Shinko LMD-100 Instruction Manual

CONSOLE/DATA LOGGER
LMD-100
INSTRUCTION MANUAL
2
Preface
Thank you for purchasing our Console/Data Logger LMD-100. This manual contains instructions for the mounting, functions, operations and notes when operating the LMD-100. To prevent accidents arising from the misuse of this instrument, please ensure the operator receives this manual.
Abbreviations used in this manual
Symbol Term
PV Process variable
SV Desired value
MV Output manipulated variable
OUT1 Control output 1
OUT2 Control output 2
AT Auto-tuning
Characters used in this manual
Indication
Number, / -1 0 1 2 3 4 5 6 7 8 9
Indication Alphabet A B C D E F G H I J K L M
Indication
Alphabet N O P Q R S T U V W X Y Z
means no indication.
Notes
• This instrument should be used in accordance with the specifications described in the manual. If it is not used according to the specifications, it may malfunction or cause a fire.
• Be sure to follow the warnings, cautions and notices. If they are not observed, serious injury or malfunction may occur.
• Specifications of the LMD-100 and the contents of this instruction manual are subject to change without notice.
• Care has been taken to assure that the contents of this instruction manual are correct, but if there are any doubts, mistakes or questions, please inform our sales department.
• This instrument is designed to be installed within a control panel. If it is not, measures must be taken to ensure that the operator cannot touch power terminals or other high voltage sections.
• Any unauthorized transfer or copying of this document, in part or in whole, is prohibited.
• Shinko Technos CO., LTD. is not liable for any damage or secondary damage(s) incurred as a result of using this product, including any indirect damage.
3
SAFETY PRECAUTIONS (Be sure to read these precautions before using this product.)
The safety precautions are classified into categories: “Warning” and “Caution”. Depending on the circumstances, procedures indicated by Caution may be linked to serious results, so be sure to follow the directions for usage.
Warning
Warning
• To prevent an electric shock or fire, only Shinko or other qualified service personnel may
handle the inner assembly.
• To prevent an electric shock, fire or damage to the instrument, parts replacement may only
be undertaken by Shinko or other qualified service personnel.
Safety precautions
To ensure safe and correct use, thoroughly read and understand this manual before using this
instrument.
• This instrument is intended to be used for industrial machinery, machine tools and measuring
equipment. Verify correct usage after consulting purpose of use with our agency or main office. (Never use this instrument for medical purposes with which human lives are involved.)
• External protection devices such as protection equipment against excessive temperature rise,
etc. must be installed, as malfunction of this product could result in serious damage to the system or injury to personnel. Also proper periodic maintenance is required.
• This instrument must be used under the conditions and environment described in this manual.
Shinko Technos Co., Ltd. does not accept liability for any injury, loss of life or damage occurring due to the instrument being used under conditions not otherwise stated in this manual.
Caution with respect to Export Trade Control Ordinance
To avoid this instrument from being used as a component in, or as being utilized in the manufacture of weapons of mass destruction (i.e. military applications, military equipment, etc.), please investigate the end users and the final use of this instrument. In the case of resale, ensure that this instrument is not illegally exported.
Caution
Procedures which may lead to dangerous conditions and cause death or serious injury, if not carried out properly.
Procedures which may lead to dangerous conditions and cause superficial to medium injury or physical damage or may degrade or damage the product, if not carried out properly.
4
1. Installation precautions
Caution
This instrument is intended to be used under the following environmental conditions (IEC61010-1): Overvoltage category , Pollution degree 2
Ensure the mounting location corresponds to the following conditions:
• A minimum of dust, and an absence of corrosive gases
• No flammable, explosive gases
• Few mechanical vibrations or shocks
• No exposure to direct sunlight, an ambient temperature of 0 to 50 (32 to 122 ) that does not change rapidly, and no icing
• An ambient non-condensing humidity of 35 to 85%RH
• No large capacity electromagnetic switches or cables through which large current is flowing
• No water, oil or chemicals or where the vapors of these substances can come
into direct contact with the unit
• Take note that ambient temperature of this unit must not exceed 50 (122 ) when mounted through a control panel. Otherwise the life of electronic components
(especially electrolytic capacitor) may be shortened.
Note: Although the case of this instrument is made of flame-resistant resin, do not
install this instrument on or near flammable material.
2. Wiring precautions
Caution
• Do not leave wire remnants in the instrument, because they could cause a fire or malfunction.
• Use the solderless terminal with an insulation sleeve in which the M3 screw fits when wiring the LMD-100.
• The terminal block of this instrument is designed to be wired from the left side. The lead wire must be inserted from the left side of the terminal, and fastened with the terminal screw.
• Tighten the terminal screw using the specified torque. If excessive force is applied to the screw when tightening, the terminal screw or case may be damaged.
• When wiring, keep power lines away from communication lines.
• This instrument has no built-in power switch or fuse. It is necessary to install them near the instrument. (Recommended fuse: Time-lag fuse, Rated voltage 250V AC, Rated current 2A)
5
3. Running and maintenance precautions
Caution
• Do not touch live terminals. This may cause electric shock or problems in operation.
• Turn the power supply to the LMD-100 OFF before retightening the terminal. Working or touching the terminal with the power switched ON may result in severe injury or death due to Electric Shock.
• Be sure to turn the power to the LMD-100 OFF before cleaning.
• Use a soft, dry cloth when cleaning the instrument. (Alcohol based substances may tarnish or deface the unit.)
• As the display section is vulnerable, do not strike or scratch it with a hard object or press hard on it.
6
--- CONTENTS ---
1. Overview Page
1.1 Overview --------------------------------------------------------------------------------- 7
1.2 system configuration ------------------------------------------------------------------ 8
2. Unpacking
2.1 Checking the accessories ----------------------------------------------------------- 9
2.2 Model ------------------------------------------------------------------------------------- 9
2.3 How to read the model label -------------------------------------------------------- 9
3. Name and functions of sections ------------------------------------------ 10
4. Mounting to the control panel
4.1 Site selection -------------------------------------------------------------------------- 12
4.2 External dimensions (Scale: mm) ------------------------------------------------ 12
4.3 Panel cutout (Scale: mm) ---------------------------------------------------------- 12
4.4 Mounting --------------------------------------------------------------------------------13
5. Wiring
5.1 Terminal arrangement -------------------------------------------------------------- 14
5.2 Wiring examples --------------------------------------------------------------------- 15
6. Settings
6.1 Setting of controller ----------------------------------------------------------------- 19
6.2 Turn the power supply to the LMD-100 ON (warm-up indication) ------- 19
6.3 Display explanation ----------------------------------------------------------------- 19
6.4 Basic operation ---------------------------------------------------------------------- 20
6.5 Controller setting mode ------------------------------------------------------------ 21
6.6 Logging condition setting mode ------------------------------------------------- 22
6.7 Main setting mode ------------------------------------------------------------------ 25
6.8 Sub setting mode ------------------------------------------------------------------- 28
6.9 All set values reading mode ------------------------------------------------------ 29
6.10 Operation flowchart --------------------------------------------------------------- 30
7. Operation
7.1 Running the LMD-100 ------------------------------------------------------------- 32
7.2 Preparation for data logging ------------------------------------------------------ 32
7.3 CF card insertion -------------------------------------------------------------------- 33
7.4 CF card ejection --------------------------------------------------------------------- 33
7.5 How to start data logging ---------------------------------------------------------- 34
7.6 How to stop data logging ---------------------------------------------------------- 35
7.7 How to edit CF card data on the personal computer ---------------------- 36
7.8 How to format the CF card ------------------------------------------------------- 37
7.9 How to lock front key using external contact --------------------------------- 37
7.10 Set value memory function ----------------------------------------------------- 38
7.11 Setting the same value to all controllers simultaneously (Broadcast setting)-39
7.12 PV, SV 5-digit indication --------------------------------------------------------- 39
8. Other functions
8.1 Power failure countermeasure --------------------------------------------------- 40
8.2 Self-diagnosis ------------------------------------------------------------------------ 40
8.3 Error indication while accessing the CF card --------------------------------- 40
8.4 Time error indication ---------------------------------------------------------------- 40
8.5 Error indication during data logging --------------------------------------------- 40
8.6 CF card remaining memory indication ----------------------------------------- 41
8.7 Momentary power failure indication -------------------------------------------- 41
8.8 Error indication during setting mode ------------------------------------------- 41
9. Specifications
9.1 Standard specifications ------------------------------------------------------------ 42
9.2 Optional specifications ------------------------------------------------------------- 47
10. Troubleshooting
10.1 Indication is abnormal or unstable --------------------------------------------- 48
10.2 Key operation is impossible ----------------------------------------------------- 48
10.3 Data logging is impossible --------------------------------------------------------- 48
10.4 Communication failure ------------------------------------------------------------ 48
11. Character table -------------------------------------------------------------------- 49
7
1. Overview
1.1 Overview
The LMD-100 indicates PV, SV and alarm status, sets various set values, and logs data by connecting up to 16 units of digital indicating controllers to which C5 (Serial communication) option is added.
The LMD-100 has the following major functions.
(1) Data logging
The LMD-100 saves data such as PV, SV, OUT1 MV, OUT2 MV and controller status (output, alarm, etc.) on the CF card with CSV format. Data on the CF card can be edited on spreadsheet applications like EXCEL.
(2) Monitoring
The LMD-100 indicates PV, SV and Alarm status of the connected controllers.
(3) Console
The LMD-100 sets values for the connected controllers.
(4) Set value memory
6 groups of SV for the connected controllers can be saved.
(5) Broadcast setting
The same set value can be set to all connected controllers simultaneously.
(6) 2-point external operation input (Edge action)
Logging Start/Stop and Front key Lock/Unlock can be switched.
(7) 1 point error output (Relay contact 1a)
ERR output is turned ON for the following cases.
• If errors occur during data logging
• If the CF card is defective
• If the CF card is not inserted
• If battery (for clock) runs down
• If the key is pressed without setting time
8
1.2 System configuration
System configuration of the LMD-100 is shown below.
System configuration example 1
(Fig. 1.2-1)
System configuration example 2
(Fig. 1.2-2)
Communication converter (IF-400)
RS-232C RS-485
LMD-100, C5 (No.0)
DCL-33A (Max 16 units)
LMD-100, C5 (No.1)
DCL-33A (Max 16 units)
Host computer
RS-485 Max 1.2km
LMD-100, C5 (No.30) (Max 31 units)
DCL-33A (Max 16 units)
RS-485 (Max. 1.2km)
LMD-100
DCL-33A (Max 16 units)
RS-485 (Max 1.2km)
9
2. Unpacking
2.1 Checking the accessories
Check whether the following accessories are included.
Name Q’ty
Mounting brackets 1 set Instruction manual 1 copy
CF card: 256MB 1
Waterproof cover (IP option) 1 piece
Terminal cover (TC option) 2 pieces
2.2 Model
Model and option codes are indicated as shown below. (e.g.) LMD-100, IP, TC
Option codes are punctuated with a comma.
IP: Dust-proof/Drip-proof (IP66) TC: Electrical shock protection terminal cover
Model: LMD-100 [96 x 96 x 100mm (W x H x D)]
Option codes
(Table 2.2-1)
Code Name
C5 Serial communication: RS-485
IP Dust-proof/Drip-proof (IP66)
TC Electrical shock protection terminal cover
BK Color: Black (Front panel frame, case)
2.3 How to read the model label
The model labels are attached to the left side of the case.
For the left side of the case
Model Option
Serial number
(Fig. 2.3-1)
10
3 Name and functions of sections
(Fig. 2-1)
(1) PV display
Indicates PV of the connected controller, or setting characters during the setting mode with the red LED.
(2) SV display
Indicates SV or each set value during the setting mode of the controller with the green LED.
(3) CH (Channel) display
Indicates the channel number of the indicated PV, SV and alarm status with the yellow LED.
(4) MEMO (Memory number) display
Indicates a set value memory number with the yellow LED.
(5) HOST T/R indicator (Host communication indicator)
The yellow LED Lights during Serial communication (C5 option) (TX output) with the host.
(6) AT indicator
When the controller of the indicated channel number is performing auto-tuning or auto-reset, the 1st decimal point from the right on the PV display flashes.
(7) CNTL ALM indicator (Controller alarm indicator)
The red LED lights when the controller alarm of the indicated channel is ON. JCS-33A, JCM-33A, JCR-33A, JCD-33A: Alarm 1, Alarm 2, Heater burnout alarm,
Loop break alarm, Overscale, Underscale JCL-33A: Alarm 1, Alarm 2, Overscale, Underscale DCL-33A: Alarm, Heater burnout alarm, Loop break alarm, Overscale, Underscale NCL-13A: Alarm 1, Alarm 2, Alarm 3, Alarm 4, Heater burnout alarm 1, Heater burnout alarm 2,
Loop break alarm, Overscale, Underscale, Actuator short circuit alarm 1, Actuator short circuit alarm 2, Memory defect
ACS-13A: Alarm 1, Alarm 2, Heater burnout alarm, Overscale, Underscale
(1)
(2)
(3) (4)
(5)
(7)
(8)
(9)
(10
(11)
(19)
(18)
(17)
(16)
(15)
(12)
(13)
(14)
(6)
11
(8) CNTL T/R indicator (Controller communication indicator)
The yellow LED lights during Serial communication (TX output) with the controller.
(9) CNTL COM ERR indicator (Controller communication error indicator)
The red LED lights when communication errors occur during Serial communication between the LMD-100 and any controller(s).
(10) (Channel) key
The channel number indication can be switched manually with this key if “Manual switching” is selected in the PV/SV display mode. In Main setting mode or Sub setting mode, pressing this key registers the set value, and switches to the next channel.
(11) Mode key
Switches the setting mode or registers the set (selected) value. To register the set (selected) value, press this key.
(12) Increase key
Increases the numeric value.
(13) Decrease key
Decreases the numeric value.
(14) (Display) key
Selects automatic or manual switching of the channel number to be indicated. If automatic switching is selected, the channel number is automatically switched from [1 2 3 (Number of connected units) 1] every 2 seconds. If manual switching is selected, the 1st decimal point from the right on the CH (Channel) display lights. The channel number can be manually changed by pressing the (Channel) key.
(15) LOG ERR indicator (Logging error indicator)
The red LED lights if errors occur during data logging, if CF card is defective, if the
(Logging) key is pressed without setting time, or while battery runs down.
(16) (Logging) key
Starts or stops data logging. Data logging stops by pressing this key for 1 second or more. Data logging does not start if items in the Data logging condition setting mode are not set. Data logging does not start if CF card is not inserted (logging error).
(17) EJECT (CF card eject button)
Pressing this button ejects the CF card.
(18) CF card LOCK switch (logging indicator)
Switch for preventing the CF card from being taken out during logging. LOCK : Data logging Enabled UNLOCK : Data logging Disabled Data logging stops when switched to UNLOCK. This switch also functions as a Logging indicator. The red LED lights during logging, and flashes while accessing the CF card.
(19) CF card insertion slot
Slot to insert the CF card.
12
4. Mounting to the control panel
4.1 Site selection
This instrument is intended to be used under the following environmental conditions (IEC61010-1): Overvoltage category , Pollution degree 2
Ensure the mounting location corresponds to the following conditions: (1) A minimum of dust, and an absence of corrosive gases (2) No flammable, explosive gases (3) No mechanical vibrations or shocks (4) No exposure to direct sunlight, an ambient temperature of 0 to 50 (32 to 122 )
that does not change rapidly, and no icing (5) An ambient non-condensing humidity of 35 to 85%RH (6) No large capacity electromagnetic switches or cables through which large current
is flowing (7) No water, oil or chemicals or where the vapors of these substances can come
into direct contact with the instrument
(8) Take note that ambient temperature of this unit must not exceed 50 (122 ) when
mounted through a control panel. Otherwise the life of electronic components
(especially electrolytic capacitor) may be shortened.
4.2 External dimensions (scale: mm)
(Fig. 4.2-1)
4.3 Panel cutout (scale: mm)
Lateral close mounting n: Number of units mounted
Note: If the IP option is applied, take the space
for opening the waterproof cover into
(Fig. 4.3-1) consideration.
130
nX96-3
0.5
0
92
0.8
0
92
0.8
0
When CF card is inserted
Screw type mounting bracket
Terminal cover
(TC option)
96
100
106 (When TC option is added)
10
15.3
91
106.2
13
4.4 Mounting
Notice
As the case is made of resin, do not use excessive force while screwing in the mounting bracket, or the case or screw type mounting bracket could be damaged. The torque should be 0.12N•m.
Mountable panel thickness is 1 to 8mm. Insert the LMD-100 from the front of the control panel. For the IP option, fitting the waterproof cover to the control panel cutout, mount it between the panel and the face of the LMD-100. (Fig. 4.4-1)
Waterproof cover
Cover : Polycarbonate 94V-2 Packing : Chloroprene rubber Panel : SUS304
Attach the mounting brackets to the slots at the top and bottom of the case, and secure the controller in place with the screws provided. (Fig. 4.4-2)
Up
Up
Waterproof cover (When the IP option is added)
(Fig. 4.4-1) (Fig. 4.4-2)
14
5. Wiring Warning
Turn the power supply to the instrument off before wiring or checking. Working or touching the terminal with the power switched on may result in severe injury or death due to Electric Shock. Moreover, the instrument must be grounded before the power supply to the instrument is turned on.
Notice
The terminal block of this instrument is designed to be wired from the left side. The lead wire must be inserted from the left side of the terminal, and fastened with the terminal screw.
5.1 Terminal arrangement
(Fig. 5.1-1)
Power supply : 100 to 240V AC ERR : Error output
Outputs if errors occur during data logging, if the CF card is defective, while battery runs down or if the key is pressed without setting time.
RS-485 (to HOST) : Serial communication RS-485 (connection to Host) (C5 option) RS-485 (to CNTL) : Serial communication RS-485 (connection to controller) EXT CONT (KEY LOCK) : External operation input (Front key LOCK/UNLOCK) EXT CONT (LOG) : External operation input (Logging Start/Stop)
POWER SUPPLY
100 to 240V AC
ERR
to HOST
to CNTL
EXT CONT
3A 250V AC
YA (
-)YB (+)
YA (
-)YB (+)
SG
RS-485
RS-485
KEY LOCK
LOG
COM
1202
3
4
5
6
78910111213
14
15
16
171819
15
Solderless terminal
Use a solderless terminal with an insulation sleeve in which the M3 screw fits as shown below. The torque should be 0.63N•m.
Solderless
terminal
Manufacturer Model
Tightening
torque
Nichifu Terminal Industries CO.,LTD.
TMEV1.25Y-3
Y type
Japan Solderless Terminal MFG CO.,LTD.
VD1.25-B3A
Nichifu Terminal Industries CO.,LTD.
TMEV1.25-3Round type
Japan Solderless Terminal MFG CO.,LTD.
V1.25-3
0.63N•m
(Fig. 5.1-2)
5.2 Wiring examples
Caution
• This instrument has neither a built-in power switch, circuit breaker nor a fuse. Therefore, it is necessary to install them in a circuit near the external instrument. (Recommended fuse: Time-lag fuse, rated voltage 250V AC, rated current 2A)
• When wiring, keep power lines away from communication lines.
5.2.1 Wiring example of power supply, error output and external operation input
(Fig. 5.2.1-1)
3.2mm
5.8mm or less
3.2mm
5.8mm or less
Power supply
LMD-100
Error output
External operation input
16
5.2.2 Wiring example of Serial communication RS-485 (connection to controller)
(1) DCL-33A (Fig. 5.2.2-1)
Connection between LMD-100 and DCL-33A
Use CDM communication cable (sold separately). Connect CDM modular plug to DCL-33A modular jack. For CDM “Y” terminal connection, refer to the following.
CDM “Y” terminal number LMD-100 terminal number
4 15 YA (-) 3 16 YB (+) 1, 6 17 SG
CDM cable length: 3000mm (Can be extended in units of 500mm fixed length)
Connection between DCL-33A units
Use communication cable CDD or CPP (sold separately), and plug into modular jack.
Cable length of CDD: 60mm. For distances larger than 60mm, use the CPP cable. Cable length of CPP: 500mm.
(For distances larger than 500mm, the CPP can be extended in units of 500mm fixed length. For distances less than 500mm, the CPP can be cut down in units of 100mm fixed length.)
(Fig. 5.2.2-1)
CDM (sold separately)
CDD or CPP (sold separately)
LMD-100
DCL-33A
17
(2) ACS-13A, JCL-33A, JCS-33A, JCM-33A, JCR-33A, JCD-33A (Fig. 5.2.2-2)
Connection between LMD-100 and controller (ACS-13A/JCL-33A/JCS-33A/
JCM-33A/JCR-33A/JCD-33A)
Connection between controllers (ACS-13A/JCL-33A/JCS-33A/JCM-33A/JCR-33A/
JCD-33A)
Connect YA (-) to YA (-), YB (+) to YB (+) and SG to SG respectively, using a shielded wire. Connect only one side of the shielded wire to the FG terminal so that current cannot
flow to the shielded wire. If both sides of the shielded wire are connected to the FG terminal, the circuit will be closed between the shielded wire and the ground. As a result, current will run through the shielded wire, and this may cause noise. Be sure to ground FG terminal.
Recommended cable: OTSC-VB 2PX0.5SQ (made by Onamba Co., Ltd.) or equivalent
(Use a twisted pair cable.)
Wiring example between LMD-100 and ACS-13A (Fig. 5.2.2-2)
Terminal numbers for connection differ depending on a controller model as follows.
LMD-100 JCL-33A JCS-33A JCM-33A JCR-33A JCD-33A
15 YA (-) 10 YA (-) 13 YA (-) 10 YA (-) 11 YA (-) 11 YA (-) 16 YB (+) 11 YB (+) 14 YB (+) 13 YB (+) 14 YB (+) 14 YB (+) 17 SG 12 SG 15 SG 14 SG 17 SG 17 SG
(Fig. 5.2.2-2)
LMD-100
ACS-13A
Shielded wire
Shielded wire
Shielded
wire
18
(3) NCL-13A (Fig. 5.2.2-3)
Connection between LMD-100 and NCL-13A
Connect YA (-) to YA (-), YB (+) to YB (+) and SG to SG respectively, using the communication cable CFP-C5 (sold separately).
Connection between NCL-13A units
Connect bus plug to bus plug.
(Fig. 5.2.2-3)
LMD-100
NCL-13A
CFP-C5 (sold separately)
Bus plug Bus plug
Screw type plug for lines Model: Terminal block ATB-001-1
(sold separately)
19
6 Settings
6.1 Setting of controller
Controllers should to be set as the following. (Refer to the instruction manual for the controller connected to the LMD-100.)
(1) Controller communication protocol : Shinko protocol (2) Controller instrument number : From 1 in numerical order
(e.g.) Set from 1 to 5 when 5 units of controller are
connected.
(3) Controller communication speed : 19200bps
6.2 Turn the power supply to the LMD-100 ON (warm-up indication)
Turn the power supply to the LMD-100 ON. After power-on, the PV display indicates “ ” for approx. 5 seconds. (Fig. 6.2-1) After that, the LMD-100 reads PV, SV and alarm status of the connected controller, and indicates them for each channel (in the case of automatic switching of the channel number, the channel is automatically switched every 2 seconds.). (Fig. 6.2-2)
(Fig. 6.2-1) (Fig. 6.2-2)
6.3 Display explanation
In this manual, the following display is used for purposes of explanation.
means no indication.
(e.g.) Set value memory selection
Display
CH MEMO
PV
SV
(Fig. 6.3-1)
20
6.4 Basic operation
SV setting (e.g. 100 ) is used for purposes of explanation of basic operation. To set (or select) each setting item, use the or key, then register the value with the or key.
PV/SV display mode
or
Data logging mode
Press the key twice in the PV/SV display mode or Data logging mode.
The unit proceeds to the SV setting in Main setting mode.
(Twice)
Main setting mode
CH MEMO
PV
SV
CH1 SV setting Set CH1 SV, using the or key.
or
CH MEMO
PV
SV
CH1 SV has been set. (e.g.) 100
(e.g.) 100 Pressing the key registers CH1 SV, and proceeds to the CH2 SV setting.
key
CH MEMO
PV
SV
CH1 SV has been registered. CH2 SV setting
CH2 SV can be set continuously. Set other channel number controllers in the same way.
Press the key 10 times or for approx. 3sec. The unit Reverts to the PV/SV display mode or Data logging mode.
(10 times or
for approx. 3sec)
Reverts to the PV/SV display mode or Data logging mode.
21
6.5 Controller setting mode
Select controller model and number of controller units to communicate with the controller. Press the key for approx. 3 seconds while holding down the key in the PV/SV display mode or Data logging mode. The unit will proceed to the Controller setting mode.
To set (or select) each setting item, use the or key, then register the value with the key. The setting item will be switched.
Display Name, Function, Setting range Default value
Controller model DCL-33A
CH MEMO
PV
SV
• Selects controller type connected to the LMD-100.
• Selection item : DCL-33A : JCS-33A, JCM-33A, JCR-33A, JCD-33A : NCL-13A : JCL-33A : ACS-13A
Number of controllers 1 unit
CH MEMO
PV
SV
• Sets the number of controller units connected to the LMD-100.
• Setting range: 1 to 16
22
6.6 Logging condition setting mode
Logging date, time, logging item, logging cycle, etc. can be set for data logging.
Press the key for approx. 3 seconds while holding down the key in the PV/SV display mode or Data logging mode. The unit will proceed to Logging condition setting mode.
To set (or select) each setting item, use the or key, then register the value with the key. The setting item will be switched.
Display Name, Function, Setting range Default value
Year 0 (2000)
CH MEMO
PV
SV
• Sets the year.
Not available during data logging.
• Setting range: 0 to 99 (2000 to 2099)
Month 1 (January)
CH MEMO
PV
SV
• Sets the month.
Not available during data logging.
• Setting range: 1 to 12 (January to December)
Day 1 (1st)
CH MEMO
PV
SV
• Sets the day.
Do not set a non-existent day such as 31st Feb. or 31st Nov. Logging file name and updated date will not coincide. Not available during data logging.
• Setting range: 1 to 31
Hour 0
CH MEMO
PV
SV
Sets the hour. Not available during data logging.
• Setting range: 0 to 23
Minute 0
CH MEMO
PV
SV
• Sets the minute.
Not available during data logging.
• Setting range: 0 to 59
PV logging Effective
CH MEMO
PV
SV
• Selects PV logging. Not available during data logging.
• Selection item: Not effective
Effective
SV logging Not effective
CH MEMO
PV
SV
• Selects SV logging. Not available during data logging.
• Selection item: Not effective
Effective
OUT1 MV logging Not effective
CH MEMO
PV
SV
• Selects OUT1 MV logging. Not available during data logging.
• Selection item: Not effective
Effective
23
Display Name, Function, Setting range Default value
OUT2 MV logging Not effective
CH MEMO
PV
SV
• Selects OUT2 MV logging. Not available during data logging.
• Selection item: : Not effective
: Effective
Status logging Not effective
CH MEMO
PV
SV
• Selects status logging. Not available during data logging.
• Selection item: : Not effective
: Effective
Logging auto-start Not effective
CH MEMO
PV
SV
• Selects Logging auto-start. Not available during data logging.
• Selection item: : Not effective
: Effective
Logging auto-start timer (start) 00:00
CH MEMO
PV
SV
• Sets logging auto-start time. Not available during data logging or if “Not effective” is selected during Logging auto-start selection.
• Setting range: 00:00 to 23:59 (Hour:Minute)
Logging auto-start timer (end) 00:00
CH MEMO
PV
SV
• Sets logging auto-start end time.
If logging auto-start start and end time are the same, logging continues until power-off or until CF card capacity is exceeded. Not available during data logging or if “Not effective” is selected during Logging auto-start selection.
• Setting range: 00:00 to 23:59 (Hour:Minute)
Logging cycle 10 seconds
CH MEMO
PV
SV
• Selects the data logging cycle.
• Selection item: : 1 second : 2 seconds : 5 seconds : 10 seconds : 15 seconds : 20 seconds : 30 seconds : 1 minute : 2 minutes : 5 minutes : 10 minutes : 15 minutes : 20 minutes : 30 minutes : 60 minutes
24
Display Name, Function, Setting range Default value
CF card used memory indication
CH MEMO
PV
SV
• Used CF card memory is indicated as a percentage from 0.0 to
100.0%. Take this into consideration when logging data.
Available only when the CF card is inserted.
CF card format No format
CH MEMO
PV
SV
• Selects whether to format the CF card.
Not available during data logging or if the CF card is not inserted
• Selection item: : No format
: Format
CF card format confirmation No format
CH MEMO
PV
SV
• Confirms whether to format the CF card.
Not available if “No format” is selected during CF card format selection
• Selection item: : No format
: Format
External operation input (LOG) priority External operation input
(LOG) has priority
CH MEMO
PV
SV
• Selects whether priority is given to the external operation.
• Selection item:
: External operation input (LOG) has priority.
: The key has priority.
Instrument number 0
CH MEMO
PV
SV
• Sets the instrument number individually to each instrument when
communicating by connecting plural instruments in serial communication. Note: Available only when C5 option is added
• Setting range: 0 to 95
Communication speed 9600bps
CH MEMO
PV
SV
• Selects the communication speed equal to that of the host
computer.
• To communicate with the controllers, the communication speed
of the host computer and LMD-100 should be set to 19200bps. Note: Available only when C5 option is added
• Selection item:
: 9600bps
: 19200bps
25
6.7 Main setting mode
SV, Alarm 1 value and PID parameters, etc. of the connected controller can be set. Press the key in the PV/SV display mode or Data logging mode. The unit will proceed to the Main setting mode.
To set (or select) each item, use the or key. Pressing the key registers the value, and switches the channel number. Pressing the key registers the value, and switches the setting item.
Display Name, Function, Setting range Default value
Set value memory number 1
CH MEMO
PV
SV
• Selects the Set value memory number.
• Up to 6 groups of SV of the connected controller can be saved. If the key is pressed after selecting Set value memory number, SVs in the selected memory number are sent to the controllers. (See p.38 for registering Set value memory number.) [When a lot of controllers are connected, operations at the next setting mode (SV setting) cannot be performed until all connected controllers SV changes are completed.]
• If set values are changed from the controller side, the LMD-100 reads and saves the sending items the LMD-100 already has. Sending items of the LMD-100:
SV, Alarm 1 value, OUT1 proportional band, OUT2 proportional band, Integral time, Derivative time, ARW, OUT1 proportional cycle, OUT2 proportional cycle, Manual reset, Set value lock,
AT/Auto-reset However, if SV is changed from the controller side, the SV of the Set value memory number cannot be changed. To change SV of the Set value memory number, set it in the next “SV setting” mode.
• Setting range: 1 to 6
SV
CH MEMO
PV
SV
• Sets the SV of the connected controllers and SV of the Set value memory number selected during Set value memory number selection.
• Setting range: Scaling low limit to Scaling high limit
SV low limit to SV high limit
Alarm 1 value
CH MEMO
PV
SV
• Sets the action point of Alarm 1 output of the connected controller.
Setting the value to 0 or 0.0 disables the function.
(Excluding process high alarm and process low alarm)
• When No alarm action is selected for the controller, the SV display
is unlit, and this setting is impossible.
• Setting range depends on the alarm type of the connected controller.
OUT1 proportional band
CH MEMO
PV
SV
• Sets OUT1 proportional band of the connected controllers.
OUT1 becomes ON/OFF action when set to 0 or 0.0.
• Setting range:
DCL-33A, JCL-33A, ACS-13A : 0.0 to 110.0% JCS-33A, JCM-33A, JCR-33A, JCD-33A: 0 to 1000 (2000 ) Thermocouple, RTD input with decimal point: 0.0 to 1000.0 ( ) DC voltage, current input: 0.0 to 100.0%
26
Display
Name, Function, Setting range
OUT2 proportional band
CH MEMO
PV
SV
• Sets OUT2 proportional band of the connected controllers.
OUT2 becomes ON/OFF action when set to 0.0. If D option is not added to the controller, or if OUT1 is ON/OFF action, the SV display is unlit, and this setting is impossible.
• Setting range: 0.0 to 10.0 times (to OUT1 proportional band)
(e.g.) When OUT1 proportional band is 2.5%:
If OUT2 proportional band is set to 1.0 time,
OUT2 proportional band: 2.5% x 1.0= 2.5%
If OUT2 proportional band is set to 2.0 times,
OUT2 proportional band: 2.5% x 2.0= 5.0%
Integral time
CH MEMO
PV
SV
• Sets OUT1 integral time of the connected controllers.
Setting the value to 0 disables the function.
• If OUT1 is ON/OFF action, the SV display is unlit, and this setting is impossible.
• Setting range: 0 to 1000 seconds
Derivative time
CH MEMO
PV
SV
• Sets OUT1 derivative time of the connected controllers.
Setting the value to 0 disables the function.
• If OUT1 is ON/OFF action, the SV display is unlit, and this setting
is impossible.
• Setting range: 0 to 300 seconds
ARW
CH MEMO
PV
SV
• Sets OUT1 ARW (anti-reset windup) of the connected controller.
• For control actions other than PID, the SV display is unlit, and this
setting is impossible.
• Setting range: 0 to 100%
OUT1 proportional cycle
CH MEMO
PV
SV
• Sets OUT1 proportional cycle for the connected controller.
• For the relay contact output type, if the proportional cycle time is
decreased, the frequency of the relay action increases and the life
of the relay contact is shortened.
If OUT1 is ON/OFF action or DC current output type, the SV display
is unlit, and this setting is impossible.
• Setting range: 1 to 120 seconds
OUT2 proportional cycle
CH MEMO
PV
SV
• Sets OUT2 proportional cycle for the connected controller.
• For the relay contact output type, if the proportional cycle time is
decreased, the frequency of the relay action increases and the life
of the relay contact is shortened.
If D option is not added to the controller, or if OUT2 is ON/OFF action, the SV display is unlit, and this setting is impossible.
• Setting range: 1 to 120 seconds
27
Manual reset
CH MEMO
PV
SV
• Sets the reset value manually for the connected controller. For control actions other than P and PD, the SV display is unlit, and this setting is impossible. Available only when DCL-33A, NCL-13A, JCL-33A is selected
during Controller model selection.
• Setting range: Proportional band converted value (For DC
voltage and current input, the placement of the decimal point follows the selection.)
28
6.8 Sub setting mode
Set value lock and AT/Auto-reset for the connected controller can be set. Press the key while holding down the key in the PV/SV display mode or Data logging mode. The unit will proceed to the Sub setting mode.
To set (or select) each setting item, use the or key. Pressing the key registers the value, and switches the channel number. Pressing the key registers the value, and switches the setting item.
Display
Name, Function, Setting range
Set value lock
CH MEMO
PV
SV
• Locks set values to prevent setting errors.
The setting item to be locked depends on the selection. Refer to the Instruction manual for the connected controller. When Lock 1 or Lock 2 is selected, AT, auto-reset cannot be performed.
• Selection item:
DCL-33A, JCS-33A, JCM-33A, JCR-33A, JCD-33A, JCL-33A, ACS-13A:
(Unlock) All set values can be changed. (Lock 1) None of the set values can be changed. (Lock 2) Only main setting mode can be changed.
(Lock 3) All set values except Input type can be changed.
However, changed values revert to their previous value after power is turned off because they are not saved in the non-volatile memory.
Do not change any setting item in Auxiliary function setting mode 2 or Setup mode. If any item in Auxiliary function setting mode 2 or Setup mode is changed, it will affect other setting items such as the SV, Alarm value, etc.
NCL-13A: Non-volatile memory data saving selection
(Unlock)
(Lock 1) Save
(Lock 2)
(Lock 3) Unable to save
AT/Auto-reset
CH MEMO
PV
SV
• AT Perform/Cancel can be carried out in the PID action.
JCS-33A, JCM-33A, JCR-33A, JCD-33A, ACS-13A:
Auto-reset Perform/Cancel can be carried out in the P, PD action. During ON/OFF, PI action, the SV display is unlit, and this setting is impossible.
• If AT is cancelled during the process, each value of P, I, D and ARW
returns to the values before the AT was performed.
• If AT is not finished after 4 hours, it is cancelled automatically.
• Auto-reset is cancelled in approximately 4 minutes. It cannot be
released while performing this function.
• Selection item:
: AT/Auto-reset Cancel
/ : AT/Auto-reset Perform
29
6.9 All set values reading mode
Reads all set values of the connected controllers. Press the key for approx. 3 seconds while holding down the and keys in the PV/SV display mode. The unit proceeds to the All set values reading mode. During data logging or setting mode, it is impossible to proceed to this mode.
Display
Name, Function, Setting range
All set values reading
CH MEMO
PV
SV
• All set values of the connected controllers can be read. The unit automatically reverts to the PV/SV display mode after reading all set values.
30
6.10 Operation flowchart
CH MEMO
PV
SV
Power ON Warm-up indication
CH MEMO
PV
SV
PV/SV display mode
key
key (Approx.1sec)
Data logging mode
CF card LOCK switch (logging
indicator) lights/flashes.
+
Main setting mode Sub setting mode
CH MEMO
PV
SV
Set value memory number
CH MEMO
PV
SV
Integral time
CH MEMO
PV
SV
Set value lock
CH MEMO
PV
SV
SV
CH MEMO
PV
SV
Derivative time
CH MEMO
PV
SV
AT/ Auto-reset
CH MEMO
PV
SV
Alarm 1 value
CH MEMO
PV
SV
ARW
Reverts to the PV/SV display
mode or Data logging mode
CH MEMO
PV
SV
OUT1 proportional band
CH MEMO
PV
SV
OUT1 proportional cycle +
Controller setting mode
CH MEMO
PV
SV
OUT2 proportional band
CH MEMO
PV
SV
OUT2 proportional cycle
CH MEMO
PV
SV
Controller model
CH MEMO
PV
SV
Manual reset
CH MEMO
PV
SV
Number of controllers
Reverts to the PV/
SV display
mode or Data logging mode
Reverts to the PV/SV display
mode or Data logging mode
Setting items with dotted lines are optional, and they appear only when the options are added.
Key operations
• To set values, use the or key. To register the value, press the key.
: This means that if the key is pressed, the unit proceeds to the next setting mode.
+ : Press the key while holding down the key.
+ (Approx.3sec) : Press the key for approx. 3sec while holding down the
key.
+ key (Approx.3sec): Press the key for approx. 3sec while holding down the
key.
+ + (Approx.3sec): Press the key for approx. 3sec while holding down the
and keys.
(Approx.3sec)
31
Each setting mode
• During setting mode, logging with the key cannot be started.
However, logging can be stopped by pressing the key for approx. 1sec.
• If the key is pressed for approx. 3sec during setting mode, the unit reverts to the
PV/SV display mode.
• If the key is pressed in the Main setting mode or Sub setting mode, the set value is registered, and the channel number is switched.
• During data logging or setting mode, it is impossible to enter the All set values reading mode
+ key (Approx. 3sec) + +
Logging conditionsettingmode All set values reading mode
CH MEMO
PV
SV
Year
CH MEMO
PV
SV
Logging auto-start
CH MEMO
PV
SV
All set values reading
CH MEMO
PV
SV
Month
CH MEMO
PV
SV
Logging auto-start timer (start)
Automatically reverts to PV/SV display after reading all set values.
CH MEMO
PV
SV
Day
CH MEMO
PV
SV
Logging auto-start timer (end)
CH MEMO
PV
SV
Hour
CH MEMO
PV
SV
Logging cycle
CH MEMO
PV
SV
Minute
CH MEMO
PV
SV
CF card used memory indication
CH MEMO
PV
SV
PV logging
CH MEMO
PV
SV
CF card format
CH MEMO
PV
SV
SV logging
CH MEMO
PV
SV
CF card format con­firmation (*)
(*) Indicated when “Format”
is selected during CF card format selection mode.
CH MEMO
PV
SV
OUT1 MV logging
CH MEMO
PV
SV
External
operation input (LOG) priority
CH MEMO
PV
SV
OUT2 MV logging
CH MEMO
PV
SV
Instrument number
CH MEMO
PV
SV
Status logging
CH MEMO
PV
SV
Communication
speed
Reverts to the PV/SV display
mode or Data logging mode
(Approx.3sec)
32
7. Operation
[Before running]
Before running the instrument, check the mounting and wiring carefully, referring to “4. Mounting to the control panel” (p.12) and “5. Wiring” (p.14). Check whether settings are applicable for the users’ conditions, referring to “6 Settings” (p.19).
7.1 Running the LMD-100
(1) Turn the power supply to the LMD-100 and connected controllers ON.
Turn the power supply to the LMD-100 and connected controllers ON. For 5 seconds after the power is turned on, the PV display indicates [ ].
After that, the LMD-100 reads PV, SV and alarm status of the connected controllers. If automatic switching is selected, the channel number is automatically switched every 2 seconds, indicating PV, SV and alarm status.
(2) Input set values of the LMD-100.
Input each set value of the LMD-100, referring to “6. Settings” (p.19).
(3) Turn the load circuit power of the connected controllers ON.
Turn the load circuit power of the connected controllers ON. Control action starts so as to keep the control target at the SV.
7.2 Preparation for data logging
7.2.1 CF cards
Notice
For data logging, please use the recommended CF card. When any other CF cards (commercially available) are used, turn the power off after data logging has stopped. If power is turned off without data logging being stopped, the data might be lost or the CF card may not be able to be used.
Recommended CF cards: CF card included and also sold separately by Shinko Technos
Co., Ltd. Type I (Thickness 3.3mm), Maximum capacity 2GB
Format : FAT16 Writing method : Writing in a new file (Opens a new file every time logging
starts, and saves data in it.)
CF card memory usage: In the case of 2 controller units being connected, and when
logging all items with a logging cycle of 5 seconds, 1.7 to 2.0MB
of the CF card can be used every 24 hours.
7.2.2 Data reliability when power failure occurs during data logging
The set data of the LMD-100 is backed up in the non-volatile IC memory. The time it takes between detecting power failure and turning the power to the LMD-100 OFF is approx. 260ms for 85V AC and 4 seconds for 264V AC. For the recommended CF card, writing time is 200ms and closing process time is 40ms. Thus total time is 240ms. Writing and closing of the CF card can be finished within
Shinko instruments’ power failure process time. Therefore data reliability can be maintained. If any other CF cards (commercially available) are used, the data reliability is not guaranteed.
33
7.3 CF card insertion
(1) Insert the CF card with the rim toward you. See (Fig. 7.3-1).
The groove width of the top and bottom of the card differ so that the CF card will be inserted correctly. However, do not insert the card forcibly in the wrong direction. After insertion, the card should protrude approx. 5mm from the front of the instrument with the CF card ejection button also protruding. See (Fig. 7.3-2).
(2) Shift the LOCK switch to LOCK position. See (Fig. 7.3-2).
(Fig. 7.3-1) (Fig. 7.3-2)
7.4 CF card ejection
Caution
• Make sure not to press the card ejection button too hard, as this may cause the CF card to fall to the ground.
• Be sure to pull the CF card out by pressing the CF card ejection button.
• If a defective CF card is inserted, the reset function to prevent malfunction is initiated,
and the instrument reverts to the warm-up status.
(1) Shift the LOCK switch to UNLOCK. See (Fig. 7.4-1). (2) To eject the CF card, press the CF card ejection button. See (Fig. 7.4-1).
CF card ejection button
(Fig. 7.4-1)
Shift the LOCK switch to LOCK position.
Shift the LOCK switch to UNLOCK position.
CF card ejection button
Approx. 5mm
Rim toward you
Grooved edge
34
7.5 How to start data logging
7.5.1 Data logging start
There are 2 ways to start data logging. One is with the key, and the other is using the external operation input.
Data logging start with the key
Press the key. Data logging starts under conditions which have been set during Data logging condition setting mode. The LOG indicator is lit during data logging, and flashes while writing to the CF card.
Data logging start using the external operation input
Connect External operation input LOG terminals 19 and 20 (Contact from Open to Closed). Data logging starts under conditions which have been set during Data logging condition setting mode. The LOG indicator is lit during data logging, and flashes while writing to the CF card.
7.5.2 Logging auto-start function
If “Effective” is selected during “Logging auto-start selection” in Data logging condition setting mode (p.23), Logging auto-start function will initiate after power-on. Logging automatically starts between Auto-start start and end time.
If Logging auto-start start and end time are the same, logging continues until power-off or until CF card capacity is exceeded. After power is restored, Auto-start function is enabled if logging is within the selected time between Auto-start start and end time, and logging is performed. During logging, usual Logging start/stop can be performed. During logging, if external operation input LOG terminals 19 and 20 are connected (Contact from Open to Closed), logging will continue even if the logging end time has expired. Even within the data logging time, logging stops by disconnecting LOG terminals 19 and 20 (Contact from Closed to Open).
7.5.3 CF card file
Every time the LMD-100 starts data logging, LMD-100 writes the data in a new file. When logging data reaches 65,000 lines, the file is closed and a new file is opened for data writing, considering editing on spreadsheet applications. The file is named as shown below.
yymmdd_hhmmss.CSV yy : Lower 2 digits of the year (2006: 06)
mm : Month (January: 01) dd : Day (the 1st : 01) hh : Hour (8 a.m.: 08, 8 p.m.: 20) mm : Minute ss : Second
For example, if data logging is started at 8:30 a.m. on January 1st, 2006, the file will be named as “060101_083000.CSV”.
35
7.5.4 File limits
A maximum of 170 files can be saved in the CF card. If the number of files exceeds 170, an error message (Excess CF card memory capacity) appears on the PV display regardless of the remaining memory capacity in the CF card.
7.5.5 Data logging cycle
If logging time of data (depending on number of connected units, and Data logging items) exceeds the logging cycle, previous data will be saved. (e.g.) If the following are selected:
Number of connected units: 8 Data logging items: 5 (PV, SV, OUT1 MV, OUT2 MV, controller status)
Data logging cycle: 1sec Controller response time: Approx. 50ms per item 50ms x 5 (items)=250ms 250ms x 8 (units)= Approx. 2000ms If writing time to CF card is 500ms: Thus total response time: 2000ms+500ms=2500ms (2.5sec) As Data logging cycle is 1sec, the previous data will be saved 2 or 3 times.
7.5.6 Power failure during data logging
If power failure occurs during data logging, data is automatically saved in the file. After the power is restored, data logging is stopped. However, if external operation input LOG terminals 19 and 20 are connected (Contact Closed), data logging automatically resumes, and writes the data in a new file. If momentary power failure occurs while writing to the CF card, one batch of logging data might be lost.
7.6 How to stop data logging
7.6.1 Data logging stop
There are 2 ways to stop data logging. One is with the key, and the other is using the external operation input.
To stop logging with the key
Press the key for approx. 1 second. The LOG indicator goes off, and logging stops.
To stop logging using the external operation input
Disconnect LOG terminals 19 and 20 (Contact from Closed to Open).
The LOG indicator goes off, and logging stops.
7.6.2 External operation priority
If “External operation input (LOG) has priority” is selected from “External operation priority selection” in the Data logging condition setting mode, and when LOG terminals 19 and 20 are connected (Contact Closed), data logging cannot be stopped by the
key.
However, if LOG terminals 19 and 20 are disconnected (Contact Open), logging by the
key can be started or stopped.
36
7.7 How to edit CF card data on the personal computer
To edit the CF card data on the PC, the CF card Reader/Writer is required. (1) Insert the CF card into the CF card Reader/Writer. (2) Select the data in the CF card.
The following shows an example using Windows XP. Select the “Removable Disk” and double-click on the data in the CF card. (Fig. 7.7-1) Microsoft EXCEL will start, and the file will be opened.
(Fig. 7.7-1)
(3) Edit data in the CF card.
The logged data can be edited. See (Fig. 7.7-2).
(Fig. 7.7-2)
37
7.8 How to format the CF card
Caution
• Please format the CF card on the LMD-100.
• When formatting on the Windows, use the FAT16.
Clears all data in the CF card, and formats the card on the LMD-100. The card can also be formatted on Microsoft Windows using commercially available CF card Reader/Writer. Formatting the CF card is effective only when the CF card is inserted.
The procedures for CF card formatting are shown below. (1) Enter the Data logging condition setting mode.
Press the key for approx. 3 seconds while holding down the key. The unit enters Data logging condition setting mode.
(2) Proceed to the CF card format selection mode.
Press the key several times until CF card format mode [ ] appears.
(3) Select “ Format” in the CF card format selection mode.
By pressing the key, select “ Format” in the CF card format selection mode, then press the key. The unit proceeds to the CF card format confirmation mode.
(4) Perform formatting the CF card.
Press the key after confirming that “ Format” has been selected. The unit proceeds to External operation input (LOG) priority [ ] mode, and the formatting is completed.
7.9 How to lock front key using external contact
Front key LOCK/UNLOCK can be set, using external contact. Circuit current when contact is closed: 6mA
KEY LOCK terminals 18 and 20 are disconnected (Contact from Closed to Open): Front key
“UNLOCK”
KEY LOCK terminals 18 and 20 are connected (Contact from Open to Closed): Front key
“LOCK”
If front key “LOCK” is selected, keys (except DISP and CH keys) cannot be operated. If front key “LOCK” is selected during setting mode, keys can be operated until the setting mode ends.
38
7.10 Set value memory function
Up to 6 groups of SV for the connected controllers can be saved. If the key is pressed after selecting Set value memory number in Main setting mode, SVs in the selected memory number are sent to the connected controllers. (See p.38 for registering Set value memory number.) [When a lot of controllers are connected, operations at the next setting mode (SV setting) cannot be performed until all connected controllers SV changes are completed.]
If set values are changed from the controller side
If set values are changed from the controller side, the LMD-100 reads and saves the sending items the LMD-100 already has: Sending items of the LMD-100: SV, Alarm 1 value, OUT1 proportional band, OUT2
proportional band, Integral time, Derivative time, ARW, OUT1 proportional cycle, OUT2 proportional cycle,
Manual reset, Set value lock, AT/Auto-reset However, even if SV is changed from the controller side, the SV of the Set value memory number cannot be changed. To change SV of the Set value memory number, set it in the “SV setting” mode.
How to register the Set value memory number
(e.g.) When 5 units of controller are connected, 30 types of SV can be registered as follows.
Set value memory No.
Channel No.
1 2 3 4 5 6
1 100 200 150 125 140 230 2 110 210 170 135 150 230 3 120 220 190 120 150 220 4 130 230 210 120 160 220 5 140 240 230 100 160 210
When registering SV in Set value memory number 3
(1) Enter the Main setting mode.
Press the key in the PV/SV display mode or Data logging mode. Set value memory number selection mode in the Main setting mode appears.
(2) Select the Set value memory number.
Select Set value memory number “3” with the or key, and press the key. The unit will proceed to the SV setting mode.
(3) Register the SV.
Set SV with the or key, then press the key. SV will be registered and the channel will be switched. Set SV for other channels in the same way as the above.
(4) Revert to the PV/SV display mode or Data logging mode.
Press the key for 10 times or hold down the key for approx. 3 seconds. The unit will revert to the PV/SV display mode or Data logging mode. To set other Set value memory numbers, follow steps (1) to (4) above.
39
7.11 Setting the same value to all controllers simultaneously (Broadcast setting function)
Press the CH key for approx. 1 second in the Main setting mode or Sub setting mode. The unit enters Broadcast setting status, indicating on the CH display. Set items, then press the key. The same set value will be set to all connected controllers simultaneously. If SV is changed, the SV in the Set value memory number will also be changed. If the controllers connected to the LMD-100 are not under the same condition, broadcast setting is not always possible. To release Broadcast setting function, press the key for approx. 1 second again.
7.12 PV, SV 5-digit indication
When PV or SV is 5-digit number, the indication will be as follows.
• (e.g.) 10000 : [ ] and [ ] are alternately indicated.
• (e.g.) –2000 : [ ] and [ ] are alternately indicated.
• (e.g.) –10000 : [ ] and [ ] are alternately indicated.
40
8. Other functions
8.1 Power failure countermeasure
The set data is backed up in the non-volatile IC memory. If power failure occurs during data logging, the data is automatically saved in the file. After the power is restored, the data logging stops. However, if external operation input LOG terminals 19 and 20 are connected (Contact Closed), data logging is automatically starts after the power is restored and the data is written in a new file. If momentary power failure occurs while logging data, one batch of logging data might be lost.
8.2 Self-diagnosis
The CPU is monitored by a watchdog timer, and when an abnormal status is found on the CPU, all outputs are turned off and the LMD-100 is switched to warm-up status.
8.3 Error indication while accessing the CF card
PV display Error contents
Format error (CF card is not inserted)
Format error (CF card cannot be formatted. CF card is defective)
Error when writing to CF card (Unformatted CF card. CF card format does not coincide with the LMD format.)
Error when writing to CF card (CF card is not inserted. Excess CF card memory capacity)
Undefined error
Error when reading from CF card (CF card is not inserted)
Error when reading from CF card (Non-existent file number or data number)
When errors occurred, data logging is stopped, and the error indication remains until it is released by the key. The error indication cannot be released with Logging Start/Stop by external operation input.
8.4 Time error indication
PV display Error contents
Clock lithium battery voltage for backup in a power failure is low.
Logging when current date or time has not been set (Data logging cannot be started until date and time is set)
When errors occurred, its indication can be released by the key.
8.5 Error indication during data logging
PV display Error contents
When errors occur during data logging
When errors occurred, it is required to repair the LMD-100, controllers or communication line since it may break. To release errors, turn the power on again, or press the key.
41
8.6 CF card remaining memory indication
SV display Error contents
When remaining memory of the CF card is 5% or less SV and are indicated alternately.
This indication can be released by stopping data logging or by using another card which has sufficient memory.
8.7 Data logging forced stop
SV display Error contents
Indicates if CF card used memory reaches 98%.
If CF card used memory reaches 98%, is indicated, and data logging is forced to stop.
8.8 Momentary power failure indication
If momentary power failure occurs, the CH display flashes. This can be released by the key.
8.9 Error indication during setting mode
PV display Error contents
Setting error during the setting mode
When changing settings from the LMD-100
If settings are changed from the LMD-100, and if the controllers are in setting mode, the PV display of the LMD-100 indicates as above for approx 2 seconds, and the LMD-100 reverts to the PV/SV display mode without updating set values. At this time, the LMD-100 reads all set values of the controllers, sets them on the LMD-100 to make values even.
When changing settings from the controller
If settings are changed from the controller, and if the LMD-100 is in setting mode, the PV display of the LMD-100 indicates as above, and the LMD-100 reverts to the PV/SV display mode after updating set values. At this time, the LMD-100 reads all set values of the controllers, sets them on the LMD-100 to make values even. If the controller is in setting mode even after all values are read, the LMD-100 reads the changed values. If the controller completes the setting mode, the LMD-100 releases the error indication.
42
9. Specifications
9.1 Standard specifications
Model : Console/Data logger Name : LMD-100 Mounting : Flush Setting : Input system using membrane sheet key Display (CH1, CH2)
PV display : Red LED 4 digits, Character size, 14.3 (H) x 8.0 (W)mm SV display : Green LED 4 digits, Character size, 10.0 (H) x 5.6 (W)mm CH display : Yellow LED 2 digits, Character size, 10.0 (H) x 5.6 (W)mm MEMO display : Yellow LED 1 digit, Character size, 10.0 (H) x 5.6 (W)mm
Time setting accuracy: Within 0.5% 1 second Clock
Time indication : 24-hour clock (00:00 to 24:00) Error : Within 60 seconds/month (at 25 ambient temperature) Power failure guarantee: Backed up by lithium battery.
Lithium battery life: 10 years or more (at 20 ambient
temperature)
External memory device
Media : Recommended CF cards: CF card included and also sold separately
by Shinko Techos Co., Ltd. Type I (thickness 3.3mm)
Maximum capacity: 2GB Format : FAT16 (For commercially available CF card, it may be FAT32) Writing method : Writing in a new file (Opens a new file every time logging starts,
and saves in it)
CF card memory usage: In the case of 2 controller units being connected, and
when logging all items with a logging cycle of 5 seconds, 1.7 to
2.0MB of the CF card can be used every 24 hours.
Others : If logging data reaches 65,000 lines, the file is closed and saves
the data in a new file.
Note : If a defective CF card is inserted, the reset function to prevent
malfunction is initiated, and the instrument reverts to warm-up status. Number of files: Max. 170 If the number of files exceeds 170, an error message is indicated regardless of CF card remaining memory capacity.
43
Console, logging function
Console : Set values can be read and set to the controllers by connecting a
maximum of 16 units of controllers in Serial communication (RS-485). The number indicated on the CH display is an instrument number set to the controllers connected. The instrument number is set from 1 (one) in numerical order. If an error occurs during communication with the controller, the PV display indicates the error message ( ) and the “CNTL COM ERR” (Controller communication error) indicator lights if the error occurred channel is indicated. The error message ( ) is maintained even if communication is recovered until it is released by pressing the (Mode) key. If the error message is released, all set values are read.
Logging : The LMD-100 constantly reads data from the connected controller,
and writes it on the CF card every logging cycle. If the LMD-100 cannot save data due to communication failure, there will be no data on the CF card. If logging time of data (depending on number of connected units, and data logging items) exceeds the logging cycle, the previous data will be saved.
Controller : Controller models are classified as shown below. (Default: DCL-33A)
0: DCL-33A 1: JCS-33A, JCR-33A, JCD-33A, JCM-33A 2: NCL-13A 3: JCL-33A 4: ACS-13A
Logging cycle : 1sec, 2sec, 5sec, 10sec, 15sec, 20sec, 30sec, 1min, 2min, 5min,
10min, 20min, 30min, 60min (Default: 10sec)
Logging item : Selects “Effective” or “Not effective” for PV, SV, OUT1 MV,
OUT2 MV and controller status (Default: PV: “Effective”, Others: “Not effective”)
Serial communication (Between LMD-100 and Controller)
Communication line : EIA RS-485 Communication method : Half-duplex communication Synchronization method: Start-stop synchronization Communication speed : 19200bps Communication protocol: Shinko protocol Data format Start bit: 1
Data bit: 7 Parity : Even parity Stop bit: 1
Sending data : SV, Alarm 1 value, OUT1 proportional band, OUT2
proportional band, Integral time, Derivative time, ARW, OUT1 proportional cycle, OUT2 proportional cycle, Manual reset, Set value lock, AT/Auto-reset
Receiving data : Receives the following data including the sending data.
PV, OUT1 MV, OUT2 MV, controller status
44
Terminals Closed
Logging Start
Power ON
Power OFF
Power OFF
Logging Stop
LOG key
Terminals Open
LOG key(Approx.1 sec)
External operation input (edge action)
Logging Start/Stop using External contact:
Logging Start/Stop can be switched using External contact.
LOG terminals 19 and 20 are disconnected (Contact from Closed to Open): Logging Stop LOG terminals 19 and 20 are connected (Contact from Open to Closed): Logging Start Circuit current when closed: 6mA
If power failure occurs during logging, logging stops when power is restored. If power failure occurs while the External contact is closed, logging automatically starts and the data is saved in a new file. If priority is given to the external operation, logging cannot be stopped by front key operation while external contact is closed. However, while external contact is open, logging Start/Stop by front key is possible.
Front key Lock/Unlock using External contact
Front key LOCK/UNLOCK can be set using external contact.
KEY LOCK terminals 18 and 20 are disconnected (Contact from Closed to Open): Front key
“UNLOCK”
KEY LOCK terminals18 and 20 are connected (Contact from Open to Closed): Front key
“LOCK”
Circuit current when contact is closed: 6mA
If front key “LOCK” is selected, keys which are related to the setting mode cannot be operated (The DISP key and CH key are operable). If front key “LOCK” is selected during setting mode, keys can be operated until the setting mode ends.
ERR (error) output
If errors occur during data logging, if the CF card is defective, when the LMD-100 battery runs down, or if the key is pressed without setting time, ERR output is turned ON. Action: ON/OFF action Output: Relay contact, 1a
Control capacity, 3A 250V AC (resistive load) Electric life: 100,000 cycles
45
Logging auto-start function
If Logging auto-start “Effective” is selected during Logging auto-start selection (p.23), auto-start start and end time can be set, and logging automatically performs within the selected time after power-on. If logging auto-start start and end time are the same, logging continues until power-off or until CF card capacity is exceeded. After power is restored, Auto-start function is enabled if logging is within the selected time between Auto-start start and end time, and logging is performed. During logging, usual Logging start/stop can be performed. During logging, if external operation input LOG terminals 19 and 20 are connected (Contact from Open to Closed), logging will continue even if the logging end time has expired. Even within the data logging time, logging stops by disconnecting LOG terminals 19 and 20 (Contact from Closed to Open).
Set value memory function
Up to 6 groups of SV for the connected controllers can be saved. If the key is pressed after selecting Set value memory number in Main setting mode, SVs in the selected memory number are sent to the connected controllers. [When a lot of controllers are connected, operations at the next setting mode (SV setting) cannot be performed until all connected controllers SV changes are completed.] If set values are changed from the controller side, the LMD-100 reads and saves the sending items the LMD-100 already has: Sending items of the LMD-100: SV, Alarm 1 value, OUT1 proportional band, OUT2
proportional band, Integral time, Derivative time, ARW, OUT1 proportional cycle, OUT2 proportional cycle,
Manual reset, Set value lock, AT/Auto-reset However, even if SV is changed from the controller side, the SV of the Set value memory number cannot be changed. To change SV of the Set value memory number, set it in the “SV setting” mode.
Broadcast setting function
Press the CH key for approx. 1 second in the Main setting mode or Sub setting mode. The unit enters Broadcast setting status, indicating on the CH display. Set items, then press the key. The same set value will be set to all connected controllers simultaneously. If SV is changed, the SV in the Set value memory number will also be changed. If the controllers connected to the LMD-100 are not under the same condition, broadcast setting is not always possible. To release Broadcast setting function, press the key for approx. 1 second again.
CF card LOCK switch
This switch prevents the CF card being taken out during data logging. By setting the LOCK switch to LOCK position, data logging can be performed. By setting the LOCK switch to UNLOCK position, data logging cannot be performed. If the LOCK switch is set to UNLOCK during logging, logging stops immediately.
This switch also functions as a Logging indicator. The red LED lights during logging,
and flashes while accessing the CF card.
46
5-digit indication function
When PV or SV is 5-digit number, the indication will be as follows.
• (e.g.) 10000 : [ ] and [ ] are alternately indicated.
• (e.g.) –2000 : [ ] and [ ] are alternately indicated.
• (e.g.) –10000 : [ ] and [ ] are alternately indicated.
Supply voltage : 100 to 240V AC 50/60Hz Allowable voltage fluctuation: 85 to 264V AC
Ambient temperature : 0 to 50 (32 to 122 )
Ambient humidity : 35 to 85%RH (non-condensing) Power consumption : Approx. 6VA Weight : Approx. 400g External dimensions : 96 x 96 x 100mm (W x H x D)
With waterproof cover, 115.6 x 131.7 x 100mm (W x H x D)
Material : Case, Flame-resistant resin Color : Case, Light gray
Circuit insulation configuration
Insulation resistance
10M or more, at 500V DC
Dielectric strength
Between power terminal and communication terminal: 1.5kV AC for 1 minute Between power terminal and output terminal : 1.5kV AC for 1 minute Between communication terminal and output terminal: 1.5kV AC for 1 minute
Attached functions : Power failure countermeasure
Self-diagnosis Warm-up indication Error indications Momentary power failure indication
Accessories included: Mounting brackets: 1 set, Instruction manual: 1 copy
CF card (256MB) : 1 Water-proof cover : 1 piece (When IP option is added) Terminal cover : 2 pieces (When TC option is added)
Accessories sold separately: CF card (256MB)
CPU
ERR output
(to HOST)
(to CNTL)
15
5
4
14
3
9
8
10
1
2
12
13
7
6
18
20
19
17
16
11
CF card
Reader/Writer
Power
supply
Communication
Communication
Insulated
External
operation input
47
9.2 Optional specifications
Communication function (Option code: C5)
Data of the LMD-100 and the connected controllers can be read and set from the external computer or PLC, etc. Cable length : Maximum communication distance 1.2km
Cable resistance: Within 50 (Terminator is not necessary
or 120 or more on one side.) Communication line : EIA RS-485 Communication method : Half-duplex communication Synchronization method : Start-stop synchronization Communication speed : 9600, 19200bps (Selectable by keypad) (Default: 9600bps) Code form : ASCII Error correction : Command request repeat system Error detection : Parity check, Checksum Data format
Communication
protocol
Shinko protocol
Start bit 1 Data bit 7 Parity Even Stop bit 1
Instrument number : 0 to 95
Dust-proof/Drip-proof (Option code: IP)
Dust-proof/Drip-proof specification waterproof cover (IP66)
Terminal cover (Option code: TC)
Electrical shock protection terminal cover
Color Black (Option code: BK) Front panel frame and case: Black
48
10. Troubleshooting
If any malfunctions occur, refer to the following items after checking the power and the wiring.
Warning
Turn the power supply to the instrument off before checking the wiring. Working or touching the terminal with the power switched on may result in severe injury or death due to Electric Shock.
10.1 Indication is abnormal or unstable.
Problem Presumed cause and solution
The PV display indicates the following.
, , , , , ,
Error while accessing the CF card, Time error, Error during data logging, Error while changing set values Refer to “8. Other functions”. (p.40, 41)
The SV display indicates
.
Remaining memory capacity of the CF card is low. Refer to “8. Other functions”. (p.41)
The SV display indicates
.
Data logging is forced to stop.
Refer to “8. Other functions”. (p.41)
The CH display is flashing. Momentary power failure has occurred.
Refer to “8. Other functions”. (p.41)
10.2 Key operation is impossible.
Problem Presumed cause and solution
Keys cannot be operated.
• Check the Set value lock. (p.28)
• Check whether the front keys are locked by external contact. (p.37)
10.3 Data logging is impossible.
Problem Presumed cause and solution
Data logging is impossible.
• Check whether the CF card LOCK switch is set to
LOCK position. (p.33)
• Errors occurred during data logging.
Refer to “8. Other functions”. (p.40, 41)
10.4 Communication failure
Problem Presumed cause and solution
Communication failure
• The connection or wiring of communication cable is not secure. (p.16 to 18)
• Burnout or imperfect contact on the communication
cable and the connector.
• Communication protocol of the controller does not coincide with that of the LMD-100(Shinko protocol).(p.19)
• Communication speed of the controller does not
coincide with that of the LMD-100 (19200bps). (p.19)
• The instrument numbers are duplicated in multiple
controllers. (p.19) There are setting items which are impossible to communicate.
Check the controller model. (p.21) Check the number of connected controllers. (p.21)
For further inquiries, please consult our agency or the shop where you purchased the unit.
49
11. Character table
Photocopiable material
[Main setting mode]
Display Setting item Default value Data
CH MEMO
PV
SV
Set value memory number 1
CH MEMO
PV
SV
SV
CH MEMO
PV
SV
Alarm 1 value
CH MEMO
PV
SV
OUT1 proportional band
CH MEMO
PV
SV
OUT2 proportional band
CH MEMO
PV
SV
Integral time
CH MEMO
PV
SV
Derivative time
CH MEMO
PV
SV
ARW
CH MEMO
PV
SV
OUT1 proportional cycle
CH MEMO
PV
SV
OUT2 proportional cycle
CH MEMO
PV
SV
Manual reset
[Sub setting mode]
Display Setting item Data
CH MEMO
PV
SV
Set value lock
CH MEMO
PV
SV
AT/Auto-reset
50
[Controller setting mode]
Display Setting item Default value Data
CH MEMO
PV
SV
Controller model DCL-33A
CH MEMO
PV
SV
Number of controllers 1
[Data logging condition setting mode]
Display Setting item Default value Data
CH MEMO
PV
SV
Year 0 (2000)
CH MEMO
PV
SV
Month 1 (January)
CH MEMO
PV
SV
Day 1 (1st)
CH MEMO
PV
SV
Hour 0 hours
CH MEMO
PV
SV
Minute 0 minutes
CH MEMO
PV
SV
PV logging Effective
CH MEMO
PV
SV
SV logging Not effective
CH MEMO
PV
SV
OUT1 MV logging Not effective
CH MEMO
PV
SV
OUT2 MV logging Not effective
CH MEMO
PV
SV
Status logging Not effective
CH MEMO
PV
SV
Logging auto-start Not effective
CH MEMO
PV
SV
Logging auto-start timer (start) 00:00
51
Display Setting item Default value Data
CH MEMO
PV
SV
Logging auto-start timer (end) 00:00
CH MEMO
PV
SV
Logging cycle 10 seconds
CH MEMO
PV
SV
CF card used memory indication
CH MEMO
PV
SV
CF card format No format
CH MEMO
PV
SV
CF card format confirmation No format
CH MEMO
PV
SV
External operation input (LOG) priority
External operation input (LOG) has priority
CH MEMO
PV
SV
Instrument number 0
CH MEMO
PV
SV
Communication speed 9600bps
[All set values reading mode]
Display Setting item Default value Data
CH MEMO
PV
SV
All set values reading
***** Inquiry *****
For any inquiries about this unit, please contact the shop where you purchased the unit after checking the following.
[Example]
• Model --------------------------- LMD-100
• Option --------------------------- IP
• Serial number ----------------- No. xxxxxx
In addition to the above, please let us know the details of the malfunction, if any, and the operating conditions.
LMD11E4 2009.06
SHINKO TECHNOS CO.,LTD.
OVERSEAS DIVISION
: : :
Reg. Office URL E-mail
2-5-1, Senbahigashi, Minoo, Osaka, Japan
http://www.shinko-technos.co.jp
overseas@shinko-technos.co.jp
Tel : Fax:
81-72-727-6100 81-72-727-7006
Loading...