18
5.2 Main setting mode
Press the
key in the PV/SV display mode to enter the Main setting mode.
The SV can be increased or decreased by pressing the
or key.
If the
key is pressed, the SV is registered, and the controller will revert
to the PV/SV display mode.
Character Name, Function, Setting range Default value
SV 0
• Sets SV1 (desired value).
• Setting range: SV low limit to SV high limit or
Scaling low limit value to Scaling high limit value
SV2 0
• Sets SV2 (desired value).
• Not available if Serial communication (option) is added
• Setting range: SV low limit to SV high limit or
Scaling low limit value to Scaling high limit value
5.3 Sub setting mode
Press the
key while holding down the key in the PV/SV display mode to enter
the Sub setting mode.
The
or key increases or decreases the set value (numeric value).
By pressing the
key, the set value is register ed, and the unit moves to the next
setting item.
Character Name, Function, Setting range Default value
AT/Auto-reset Perform/Cancel AT/Auto-reset Cancel
• Selects AT or Auto-reset (offset correction) Perform/Cancel.
• Auto-reset can be performed only during PD and P control.
• Not available for PI and ON/OFF control.
• Selection item:
: AT/Auto-reset Cancel
/ : AT/Auto-reset Perform
• Default: AT/Auto-reset Cancel
[About AT]
• If the AT Perform is selected, the AT indicator flashes, and the controller
reverts to the PV/SV display mode.
• After AT is finished, the AT indicator is turned off, and P, I, D and ARW
values are automatically set.
• During AT, none of the settings can be performed.
• If the AT is cancelled during the proces s, P, I, D and ARW values revert
to the previous value at which AT was performed.
• If the
key is pressed during AT, control output OFF function is
activated, and if the
key is pressed again, AT is cancelled.
• AT will be forced to stop if it has not been completed within 4 hours.
[About Auto-reset (offset correction)]
• If the auto-reset is performed, offset correction immediately starts, and
the controller reverts to the PV/SV display mode.
(The corrected value is automatically set and the AT indicator flashes.)
• During 4 minutes of auto-reset performance, other s ettings cannot be
performed to prevent key misoperations.
• After auto-reset ends, the AT indicator is turned off, and all settings can
be performed.
OUT1 proportional band 10
• Sets OUT1 proportional band.
ON/OFF control when set to 0 or 0.0.
• Setting range: 0 to 1000
(0 to 2000 )
With a decimal point: 0.0 to 999.9
(0.0 to 999.9 )
DC input: 0.0 to 100.0%