Shinko IF-400 Instruction Manual

Page 1
1
INSTRUCTION MANUAL
COMMUNICATION CONVERTER IF-400
No.IF41E3 2007.06
Preface
Thank you for purchasing the IF-400 Communication Converter. This manual contains instructions for the mounting, functions, operations and notes for operating the IF-400. To prevent accidents arising fro m the misu se of this unit, please ensure the operator receives this manual.
Notes
This instrument should be used in accordance wi th the specifications describe d in the manual.
If it is not used according to the specifications, it may malfunction or cause a fire.
Be sure to follow the warnings, cautions and notices. If they are not observed, serious injury or malfunction may
occur.
Specifications and the conten ts of this instruction manual are subject to change without notice. Care has been taken to ensure that the content s of this instru ction manual are correct, bu t if there are any doubt s,
mistakes or questions, please inform our sales dep artmen t.
This instrument is designed to be installed on a DIN rail wi thin a control panel. If it is not, measures must be taken
to ensure that power terminals or other high volt age sections ca nnot be tou ched.
Any unauthorized transfer or copying of th is docume nt, in pa rt or in whole, is pr ohibited. Shinko Technos CO., LTD. is not liable for any damage or secondary da mage(s) incurred a s a re sult of using this
product, including any indirect damages.
Safety precautions (Be sure to read these precautions before using this product.)
The safety precautions are classified into two categories: “Warning” and “Caution”. Depending on the circumstances, procedures indicated by Caution may have serious consequences, so be sure to follow the directions for correct usage.
Warning
Warning
To prevent an electric shock or fire, only Shinko or other qualified service personnel may handle the inner
assembly.
To prevent an electric shock, fire or damage to the instrument, parts replacement may only be undertaken
by Shinko or other qualified service personnel.
Safety precautions
To ensure safe and correct use, thoroughly read and understand this manual before using this instrument. This instrument is intended to be used for industrial machinery, machine tools and measuring equipment.
Verify correct usage after consulting purpose of use with our agency or main office.
(Never use this instrument for medical purposes with which human lives are involved.)
External protection devices such as protection equipment against excessive temperature rise, etc. must be installed, as malfunction of this product could result in serious damage to the system or injury to personnel. Also proper periodic maintenance is required.
This instrument must be used under the conditions and environment described in this manual. Shinko Technos Co., Ltd. does not accept liability for any injury, loss of life or damage occurring due to the instrument being used under conditions not otherwise stated in this manual.
Caution with respect to Export Trade Control Ordinance
To avoid this instrument from being used as a component in, or as being utilized in the manufacture of
weapons of mass destruction (i.e. military applications, military equipment, etc.), please investigate the end
users and the final use of this instrument.
In the case of resale, ensure that this instrument is not illegally exported.
Caution
Procedures which may lead to dangerous conditions and cause death or serious injury, if not carried out properly.
Procedures which may lead to dangerous conditions and cause superficial to medium injury or physical damage or may degrade or damage the product, if not carried out properly.
Page 2
2
11.. IInnssttaallllaattiioonn pprreeccaauuttiioonns
s
Caution
This unit is intended to be used under the following environmental conditions (IEC61010-1): Overvoltage category
, Pollution degree 2
Ensure the mounting location corresponds to the following conditions:
A minimum of dust, and an absence of corrosive gases
No flammable, explosive gases
No mechanical vibrations or shocks
No exposure to direct sunlight, an ambient temperature of 0 to 50 (32 to 122 )
that does not change rapidly, no icing An ambient non-condensing humidity of 35 to 85%RH No large capacity electromagnetic switches or cables through which large current flows No water, oil or chemicals or where the vapors of these substances can come into direct contact
with the unit When this unit is installed inside a control panel, the ambient temperature of this unit must be kept
to under 50
. Otherwise the life of electronic components (especially electrolytic capacitors) will be
shortened.
Note: Avoid setting this unit directly on or near flammable material even though the case of this unit
is made of flame-resistant resin.
22.. WWiirriinngg pprreeccaauuttiioonns
s
Caution
Do not leave bits of wire in the un it, because they could cause fire , malfunction or trouble . Insert the connecting cable into the designated connector securely to prevent malfunction.
Connect the wire for the AC power source with its designated terminal as described in this instruction
manual.
The IF-400 will be damaged if the AC power source wire is connected to an incorrect terminal. When wiring terminals of the IF-400 at the terminal block, use corr ect fi tting ferr ules with an i nsulatio n slee ve
for the terminal screw . Tighten the terminal screw within the specified torqu e. If excessiv e force is app lied to the screw when
tightening, the screw or case may be da maged. For a 24V AC/DC power source, do not confuse polarity when using direct current (DC). This unit does not have a built-in power switch, circuit breaker or fuse. Therefore, it is necessary to install
them in the circuit near the unit externally.
(Recommended fuse: Time-lag fuse, rated voltage 250V AC, rated current 2A)
33.. RRuunnnniinngg aanndd mmaaiinntteennaannccee pprreeccaauuttiioonnss
Warning
Do not touch live terminals. This may cause electric shock or problems in operation. Turn the power supply to the instrument OFF before retightening the terminal or cleaning.
Working or touching the terminal with the power switched ON may result in severe injury or death
due to Electric Shock. Use a soft, dry cloth when cleaning the unit.
(Alcohol based substances may tarnish or deface the unit) As the display section is vulnerable, do not strike or scratch it with a hard object.
Page 3
3
Host computer
or PLC
RS-232C RS-422
Communication converter
IF-400
RS-485
Max. 1.2km
RS-232C: Max.15m RS-422: Max.1.2km
Digital indicating controlle
r
Max. 31 units
Max. 1.2km
RS-485
Repeate
r
IF-400
Digital indicating controlle r
Max. 30 units
1. Overview
1.1 Overview
The IF-400 is a communication converter to relay communications between a host computer/PLC (RS-232C or RS-422) and controllers (Serial communication function RS-485, C5 option). Shinko protocol and Modbus protocol are available.
The IF-400 can also be used as a repeater by connecting another IF-400 unit to the controller side communication line. The repeater will be the 31st connected unit, and up to 31 units of controller can be connected to the repeater. A maximum of 3 units of repeater can be connected. Up to 95 units of controllers (Controller address is limited to 95) can be connected.
1.2 System configuration
1.2.1 When the IF-400 is used as a communication converter
When IF-400 is used as a communication converter, a maximum of 31 units of controller can be connected.
(Fig.1.2.1-1)
1.2.2 When the IF-400 is used as a repeater When the IF-400 is used as a repeater, more than 32 units of controller can be connected. Communication line can be extended more than 1.2km. Up to 3 units of repeater can be used, therefore, up to 95 units of controller can be connected (A maximum of 4.8km of communication line can be extended).
(Fig.1.2.2-1)
Host computer
or PLC
Communication converte
r
IF-400
RS-232C RS-422
RS-485
Digital indicating controlle
r
Max. 31 units
Max. 1.2km
RS-232C: Max.15m RS-422: Max.1.2km
Page 4
4
2. Model
2.1 Model
IF-400
2.2 How to read the model label
Warning
Turn the power supply to the instrument off before confirming the model labels. Working or touching the terminal with the power switched on may result in severe injury or death due to Electric Shock.
Model labels are attached to the case and the inner assembly. (Fig. 2.2-1) (e.g.)
(Fig. 2.2-1)
3. Name and functions of the sections
(Fig. 3-1)
IF-400
No.xxxxxx
1
Model: IF-400
2
Serial number (only on the inner assembly)
1
PWR indicator (Green):
Lights when power supply to the instrument is switched on.
2
MST (Master) indicator (Green):
LCL (Local) MST (Master) Lights while data signal is transmitted from the controller side communication line to the host computer/PLC side communication line.
3
LCL (Local) indicator (Green):
MST (Master) LCL (Local) Lights while data signal is transmitted from the host computer/PLC side communication line to the controller side communication line.
4
Setting display:
Unlit during communication mode. Indicates the selected item in the Setup mode.
5
Increase key: Switches the selection item.
6
Decrease key: Switches the selection item.
7
Mode key: Switches the setting mode, and registers
the selected item.
1
2 3
4
5
6
7
Page 5
5
4. Mounting
4.1 Site selection
Caution
Use within the following temperature and humidity ranges. Temperature: 0 to 50
(32 to 122 ), Humidity: 35 to 85%RH (No icing, no condensation) If the IF-400 is installed t within a control panel, the ambient temperature of the IF-400 must be kept to under 50 . Otherwise the life of electronic parts (especially electrolytic capacitors) of the IF-400 will be shortened.
This unit is intended to be used under the following environmental conditions (IEC61010-1): Overvoltage category
, Pollution degree 2
Ensure the mounting location corresponds to the following conditions:
A minimum of dust, and an absence of corrosive gases
No flammable, explosive gases
No mechanical vibrations or shocks
No exposure to direct sunlight, an ambient temperature of 0 to 50 (32 to 122 ) that does not
change rapidly
An ambient non-condensing humidity of 35 to 85%RH
No large capacity electromagnetic switches or cables through which large current flows
No water, oil or chemicals or where the vapors of these substances can come into direct contact
with this unit
4.2 External dimensions (Scale: mm)
(Fig.4.2-1)
4.3 Mounting to the DIN rail
Caution
Mount the DIN rail horizontally. When the DIN rail is mounted vertically, be sure to use commercially available fastening plates at the end of the IF-400. Mount the IF-400 to the DIN rail so that the IF-400 may be fixed. However, if the DIN rail is mounted horizontally in a position susceptible to vibration or shock, the fastening plates must be used as well.
Recommended fastening plate
Omron Corporation End plate PFP-M IDEC Corporation Fastening plate BNL6 Matsushita Electric Works, Ltd. Fastening plate ATA4806
First, hook
1
of the IF-400 on the upper side of the DIN rail. (Fig. 4.3-1)
Second, making
1
part of the IF-400 as a support, fit the lower part 2 of the IF-400 to the DIN rail.
The IF-400 will be completely fixed to DIN rail with a “Click” sound. (Fig. 4.3-1)
Page 6
6
4.4 Removal from the DIN rail
Caution
A flat blade screwdriver is required for removing the IF-400 from the DIN rail. Do not turn the screwdriver when releasing the lever for removal. If excessive force is applied to the lever for removal, it may be damaged.
1
: Put a flat blade screwdriver to the lever and pull down the lever with it. (Fig.4.4-1)
2
: The lock to the DIN rail will be released.
Be careful that the unit does not drop to the ground when it is removed. (Fig.4.4-1)
(Fig.4.3-1) Mounting (Fig.4.4-1) Removal
5. Wiring
Warning
Turn the power supply to the instrument off before wiring. Working or touching the terminal with the power switched on may result in severe injury or death due to Electric Shock.
Caution
Do not leave bits of wire in the instrument, because they could cause fire, malfunction or trouble. Insert the connecting cable into the designated connector securely to prevent malfunction. Connect the wire for AC power source with its designated terminal as described in this instruction
manual. The IF-400 will be damaged if the AC power source wire is connected to an incorrect terminal.
Tighten the terminal screw with the specified torque.
If excessive force is applied to the screw when tightening, the screw or case may be damaged. When using a 24V DC for the power source, do not confuse polarity. This unit does not have a built-in power switch, circuit breaker or fuse. Therefore, it is necessary to
install them in the circuit near the unit externally.
(Recommended fuse: Time-lag fuse, rated voltage 250V AC, rated current 2A)
1
2
1
2
Lever for removal
Page 7
7
Ferrules and tightening torque
When using ferrules, use the following recommended ferrules and crimping pliers made by Phoenix
Contact GMBH &CO. See (Table 5-1).
Take note that terminal screws and tightening torque differ depending on a terminal number.
(Table 5-1)
Terminal
number
Terminal
screw
Ferrules with
insulation sleeve
Conductor cross
sections
Tightening torque
Crimping pliers
AI 0.25-8 YE 0.2 to 0.25mm2 AI 0.34-8 TQ 0.25 to 0.34mm2 AI 0.5-8 WH 0.34 to 0.5mm2 AI 0.75-8 GY 0.5 to 0.75mm2 AI 1.0-8 RD 0.75 to 1.0mm2
1 to 4 M2.6
AI 1.5-8 BK 1.0 to 1.5mm
2
0.5 to 0.6N・m
AI 0.25-8 YE 0.2 to 0.25mm2 AI 0.34-8 TQ 0.25 to 0.34mm2
5 to 9 M2.0
AI 0.5-8 WH 0.34 to 0.5mm
2
0.22 to 0.25N・m
CRIMPFOX ZA 3 CRIMPFOX UD 6
Terminal arrangement
to HOST : Communication terminals
for the Host computer/PLC
RS-232C, RS-422, RS-485
Modular jack: For controller side communication
RS-485
(Fig. 5-1)
Page 8
8
5.1 Wiring of power supply
Use terminals 1 and 2 for power supply. When using a 24V DC for the power source, do not confuse polarity.
5.2 Wiring of the host computer/PLC side when using the IF-400 as a communication converter
5.2.1 RS-232C
Use terminals 3, 4 and 9. Use CFP-C2 (D-sub 9-pin connector for the host computer side, ferrules for the IF-400 side) as a cable between host computer/PLC and the IF-400.
If host computer has only USB connector, use commercially available USB serial conversion cable (USB connector for the host computer side, D-sub 9-pin connector for CFP-C2 side) to connect the host computer and CFP-C2.
(Fig. 5.2.1-1)
5.2.2 RS-422
Use terminals 5 through 9. Use CFP-C4 (Y terminal for the host computer, ferrules for the IF-400) as a cable between host computer/PLC and the IF-400.
(Fig. 5.2.2-1)
Host computer
Host computer
IF-400
IF-400
D-sub 25-pin connector
D-sub 9-pin connector
Shielded wire
Shielded wire
Host computer
IF-400
Shielded wire
Page 9
9
5.3 Wiring of the controller side
5.3.1 DCL-33A
Use communication cable CDD or CPP, and plug into a modular jack.
(Fig.5.3.1-1)
(*) Cable length of CDD: 60mm. For distances larger than 60mm, use the CPP cable.
Cable length of CPP: 500mm. For distances larger than 500mm, the CPP can be extended in units of 500mm fixed length. For distances less than 500mm, the CPP can be cut down in units of 100mm fixed length.
CDD or CPP (*)
IF-400
DCL-33A (Max.31 units)
Bottom of the IF-400, DCL-33A
Page 10
10
5.3.2 Controllers such as ACS-13A, JC series, FC series, PC-900 which have terminal block
Use CDM communication cable, and plug into a modular jack. Cable length of CDM: 3000mm The CDM cable can be extended in units of 1000mm fixed length.
(Fig.5.3.2-1)
5.3.3 NCL-13A
Use CNS communication cable, and plug into a modular jack. Cable length of CNS: 500mm The CNS cable can be extended in units of 500mm fixed length.
(Fig.5.3.3-1)
IF-400
JCS-33A (Max. 31 units)
Shielded wire
Shielded wire
Plug into the modular jack a
t
the bottom of the IF-400. (There are 2 modular jacks. Use either of them.)
IF-400
NCL-13A (Max.31 units)
Bus plug
Screw type plug for lines (sold separately)
Plug into the modular jack a
t
the bottom of the IF-400. (There are 2 modular jacks. Use either of them.)
Page 11
11
5.4 Wiring of the host computer/PLC side when using the IF-400 as a repeater
When connecting more than 32 units of controllers, use the IF-400 as a repeater.
For wiring between the IF-400 and controllers, refer to Section 5.3.
5.4.1 DCL-33A
Use CNS communication cable, and connect it to terminals 7 through 9. Cable length of CNS: 500mm The CNS cable can be extended in units of 500mm fixed length.
(Fig.5.4.1-1)
5.4.2 Controllers such as ACS-13A, JC series, FC series, PC-900 which have terminal block
Use CNM communication cable, and connect it to terminals 7 through 9. Cable length of CNM: 500mm The CNM cable can be extended in units of 500mm fixed length.
(Fig.5.4.2-1)
IF-400
(comm. converter)
IF-400 (repeater)
DCL-33A (Max.30 units)
JCS-33A (Max.30 units)
IF-400 (repeater)
IF-400
(Comm. converter)
Shielded wire
Shielded wire
Notice
The repeater will be the 31st connected unit, and up to 30 units of the DCL-33A can be connected.
Plug into the modular jack at the bottom of the IF-400. (There are 2 modular jacks. Use either of them.)
Notice
The repeater will be the 31st connected unit, and up to 30 units of JCS-33A can be connected.
Page 12
12
5.4.3 NCL-13A Use CNS communication cable, and connect it to terminals 7 through 9. Cable length of CNS: 500mm The CNS cable can be extended in units of 500mm fixed length.
(Fig. 5.4.3-1)
6. Setup
Setup should occur before using the IF-400, to set the Communication speed and Sending/Receiving switching character, according to the users’ conditions. If the users’ specification is the same as the default value of the IF-400 (Table 6-1), it is not necessary to set up the IF-400. Proceed to Chapter “7. Running”. (Table 6-1)
Setting item Default value
Communication speed 9600bps Sending/Receiving
switching character
1 character
Setup items and communication line control
After detecting the Start bit of the 1st character upon receiving a data signal from the host computer/PLC, the IF-400 switches the controller communication line to Sending status. When data signal from the host computer/PLC stops, the IF-400 sets the controller communication line back to Receiving status after Sending/Receiving switching time has passed (*).
After detecting the S tart bit of the 1st character upon receiving a data signal from the controller, the IF-400 switches the host computer/PLC communication line to Receiving status.
When data signal from the controller stops, the IF-400 sets the host computer/PLC communication line back to Receiving status after Sending/Receiving switching time has passed (*).
CNS
IF-400 (Communication converter)
IF-400 (Repeater)
NCL-13A (Max. 30 units)
CNS
Plug into the modular jack a
t
the bottom of the IF-400. (There are 2 modular jacks. Use either of them.)
Screw type plug for lines (sold separately)
Notice
The repeater will be the 31st connected unit, and up to 30 units of NCL-13A can be connected.
Page 13
13
When communication is not performed, the communication line for both host computer/PLC and controller are in data Receiving status.
(*) Sending/Receiving switching time is determined by the selection of communication speed and
Sending/Receiving switching character.
(e.g.) Communication speed: 9600bps
Sending/Receiving switching character: 1 character If 1 character is 10 bits, then Sending/Receiving switching time will be 0.001 seconds (1ms).
Communication timing
The IF-400 performs control within the communication time above. Therefore, if data is transmitted with a shorter interval than the Sending/Receiving switching time, normal communication cannot be performed. Set the Sending/Receiving time from the host computer side so that the next piece of data can be sent after the communication line is switched from Sending to Receiving status.
Turn the power ON
The PWR indicator lights when power supply to the unit is switched on. Other indicators are unlit. (See Fig. 6-1)
(Fig. 6-1)
Basic setup operation To proceed to the setup mode, press the key. The unit will proceed to the “Communication speed selection” mode, and its characters will be indicated on the display. Make a selection using the and keys, and register the selected item with the key. (See Fig. 6-2.)
(Fig. 6-2)
Unlit
Lit
Make a selection.
Proceeds to the Setup mode, and registers the selected item.
Page 14
14
Communication
mode
6.1 Operation flowchart
-
6.2 Contents of Setup mode Communication speed selection
Indication Communication speed
2400bps 4800bps 9600bps 19200bps
Sending/Receiving switching character selection
Indication Sending/Receiving switching character
1 character 2 characters
7. Running
Check the wiring and setup. Confirm the communication between a host computer/ PLC and controller. For communication confirmation, simplified communication software and monitoring software are provided. The monitoring software can be downloaded from Shinko website (http://www.shinko-technos.co.jp). (Registration for membership is required.) For further details, contact our dealers or us.
8. Specifications
Rating
Communication : Host computer/PLC side: RS-232C or RS-422 (terminal)
RS-485 (terminal, when used as a repeater) Controller side: RS-485 (modular jack) Supply voltage : 100 to 240V AC or 24V AC/DC, 50/60Hz
Allowable voltage fluctuation range:
100 to 240V AC : 85 to 264V AC
24V AC/DC : 20 to 28V AC/DC
Setup mode
Communication speed
Make a selection with the or key.
Press the key.
Sending/Receiving switching character
Make a selection with the or key.
Press the key.
Power ON
Press the key.
Page 15
15
General structure
External dimensions : 22.5 x 75 x 100 mm (W x H x D) Mounting : DIN rail Case : Flame-resistant resin, Light gray Panel : Membrane sheet
Insulation/Dielectric strength
Circuit insulation configuration:
Insulation resistance : 10M
or more, at 500V DC
Dielectric strength:
Between power terminal and controller communication modular jack --------- 1.5kV AC for 1 minute Between power terminal and host computer/PLC communication terminal --- 1.5kV AC for 1 minute Between host computer/PLC communication terminal
and controller communication modular jack ----------------------------- 1.5kV AC for 1 minute
Others
Power consumption : Approx. 5VA Ambient temperature : 0 to 50
(32 to 122 ) Ambient humidity : 35 to 85%RH (non-condensing) Weight : Approx. 150g Accessories : Instruction manual 1 copy
9. Troubleshooting
If any malfunctions occur, refer to the following items after checking the power supply to the IF-400, the host computer and controller.
Warning
Turn the power supply to the instrument OFF before wiring or checking. Working with the power switched ON may result in severe injury or death due to Electric Shock.
Communication failure
Problem Solution
Connector or communication cable is not connected.
Connect it securely.
Imperfect contact with the connector or broken cables
Securely connect the connector.
Change the cable. The wiring of communication cable (connector) is not correct.
Wire it correctly.
Refer to “5. Wiring”. Setup of the IF-400 is not correct. Set up the unit properly.
Refer to “6. Setup”. Instrument number of the controller is duplicated.
Sets an individual instrument number for each unit of
controllers.
When using Shinko monitoring software, set the controllers’
instrument number from 0 (zero) in numerical order, referring to
the Instruction manual for the controller.
Communication
Controller
(DCL-33A, JCx-33A)
Host computer/PLC
Power suppl
y
Insulated
CPU
Insulated
Communication
Page 16
***** Inquiry *****
For any inquiries about thi s u n it, pl ease c o ntact our agency or the shop where you purchased the unit after checking the following.
(Example)
• Model ----------------------------- IF-400
• Serial number ------------------- No. xxxxxx
In addition to the above, please let us kn ow th e det a ils of the malfu nc tion and operating conditions.
SHINKO TECHNOS CO., LTD.
OVERSEAS DIVISION
: :
:
Reg. Office URL
E-mail
2-5-1, Senbahigashi, Minoo, Osak a, Japan
http://www.shinko-technos.co.jp overseas@shinko-technos.co.jp
Tel : Fax:
81-72-727-6100 81-72-727-7006