV 510mm 600mm
! It is highly recommended that a tool suitable
for the removal of the semi-conductive screen is used to provide a reliable discharge free termination screen point
! Use a propane gas torch with a soft flame ! Avoid a pencil like blue flame which is caused by
unregulated supply
! Keep the flame on the move to ensure even
shrinkage of all the materials and also helps to reduce scorching
! Ensure that all components are kept clean and
grease free during installation
! Allow to cool before applying any mechanical
strain
Remove Outer Cable Sheath:
X
L
Table 1
Single Core Armoured Cables
If the Cable is Armoured, bonding of the Armours must be completed
using the appropriate Armour Earthing kit. A) For Indoor T erminations (Cable End Box) - Order Bolt On
Aluminium Earth Gland Ref: SPS 560* B) For Outdoor Terminations (Pole Top) - Please advise
Conductor and Voltage rating.
* SPS 560 size range = 50-630mm2 7.2-36kV
IMPORTANT NOTICE TO PURCHASER:- Sellers and Manufacturere’s only obligation shall be to replace such quantity of the product proved to be defective. Neither the Seller nor Manufacturer shall be liable for any injury, loss or damage, direct or consequential, arising out of the use or inability to use the product. Before using, User shall determ ine th e suitability of the product for his or her intended use and User assumes all risk and liability whatsoever in connection therewith.
60
mm
Fig1
30mm
Fig 2
CONSTANT
FORCE
1. Installation
Remove the Outer Cable Sheath to the dimensions L + X given in Table 1.
Remove any fillers before cleaning and de-greaseing the Cable Sheath below.
2. Screen Treatment
Copper Wire Screen
Apply one turn of the Red Mastic Sealant Tape at a point 30mm below the sheath cut (Fig 2).
Bend back the Copper Wires and press them into the Tape. Apply one more turn of Red Mastic Tape over this point. The Wires should be twisted together and Bonded to a suitable earth point.
PRIMARY
INSULATION
40mm
RED
MASTIC
40mm
30mm
Fig 3
20mm
MOISTURE
BLOCK
CONDUCTIVE
LAYER
CONSTANT
FORCE
SPRING
Copper Tape Screen
Apply one turn of the red Mastic Tape at a point 30mm below the sheath cut (Fig 3).
Remove the Copper Tape Screens to a point 40mm above the Cable Sheath cut as shown opposite in Fig 3.
Position a Copper Earth Braid onto the Copper Screen and secure with a Constant Force Roll Spring. Ensure the Moisture Block in the Braid is bedded into the Red Mastic and apply one more turn of Tape over this point. Secure the end of the Braid to a suitable Earth point.
Note:- A full range of Solderless Earth Bonding kits are available for all Voltages and Conductor sizes.
3. Conductive Layer Treatment
INSULATION
10mm
10mm
PRIMARY
Fig 4
Fig 5
Extruded Conductive Layer
Remove the Conductive layer using a suitable Tool to the dimensions shown in Fig 3 and 4. Avoid scoring and damage to the Primary Insulation.
Note:- The Screen should be removed leaving a cleanly cut end. Do not roughen the Insulation with Emery Cloth.
STRESS
RELIEF
TAPE
STRESS
RELIEF
TAPE
10mm
Soluble Conductive Layer
Cover the Conductive screen with Non adhesive Tape for 40mm on Wire Screened Cables and 20mm on Copper Tape Screened Cables (see Fig 4).
10mm
Fig 6
STRESS CONTROL TUBES
Remove the layer after this point with a suitable solvent until totally clean. Remember to remove the Tape when finished.
4. Apply Stress Relief Tape
Remove the release paper, stretch the TS31785Y Yellow Stress Tape to double its length and apply around the end of each Core Screen to cover Copper Tape(if present) and Insulation by 10mm (see fig 5,6).
5. Stress Control Tubes
Position the Stress Control Tubes so that they cover the Earth connection point and the Conductive Screen end. However do not extend past this point onto the Outer Cable Sheath.
Fig 7
L + X
Fig 8
RED SEALANT TAPE
Shrink the Tubes one at a time starting from the bottom. Ensure the tubes are wrinkle free and have an even wall thick­ness.
6. Installing Cable Lugs
The Cable should be cut to dimension L+X as given in Table 1. Remove the Insulation at X and install the Lug using the appro-
X
priate method.
Preheat each Lug and wrap two layers of Red Sealant Tape over the Lug barrel and extend onto the Insulation by approx 10mm. Ensure the Tape is applied as shown.
Fig 9
NUMBER OF SHEDS PER PHASE
VOLTAGE INDOOR OUTDOOR
7.2kV - 2 12kV - 2
17.5kV - 2 24kV - 3 36kV 1 4
60mm
VOLTAGE (kV) 7.2 12 17.5 24 36
DIS TANCE (mm ) 15 20 20 25 35
ANTI-TRACK TUBE
Fig 10
7. Installing Anti-Track Tube
Position the Anti-Track Tubes so that they overlap the Earth connection point and outer Cable Sheath by 60mm as shown in Fig 10.
Shrink the Tubes starting from the bottom towards the top. Keep the flame on the move to ensure an even wall thickness. User may trim the Tubes at the Lug end with a sharp knife if necessary.
8. Indoor Terminations
Anti-Track Rain Sheds are not required on Indoor Terminations rated between 7.2 and 24kV. One Shed per phase is required on 36kV types (see Table 2).
Table 2
Clearance Dimen ions
s
Minimum clearances should be observed for phase to phase and phase to ground (see Table 3).
Table 3
9. Outdoor Terminations
Anti-Track Sheds should be fitted starting from the bottom up as per the dimensions given in Fig 12.
The number of Sheds required depends on the system voltage (see Table 2).
Fig 11
80mm
Fig 12
200mm
Positioning of Sheds
The first Shed should be fitted at a dis­tance of 200mm from the lower edge of the Anti-Track Tube to the edge of the Shed. All subsequent Sheds should be fitted at a distance of 80mm from edge to edge.
Note:- It is advisable not to position Sheds at the top of the Stress Control Tubes. Re-position if necessary.
Fig 13
Min Bending Radius r=15xD
Reverse Connection
If a Termination is to be mounted for connection above the equipment i.e in the reverse position, Sheds should be installed through 180º.
10. Cable Bending Radius
If required The Cable can be heated to approximately 70ºC to enable a bend to be introduced. See Fig 14 showing the bending radius.
D
Fig 14
IMPORTANT NOTICE T O PURCHASER:- Sellers and Manufacturere’s only obligation shall be to replace such quantity of the product proved to be defective. Neither the Seller nor Manufacturer shall be liable for any injury, loss or damage, direct or consequential, arising out of the use or inability to use the product. Before using, User shall determine the suitability of the product for his or her intended use and User assumes all risk and liability whatsoever in connection therewith.
UNITS P1-P3 GROVEMERE COURT BICTON INDUSTRIAL PARK KIMBOLTON CAMBS PE28 OEY TEL: +44 (1480) 861001 FAX: +44 (1480) 861002 E-MAIL: info@shrinkpolymersystems.co.uk
WEBSITE: www.shrinkpolymersystems.co.uk
©
Loading...