Shinko JCD-33A-R/M Instruction Manual

1
INSTRUCTION MANUAL
DIGITAL INDICATING LIMIT CONTROLLER JCD-33A-R/M T5909-1
JCD33T5909-1E1 2006.12
To prevent accidents arising from the misuse of this controller, plea se en sure the operator receives this manual.
Safety precautions (Be sure to read these precautions before using our products.)
Caution may be linked to serious results, so be sure to follow the directions for
usage.
Warning
Warning
• To prevent an electric shock or fire, only our or other qualified service personnel may handle the inner assembly.
• To prevent an electric shock, fire or damage to the instrument, parts replacement may only be undertaken
by our or other qualified service personnel.
Safety precautions
To ensure safe and correct use, thoroughly read and understand this manual before using this instrument.
• This instrument is intended to be used for industrial machinery, machine tools and measuring equipment. Verify
correct usage after consulting purpose of use with our agency or main office. (Never use this instrument for medical purposes with which human lives are involved.)
• External protection devices such as protection equipment against excessive temperature rise, etc. must be
installed, as malfunction of this product could result in serious damage to the system or injury to personnel. Also proper periodic maintenance is required.
• This instrument must be used under the conditions and environment described in this manual. We do not accept
liability for any injury, loss of life or damage occurring due to the instrument being used under conditions not otherwise stated in this manual.
Caution with respect to Export Trade Control Ordinance
To avoid this instrument from being used as a component in, or as being utilized in the manufa cture of weap ons of mass destruction (i.e. military applications, military equipment, etc.), please investigate the end users and the final use of this instrument. In th e case of re sale, en sure that this instrument is no t illegally exported.
Caution
• This instrument should be used according to the specifications described in the manual. If it is not used according to the specifications, it may malfunction or cause a fire.
• Be sure to follow the warnings, cautions and notices. Not doing so could cause seriou s injury or malfunction.
• Specifications of the JCD-33A and the conten ts of this instruction manual are subject to change withou t notice .
• Measures must be taken to ensure that the operator cannot touch power terminals or other high voltage
sections.
• Be sure to turn the power supply to the instrument OFF before cleaning this instrument.
• Use a soft, dry cloth when cleaning the instrument.
(Alcohol based substances may tarnish or deface the unit.)
• As the display section is vulnerable, do not strike or scratch it with a hard object.
• Any unauthorized transfer or copying of this document, in part or in whole, is prohibited.
Shinko Technos CO., LTD. is not liable for any damages or secondary damages incurred as a result of using
this product, including any indirect damages.
Caution
Procedures which may lead to dangerous conditions and cause death or serious injury, if not carried out properly.
Procedures which may lead to dangerous conditions and cause superficial to medium injury or physical damage or may degrade or damage the product, if not carried out properly .
2
1. Model
1.1 Model
JCD–33 A – R / M T5909-1 , W96 x H96 x D100mm A1 A A1 output (Alarm type can be selected by keypad) *1 OUT1 R Limit control output (Relay contact: 1a) Input M Multi-range *2 Control action T5909-1 High limit or low limit control action
100 to 240V AC (standard)
Supply voltage
1 24V AC/DC *3
A2 A2 output (Alarm type can be selected by keypad) *1 C5 Serial communication (RS-485) TC Terminal cover
Option
BK Color: Black *1: Alarm actions (9 types and No alarm action) and Energized/Deenergized can be sele cted by keyp a d. *2: Thermocouple, RTD, DC current and DC voltage can be selected by keypad.
*3: Supply voltage 100 to 240V AC is standard. When ordering 24V AC/DC , enter “1” af ter the input code.
+
1.2 How to read the model label
Model labels are attached to the case and the inner assembly. (1) Model (2) Option, supply voltage
(“1” is entered only for 24V AC/DC)
(3) Serial number (Only on inner assembly)
2. Name and functions of the sections
(Fig. 2-1)
(1) PV display
Indicates the PV (process variable) with a red LED. Indicates setting item characters during the setting mode.
(2) SV display
Indicates the SV (desired value) with a green LED. Indicates set (selected) value during the setting mode.
(3) RST (RESET) indicator
Lights when OUT1 NO contact (terminals between 5 and 6) is OFF with a green LED.
(4) EXCD (EXCEEDED) indicator
High limit action: The yellow LED lights when PV SV. Low limit action: The yellow LED lights when PV SV.
(1)
(2) (3)
(4)
(5) (6)
(8)
(7)
(9)
(10) (11)
(12)
Relay contact output/Multi-range input
(1) (2)
(Model label)
(e.g.)
(3)
JCD-33A-R/M T5909-1
No. 06KF05000
A2 outputA2
MULTI RANGE
1
3
(5) AUTO indicator
The yellow LED lights for Auto limit control action.
(6) TX/RX indicator
The yellow LED lights during Serial communication TX output (sending) (C5 option).
(7) A1 indicator
When Alarm 1 output is ON, the red LED lights.
(8) A2 indicator
When Alarm 2 output is ON, the red LED lights.
(9) Increase key (
)
Increases the numerical value, switches the setting item during the setting mode.
(10) Decrease key (
)
Decreases the numerical value, switches the setting item during the setting mode.
(11) Mode key (
)
Switches setting mode, and registers the set (selected) value.
(12) RESET key (
RESET
)
Resets OUT1 (limit control output).
Notice
When setting the specifications and functions of this controller, connect terminals 2 and 3 for power source first, then set them referring to Chapter “5. Settings” before performing “3. Mounting to the control panel” and “4. Wiring”.
3. Mounting to the control panel
3.1 Site selection
Caution
• Use within the following temperature and humidity ranges. Temperature: 0 to 50 (32 to 122 ), Humidity: 35 to 85%RH (No condensation, no icing)
• When this unit is installed through the control panel, the ambient temperature of this unit must be kept to under 50
. Otherwise the life of electronic components (especially electrolytic capacitors) will be
shortened.
This instrument is intended to be used under the following environmental conditions (IEC61010-1): Overvoltage category
, Pollution degree 2
Ensure the mounting location corresponds to the following conditions:
A minimum of dust, and an absence of corrosive gases
No flammable, explosive gases
Few mechanical vibrations or shocks
No exposure to direct sunlight, an ambient temperature of 0 to 50 (32 to 122 )
that does not change rapidly
An ambient non-condensing humidity of 35 to 85%RH
• No large capacity electromagnetic switches or cables through which large current flows
No water, oil or chemicals or where the vapors of these substances can come into direct contact with the controller
4
3.2 External dimensions (Scale: mm)
(Fig. 3.2-1)
3.3 Panel cutout (Scale: mm)
Lateral close mounting n: Number of units mounted
Caution: If lateral close mounting is used for the controller, IP66 specification (Dust-proof/Drip-proof) may be compromised, and all warranties will be invalidated.
(Fig. 3.3-1)
Caution
As the case is made of resin, do not use excessive force while screwing in the mounting bracket, or the case or screw type mounting bracket could be damaged. The torque is approximately 0.12N•m.
3.4 Mounting
Mount the controller vertically to ensure it adheres to the Dust-proof/Drip-proof specification (IP66).
Mountable panel thickness: 1 to 15mm (1) Insert the controller from the front side of the panel. (Fig.3.4-1) (2) Attach the mounting brackets by the holes at the top and bottom of the case and secure the controller
in place with the screws. (Fig.3.4-2)
Gasket A
Screw type mounting bracket
Terminal cover (TC option)
96
91
106.2
11.5
98.5
104.5 (for TC option)
92
+ 0.8
0
130
92
+0.8
0
n x96-3
0.5
0
(Fig.3.4-1)
(Fig.3.4-2)
5
3.2mm
5.8mm or less
3.2mm
5.8mm or less
4. Wiring
Warning
Turn the power supply to the instrument off before wiring or checking. Working or touching the terminal with the power switched on may result in severe injury or death due to Electric Shock.
OUT1 : Limit control output
• A1 : Alarm 1 (A1) output
• TRANSMIT : Transmission output
• EXT.RESET: External reset input
• RS-485 : Serial communication (C5 option)
DC
: DC current, DC voltage input For DC current input,
c
onnect 50 shunt
resistor between input
terminals.
• TC : Thermocouple input
RTD : Resistance temperature detector input
Notice
• The terminal block of the JCD-33A is designed to be wired from the left side. The lead wire must be inserted from the left side of the te rminal, and fa stened by the terminal screw.
• Use a thermocouple and compensating lead wire that correspond to the sensor input
specification of this controller.
• Use the 3-wire RTD which corresponds to the input specification of this controller.
• This controller does not have built-in power switch, circuit breaker or fuse. Therefore, it is
necessary to install them in the circuit near the external controller. (Recommended fuse: Time-lag fuse, rated voltage 250V AC, rated current 2A)
• For a 24V AC/DC power source, do not confuse polarity when using direct current (DC).
• For the OUT1 (Limit control output terminals 5-6), externally use a relay according to the
capacity of the load to protect the built-in relay contact.
• When wiring, keep input wires (thermocouple, RTD, etc.) away from AC sources or load wires
to avoid external interference.
• Do not apply a commercial power source to the sensor connected to the input terminal nor
allow the power source to come into contact with the sensor.
Lead wire solderless terminal
Use a solderless terminal with an insulation sleeve in which an M3 screw fits as shown below. The torque is approximately 0.6N•m to 1.0N•m.
Solderless
terminal
Manufacturer Model Tightening torque
Nichifu Terminal Industries CO.,LTD.
TMEV1.25Y-3
Y type
Japan Solderless Terminal MFG CO.,LTD.
VD1.25-B3A
0.6N•m
Nichifu Terminal Industries CO.,LTD.
TMEV1.25-3
Max. 1.0N•m
Round type
Japan Solderless Terminal MFG CO.,LTD.
V1.25-3
(Fig. 4-1)
(Fig. 4-2)
6
A2 value
PV SV
Value
• Set the value with the or key.
• Not available if
is selected
during A2 type selection
5. Settings
5.1 Operation flowchart
PV/SV display
[Main setting mode]
POWER ON
Press the key.
A1 value
PV SV
Value
• Set the value with the or key.
• Not available if
is selected
during A1 type selection
SV
PV
SV
SV
• Set the value with the
or key.
Set value lock
PV SV
Selection
• Make a selection with the
or key.
• Be sure to select Lock 3 when using Serial communication.
Reverts to the PV/SV display.
[
Display mode]
Sensor correction
PV SV
Value
• Set the value with the
or key.
Transmission output mode
PV SV
Selection
• Make a selection with the
or key.
Transmission output
high limit
PV SV
Value
• Set the value with the
or key.
(7)
Press the while holding down the key .
Press the for 3sec while holding down the .
[Sub setting mode]
*1
Maximum (or Minimum) value will be indicated if high (or low) limit control action is selected during Limit control action selection in the Setup mode.
( ), Max(Min) *1
PV
(
)
SV
Max value
(Min value)
, EXCD lighting time
PV
SV
EXCD lighting
duration time
Reverts to the PV/SV display.
Communication protocol
PV SV
Selection
• Make a selection with the
or key.
Instrument number
PV SV
Value
• Set the value with the
or key.
Communication speed
PV SV
Selection
• Make a selection with the
or key.
Parity
PV SV
Selection
• Make a selection with the
or key.
Transmission output
low limit
PV SV
Value
• Set the value with the
or key.
Stop bit
PV SV
Selection
• Make a selection with the
or key.
Outline of operation procedure
Set Input type, Alarm (type, value, etc.) and SV (desired value), following the procedures below . Setting item numbers (1) to (7) are indicated on the flowchart.
[Step 1 Operation befo re run] Turn the load circuit power OFF, and turn the power supply to the JCD-33A ON. [Step 2 Auxiliary function
setting mode 2]
Set Input type, Alarm type, etc. in the Setup mode.
(1) Input type: Select an input type. Refer to “Input type (character indication) and range” on page 7. (2) A1 type: Select an alarm type. Refer to “Alarm type” on page 7.
[If an alarm type except for “
” is selected, items (3) to (5) will be indicated and they
can be set if necessary.]
Note: If an alarm type is changed, the alarm set value becomes 0 (0.0). Therefore it is necessary to set it again.
(3) A1 action Energized/Deenergized: Select Alarm 1 action Energized or Deenergized. (4) A1 hysteresis: Set A1 hysteresis. (5) A1 action delayed timer: Set A1 action delayed timer.
(6) SV: Set SV (desired value) in the Main setting mode. [Step 3 Main setting mode] (7) A1 value: Set action point of A1 output in the Main setting mode.
[Step 4 Run] Turn the load circui t pow er ON. Co ntr ol actio n st art s s o as t o kee p the c ontrol t arget at the SV (Des ired v alu e).
(6)
: This means that if the key is pressed,
the set value is saved, and the controller proceeds to the next setting item.
• Setting items with dotted lines are optional and they appear only when the options are added.
• If the
key is pressed for approx. 3sec, the controller reverts to the PV/SV display mode from any mode.
7
Press the
for 3sec while holding down the and .
Scaling low limit
PV
SV
Value
• Set the value with the
or key.
Scaling high limit
PV
SV
Value
• Set the value with the
or key.
Decimal point place
PV
SV
Selection
• Make a selection with the
or key.
• Available for DC current, voltage input
PV filter time constant
PV
SV
Value
• Set the value with the
or key.
[Setup mode]
Auto/Manual limit control
PV SV
Selection
• Make a selection with the or key.
• Default:
EXCD indicator
lighting duration time unit
PV SV
Selection
• Make a selection with the or key.
• Default:
Reverts to the PV/SV display.
A1 type
PV
SV
Selection
• Make a selection with the
or key.
• Default:
A1 hysteresis
PV SV
Value
• Set the value with the
or key.
• Not available if
is selected during A1
type selection
A2 type
PV
SV
Selection
• Make a selection with the
or key.
• Available when A2 option is added.
A1 action
Energized/Deenergized
PV
SV
Selection
• Make a selection with the
or key.
• Not available if
is selected during A1
type selection
A2 action
Energized/Deenergized
PV
SV
Selection
• Make a selection with the
or key.
• Not available if
is selected during A2
type selection
A1 action
delayed timer
PV SV
Value
• Set the value with the
or key.
• Not available if
is selected
during A1 type selection
High/Low limit control
PV SV
Selection
• Make a selection with the or key.
• Default:
A2 action
delayed timer
PV SV
Value
• Set the value with the
or key.
• Not available if
is selected
during A2 type selection
A2 hysteresis
PV SV
Value
• Set the value with the
or key.
• Not available if
is selected during A2
type selection
(2)
Input type (character indication) and range
: K -200 to 1370 : -199.9 to 400.0 : J -200 to 1000 : R 0 to 1760 : S 0 to 1760 : B 0 to 1820 : E -200 to 800 : T -199.9 to 400.0 : N -200 to 1300 : PL- 0 to 1390 : C(W/Re5-26) 0 to 2315
: K -320 to 2500 : -199.9 to 750.0 : J -320 to 1800 : R 0 to 3200 : S 0 to 3200 : B 0 to 3300 : E -320 to 1500 : T -199.9 to 750.0 : N -320 to 2300 : PL- 0 to 2500 : C(W/Re5-26) 0 to 4200
: Pt100 -199.9 to 850.0 : JPt100 -199.9 to 500.0 : Pt100 -200 to 850 : JPt100 -200 to 500
: Pt100 -199.9 to 999.9 : JPt100 -199.9 to 900.0 : Pt100 -300 to 1500 : JPt100 -300 to 900
: 4 to 20mA DC -1999 to 9999 : 0 to 20mA DC -1999 to 9999 : 0 to 1V DC -1999 to 9999 : 0 to 5V DC -1999 to 9999 : 1 to 5V DC -1999 to 9999 : 1 to 10V DC -1999 to 9999
Alarm type
(High limit alarm) : The alarm action is deviation setting from the SV. The alarm is
activated if the PV (process variable) reaches the high limit set value.
(Low limit alarm) : The alarm action is deviation setting from the SV. The alarm is
activated if the PV (process variable) goes under the low limit set value.
(High/Low limits alarm): Combines High limit and Low limit alarm actions. When PV (process variable) reaches high limit set value or goes under the low limit set value, the alarm is activated.
(High/Low limit range alarm): When PV (process variable) is between the high limit set value and low limit set value, the alarm is activated. If PV exceeds the high limit set value or goes under the low limit set value, the alarm output is turned off.
(Process high alarm) Within the scale range of the controller, alarm action points
(Proces s l ow a l a rm ) can be set at random and if the PV (process variable) reaches the randomly set action point, the alarm is activated.
(High limit alarm with standby) When the power to the controller is turned on, even if
(Low li mi t a la r m w it h s t an d by ) the PV (process variable) enters the alarm action range,
(High/L ow l im i t s w it h s t a n db y ) the alarm is not activated. Even if the PV enters the alarm action range due to SV change during running,
the alarm is not activated, either. If the controller is allowed to keep running, once the input exceeds the alarm action point, the standby function will be released.
Input type
PV
SV
Selection
• Make a selection with the
or key.
• Default:
(3)
(5)
(4)
(1)
OUT1 ON/OFF action
hysteresis
PV SV
Value
• Set the value with the
or key.
• Available only for ON/OFF action
8
After the power is turned on, the input characters and temperature unit are indicated on the PV display, and the input range high limit value is indicated on the SV display for approximately 3 seconds. (Table 5-1) (If any other value is set during the scaling high limit setting, the set value is indicated on the SV display) During this time, all outputs and the LED indicators are in OFF status. Control will then start indicating the PV (process variable) on the PV display and SV (desired value) on the SV display.
(Table 5-1)
Input type
PV display SV display PV display SV display
K J
R S B E T N PL­C (W/Re5-26)
Pt100 JPt100
4 to 20mA DC * 0 to 20mA DC * 0 to 1V DC 0 to 5V DC 1 to 5V DC 0 to 10V DC
Scaling high limit value
5.2 Display mode
Selects an item to be indicated on the PV and SV display. Every time the
key is pressed in the PV/SV display mode, the following indications are switched.
When power is turned ON, the PV display indicates PV, and the SV display indicates SV.
Display Name, Function, Setting range
, EXCD duration time
, EXCD indicator lighting duration time indication
• The PV display indicates
, and the SV display indicates “EXCD indicator
lighting duration time”.
• Measurement range: 0:00 to 99:59 (The time unit can be selected during the “EXCD indicator lighting duration time unit selection” in the Setup mode.)
• Reverts to the default value (0:00 Hour:Minute/Minute:Second) if the
RESET
key is
pressed or if the external reset input terminals 15 and 17 are shorted.
(
), Max (Min) value
( ), Max (Min) value indication
• While the EXCD indicator lights, the PV display indicates
or , and the SV display indicates the maximum or minimum value. If High limit control action (or Low limit control action) is selected during “Limit control action selection” in the Setup mode, the maximum value (or minimum value) is Indicated.
• Reverts to the current PV (input value) if the
RESET
key is pressed or if the external
reset input terminals 15 and 17 are shorted.
* Connect 50 shunt
resistor (sold separately) between input terminals.
9
5.3 Main setting mode
Sets SV, A1 and A2 value. In the PV/SV display mode, press the
key while holding down the key to proceed to the Main setting mode. To set values, use the
or key.
To register the value, use the
key.
Character Name, Function, Setting range Default value
SV setting 0
• Sets SV (desired value).
• Setting range: Scaling low limit to Scaling high limit A1 value setting 0
• Sets the action point of Alarm 1 (A1) output.
• Not available if No alarm is selected during A1 type selection.
• Setting range: Refer to (Table 5.3-1). A2 value setting 0
• Sets the action point of Alarm 2 (A2) output.
• Not available if No alarm is selected during A2 type selection.
• Setting range: Refer to (Table 5.3-1).
(Table 5.3-1)
Alarm type
Setting range
High limit alarm – (Input span) to input span ( ) *1 Low limit alarm – (Input span) to input span ( ) *1 High/Low limits alarm 0 to input span ( ) *1 High/Low limit range alarm 0 to input span ( ) *1 Process high alarm Input range low limit value to input range high limit value *2 Process low alarm Input range low limit value to input range high limit value *2 High limit alarm with standby – (Input span) to input span ( ) *1 Low limit alarm with standby – (Input span) to input span ( ) *1 High/Low limits alarm with standby 0 to input span ( ) *1
• When input has a decimal point, the negative low limit value is –199.9, and the positive high limit value is 999.9.
• All alarm actions except process alarm are
deviation setting from the SV (desired value).
*1: For DC input, the input span is the same as the scaling span.
*2: For DC input, input range low (or high) limit value is the same as scaling low (or high) limit value.
5.4 Sub setting mode
Sets Set value lock, Sensor correction, Communication parameters (when C5 option is added), etc. In the PV/SV display mode, press the
key for approx. 3 seconds while holding down the key to proceed to the Sub setting mode. To set values, use the
or key.
To register the value, use the
key.
Character Name, Function, Setting range Default value
Set value lock selection Unlock
• Locks the set values to prevent setting errors. The setting item to be locked depends on the selection.
• Selection range:
(Unlock): All set values can be changed. (Lock 1): None of the set values can be changed. (Lock 2): Only SV (desired value) can be changed. (Lock 3): All set values can be changed.
However, do not change any setting item in the Setup mode. Changed values revert to their previous value after power is turned off because they are not saved in the non-volatile memory.
Sensor correction setting 0.0
• Sets the correction value for the sensor.
(Effective within the input rating value regardless of the sensor correction value)
PV= Current actual temperature + Sensor correction value
• Setting range: –100.0 to 100.0
( )
10
Transmission output mode selection PV transmission
• Selects PV or SV transmission.
• Selection item:
: PV transmission : SV transmission
Transmission output high limit setting 1370
• Sets Transmission output high limit value.
• Setting range: Transmission output low limit value to Input range high limit value
Transmission output low limit setting -200
• Sets Transmission output low limit value.
• Setting range: Input range low limit value to Transmission output high limit value.
Communication protocol selection Shinko protocol
• Selects the communication protocol.
• Available only when the C5 option is applied.
• Selection:
: Shinko protocol : Modbus ASCII mode : Modbus RTU mode
Instrument number setting 0
• Sets the instrument number individually to each instrument when communicating
by connecting plural instruments in serial communication.
• Available only when the C5 option is added.
• Setting range: 0 to 95
Communication speed selection 9600bps
• Selects a communication speed equal to that of the host computer.
• Available only when the C5 option is added.
• Selection:
: 2400bps : 4800bps : 9600bps : 19200bps
Parity selection Even parity
• Selects the parity.
• Not available if the C5 option is not added or if Shinko protocol is selected
during the Communication protocol selection.
• Selection:
: No parity : Even parity : Odd parity
Stop bit selection 1
• Selects the stop bit.
• Not available if the C5 option is not added or if Shinko protocol is selected
during the Communication protocol selection.
• Selection:
: 1 : 2
11
5.5 Setup mode
Sets an input type, A1, A2 type, High/Low limit control action, etc. In the PV/SV display mode, press the
key for approx. 3 seconds while holding down the and
keys to proceed to the Setup mode.
To set values, use the
or key.
To register the value, use the
key.
Character
Name, Function, Setting range
Default value
Input type selection K (–200 to 1370 )
• The input type can be selected from thermocouple (10 types), RTD (2 types), DC
current (2 types) and DC voltage (4 types), and the unit
/ can be selected as well.
• When changing the input from DC voltage to other inputs, remove the sensor
connected to this controller first, then change for the input. If the input is changed with the sensor connected, the input circuit may break.
• Selection range:
: K -200 to 1370 : K -199.9 to 400.0 : J -200 to 1000 : R 0 to 1760 : S 0 to 1760 : B 0 to 1820 : E -200 to 800 : T -199.9 to 400.0 : N -200 to 1300 : PL- 0 to 1390 : C(W/Re5-26) 0 to 2315 : Pt100 -199.9 to 850.0 : JPt100 -199.9 to 500.0 : Pt100 -200 to 850 : JPt100 -200 to 500
: K -320 to 2500 : K -199.9 to 750.0 : J -320 to 1800 : R 0 to 3200 : S 0 to 3200 : B 0 to 3300 : E -320 to 1500 : T -199.9 to 750.0 : N -320 to 2300 : PL- 0 to 2500 : C(W/Re5-26) 0 to 4200 : Pt100 -199.9 to 999.9 : JPt100 -199.9 to 900.0 : Pt100 -300 to 1500 : JPt100 -300 to 900
: 4 to 20mA DC -1999 to 9999
: 0 to 20mA DC -1999 to 9999 : 0 to 1V DC -1999 to 9999 : 0 to 5V DC -1999 to 9999 : 1 to 5V DC -1999 to 9999
: 0 to 10V DC -1999 to 9999
Scaling high limit setting
1370
• Sets scaling high limit value.
• Setting range: Scaling low limit value to input range high limit value
Scaling low limit setting
–200
• Sets scaling low limit value.
• Setting range: Input range low limit value to scaling high limit value
Decimal point place selection
No decimal point
• Selects decimal point place.
• Available only for DC input
• Selection range:
: No decimal point : 1 digit after decimal point : 2 digits after decimal point : 3 digits after decimal point
PV filter time constant setting
0.0 seconds
• Sets PV filter time constant.
(If the value is set too large, it affects control result due to the delay of response)
• Setting range: 0.0 to 10.0 seconds
12
A1 type selection
No alarm action
• Selects an action type for A1.
• Selection range:
: No alarm action
: High limit alarm : Low limit alarm : High/Low limits alarm : High/Low limit range alarm : Process high alarm : Process low alarm : High limit alarm with standby : Low limit alarm with standby : High/Low limits alarm with standby
A2 type selection
No alarm action
• Selects an action type for A2.
• Available only when A2 option is added
• Selection range and default value are the same as those of A1 type selection.
A1 action Energized/Deenergized selection
Energized
• Selects Energized/Deenergized for A1.
• Not available if No alarm action is selected during A1 type selection
• Selection range:
: Energized
: Deenergized
A2 action Energized/Deenergized selection
Energized
• Selects Energized/Deenergized for A2.
• Not available if A2 option is not added or if No alarm action is selected during
A2 type selection
• Selection range and default value are the same as those of A1 action
Energized/Deenergized selection.
A1 hysteresis setting
1.0
• Sets A1 hysteresis.
• Not available if No alarm action is selected during A1 type selection
• Setting range: 0.1 to 100.0
( ), or 1 to 1000
A2 hysteresis setting
1.0
• Sets A2 hysteresis.
• Not available if A2 option is not added or if No alarm action is selected during A2 type
selection
• Setting range: 0.1 to 100.0
( ), or 1 to 1000
A1 action delayed timer setting
0 seconds
• Sets A1 action delayed timer.
When setting time has elapsed after the input enters the alarm output range, the alarm
is activated.
• Not available if No alarm action is selected during A1 type selection
• Setting range: 0 to 9999 seconds
A2 action delayed timer setting
0 seconds
• Sets A2 action delayed timer. When setting time has elapsed after the input enters the alarm output range, the alarm is activated.
• Not available if A2 option is not added or if No alarm action is selected during A2 type
selection
• Setting range: 0 to 9999 seconds
High/Low limit control selection High limit control
• Selects either High limit or Low limit control action.
(Refer to Section 7.1, 7.2)
• Selection item:
: High limit control
: Low limit control
OUT1 ON/OFF action hysteresis setting
1.0
• Sets OUT1 (Limit control output) ON/OFF action hysteresis.
• Setting range: 0.1 to 100.0 ( ), or 1 to1000
13
Auto/Manual limit control selection
Auto limit control
• Selects either auto or manual limit control action. (Refer to Section 7.3)
• Selection item:
: Auto limit control : Manual limit control
EXCD indicator lighting duration time unit selection
Hour:Minute
• Selects unit of “EXCD indicator lighting duration time”.
• Selection range:
: Hour:Minute : Minute:Second
Sensor correction function
This corrects the input value from the sensor. When a sensor cannot be set at a location where control is desired, the sensor measuring temperature may deviate from the temperature in the controlled location. When controlling with plural controllers, sometimes the measured temperatures (PV) do not concur due to differences in sensor accuracy or dispersion of load capacities. In such a case, the control can be set at the desired temperature by adjusting the input value of sensors.
Energized/Deenergized
When A1/A2 Energized is selected, the A1/A2 output (between terminals 7-8, or 12-13) is conducted (ON) while the A1/A2 output indicator is lit. The A1/A2 output is not conducted (OFF) while the A1/A2 output indicator is not lit.
When A1/A2 Deenergized is selected, the A1/A2 output (between terminals 7-8, or 12-13) is not conducted (OFF) while the A1/A2 output indicator is lit. The A1/A2 output is conducted (ON) while the A1/A2 output indicator is not lit.
High limit alarm (when Energized is set) High limit alarm (when Deenergized is set)
A1: Alarm 1 (Fig. 5.5-1) (Fig. 5.5-2) For Al arm 2(A2 ), re ad A 2 for A1
6. Running
After the unit is mounted to the control panel and wiring is completed, operate the unit following the procedures below.
(1) Turn the power supply to the JCD-33A ON.
Turn the power supply to the JCD-33A ON.
• For approx. 3sec after the power is switched ON, the input characters and the temperature unit are indicated on the PV display and input range high limit value is indicated on the SV display. See (Tabl e 5-1). (If any other value has been set during scaling high limit setting, the set value is indicated
on the SV display. )
During this time, all outputs and LED indicators are in OFF status.
• After that, control starts indicating PV (process variable) on the PV display, and SV (desired value) on
t he SV display.
(2) Input each set value.
Input each set value, referring to “5. Settings”.
(3) Turn the load circuit pow er ON.
Limit control action starts.
OFF
ON
A1 hysteresis
SV setting + A1 set point
OFF
ON
SV setting
+ A1 set point
A1 hysteresis
14
SV
PV
Open
OUT1 5-6
OUT1
Lit
hysteresis
EXCEEDED Indicator
RESET Indicator
POWER OFF
POWER ON
Lit
Unlit
Unlit
Unlit
Unlit
OUT1 4-5
Closed
Closed
Closed
Open Open
SV
PV
OUT1
POWER ON
POWER OFF
EXCEEDED Indicator
hysteresis
RESET Indicator
Unlit
Lit Unlit
UnlitUnlit
Lit
OUT1 5-6 OUT1 4-5
Closed
Open
Closed
Closed
Open Open
7. Action explanation
7.1 High limit control action (Fig. 7.1-1)
Auto limit control will be used for purposes of explanation of the High limit control action. (Refer to Section 7.3)
(Fig. 7.1-1)
(1) Limit control action will initiate after power supply to the controller is turned on. (2) If PV exceeds SV, the EXCEEDED and RESET indicators light, and
OUT1 (Limit control output terminals between 5-6) is turned OFF.
(3) If PV drops below [SV-OUT1 hysteresis], the EXCEEDED indicator goes off.
At this time, the RESET indicator is lit, and OUT1 (Limit control output terminals between 5-6) is in OFF status.
(4) If the
RESET
key is pressed, or if external reset input terminals between 15-17 are shorted, the RESET indicator goes off, OUT1 (Limit control output terminals between 5-6) is turned ON, and limit control action initiates again.
(5) While the EXCEEDED indicator is lit, even if the
RESET
key is pressed or even if external reset input
terminals between 15-17 are shorted, limit control action does not initiate.
7.2 Low limit control action (Fig. 7.2-1) Auto limit control will be used for purposes of explanation o f the Lo w limit con trol action. (Refer to Section 7.3)
(Fig. 7.2-1)
key or External
reset input
(1)
(2) (3)
(4)
(5)
key or External
reset input
(1)
(2)
(3)
(4)
(5)
Deenergized action
Energized action
RESET
RESET
15
: A1 output terminals 7-8 (A2 output terminals 12-13 ) ON : A1 output terminals 7-8 (A2 output terminals 12-13) ON or OFF : A1 output terminals 7-8 (A2 output terminals 12-13 ) OFF : The standby functions.
(1) Limit control action will initiate after power supply to the controller is turned on. (2) If PV drops below SV, the EXCEEDED and RESET indicators light, and OUT1 (Limit control output
terminals between 5-6) is turned OFF.
(3) If PV exceeds [SV+OUT1 hysteresis], the EXCEEDED indicator goes off.
At this time, the RESET indicator is lit, and OUT1 (Limit control output terminals between 5-6) is in OFF status.
(4) If the
RESET
key is pressed, or if external reset input terminals between 15-17 are shorted, the RESET indicator goes off, OUT1 (Limit control output terminals between 5-6) is turned ON, and limit control action initiates again.
(5) While the EXCEEDED indicator is lit, even if the
RESET
key is pressed or even if external reset input
terminals between 15-17 are shorted, limit control action does not initiate.
7.3 Auto/Manual limit control
Auto limit control
When the power supply is turned on, or after the power is restored, the AUTO indicator lights, and limit control starts automatically even though the
RESET
key has not been pressed.
However, limit control action does not initiate while the EXCEEDED indicator is lit.
Manual limit control
In the following cases, the RESET indicator lights, and it is necessary to reset the unit manually.
• When power is turned on
• When power is restored
• For high limit control action, when PV drops below the SV-Hysteresis after PV exceeded SV For low limit control action, when PV exceeds the SV+Hysteresis after PV dropped below SV
Limit control action does not initiate while the EXCEEDED indicator is lit.
7.4 A1, A2 action
A1 action
A1 output
+ side
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
High/Low limits alarm
High/Low limit range alarm
Low limit alarm
Process high alarm
Process low alarm
A1 hysteresis
A1 hysteresis
+ A1 set point
A1 set point
SV
High limit alarm
A1 hysteresis A1 hysteresis
A1 hysteresis
High limit alarm with standby
Low limit alarm with standby
A1 hysteresis
A1 set point
A1 set point
A1 set point
A1 set point
A1 set pointA1 set point
+ A1 set point
+ A1 set point
A1 set point
SV
SV
SV
SV
A1 set point
A1 set point
A1 hysteresis
A1 hysteresis A1 hysteresis
High/Low limits alarm with standby
A1 action
A1 action
A1 output
A1 output
- side
+ side
- side
+ side
- side
+ side
- side
SV
A1 set point
SV
+ A1 set point
A1 set point
• For A2, read A2 for A1.
• A1 indicator light s when output terminals b etween 7-8 are ON, and goes off when output terminals between 7-8 are OFF.
• A2 indicator light s when output terminals b etween
12-13 are ON, and goes off when output terminals
between 12-13 are OFF.
16
OUT1
A1
output
Transmission output
Ground
A2 output
EXT.
RESET
A
B
C
5
4
3
9
8
10
1
2
7
6
Insulated
Power supply
Input
11
12 13
14
15
17
18
19
20
17
Communication
8. Specifications
8.1 Standard specifications
Mounting : Flush Setting : Input system using membrane sheet key Display PV display : Red LED 4 digits, character size 18 x 8mm (H x W)
SV display : Green LED 4 digits, character size 12. 6 x 6 mm (H x W)
Accuracy (Setting and Indication):
Thermocouple : Within
0.2% of each input span 1digit, or within 2 (4 ), whichever is greater However R, S inputs, 0 to 200
(400 ): Within 6 (12 )
B input, 0 to 300
(600 ): Accuracy is not guaranteed.
K, J, E, T, N inputs, less than 0
(32 ): Within 0.4% of input span 1digit
RTD : Within
0.1% of each input span 1digit, or
within
1 (2 ), whichever is greater
DC current : Within
0.2% of each input span 1digit DC voltage : Within
0.2% of each input span 1digit
Input sampling period : 0.25 seconds Input Thermocouple : K, J, R, S, B, E, T, N, PL-
, C(W/Re5-26), External resistance, 100 or less
(However, B input: External resistance, 40
or less) RTD : Pt100, JPt100, 3-wire system Allowable input lead wire resistance (10
or less per wire) DC current : 0 to 20mA DC, 4 to 20mA DC Input impedance: 50 [Connect 50
shunt resistor (sold separately) between input terminals.]
Allowable input current: 50mA or less [when shunt resistor (sold separately) is used] DC voltage : 0 to 1V DC
Input impedance: 1M
or more Allowable input voltage: 5V or less Allowable signal source resistance: 2k
or less : 0 to 5V DC, 1 to 5V DC, 0 to 10V DC Input impedance: 100k
or more Allowable input voltage: 15V or less Allowable signal source resistance: 100
or less
OUT1 (Limit control output)
Relay contact : 1a1b, Control capacity: 3A 250V AC (resistive load) 1A 250V AC (inductive load cosø=0.4) Electrical life: 100,000 times
A1 output
Action : ON/OFF action
Hyste r esis : 0.1 t o 100.0
( ), 1 to 1000 (DC input) (Default: 1.0 ) Output : Relay contact 1a Control capacity: 3A 250V AC (resistive load) Electrical life: 100,000 times
Control action
High limit control action, Low limit control action OUT1 (Limit control output) hysteresis: 0.1 to 100.0
( ), or 1 to 1000 (DC input)
Circuit insulation configuration
A is not insulated from B, and A is not insulated from C.
17
Insulation resistance : 10M
or more, at 500V DC
Dielectric strength : 1.5kV AC for 1 minute between input terminal and ground terminal
1.5kV AC for 1 minute between input terminal and power terminal
1.5kV AC for 1 minute between output terminal and ground terminal
1.5kV AC for 1 minute between output terminal and power terminal
1.5kV AC for 1 minute between power terminal and ground terminal Supply voltage : 100 to 240V AC 50/60Hz, 24V AC/DC 50/60Hz Allowable voltage fluctu atio n: 100 to 240V AC: 85 to 264V AC,
24V AC/DC : 20 to 28V AC/DC
Power consumption : Approx. 8VA
Ambient temperature
: 0 to 50 (32 to 122 )
Ambient humidity : 35 to 85%RH (no condensation) Weight : Approx. 370g External dimensions : 96 x 96 x 100mm (W x H x D) Material : Flame-resistant resin (Case) Color : Light gray (Case)
Attached functions : [Set value lock], [Sensor correction], [Auto/Manual limit control],
[Input abnormality indication]
Thermocouple, RTD input:
If measured value exceeds Indication range high limit value, the PV display flashes “
”. If measured value drops below Indication range low limit value, the PV display flashes “ ”. If measured value goes out of the Control range, OUT1 (Limit control output) is turned OFF.
Input Input range Indication range Control range
–199.9 to 400.0 –199.9 to 450.0 –205.0 to 450.0
KT
–199.9 to 750.0
–199.9 to 850.0 –209.0 to 850.0
–199.9 to 850.0 –199.9 to 900.0 –210.0 to 900.0
–200 to 850 –210 to 900 –210 to 900
–199.9 to 999.9 –199.9 to 999.9 –211.0 to 1099.9
Pt100
–300 to 1500
–318 to 1600 –318 to 1600 –199.9 to 500.0 –199.9 to 550.0 –206.0 to 55 0.0 –200 to 500 –207 to 550 –207 to 550 –199.9 to 900.0 –199.9 to 999.9 –211.0 to 999.9
JPt100
–300 to 900
–312 to 100 0 –312 to 1000
Indication range and Control range for thermocouple inputs other than the above: Input range low limit value –50
(100 ) to Input rang e high limit value +50 (100 )
Output status
Contents and Indication
(4)-(5) (5)-(6)
Measured value has exceeded Indication range
high limit value. "
" flashes.
Closed Open
Measured value has dropped below Indication
range low limit value. "
" flashes.
Closed Open
DC input:
Indication range: [Scaling low limit value–Scaling span x 1%] to [Scaling high limit value +Scaling
span x 10%]
However,
” or “ ” flashes when a range of –1999 to 9999 is
exceeded.
Control range: [Scaling low limit value–Scaling span x 1%] to [Scaling high limit value +Scaling span x 10%]
DC input disconnection: When DC input is disconnected, the PV display flashes “
” for 4 to 20mA
DC and 1 to 5V DC inputs, and “
” for 0 to 1V DC input. For 0 to 20 mA DC, 0 to 5V DC and 0 to
10V DC inputs, the PV display indicates the value corresponding with 0mA or 0V input.
[Burnout]
When the thermocouple or RTD input is burnt out, OUT1 (Limit control output) is turned off, the PV
becomes its maximum value and the PV display flashes “
”.
[Self-diagnosis]
The CPU is monitored by a watchdog timer, and if an abnormal status is found on the CPU,
the controller is switched to warm-u p status .
18
[Automatic cold junction temperature compensation] (Only thermocouple input type)
This detects the temperature at the connecting terminal between the thermocouple and the instrument, and always maintains at the same status as when the reference junction is located at 0
(32 ).
[Power failure countermeasure]
The setting data is backed up in the non-volatile IC memory.
[Warm-up indication]
After the power supply to the instrument is turned on, the PV display indicates input type, and the SV display indicates scaling high limit value for 3 seconds.
[Peak (or Bottom) value hold function]
While the EXCEEDED indicator is lit, the peak value is maintained during high limit action, or Bottom (the lowest) value is maintained during low limit action. Present measured value will be initialized after reset using the RESET key or the external reset input function.
[EXCEEDED indicator lighting duration time]
EXCEEDED indicator lighting time can be measured and indicated by pressing the Mode (
) key in the PV/SV display mode. Measurement range: 0:00 to 99:59 (Hour:Minute, Minute:Second) Lighting time will be initialized to 0:00 after reset using the RESET key or the external reset input
function.
[Transmission output]
Converting the value (PV transmission, SV transmission) to analog signal every 0.25 seconds, the value is outputted in current. (Default: PV transmission) Resolution :1/8192 Current : 4 to 20mA DC (load resistance, maximum 550
)
Output acc ura c y: Wi t hi n
0.3% of each input span
Accessories: Screw type mounting brackets, 1 set
Instruction manual, 1 copy Terminal cover, 2 pieces (when TC option is added)
8.2 Optional specifications A2 output (Option code: A2)
Action : ON/OFF action Hysteresis : 0.1 to 100.0
( ), or 1 to 1000 (DC input) (Default: 1.0 ) Output : Relay contact, 1a Control capacity: 3A 250V AC (Resistive load) Electrical life: 100,000 times
Serial communication (Option code: C5)
The following operations can be carried out from the external computer. (1) Reading and setting of the SV and each set value (2) Reading of the PV and action status (3) Change of the functions Cable length : Maximum communication distance 1.2km
Cable resistance: Within 50
(Terminator is not necessary or 120 or
more on one side.)
Communication interface : EIA RS-485 Communication method : Half-duplex communication start-stop synchronization Communication speed : 2400, 4800, 9600, 19200bps (Selectable by keypad) (Default: 9600bps) Parity : Even, Odd and No parity (Selectable by keypad) (Default: Even parity) Stop bit : 1, 2 (Selectable by keypad) (Default: 1) Communication protocol : Shinko protocol, Modbus ASCII, Modbus RTU (Selectable by keypad) Data format
Communication protocol
Shinko protocol Modbus ASCII Modbus RTU Start bit 1 1 1 Data bit 7 7 8 Parity Even Selection (Even) Selection(No parity) Stop bit 1 Selection (1) Selection (1)
Data bit is automatically selected upon selecting the communication protocol. ( ): Basic set value Number of units connectable : Maximum 31 units to 1 host computer Communication error detection : Double detection by parity and checksum
Terminal cover (Option code: TC): Electrical shock protection terminal cover Color Black (Option code: BK): Front panel frame and Case: Black
19
9. Troubleshooting
If any malfunctions occur, refer to the following items after checking the power supply to the controller.
9.1 Indication
Problem
Presumed cause and solution
” is indicated on the PV display.
• The controller is in the EXCEEDED indicator lighting duration time mode.
Press the key twice to revert to the PV/SV display.
” or ” is indicated on the PV display.
• Maximum or Minimum value is indicated.
Press the
key once to revert to the PV/SV display.
” is flashing on the PV display.
• Burnout of thermocouple, RTD or disconnection of DC voltage (0 to
1V DC)
Change each sensor.
How to check whether the sensor is burnt out
[Thermocouple]
If the input terminals of the instrument are shorted, and if a value around room temperature is indicated, the instrument is likely to be operating normally, however, the sensor may be burnt out.
[RTD]
If approx. 100
of resistance is connected to the input terminals between A-B of the instrument and between B-B is shorted, and if a value around 0
(32 ) is indicated, the instrument is likely to
be operating normally, however, the sensor may be burnt out.
[DC voltage (0 to 1V DC)]
If the input terminals of the instrument are shorted, and if a scaling low limit value is indicated, the instrument is likely to be operating normally, however, the signal wire may be disconnected.
• Check whether the input terminals of thermocouple, RTD or DC voltage (0 to 1V DC) are securely mounted to the instrument input terminals.
Connect the sensor terminals to the instrument input terminals securely.
” is flashing on the PV display.
• Check whether input signal wire for DC voltage (1 to 5V DC) or DC current (4 to 20mA DC) is disconnected.
How to check whether the input signal wire is disconnected [DC voltage (1 to 5V DC)]
If the input to the input terminals of the instrument is 1V DC and if a scaling low limit value is indicated, the instrument is likely to be operating normally, however, the signal wire may be disconnected.
[DC current (4 to 20mA DC)]
If the input to the input terminals of the instrument is 4mA DC and if a scaling low limit value is indicated, the instrument is likely to be operating normally, however, the s ignal wire may be disconnected.
Check whether input signal wire for DC volt age (1 to 5V DC) or DC current
(4 to 20mA DC) is securely connected to the instrument input terminals.
• Check if polarity of thermocouple or compensating lead wire is correct.
Check whether codes (A, B, B) of RTD agree with the instrument termi nals.
The indication of PV display is abnormal or unstable.
• Check whether sensor input or temperature unit (
or ) is correct.
Select the sensor input and temperature unit (
or ) properly.
• Sensor correcting value is unsuitable. Set it to a suitable value.
• Check whether the specification of the sensor is correct.
• AC may be leaking into the sensor circuit. Use an ungrounded type sensor.
• There may be equipment that interferes with or makes noise near the controller.
Keep equipment that interferes with or makes noise away from the
controller.
20
The PV display keeps indicating the value which was set during Scaling low limit setting.
• Check whether the input signal wire for DC voltage (0 to 5V DC, 0 to 10V DC) and DC current (0 to 20mA DC) is disconnected.
How to check whether the input signal wire is disconnected [DC voltage (0 to 5V DC, 0 to 10V DC)]
If the input to the input terminals of the instrument is 1V DC and if the value corresponding to 1V DC is indicated, the instrument is likely to be operating normally, however, the signal wire may be disconnected.
[DC current (0 to 20mA DC)]
If the input to the input terminals of the instrument is 1mA DC and if the value corresponding to 1mA DC is indicated, the instrument is likely to be operating normally, however, the signal wire may be disconnected.
• Check whether the input lead wire terminals for DC voltage (0 to 5V
DC, 0 to 10V DC) or DC current (0 to 20mA DC) are securely
mounted to the instrument input terminals. The PV display is indicating “
”.
• Internal memory is defective. Contact our agency or us.
9.2 Key operation Problem
Presumed cause and solution
• Unable to set the SV, A1 value, etc.
• The values do not change by
or key.
• Set value lock (Lock 1 or Lock 2) is selected. Release the lock.
The setting indication does not change within the input range
even if the
or key is pressed, and new values are unable to be set.
• Scaling high or low limit value in the Setup mode may be set at the point where the value does not change. Set it to a suitable value while in the Setup mode.
9.3 Control Problem
Presumed cause and solution
Temperature does not rise. • Sensor is out of order. Replace the sensor.
• Check whether the Sensor or control output terminals are securely mounted to the instrument input terminals. Ensure that the sensor or control output terminals are mounted to the instrument input terminals securely.
• Check whether the wiring of sensor or control output terminals is
correct.
• For all other malfunctions, please contact our main office or dealers.
SHINKO TECHNOS CO.,LTD.
OVERSEAS DIVISION
: :
:
Reg. Office URL
E-mail
2-5-1, Senbahigashi, Minoo, Osaka , Japan
http://www.shinko-technos.co.jp overseas@shinko-technos.co.jp
Tel : Fax:
81-72-727-6100 81-72-727-7006