Shinko FCR-13A Instruction Manual

Page 1
DIGITAL INDICATING CONTROLLER
FCR-13A
INSTRUCTION MANUAL
Page 2
2
Preface
Thank you for purchasing our Digital indicating con troller FCR-13 A. This manual contains instructions for the mounting, functions, operations and notes when operating the FCR-13A. To prevent accidents arising from the misuse of this controller, please ensure the operator receives this manual
.
Abbreviations Used in This Manual
Symbol Term PV Process variable SV Desired value MV Output manipulated variable OUT1 Control output 1 OUT2 Control output 2 (option) AT Auto-tuning DC input Direct current input
DC voltage input
Characters Used in This Manual
Indication Number, /
-1 0 1 2 3 4 5 6 7 8 9 Indication Alphabet A B C D E F G H I J K L M Indication Alphabet N O P Q R S T U V W X Y Z
Page 3
3
Notes
• This instrument should be used in a ccordance with the specifications describe d in the manual. If it is not used according to the specifications, it may malfunction or cause a fire.
• Be sure to follow the warnings, cautions and notices. If they are not observed, serious injury or malfunction may occur.
• Specifications of the FC R-13A and the contents of this instruction manual are subject to change
without notice.
• Care has been taken to assure that the contents of this instruction manual are correct, but if
there are any doubts, mistakes or questions, plea se inform our sales dep artment.
• This instrument is designed to be installed through a con trol p anel. If it is not, measure s must be
taken to ensure that the operator canno t touch power terminals or other high volt age sections.
• Any unauth orized transfe r or copy ing of th is docu ment, in p art or in whole, is pr ohibited.
• Shinko Technos CO., LTD. is not liable for any damage or secondary damage(s) incurred as a
result of using this product, including any indirect damage.
SAFETY PRECAUTIONS (Be sure to read these precautions before using our products.)
The safety precautions are classified into categories: “Warning” and “Caution”. Depending on the circumstances, procedures indicated by
Caution may cause serious
results, so be sure to follow the directions for usage.
Warning
Warning
• To prevent an electric shock or fire, only Shinko or other qualified service personnel may
handle the inner assembly.
• To prevent an electric shock, fire or damage to the instrument, parts replacement may only
be undertaken by Shinko or other qualified service personnel.
SAFETY PRECAUTIONS
• To ensure safe and correct use, thoroughly read and understand this manual before using
this instrument.
• This instrument is intended to be used for industrial machinery, machine tools and measuring
equipment. Verify correct usage after purpose-of-use consultation with our agency or main of fice. (Never use this instrument for medical purposes with which human lives are involved.)
• External protection devices such as protection equipment against excessive temperature rise,
etc. must be installed, as malfunction of this product could result in serious damage to the system or injury to personnel. Also proper periodic maintenance is required.
• This instrument must be used under the conditions and environment described in this manual.
Shinko Technos Co., Ltd. does not accept liability for any injury, loss of life or damage occurring due to the instrument being used under conditions not otherwise stated in this manual.
Caution with respect to Export Trade Control Ordinance
To avoid this instrument from being used as a component in, or as being utilized in the manufacture of weapons of mass destruction (i.e. military applications, military equipment, etc.), please investigate the end users and the final use of this instrument. In the case of resale, ensure that this instrument is not illegally exported.
Caution
Procedures which may lead to dangerous conditions and cause death or serious injury, if not carried out properly.
Procedures which may lead to dangerous conditions and cause superficial to medium injury or physical damage or may degrade or damage the product, if not carried out properly.
Page 4
4
11..
IInnssttaallllaattiioonn PPrreeccaauuttiioonnss
Caution
This instrument is intended to be used under the following environmental conditions (IEC61010-1): Overvoltage category
, Pollution degree 2
Ensure the mounting location corresponds to the following conditions:
• A minimum of dust, and an absence of corrosive gases
• No flammable, explosive gases
• No mechanical vibrations or shocks
• No exposure to direct sunlight, an ambient temperature of 0 to 50
(32 to 122 )
that does not change rapidly, and no icing
• An ambient non-condensing humidity of 35 to 85%RH
• No large capacity electromagnetic switches or cables through which large current is flowing.
• No water, oil or chemicals or where the vapors of these substances can come into direct contact with the unit
• Take note that ambient temperature of this unit - not the ambient temperature of the control
panel - must not exceed 50
(122 ) if mounted through the control panel. Otherwise the life
of electronic components (especially electrolytic capacitor) may be shortened.
Note: Avoid setting this instrument directly on or near flammable material even
though the case of this instrument is made of flame-resistant resin.
22.. WWiirriinngg PPrreeccaauuttiioonnss
Caution
• Do not leave bits of wire in the instrument, because they could cause a fire or malfunction.
• Use the solderless terminal with an insulation sleeve in which an M3 screw fits when wiring the FCR-13A.
• The terminal block of this instrument is designed to be wired from the left side.
The lead wire must be inserted from the left side of the terminal, and fastened with the
terminal screw.
• Tighten the terminal screw within the specified torque. If excessive force is applied to the screw when tightening, the screw or case may be damaged.
• Do not apply a commercial power source to the sensor connected to the input terminal
nor allow the power source to come into contact with the sensor, as the input circuit
may be burnt out.
• This controller has no built-in power switch, circuit breaker or fuse. It is necessary to install them near the controller. (Recommended fuse: Time-lag fuse, rated voltage 250V AC, rated current 2A)
• For a 24V AC/DC power source, do not confuse polarity when using direct current (DC).
33.. OOppeerraattiioonn aanndd MMaaiinntteennaannccee PPrreeccaauuttiioonns
s
Caution
• It is recommended that AT (auto-tuning) be performed on the trial run.
• Do not touch live terminals. This may cause electric shock or problems in operation.
• Turn the power supply to the instrument OFF when retightening the terminal and cleaning. Working on or touching the terminal with the power switched ON may result in severe injury or death due to electric shock.
• Use a soft, dry cloth when cleaning the instrument.
(Alcohol based substances may tarnish or deface the unit.)
• As the display section is vulnerable, do not strike or scratch it with a hard object or put pressure on it.
Page 5
5
--- CONTENTS ---
1. Model
1.1 Model ---------------------------------------------------------------------------------------- 8
1.2 Rated Input --------------------------------------------------------------------------------- 9
1.3 How to Read the Model Label --------------------------------------- ------------------ 9
2. Name and Functions of Sections ----------------------------------------------- 10
3. Setup
3.1 Drawing the Internal Assembly Out ------------------------------------------------ 12
3.2 Switch Setting (Multi-function) ------------------------------------------------------- 12
3.3 Inserting the Internal Assembly ----------------------------------------------------- 15
4. Mounting to the Control Panel
4.1 Site Selection ----------------------------------------------------- ----------------------- 15
4.2 External Dimensions (Scale: mm) -------------------------------------------------- 15
4.3 Panel Cutout (Scale: mm) ------------------------------------------------------------ 16
4.4 Current Transformer (CT) Dimensions (Scale: mm) --------------------------- 16
4.5 Mounting ---------------------------------------------------------------------------------- 17
5. Wiring
5.1 Terminal Arrangement ----------------------------------------------------------------- 19
5.2 Wiring Examples ------------------------------------------------------------------------ 20
5.2.1 Current Transformer 1(CT1), 2(CT2) Input Wiring (W/W3 Option) --- 21
6. Settings
6.1 Operation Flowchart ------------------------------------------------------------------- 22
6.2 Settings ----------------------------------------------------------------------------------- 24
6.2.1 Main Setting Mode ----------------------------------------------------------------- 25 SV ----------------------------------------------------------------------------------------- 25
6.2.2 Sub Setting Mode Set value memory number ----------------------------------------- ----------------- 25 AT Perform/Cancel -------------------------------------------------------------------- 25 OUT1 proportional band ------------------------------------------------------------- 25 OUT2 proportional band ------------------------------------------------------------- 25 Integral time ----------------------------------------------------------------------------- 26 Derivative time ------------------------------------------------------------------------- 26 OUT1 proportional cycle ------------------------------------------------------------- 26 OUT2 proportional cycle ------------------------------------------------------------- 26 Manual reset ---------------------------------------------------------------------------- 26 A1 value ---------------------------------------------------------------------------------- 26 A2 value ---------------------------------------------------------------------------------- 26 Heater burnout alarm value ------------------------------------- -------------------- 27 Loop break alarm time ---------------------------------------------------------------- 27 Loop break alarm span --------------------------------------------------------------- 27
Page 6
6
6.2.3 Auxiliary Function Setting Mode 1 Set value lock --------------------------------------------------------------------------- 28 SV high limit ----------------------------------------------------------------------------- 29 SV low limit --------------------------------------------------- --------------------------- 29 Sensor correction ---------------------------------------------------------------------- 29 Overlap/Dead band ------------------------------------------------------------------- 29 Remote/Local setting -------------------------------------------------- --------------- 29 Instrument number -------------------------------------------------------------------- 30 Communication speed --------------------------------------------------------------- 30 Communication protocol -------------------------------------------- ----------------- 30
6.2.4 Auxiliary Function Setting Mode 2 Scaling high limit value --------------------------------------------------------------- 30
Scaling low limit value ---------------------------------------------------------------- 30 Decimal point place ----------------------------------------- -------------------------- 31 PV filter time constant ------------------------------------------------------------ ---- 31 OUT1 high limit value ----------------------------------------------------------------- 31 OUT1 low limit value ------------------------------------------------------------------ 31 OUT1 ON/OFF hysteresis ------------------------------------------------ ----------- 31 OUT2 action mode -------------------------------------------------------------------- 31 OUT2 high limit value ----------------------------------------------------------------- 31 OUT2 low limit value ------------------------------------------------------------------ 31 OUT2 ON/OFF hysteresis ------------------------------------------------ ----------- 32 A1 action Energized/De-energized ------------------------------------------------ 32 A2 action Energized/De-energized ------------------------------------------------ 32 A1 hysteresis --------------------------------------------------------------------------- 32 A2 hysteresis --------------------------------------------------------------------------- 32 A1 action delay time ---------------------------------------------- -------------------- 32 A2 action delay time ---------------------------------------------- -------------------- 32 External setting input high limit ----------------------------------------------------- 33 External setting input low limit ------------------------------------------------------ 33 Transmission output ------------------------------------------------------------------- 33 Transmission output high limit ------------------------------------------------------ 33 Transmission output low limit ------------------------------------------------------- 33 Indication when control output OFF ------------------------------------------- ---- 33 SV rise rate --------------------------------------------------- --------------------------- 33 SV fall rate ------------------------------------------------------------------------------- 34 Output status when input error ------------------------------------------- ---------- 34
6.2.5 Program Mode --------------------------------------- -------------------------------- 34
Fixed value control/Program control switching --------------------------------- 35 Step 1 time ------------------------------------------------------------------------------- 35 Step 2 time ------------------------------------------------------------------------------- 35 Step 3 time ------------------------------------------------------------------------------- 35 Step 4 time ------------------------------------------------------------------------------- 35 Step 5 time ------------------------------------------------------------------------------- 35 Step 6 time ------------------------------------------------------------------------------- 36 Step 7 time ------------------------------------------------------------------------------- 36
Page 7
7
6.2.6 Auto/Manual Control Switching -------------------------------------------------- 36
6.2.7 Control Output OFF Function ---------------------------------------------------- 36
6.2.8 MV, Remaining Step Time Indication ------------------------------------------- 36
7. Set Value Memory Function (SM Option) -------------------------------------- 37
8. Operation
8.1 When Using the FCR-13A as a Temperature Controller ---------------------- 38
8.2 When Using the FCR-13A as a Simplified Programmable Controller ----- 39
9. Action Explanations
9.1 OUT1 Standard Control Action --------------------------------------- --------------- 40
9.2 Heater Burnout Alarm Action (Optional) ------------------------------------------ 40
9.3 OUT1 ON/OFF Control Action ------------------------------------------------------ 41
9.4 Pattern End Action --------------------------------------------------------------------- 41
9.5 Heating/Cooling Control Action (DR, DS, DA Option)
9.5.1 Heating/Cooling Control Action ------------------------------------------------- 42
9.5.2 When Setting Dead Band -------------------------------------------------------- 43
9.5.3 When Setting Overlap Band with Relay Contact Output ----------------- 44
9.6 Alarm 1 (A1), Alarm 2 (A2) Action -------------------------------------------------- 45
10. Control Actions
10.1 Fuzzy Self-tuning --------------------------------------------------------------------- 47
10.2 PID --------------------------------------------------------------------------------------- 47
10.3 AT of This Controller ----------------------------------------------------------------- 48
11. Specifications
11.1 Standard Specifications ------------------------------------------------------------- 49
11.2 Optional Specifications -------------------------------------------------------------- 54
12. Troubleshooting ---------------------------------------------------------------------- 57
13. Character Table ------------------------------------------------------------------------ 59
Page 8
8
1. Model
1.1 Model
Alphanumeric characters to represent the control output (OUT1), input or options are entered where underlined.
[Example]
FCR - 13A - R / M, A2
Alarm 2 (A2) output Multi-range input Relay contact output
Standard specifications
F C R – 1 3 A -
/ Control action 3 PID control *1 Alarm 1 (A1) A Alarm types can be selected. *2
Control output (OUT1)
R Relay contact S Non-contact voltage (for SSR drive) A Direct current
Input M Multi-range *3
*1: Fuzzy self-tuning PID, PID, PD, ON/OFF control can be selected by internal DIP switch. *2: 12 types of alarm plus No alarm action can be selected by internal DIP and Rotary
switches.
*3: An input type can be selected by DIP and Rotary switches from a choice of:
Thermocouple (10 types), RTD (3 types), Direct current (2 types) and DC voltage (1 type).
Optional specifications
Code Option name
A2 Alarm 2 (A2) output (including Pattern end 2 output) DR
Heating/Cooling control output (OUT2)
Relay contact DS Non-contact voltage DA Direct current TA
Transmission output
Direct current (4 to 20mA DC) TV DC voltage (0 to 1V DC) C5 Serial
communication
RS-485 C RS-232C SM Set value memory external selection EA
External setting input
Direct current (0 to 20mA DC, 4 to 20mA DC) EV DC voltage (0 to 1V DC, 1 to 5V DC) W HB (Heater burnout
alarm)
Single-phase W3 Three-phases LA Loop break alarm P24 Insulated power output BL Screw type mounting bracket BK Color: Black IP Drip-proof/Dust-proof TC Terminal cover
(For options in detail, see Section “11.2 Optional Specifications”.)
Page 9
9
Warning
Do not take the inner assembly out nor touch the terminal with the power
supply ON. Touching the terminal with the power switched ON may result in severe injury or death due to electric shock.
1.2 Rated Input Input type Input range Resolution
K –200 to 1370 –320 to 2500 1 ( )
J
–200 to 1000
–320 to 1800 1 ( )
R 0 to 1760 0 to 3200 1 ( )
B 0 to 1820 0 to 3300 1 ( )
PL- 0 to 1390 0 to 2500 1 ( )
N 0 to 1300 0 to 2300 1 ( )
S 0 to 1760 0 to 3200 1 ( ) E
0 to 1000
0 to 1800 1 ( )
T –199.9 to 400.0 –199.9 to 750.0 0.1 ( )
C(W/Re5-26) 0 to 2315 0 to 4200 1 ( )
Pt100
–199.9 to 850.0
–199.9 to 999.9 0.1 ( )
–200 to 850 –320 to 1560 1 ( )
JPt100 –199.9 to 500.0 –199.9 to 900.0 0.1 ( ) 4 to 20mA DC –1999 to 9999 * 1 0 to 20mA DC –1999 to 9999 * 1
0 to 1V DC
–1999 to 9999 * 1
*: For DC input, input range and decimal point place can be changed.
1.3 How to Read the Model Label
Model labels are attached to the case and the inner assembly.
Model label
Model Option Input Output Power supply, power consumption
A
mbient temperature
Serial number
Page 10
10
2 Name and Functions of Sections
(1)
(2) (4) (5) (3) (6) (11) (7) (12) (8) (13) (14) (9) (15) (16) (10) (17)
(Fig. 2-1)
(1) PV display (Red)
Indicates the PV or setting characters in the setting mode.
(2) SV/MV/TIME display (Green)
Indicates the SV, MV, Time or set values in each setting mode.
(3) MEMO display (Yellow)
Indicates the Set value memory number.
(4) SV indicator (Green)
Lights while the SV is indicated on the SV/MV/TIME display.
(5) MV indicator (Red)
Lights while the MV is indicated on the SV/MV/TIME display.
(6) TIME indicator (Yellow)
Lights while the Time is indicated on the SV/MV/TIME display.
(7) MAN indicator (Red)
Lights during Manual control.
(8) OUT1 indicator (Green)
Lights when OUT1 (control output 1) is on. (For Direct current output type, flashes corresponding to the MV in 125ms cycles.)
Page 11
11
(9) OUT2 indicator (Yellow)
Lights when OUT2 (control output 2) is on. (For Direct current output type, flashes corresponding to the MV in 125ms cycles.)
(10) TX/RX indicator (Green)
Lights during Serial communication [TX (transmitting) output].
(11) A1 indicator (including Pattern end 1 output) (Red)
Lights when the Alarm 1 (A1) output or Pattern end 1 output is on.
(12) A2 indicator (including Pattern end 2 output) (Red) (Option)
Lights when the Alarm 2 (A2) output or Pattern end 2 output is on.
(13) HB indicator (Red)
Lights when the Heater burnout alarm output is on.
(14) SB indicator (Red)
Lights when Sensor is burnt out.
(15) REM indicator (Red)
Lights during Remote operation.
(16) LA indicator (Red)
Lights when the Loop break alarm output is on.
(17) AT indicator (Yellow)
Flashes during AT (auto-tuning).
Keys
Increase key: Increases the numeric value on the SV/MV/TIME display
in the setting mode.
Decrease key: Decreases the numeric value on the SV/MV/TIME display
in the setting mode.
Mode key: Switches a setting mode and registers set values.
[To register each set (or selected) value, press this key.]
OUT/OFF key: Performs the control output ON or OFF (Fixed value control).
Starts/Stops the program control (Program control).
Auto/Manual key: Switches either Automatic control or Manual control. Fast key: Makes the numerical value change faster by pressing the
key with the or key simultaneously.
Page 12
12
3. Setup
3.1 Drawing the Internal Assembly Out
Before the power supply to this instrument is turned on, take the internal assembly out from the case in the direction indicated by the arrow by pushing the latch (bottom of the instrument) while holding the instrument by the top and bottom.
(Fig. 3.1-1)
3.2 Switch Setting (Multi-function)
Using a small flat blade screwdriver and tweezers, set the following with the DIP and Rotary switches.
Sensor input, Alarm 1 (A1) type, Alarm 2 (A2) type, Control action, Heating (reverse)/Cooling (direct) action, Alarm 1 (A1) and Alarm 2 (A2) standby actions,
/ , Program start Auto/Manual
Rotary switch (SW301) will be equipped only when A2 option is ordered.
Control action Alarm 2 type Heating/Cooling action Alarm 1 type Alarm 1 standby action Sensor input Alarm 2 standby action
/
Sensor input Program start Auto/Manual
(Fig. 3.2-1)
DIP switch
Rotary switch
Latch
Draw out the FCR-13A toward you by pushing the latch.
Page 13
13
The following items can be selected by the DIP switch (SW304). Default value: All switches OFF.
(Table 3.2-1)
Item
DIP
SW304
No.
Selection Switch status
Control action 1 and
2
Fuzzy self-tuning PID control No.1: OFF No.2: OFF PID control No.1: ON No.2: OFF PD control No.1: OFF No.2: ON
ON/OFF control No.1: ON No.2: ON Heating/Cooling action
3
Heating (reverse) action No.3: OFF
Cooling (direct) action No.3: ON Alarm 1 (A1) standby action
4
Without standby action No.4: OFF
Standby action No.4: ON Alarm 2 (A2) standby action (*1)
5
Without standby action No.5: OFF
Standby action
No.5: ON
/
6
No.6: OFF No.6: ON
Sensor input (*2)
7
K, J, R, B, N, PL-
, Pt100, JPt100
No.7: OFF S, E, T, C, 4 to 20mA, 0 to 20mA, 0 to 1V, Pt100
No.7: ON
Program start Auto/Manual (*3)
8
Manual start No.8: OFF Automatic start
No.8: ON
(*1) The standby function will work only when the A2 option is ordered. (*2) Use the Rotary switch (SW303) and DIP switch (SW304) together for making a
selection.
(*3) Program start Auto/Manual: For program control
Manual start: The preset program starts by pressing the
key. Automatic start: The preset program automatically starts from Step 1 after 2 seconds of warm-up status after power-on.
Page 14
14
Select a sensor type using the Rotary switch (SW303) and DIP switch (SW304). Default value: K -200 to 1370
Note: If the input type is changed, Scaling high/low limit, External setting
input high/low limit and transmission output high/low limit values (optional) will become the altered input range high/low limit value.
(Table 3.2-2)
Rotary SW303
No.
DIP
SW304
No. 7
Sensor type
Range (DIP SW304 No.6) OFF ON
0 OFF K -200 to 1370 -320 to 2500 1 OFF J -200 to 1000 -320 to 1800
2 OFF R 0 to 1760 0 to 3200 3 OFF B 0 to 1820 0 to 3300 4 OFF PL- 0 to 1390 0 to 2500 5 OFF N 0 to 1300 0 to 2300 6 OFF Pt100 -199.9 to 850.0 -199.9 to 999.9 7 OFF JPt100 -199.9 to 500.0 -199.9 to 900.0
0 ON S 0 to 1760 0 to 3200 1 ON E 0 to 1000 0 to 1800 2 ON T -199.9 to 400.0 -199.9 to 750.0 3 ON C (W/Re5-26) 0 to 2315 0 to 4200 4 ON 4 to 20mA DC -1999 to 9999 5 ON 0 to 20mA DC -1999 to 9999 6 ON 0 to 1V DC -1999 to 9999 7 ON Pt100 -200 to 850 -320 to 1560
The alarm type and the pattern end output for program control can be selected by the Rotary switches (SW302) and (SW301). Rotary switch (SW301) will be equipped only when A2 option is ordered.
Rotary SW302: Alarm 1 (A1) type, Pattern end 1 output Rotary SW301: Alarm 2 (A2) type, Pattern end 2 output
Note: If an alarm type is changed, the alarm set value becomes 0 (0.0).
Default value: No alarm action
(Table 3.2-3)
Alarm 1 (A1) type
Rotary
SW302
No.
Alarm 2 (A2) type
Rotary
SW301
No.
No alarm action 0 No alarm action 0 High limit alarm 1 High limit alarm 1 Low limit alarm 2 Low limit alarm 2 High/Low limits alarm 3 High/Low limits alarm 3 High/Low limit range alarm 4 High/Low limit range alarm 4 Process high alarm 5 Process high alarm 5 Process low alarm 6 Process low alarm 6 Pattern end 1 output 7 Pattern end 2 output 7
Page 15
15
3.3 Inserting the Internal Assembly
After the setup is completed, insert the internal assembly into the case. Firmly insert the assembly until it is locked by the latch at the bottom of the instrument. (There will be a clicking sound.)
Caution
Do not confuse the top and bottom of the internal assembly. If inserting the assembly into the case by force in the wrong direction, the PCB may be damaged.
4. Mounting to the Control Panel
4.1 Site Selection
Ensure the mounting location corresponds to the following conditions (IEC61010-1): Overvoltage category
, Pollution degree 2 (1) A minimum of dust, and an absence of corrosive gases (2) No flammable, explosive gases (3) No mechanical vibrations or shocks (4) No exposure to direct sunlight, an ambient temperature of 0 to 50
(32 to 122 )
that does not change rapidly, and no icing (5) An ambient non-condensing humidity of 35 to 85%RH (6) No large capacity electromagnetic switches or cables through which large current
flows (7) No water, oil or chemicals or where the vapors of these substances can come into
direct contact with the unit (8) Take note that ambient temperature of this unit - not the ambient temperature of the
control panel - must not exceed 50
(122 ) if mounted through the control panel. Otherwi se t he l if e o f electronic components (especially electrolytic capacitor) may be shortened.
4.2 External Dimensions (Scale: mm)
(Fig. 4.2-1)
48
96
10
100
106 (for TC option)
91
106.2 (for BL option)
109
Page 16
16
4.3 Panel Cutout (Scale: mm)
Lateral close mounting n: Number of units mounted
(Fig. 4.3-1)
4.4 Current Transformer (CT) Dimensions (Scale: mm)
CT L- 6 S (f o r 20 A ) CTL-12-S36-10L1U (for 50 A ) (Fig. 4.4-1)
130
92
+0.8
0
45
+0.5
0
n x 48-3
+0.5
0
92
+0.8
0
Page 17
17
4.5 Mounting
Warning
As the case is made of resin, do not use excessive force while screwing in the mounting bracket, or the case could be damaged. The torque should be 0.12N•m.
• When using the One-touch type mounting bracket
Mountable panel thickness: 1 to 3mm. If Soft front cover (FC-R-S) is used, mounting
panel thickness will be 1 to 2.5mm. Mount one-touch mounting bracket
1
to the
instrument first, and then insert the FCR-13A
2
fr om th e f r ont of the panel.
(Fig. 4.5-1)
• When using the Screw type mounting bracket (BL option)
Mountable panel thickness: 1 to 8mm.
If Soft front cover (FC-R-S) is used, mounting panel thickness will be 1 to 7.5mm.
Insert the FCR-13A from the front of the panel.
Attach the mounting brackets to the slots at the top and bottom of the case,
and secure the controller in place with the screws provided.
(Fig. 4.5-2)
2
1
1
Page 18
18
5. Wiring Warning
Turn the power supply to the instrument off before wiring or checking. Working on or touching the terminal with the power switched on may result in severe injury or death due to electric shock. Moreover, the instrument must be grounded before the power supply to the
instrument is turned on.
Caution
• Do not leave wire remnants in the instrument, as they could cause a fire or a malfunction.
• Use a solderless terminal with an insulation sleeve in which the M3 screw fits when wiring the controller.
• The terminal block of this instrument is designed to be wired from the left side. The lead wire must be inserted from the left side of the terminal, and fastened by the terminal screw.
• Tighten the terminal screw using the specified torque. If excessive force is applied to the screw when tightening, the terminal screw may be damage d .
• Do not apply a commercial power source to the sensor which is connected to the input terminal nor allow the power source to come into contact with the sensor.
• This controller does not have a built-in power switch, circuit breaker or fuse. Therefore, it is necessary to install them in a circuit externally, near the controller.
(Recommended fuse: Time-lag fuse, rated voltage 250V AC, rated current 2A)
• For a 24V AC/DC power source, do not confuse polarity when using direct current (DC).
• Use a thermocouple and compensating lead wire according to the sensor input specifications of this controller .
• Use a 3-wire RTD according to the sensor input specifications of this controller.
• When using a relay contact output type, use a relay according to the capacity of the load to protect the built-in relay contact.
• When wiring, keep input wires (thermocouple, RTD, etc.) away from AC sources or load wires.
• Use a thick wire (1.25 to 2.0mm
2
) for grounding.
Lead Wire Solderless Terminal Use a solderless terminal with an insulation sleeve in which an M3 screw fits as shown below. The torque should be 0.63N•m.
Solderless
terminal
Manufacturer Model Torque
Y type
Nichifu Terminal Industries CO.,LTD. TMEV1.25Y-3
0.63N•m
Japan Solderless Terminal MFG CO.,LTD. VD1.25-B3A
Ring type
Nichifu Terminal Industries CO.,LTD. TMEV1.25-3 Japan Solderless Terminal MFG CO.,LTD. V1.25-3
(Fig. 5-1)
3.2mm
5.8mm or less
3.2mm
5.8mm or less
Page 19
19
COM
b2
b1
b0
SM
W or W3
TA or TV
EA or EV
CT2
CT1
A1/P.END1
OUT1
(R/M)
H
C
L
TC
TX [YA( )]
RX [YB( )]
100 to240V AC
AC/DC or 24V
A
B
B
OUT1
(S/M, A/M)
V DC
mA DC
RS-232C (RS-485)
OUT2(DR)/A2/
P.END2/LA/P24
OUT2(DS,DA)/A2
/P.END2/LA/P24
Ground
+
-
+
+
-
-
+
-
+
-
+
-
+
-
-
+
+
-
8
7
9
10
20
19
19
19
17
16
17
18
18
18
8
7
6
5
4
3
2
1 11
12
13
14
15
5
6
RTD
5.1 Terminal Arrangement
(Fig. 5.1-1)
Dotted lines show options, and no terminal is equipped unless specified. If Alarm 2 (A2 option/Pattern end 2) and Loop break alarm (LA option)
are ordered together, they will utilize common output terminals. OUT1: Control output 1
OUT2: Control output 2 A1: Alarm 1 output A2: Alarm 2 output P.END1: Pattern end 1 output P.END2: Pattern end 2 output LA: Loop break alarm output P24: Insulated power output RS-232C (RS-485): Serial communication SM: Set value memory number external selection TC: Thermocouple input RTD: RTD input DC: DC voltage, current input EA or EV: External setting input CT1, CT2: CT1 input (W, W3 option), CT2 input (W3 option) W or W3: Heater burnout alarm output TA or TV: Transmission output
Page 20
20
5.2 Wiring Examples [FCR-13A-R/M]
* To prevent the unit from harmful effects of unexpected level noise, it is recommended
that a surge absorber be installed between the electromagnetic switch coils.
(Fig. 5.2-1)
[FCR-13A-S/M, W Power supply: 24V DC]
• The connectable SSRs in parallel are 2 units if the Shinko SSRs (SA-500 series) are
used.
• For a 24V AC/DC power source, do not confuse polarity when using direct current (DC).
(Fig. 5.2-2)
3-phase
Heater
Electric furnace
Thermocouple
100 to 240V AC
Power supply for Alarm unit
Alarm unit
Electro-
magnetic
switch
*
CT
SSR
Single-phase
Alarm unit
24V
Thermocouple
Heater
Electric furnace
W
CT1
Ground
Page 21
21
5.2.1 Current Transformer 1 (CT1), 2 (CT2) Input Wiri ng (W /W 3 Op tion)
[Heater burnout alarm output]
(1) This alarm is not usable for detecting current under phase control. (2) Use the current transformer (CT) provided, and pass one lead wire of heater
circuit into the hole of the CT.
(3) When wiring, keep CT wire away from AC sources and load wires to avoid the
external interference.
[Single-phase heater]
CT1 input connector CT1
Power supply
Heater (Fig. 5.2-3)
[Three-phase heater]
(Fig. 5.2-4)
[Mounting the wire harness]
(Fig. 5.2-5)
3-phase heater
CT1
CT2
R
S
T
Power supply
CT1 input connector
CT2 input connector
CT1
CT2
W or W3
Page 22
22
6. Settings
6.1 Operation Flowchart
Power ON
(*1) (*1)
Control output OFF function (Fixed value control)
Manual control (Fixed value control) (*1) Standby mode (Program control)
MV indication Remaining step time indication (*2)
[Main setting mode] [Sub setting mode] [Auxiliary function setting mode 1]
[
] SV [ ] Set value memory number [ ] Set value lock
[ ] AT Perform/Cancel (*3) [ ] SV high limit
[ ] OUT1 proportional band [ ] SV low limit
[ ] OUT2 proportional band [ ] Sensor correction
[ ] Integral time [ ] Overlap/Dead band
[ ] Derivative time [ ] Remote/Local
[ ] OUT1 proportional cycle [ ] Instrument number
[ ] OUT2 proportional cycle [ ] Communication speed
[ ] Manual reset [ ] Communication protocol
[ ] Alarm 1 (A1) value
[ ] Alarm 2 (A2) value
[ xx.x] Heater burnout alarm value
[ ] Loop break alarm time
[ ] Loop break alarm span
+
+ (appprox. 3sec)
(approx. 1sec)
(approx. 1sec)
(approx. 3sec)
PV/SV display mode
Page 23
23
: Setting items with dotted lines are optional, and they appear only when the options are ordered.
: This means that if the is pressed, the unit proceeds to the next setting item.
+ : Press the key while holding down the key. +
(approx.3sec):
Press the key for approx. 3 sec while holding down the key.
+ +
(approx.3sec):
Press the for approx.3 sec while holding down the , .
+
(approx.3sec):
Press the for 3 sec while holding down the key.
If the
is pressed for 3 sec, the unit reverts to the PV/SV display mode from any mode.
(*1)
: Warm-up status lasts 2 sec a fter power-on, then start s from previous controller status (last shutdown).
(*2): Remaining step time is indicated only during program control. (*3): If AT is performed, the unit reverts to the PV/SV display mode.
If AT is cancelled, the unit proceeds to the [OUT1 proportional band].
(*4):
Select in this mode and press the . The unit reverts to the PV/SV display mode.
[Auxiliary function setting mode2]
[Program mode]
[ ] Scaling high limit [ ]
A1 action delay time
[ ] Program control
(*4)
[ ] Scaling low limit [ ]
A2 action delay time
[ ] Step 1 time
[ ] Decimal point place [ ] External setting
input high limit
[ ] Step 2 time
[ ] PV filter time constant [ ] Step 3 time
[ ] External setting
input low limit
[ ] OUT1 high limit [ ] Step 4 time [ ] OUT1 low limit [ ] Transmission output [ ] Step 5 time
[ ]
OUT1 ON/OFF hysteresis
[ ] Transmission
output high limit
[ ] Step 6 time
[ ] OUT2 action mode [ ] Step 7 time
[ ] Transmission
output low limit
[ ] OUT2 high limit [ ] OUT2 low limit [ ] Indication when
control output OFF
[ ]
OUT2 ON/OFF hysteresis
[ ] SV rise rate
[ ]
A1 Energized/De-energized
[ ] SV fall rate
[ ]
A2 Energized/De-energized
[ ]
Output status when
input error
[ ] A1 hysteresis
[ ] A2 hysteresis
+ +
(Appprox. 3sec)
+
(Appprox. 3sec)
Page 24
24
6.2 Settings
The PV display indicates the sensor characters selected in [Sensor input], and the SV/MV/TIME display indicates input range high limit (or Scaling high limit value for DC voltage, current inputs) for approx. 2 seconds (warm-up status) after power-on. See (Table 6.2-1). During this time, all outputs and LED indicators are in OFF status. Control will then start, indicating PV on the PV display and SV on the SV/MV/TIME display. While control output OFF function is working, the PV display indicates the item selected in [Indication when control output OFF].
(Table 6.2-1)
Input
PV display
SV/MV/TIME
display
PV display
SV/MV/TIME
display
K
J R B
PL-
N S E T
C(W/Re5-26)
Pt100
JPt100
Pt100
4 to 20mA DC
Scaling high limit value
Scaling high limit value
0 to 20mA DC 0 to 1V DC
Notes before key operation
• Pressing the
key for approx. 1 second from any mode enables the control output OFF function. Once the control output OFF function is enabled, the function cannot be released even if the power to the instrument is turned OFF and ON again. To cancel the function, press the
key again for appro x. 1 second.
In the program control, the
key works as program Start/Stop key.
The control output OFF function does not work.
• If the
is pressed for 3 sec, the unit will revert to the PV/SV display mode from any
mode.
Page 25
25
6.2.1 Main Setting Mode
In the PV/SV display mode, if the
key is pressed, the unit proceeds to the Main
setting mode. The SV can be increased or decreased using the , and keys. If the
key is pressed, the SV will be registered, and the controller will revert to the
PV/SV display mode.
Character Name, Function, Setting range Default value
SV 0
• Sets SV (desired value).
• Setting range: SV low limit to SV high limit
6.2.2 Sub Setting Mode
In the PV/SV display mode, if the
key is pressed while holding down the key, the unit moves to the Sub setting mode. The set value can be increased or decreased using the
, and keys. Pressing the key registers the set value, and proceeds to the next setting item. Pressing the
key at the last setting item registers the set value, and the unit
reverts to the PV/SV display mode.
Character Name, Function, Setting range Default value
Set value memory number 1
• Selects the number (file) to be set or to be retrieved.
• Selection range: 1 to 7 AT Perform/Cancel AT Cancel
• Sets AT (Auto-tuning) Perform or Cancel. If the
key is pressed after selecting AT Perform, the unit reverts to
the PV/SV display mode.
• Not available if ON/OFF or PD control is selected in [Control action].
• During AT, none of the settings can be per formed .
• If the AT is cancelled during the process, P, I, D values revert to the
values before AT was performed.
• Selection item:
: A T Cancel : A T Perform
OUT1 proportional band 2.5%
• Sets OUT1 proportional band.
OUT1 proportional band depends on the scaling span. (e.g.) When OUT1 proportional band: 2.5%, -200 to 1370
: OUT1 proportional band converted value: (1370-(-200))x2.5/100=39.25 When scaling high limit value: 100
, scaling low limit value: 0
OUT1 proportional band converted value: (100-0)x2.5/100=2.5
• Not available if ON/OFF control is selected in [Control action].
• Setting range: 0.1 to 999.9%
OUT2 proportional band
• Sets OUT2 proportional band.
1.0 times (2.5%)
• OUT2 becomes ON/OFF control when set to 0.0.
• Not available if Heating/Cooling control (DR, DS, DA option) is not
ordered, or if ON/OFF control is selected in [Control action].
• Setting range: 0.0 to 10.0 times (multiplied value of OUT1 proportional band)
Page 26
26
Character Name, Function, Setting range Default value
Integral time 200 sec
• Sets the integral time. Setting the value to 0 disables the function (PD control).
• Not available if ON/OFF control or PD control is selected in [Control
action].
• Setting range: 0 to 3600 seconds Derivative time 50 sec
• Sets the derivative time. Setting the value to 0 disables the function (PI control).
• Not available if ON/OFF control is selected in [Control action].
• Setting range: 0 to 3600 seconds OUT1 proportional cycle
• Sets OUT1 proportional cycle.
Relay contact output: 30 sec Non-contact voltage output: 3 sec
• Not available for Direct current output type or if ON/OFF control is selected in [Control action].
For the relay contact output type, if the proportional cycle time is
decreased, the frequency of the relay action increases, and the life of the relay contact is shortened.
• Setting range: 1 to 120 seconds OUT2 proportional cycle
• Sets OUT2 proportional cycle.
Relay contact output: 30 sec Non-contact voltage output: 3 sec
• Not available for Direct current output type.
Not available if Heating/Cooling control (DR, DS, DA option) is not ordered, or if ON/OFF control is selected in [Control action].
For the relay contact output type, if the proportional cycle time is
decreased, the frequency of the relay action increases, and the life of the relay contact is shortened.
• Setting range: 1 to 120 seconds Manual reset 0.0
• Sets the reset value to correct the offset (deviation between SV and PV
in equilibrium status).
• Available only when PD control is sele cted in [Contro l action].
• Setting range:
Proportional band converted value
Thermocouple, RTD inputs: -199.9 to 999.9
DC voltage input: -1999 to 9999 (The placement of the decimal point
follows the selection.)
How to set manual reset:
When SV>PV, set the positive (+) value (SV–PV). When SV<PV, set the negative (–) value (SV–PV).
A
1 value 0
• Sets the action point of Alarm 1 (A1) output.
Setting the value to 0 or 0.0 disables the function (except Process
high and Process low alarm).
• Not available if the Rotary switch is set to No.0 or No.7
• Setting range: Refer to (Table 6.2.2-1).
A2 value
0
• Sets the action point of Alarm 2 (A2) output.
Setting the value to 0 or 0.0 disables the function (except Process high and Process low alarm).
• Not available if A2 output (option) is not ordered, or if Rotary switch is
set to No.0 or No.7 in [A2 type] even if it is ordered.
• Setting range: Refer to (Table 6.2.2-1).
Page 27
27
Characte
r
Name, Function, Setting range Default value
xx.x
(xx.x:
Heater current value)
Heater burnout alarm value 0.0A
• Sets the heater current value for Heater burnout alarm.
• Setting the value to 0.0 disables the function.
• Available only when Heater burnout alarm (W, W3 option) is ordered.
• It is recommended to set approx. 80% of the heater current value (set value) considering the voltage fluctuation.
• Upon returning to set limits, the alarm will stop.
• Setting range:
Rated current 20A: 0.0 to 20.0A (Indication: 0.0 to 50.0) Rated current 50A: 0.0 to 50.0A
Loop break alarm time
0 minutes
• Sets the time to assess the Loop break alarm.
• Available only when Loop break alarm (LA option) is ordered
• Setting range: 0 to 200 minutes Loop break alarm span 0
• Sets the span to assess the Loop break alarm.
• Available only when Loop break alarm (LA option) is ordered
• Setting range:
Thermocouple, RTD without decimal point: 0 to 150 Thermocouple, RTD with decimal point: 0.0 to 150.0
DC input: 0 to 1500 (The placement of the decimal point follows the
selection.)
[A1, A2 setting range] Alarms with the standby function have the same setting range.
(Table 6.2.2-1)
Alarm type Setting range High limit alarm –Input span to Input span ( ) *1 Low limit alarm –Input span to Input span ( ) *1 High/Low limits alarm 0 to Input span ( ) *1 High/Low limit range alarm 0 to Input span ( ) *1 Process high alarm Input range low limit to Input range high limit *2 Process low alarm Input range low limit to Input range high limit *2
• For RTD input, the negative low limit value is –199.9.
• For DC input, the negative low limit value is –1999. (The placement of the decimal point follows the selection.) *1: For DC input, the Input span is the same as the Scaling span. *2: For DC input, Input range low (or high) limit value is the same as the Scaling low
(or high) limit value.
[Loop break alarm]
Detects the breaking status on the loop such as heater burnout, sensor burnout or actuator trouble. When the control action is Heating (Reverse) control:
• The alarm will be activated when the PV does not rise as much as the alarm span or more within the loop break alarm time after the MV has reached 100% or the output high limit value.
• The alarm will also be activated when the PV does not fall as much value as the span or more within the loop break alarm time after the MV has reached 0% or the output low limit value.
When the control action is Direct (Cooling), read “fall” for “rise” and vice versa.
Page 28
28
6.2.3 Auxiliary Function Setting Mode 1 In the PV/SV display mode, if the
key is pressed for approx. 3 seconds while
holding down the
key, the unit proceeds to Auxiliary function setting mode 1.
The set value can be increased or decreased by pressing the
, and
keys.
Pressing the
key registers the set value and proceeds to the next setting item.
If the
key is pressed at the last setting item, the set value will be registered and
the unit will revert to the PV/SV display mode.
Character Name, Function, Setting range Default value
Set value lock Unlock
• Locks the set value to prevent setting errors. The setting item to be locked differs depending on the selection.
• When selecting Lock, set the necessary items in the status Unlock, then select Lock 1, Lock 2 or Lock 3.
Fuzzy self-tuning or AT will not function if [
] or [ ] is
selected.
• Be sure to select Lock 3 when changing the set value frequently via communication function considering the life of non-volatile memory.
• Selection item:
(Unlock): All set values can be changed. (Lock 1): None of set values can be changed. (Lock 2): Only SV can be changed.
(Lock 3): All set values can be changed temporarily. However,
changed values revert to their previous value after power-off because they are not saved in the non-volatile memory.
Since this function has no relation to the memory life, it is well suited when using with Shinko programmable controllers (with SVTC option).
[About Lock 3] When using the FCR -13A as a Fixed value controller
The data in the selected Set value memory number can be temporarily changed. However, if the memory number is changed, the data in the previous memory number is cancelled, and returns to the previous values.
When using the FCR -13A as a Programmable controller
The data in the currently performing step number can be temporarily changed. However, if the step number is changed, the data is cancelled, and returns to the previous values.
During program standby status, the data changes will be invalidated.
Page 29
29
Character Name, Function, Setting range Default value
SV high limit 400
• Sets SV high limit value within the Scaling low limit value/Scaling high limit value range.
• Setting range: SV low limit to Scaling high limit value
(For DC input, the placement of the decimal point follows the selection.) SV low limit 0
• Sets SV low limit value within the Scaling low limit value/Scaling high
limit value range.
• Setting range: Scaling low limit value to SV high limit
(For DC input, the placement of the decimal point follows the selection.)
Sensor correction 0.0
• Sets the sensor correction value.
• Setting range: –100.0 to 100.0
( )
[Sensor correction function]
This corrects the input value from the sensor. When a sensor cannot be set at the exact location where control is desired, temperatures measured by the sensor may deviate from the temperature in the controlled location. When controlling with plural controllers, sometimes the measured temperatures (input value) do not concur due to differences in sensor accuracy or dispersion of load capacities. In such a case, the control can be set at the desired temperature by adjusting the input value of sensors. However, it is effective within the input rated range regardless of the sensor correction value. PV after sensor correction= Current PV+ (Sensor correction value) Overlap/Dead band 0.0
• Sets the Overlap or Dead band for OUT1 and OUT2.
• + Set value: Dead band
– Set value: Overlap band
• Not available if Heating/Cooling control (DR, DS, DA option) is not
ordered, or if ON/OFF control is selected in [Control action].
• Setting range:
OUT1 proportional band converted value
Thermocouple, RTD : -199.9 to 999.9
( )
DC voltage, current : -1999 to 9999 (The placement of the decimal point follows the selection.)
Remote/Local setting
Local setting
• SV can be set with either Remote or Local method.
• Available only when External setting input (EA, EV option) is ordered.
• Selection item:
: Local setting. The SV can be set by the front keypad. : Remote setting. The SV can be set by external remote operation.
Page 30
30
Character Name, Function, Setting range Default value
Instrument number 0
• Sets the instrument number of this unit. (The instrument numbers should
be set one by one when multiple instruments are connected in series in Serial communication, otherwise communication is impossible.)
• Available only when the Serial communication (C, C5 option) is ordered
• Setting range: 0 to 95 Communication speed 9600bps
• Selects the communication speed of this instrument.
(The communication speed of this instrument must be equal to that of host computer, otherwise communication is impossible.)
• Available only when the Serial communication (C, C5 option) is ordered
• Selection item:
: 2400bps : 4800bps : 9600bps : 19200bps
Communication protocol
• Selects the communication protocol of this instrument.
Shinko protocol
• Available only when the Serial communication (C, C5 option) is ordered
• Selection item:
: Shinko protocol
: Modbus ASCII mode
6.2.4 Auxiliary Function Setting Mode 2
In the PV/SV display mode, if the
key is pressed for approx. 3 seconds while
holding down the
and keys, the unit proceeds to Auxiliary function setting mode 2. The set value can be increased or decreased using the
, and keys.
Pressing the
key registers the set value, and proc eeds to the next setting item.
If the
key is pressed at the last setting item, the set value is registered and the
unit reverts to the PV/SV display mode.
Character Name, Function, Setting range Default value
Scaling high limit value
1370
• Sets scaling high limit value. If scaling high limit value is changed, SV high limit automatically
changes to the scaling high limit value.
• Setting range: Scaling low limit to Input range high limit value
Scaling low limit value
–200
• Sets scaling low limit value. If scaling low limit value is changed, SV low limit automatically changes to the scaling low limit value.
• Setting range: Input range low limit to scaling high limit value
Page 31
31
Character Name, Function, Setting range Default value
Decimal point place
• Selects the decimal point place.
No decimal point
• Not available if RTD or thermocouple is selected in [Sensor input].
• Selection item:
: No decimal point : 1 digit after the decimal point : 2 digits after the decimal point : 3 digits after the decimal point
PV filter time constant
0.0 sec
• Sets PV filter time constant. However, if the set value is set too large, it affects control result due to the delay of response.
• Setting range: 0.0 to 10.0 sec
OUT1 high limit value 100%
• Sets the high limit value for OUT1.
• Not available if ON/OFF control is selected in [Control action]
• Setting range: OUT1 low limit value to 100%
(Direct current output: OUT1 low limit value to 105%) OUT1 low limit value 0%
• Sets low limit value for OUT1.
• Not available if ON/OFF control is selected in [Control action]
• Setting range: 0% to OUT1 high limit value
(Direct current output: –5% to OUT1 high limit value) OUT1 ON/OFF hysteresis
1.0
• Sets ON/OFF hysteresis for OUT1.
• Available only when ON/OFF control is selected in [Control action]
• Setting range: 0.1 to 100.0 ( )
OUT2 action mode
Air cooling
• Selects OUT2 cooling action from a choice of: Air cooling, oil cooling
and water cooling.
• Available only when Heating/Cooling control (DR , DS, DA option) is ordered
• Selection item:
: Air cooling (linear characteristic) : Oil cooling (1.5th power of the linear characteristic) : Water cooling (2nd power of the linear characteristic)
OUT2 high limit value
100%
• Sets the high limit value for OUT2.
• Not available if Heating/Cooling control (DR, DS, DA option) is not
ordered, or if OUT2 is ON/OFF control action
• Setting range: OUT2 low limit value to 100%
(Direct current output: OUT2 low limit value to 105%)
OUT2 low limit value 0%
• Sets the low limit value for OUT2.
• Not available if Heating/Cooling control (DR, DS, DA option) is not
ordered, or if OUT2 is ON/OFF control action
• Setting range: 0% to OUT2 high limit value
(Direct current output: –5% to OUT2 high limit value)
Page 32
32
Character Name, Function, Setting range Default value
OUT2 ON/OFF hysteresis 1.0
• Sets ON/OFF hysteresis for OUT2.
• Not available if Heating/Cooling control (DR, DS, DA option) is not
ordered, or if OUT2 is PID or PD control action.
• Setting range: 0.1 to 100.0
( )
A1 action Energized/De-energized Energized
• Selects A1 action Energized/De-energized.
• Not available if Rotary switch is set to No.0 or No.7 in [A1 type].
• Selection item:
: Energized, : De-energized
A2 action Energized/De-energized Energized
• Selects A2 action Energized/De-energized.
• Not available if A2 option is not ordered, or if Rotary switch is set to No.0
or No.7 in [A2 type].
• Selection item:
: Energized, : De-energized
A1 hysteresis 1.0
• Sets A1 hysteresis.
• Not available if Rotary switch is set to No.0 or No.7 in [A1 type].
• Setting range: Thermocouple, RTD input: 0.1 to 100.0
( )
DC input: 1 to 1000 (The placement of the decimal point follows the selection.) A2 hysteresis 1.0
• Sets A2 hysteresis.
• Not available if A2 option is not ordered.
Not available if Rotary switch is se t to No.0 o r No .7 in [A2 type ].
• Setting range: Thermocouple, RTD input: 0.1 to 100.0
( )
DC input: 1 to 1000 (The placement of the decimal point
follows the selection.)
A1 action delay time 0 sec
• Sets A1 action delay time.
When setting time has elapsed after the input enters the alarm output range, the alarm is activated.
• Not available if the Rotary switch is set to No.0 or No.7 in [A1 type].
• Setting range: 0 to 9999 seconds A2 action delay time 0 sec
• Sets A2 action delay time.
When setting time has elapsed after the input enters the alarm output range, the alarm is activated.
• Not available if A2 option is not ordered, or if the Rotary switch is set to
No.0 or No.7 in [A2 type] even if A2 option is ordered.
• Setting range: 0 to 9999 seconds
Page 33
33
Character Name, Function, Setting range Default value
External setting input high limit 400
• Sets External setting input high limit value.
For EA option (4 to 20mA), the value corresponds to 20mA input.
• Available only when External setting (EA, EV option) is ordered.
• Setting range: External setting input low limit value to
Input range high limit value
External setting input low limit 0
• Sets External setting input low limit value.
For EA option (4 to 20mA), the value corresponds to 4mA input.
• Available only when External setting (EA, EV option) is ordered.
• Setting range: Input range low limit value to External setting input high limit value Transmission output
• Selects a Transmission output type.
PV transmission
• Available only when Transmission output (TA, TV option) is ordered
• Selection item:
: PV transmission : SV transmission : MV transmission
Transmission output high limit 400
• Sets the Transmission output high limit value.
For TA option, the value correponds to 20mA output.
• Available only when Transmission output (TA, TV option) is ordered
• Setting range: Transmission output low limit value to Input range high
limit value
Transmission output low limit 0
• Sets the Transmission output low limit value.
For TA option, the value correponds to 4mA output.
• Available only when Transmission output (TA, TV option) is ordered
• Setting range: Input range low limit value to Transmission output high
limit value
Indication when control output OFF
• Selects the indication when the control output is off.
• Selection item:
: OFF is indicated on the PV display.
OFF is indicated on the PV display.
: No indication
: Only PV is indicated.
SV rise rate
0
/minute
• Sets the SV rise rate (Rising value per minute).
Setting the value to 0 or 0.0 disables the function.
• Setting range: 0 to 9999
/min.
With a decimal point: 0.0 to 999.9
/min.
DC input: 0 to 9999 (The placement of the decimal
point follows the selection.)
Page 34
34
OFF
ON
A1 hysteresis
SV
+ A1 value
OFF
ON
SV
+ A1 value
A1 hysteresis
Character Name, Function, Setting range Default value
SV fall rate
0
/minute
• Sets the SV fall rate (Falling value per minute).
Setting the value to 0 or 0.0 disables the function.
• Setting range: 0 to 9999
/min.
With a decimal point: 0.0 to 999.9
/min. DC input: 0 to 9999 (The placement of the decimal point follows the selection.)
Output status when input erro
r
• Selects control output (OUT1/OUT2) status when DC
input is in overscale or underscale.
• Available only for Direct current output type with DC input
• Selection item:
Outputs OFF(4mA) or OUT1(OUT2) low limit value.
: Outputs OFF (4mA) or OUT1 (OUT2) low limit value.
: Outputs a value between OFF (4mA) and ON (20mA) or
between OUT1 (OUT2) low limit value and OUT1 (OUT2) high
limit value, depending on a deviation.
Alarm 1 (A1), 2 (A2) Energized/De-energized function
[If the alarm action Energized is selected]
When the alarm output indicator is lit, the alarm output (terminals 7-8, 9-10) is conducted (ON). When the alarm output indicator is unlit, the alarm output is not conducted (OFF).
[If the alarm action De-energized is selected]
When the alarm output indicator is lit, the alarm output (terminals 7-8, 9-10) is not conducted (OFF). When the alarm output indicator is unlit, the alarm output is conducted (ON).
High limit alarm (when Energized is set) High limit alarm (when De-energized is set)
A1: Alarm 1. For Alarm 2(A2), (Fig. 6.2.4-1) re a d “ A 2” f o r “ A 1 ”.
6.2.5 Program Mode
In PV/SV display mode, if the
key is pressed for approximately 3 seconds while
holding down the
key, the units moves to the Program mode.
The
, and keys increase or decrease the set values (numeric value).
Pressing the
key registers the set value, and proc eeds to the next setting item.
If the
key is pressed at the last setting item, the set value is registered and the unit
reverts to the PV/SV display mode.
• Data in Set value memory numbers (1 to 7, set with Fixed value control method) is assigned to Steps 1 to 7 respectively. For example, data in Set value memory number 1 becomes Step 1 data, and data in Set value memory number 2 becomes Step 2 data, and so on.
• If the Pattern end output is selected and the program control is performed, the Pattern end output is turned on when the program is completed.
• If the
key is pressed while the Pattern end output is on, the Pattern end output is
turned off. If the
key is pressed again, the program will be performed.
Page 35
35
• The following shows the program pattern example.
Set the step time to 00.00 for the unnecessary steps.
[Program Example]
Step number
(Set
value memory number)
1 2 3 4 5 6 7
Step SV 500 500 1000 1000 200 200 100 OUT1 proportional band 2.0 1.8 2.0 1.8 2.5 1.8 2.0 Integral time 180 80 180 80 200 80 200 Derivative time 30 20 30 20 50 20 50 OUT1 proportional cycle 30 30 30 30 30 30 30 A1 value 2 5 2 5 10 0 5 A2 value 2 5 2 5 10 0 5 Step time 00:30 01:00 00:40 01:00 02:00 00:30 01:00
Character Name, Function, Setting range Default value
Fixed value control/Program control switching
• Fixed value control or program control can be selected.
Fixed value control
• If the key is pressed after selecting the fixed value control, the controller will revert to the PV/SV display mode.
If the
key is pressed after selecting the program control, step
time from Step 1 to Step 7 can be set.
• Selection item: : Fixed value control : Program control
Step 1 time 00.00
• Sets Step 1 time. (Available only for program control)
(e.g.) When setting 1 hour 58 minutes, set as [
].
• Setting range: 00.00 to 99.59
Step 2 time 00.00
• Sets Step 2 time. (Available only for program control)
• Setting range: 00.00 to 99.59
Step 3 time 00.00
• Sets Step 3 time. (Available only for program control)
• Setting range: 00.00 to 99.59
Step 4 time 00.00
• Sets Step 4 time. (Available only for program control)
• Setting range: 00.00 to 99.59
Step 5 time 00.00
• Sets Step 5 time. (Available only for program control)
• Setting range: 00.00 to 99.59
0
500
1000
Page 36
36
Step 6 time 00.00
• Sets Step 6 time. (Available only for program control)
• Setting range: 00.00 to 99.59
Step 7 time 00.00
• Sets Step 7 time. (Available only for program control)
• Setting range: 00.00 to 99.59
6.2.6 Auto/Manual Control Switching
MV can be changed manually. As a proportional action, the MV is automatically outputted in proportion to the deviation. This is called an automoatic control.
In comparison with the above, in the manual control, the value set by front keypad can be outputted regardless of the deviation. If control action is switched from automatic to manual and vice versa, balanceless­bumpless function works to prevent sudden change of MV.
Each time the
key is pressed, the control switches from Automatic to Manual
and vice versa.
• Setting range: OUT1 low limit value to OUT1 high limit value When Heating/Cooling control (DR, DS, DA option) is ordered: OUT2 low limit value to OUT1 high limit value
6.2.7 Control Output OFF Function
Control output OFF function [
]
• The control action and output of an instrument (or any instruments in series) can be
turned off without turning off the power supplies using this function.
• Pressing the
key for approx. 1 second from any mode enables the control output OFF function. The PV display indicates the setting item selected in [Indication when control output OFF].
To cancel the function, press the
key again for approx. 1 second.
• Once the control output OFF function is enabled, the function cannot be released
even if the power to the instrument is turned OFF and ON again. To cancel the function, press the
key again for approx. 1 second.
• During program control, the key becomes the Program Start/Stop key, and
the control output OFF function is disabled.
6.2.8 MV, Remaining Step Time Indication
MV indication
In the PV/SV display mode, press the
key for approx. 3 seconds.
Keep pressing the
key until the MV appears, though the SV setting mode appears during the process. The MV indicator lights. The SV/MV/TIME display indicates the output MV. The 2nd decimal point from the right on the SV/MV/TIME display flashes. For the fixed value control, when the
key is pressed again, the unit reverts
to the PV/SV display mode.
Remaining step time indication
For the program control, if the
key is pressed while in MV indication,
remaining step time will be indicated on the SV/MV/TIME display. The TI ME indicator
lights. By pressing the
key again, the unit reverts to the PV/SV display mode.
Page 37
37
7. Set Value Memory Function (SM Option)
If the SM option (Set value memory nu mber external sele ction) is ordered, a maximum of 7 files (12 pieces of data per file) of data can be memorized. Control can be performed by selecting the desired file.
One file comprises 12 kinds of data:
SV, OUT1 proportional band, Integral time, Derivative time, OUT2 proportional band, A1 value, A2 value, Overlap/Dead band, OUT1 high limit value, OUT1 low limit value, OUT2 high limit value, OUT2 low limit value
To select the Set value memory number (file number), connect terminals 13 to 16 as shown below (Table 7-1). Up to 50 units of the FCR -13A can be connected in parallel.
Terminal connection for Set value memory number selection (Table 7-1)
Set value memory No. Connecting terminals
1 2 3 4 5 6 7
13 - 16 (b0-COM) Closed Open Closed Open Closed Open Closed 14 - 16 (b1-COM) Open Closed Closed Open Open Closed Closed 15 - 16 (b2-COM) Open Open Open Closed Closed Closed Closed
• If the Set value memory number is selected externally, the number cannot be selected by front keypad.
• To select the memory number by front keypad, all terminals (b0, b1, b2 and COM) should be open.
• The Set value memory number cannot be changed during setting mode or AT.
Operation procedures for Set value memory function
(1) In the PV/SV display mode, select a Set value memory number by connecting
terminals.
(2) In the setting mode, set each value:
SV, OUT1 proportional band, Integral time, Derivative time, OUT2 proportional band, A1 value, A2 value, Overlap/Dead band, OUT1 high limit value, OUT1 low limit value, OUT2 high limit value, OUT2 low limit value.
(3) After settings are complete, press the
key to revert to the PV/SV display mode.
Registering Data
• Data is registered in the file number indicated by the MEMO display.
• When any number is retrieved by connecting terminals, the selected number is indicated, and the control is performed using data (set values) of the indicated file number.
• To change set values, repeat the Operation procedures above.
Page 38
38
8 Operation
After the controller is mounted to the control panel and wiring is completed, operate the unit following the procedures below.
8.1 When Using the FCR-13A as a Temperature Controller (1) Turn the power supply to the FCR-13A ON.
For approx. 2 seconds after power-on, the sensor characters and the temperature unit selected in [Sensor input] will be indic ated on t he PV display, and input r ange high limit value (or Scaling high limit value for DC input) will be indicated on the SV/MV/TIME display. See (Table 8.1-1). During this time, all outputs and LED indicators are in OFF status. After that, control starts, indicating PV on the PV display and SV on the SV/MV/TIME display.
When the Control output OFF function is working, the item selected in [Indication when control output OFF] mode is indicated on the PV display.
(Table 8.1-1)
Input
PV display
SV/MV/TIME
display
PV display
SV/MV/TIME
display
K
J R B
PL-
N S E T
C(W/Re5-26)
Pt100
JPt100
Pt100
4 to 20mA DC
Scaling high limit value
Scaling high limit value
0 to 20mA DC 0 to 1V DC
(2) Input each set value.
Refer to Section “6. Settings”. When controlling by Fuzzy self-tuning PID, select ”Perform” in [AT Perform/Cancel (p.25)] mode to start control in optimal conditions.
(3) Turn the load circuit power ON.
Control action starts so as to keep the control target at the SV.
Page 39
39
8.2 When Using the FCR-13A as a Simplified Programmable Controller
(1) Turn the power supply to the FCR-13A ON.
For approx. 2 seconds after power-on, the sensor type and the temperature unit selected in [Sensor input] are indicated on the PV display, and input range high limit value (or scaling high limit value for DC input) is indicated on the SV/MV/TIME display. See (Table 8.1-1). During this time, all outputs and LED indicators are in OFF status. After that, the PV display indicates the PV, and the unit enters standby mode.
(2) Input each set value and step time
Refer to Section “6. Settings”.
(3) Turn the load circuit power ON. (4) Program control start
If “Automatic start” is selected in [Program start Auto/Manual], the unit will switch to warm-up status for approx. 2 seconds after power-on. Program control automatically starts from Step 1.
If “Manual start” is selected in [Program start Auto/Manual], the unit will switch to warm-up status for approx. 2 seconds after power-on. The unit proceeds to the standby status. In this status, if the
k ey is pressed, the progra m control starts
from Step 1. For the program control start, SV start (0
) is used.
During program control (RUN), the Step number (Set value memory number) change is not effective.
To make the step time progress faster
The step time progress becomes 60 times faster than usual when the
key is
pressed.
To terminate the program control during the process
The program control will be terminated if the
key is pressed for approx. 1 sec or
longer.
To swit ch the indication of MV and Remaining step time
In the PV/SV display, if the
key is pressed for approximately 3 seconds, the MV
is indicated. If the
key is pressed again, the remaining step time will be
indicated.
Instrument status when power is restored
After restoration following a power failure during program control, the FCR-13A resumes program performance from where it stopped. (The PV display flashes until the step at which the power failure occurred is finished.)
Page 40
40
Small
Large
Load current
Indicator (HB)
Red
Heater burnout
alarm action
Unlit
Lit
ON
OFF
Heater burnout alarm value
Heater burnout
alarm output
9 Action Explanations
9.1 OUT1 Standard Control Action
9.2 Heater Burnout Alarm Action (Optional)
Heating (reverse) action Cooling (direct) action
Proportional band
(OUT1) Green
Indicator
Lit
: Turns ON (lit) or OFF (unlit).
Cycle action is performed according to deviation.
Changes continuously according to deviation.
OFF
ON
OFF
ON
5
+
6
-
12V DC
5
+
6
12/0V DC
5
+
6
0V DC
5
+
6
0V DC
5
+
6
12V DC
5
+
6
0/12V DC
5
+
6
20mA DC
5
+
6
4mA DC
5
+
6
4mA DC
5
+
6
20mA DC
5
+
6
4 to 20mA DC
4
5
6
H
C
L
4
5
6
H
C
L
4
5
6
H
C
L
4
5
6
H
C
L
4
5
6
H
C
L
4
5
6
H
C
L
+
6
20 to 4mA DC
5
Changes continuously according to deviation.
LitUnlitUnlit
Control action
SV
Proportional band
R/
SV
S/
A/
Cycle action is performed according to deviation.
Cycle action is performed according to deviation.
Cycle action is performed according to deviation.
Page 41
41
9.3 OUT1 ON/OFF Control Action
9.4 Pattern End Action
Pattern end output is turned ON when the program control is completed, and it can be released when the
key is pressed. Use terminals 7 and 8 for Pattern end 2 output. The A2 indicator lights when Pattern end 2 output is ON.
Heating (reverse) action
Control action
Cooling (direct) action
Hysteresis
SV
(OUT1) Green
Indicator
Unlit
Hysteresis
5
+
6
12V DC
5
+
6
0V DC
5
+
6
0V DC
5
+
6
12V DC
5
+
6
20mA DC
5
+
6
4mA DC
5
+
6
4mA DC
5
+
6
20mA DC
4
5
6
H
C
L
4
5
6
H
C
L
4
5
6
H
C
L
4
5
6
H
C
L
OFF
ON
OFF
ON
Lit
Unlit Lit
SV
R/
S/
A/
ON OFF
Time
Pro
g
ram control end
9
10
9
10
9
10
Unlit
Lit
Unlit
Pattern end
action
Pattern end
output
Pattern end output is released by pressing
the
key.
Indicator (A1
)
Red
: Turns ON (lit) or OFF (unlit).
Page 42
42
9.5 Heating/Cooling Control Action (DR, DS, DA Option)
9.5.1 Heating/Cooling Control Action
: Turns ON (lit) or OFF (unlit).
: Represents Heating control action.
: Represents Cooling control action.
Control
action
OUT1 P-band (OUT2 P-band)
OFF
ON
5
+
6
12V DC
5
+
6
12/0V DC
5
+
6
0V DC
5
+
6
20mA DC
5
+
6
20 to 4mA DC
5
+
6
4mA DC
4
5
6
H
C
L
4
5
6
H
C
L
4
5
6
H
C
L
7
8
7
8
7
8
7
+
8
0V DC
7
+
8
12V DC
7
+
8
0/12V DC
7
+
8
4 to 20mA DC
7
+
8
4mA DC
7
+
8
20mA DC
(OUT2) Yellow
OFF
ON
Heating
action
(Cooling
action)
SV
Cycle action is performed according to deviation.
Changes continuously according to deviation.
Lit
Unlit
Unlit
Lit
Indicator
(OUT1) Green
Indicator
R/
S/
A/
DR
DS
DA
Cycle action is performed according to deviation.
Cycle action is performed according to deviation.
Cycle action is performed according to deviation.
Changes continuously according to deviation.
Page 43
43
9.5.2 When Setting Dead Band
: Turns ON (lit) or OFF (unlit).
: Represents Heating control action.
: Represents Cooling control action.
(OUT1) Green
OFF
ON
OFF
ON
4
5
6
H
C
L
4
5
6
H
C
L
4
5
6
H
C
L
7
8
7
8
7
8
(OUT2) Yellow
5
+
6
12V DC
5
+
6
12/0V DC
5
+
6
0V DC
5
+
6
20mA DC
5
+
6
20 to 4mA DC
5
+
6
4mA DC
7
+
8
0V DC
+
8
12V DC
7
+
8
0/12V DC
7
+
8
4 to 20mA DC
7
+
8
4mA DC
7
+
8
20mA DC
Control
action
(Cooling
action)
Heating action
OUT1 P-band
Dead band (OUT2 P-band)
SV
Cycle action is performed according to deviation.
Indicator
Indicator
Lit
Unlit
Lit
Unlit
Changes continuously
according to deviation.
R/
S/
A/
DR
DS
DA
Cycle action is performed according to deviation.
Cycle action is performed according to deviation.
Cycle action is performed
according to deviation.
7
Changes continuously
according to deviation.
Page 44
44
9.5.3 When Setting Overlap Band with Relay Contact Output.
: Turns ON (lit) or OFF (unlit).
: Represents Heating control action.
: Represents Cooling control action.
OFF
ON
OFF
ON
4
5
6
H
C
L
4
5
6
H
C
L
4
5
6
H
C
L
7
8
7
8
7
8
(OUT2) Yellow
Control
action
SV
(OUT1) Green
Indicator
Lit
Indicator
OUT1 P-band
OUT2 P-band
Overlap
band
Heating action
(Cooling
action)
Cycle action is performed according to deviation.
Lit
Unlit
Unlit
R/
DR
Cycle action is performed according to deviation.
Page 45
45
OFF
ON
OFF
ON
OFF
OFF
OFF
OFF
OFF OFF
Alarm action
High limit alarm Low limit alarm
A1
hysteresis
Process high alarm Process low alarm
High/Low limit range alarm
Alarm output
+side
-side
Alarm output
Alarm action
Alarm action
Alarm output
Alarm action
High limit alarm with standby
Low limit alarm with standby
Alarm output
+side
-side
+side
-side
SV
-A1 value
A1
hysteresis
A1
hysteresis
A1
hysteresis
A1
hysteresis
A1
hysteresis
A1
hysteresis
A1
hysteresis
SV
SVSV
SV SV+A1 value +A1 value-A1 value
+side
-side
ON
High/Low limits alarm
A1 value
A1 value
A1 value A1 value
ON
ONON
A1 value
A1 value
ON
ON
+A1 value-A1 value-A1 value +A1 value
9.6 Alarm 1 (A1), Alarm 2 (A2) Action
Page 46
46
Process high alarm with standby Process low alarm with standby
High/Low limits alarm with standby High/Low limit range alarm with standby
Alarm output
Alarm action
Alarm action
Alarm output
OFF
A1
hysteresis
OFF
ON
SV
A1
hysteresis
OFF
hysteresis
OFF
hysteresis
A1 value
A1 value
SV
A1 value
A1 value
A1 valueA1 value
A1
A1
ON
ON ON
A2 output terminals: 7 and 8
A1 and A2 indicators light when their output terminals are closed, and go off when their output terminals are opened.
For A2, read “A2” for “A1”.
:
A
1
output terminals 9 and 10 are closed.
: Standby functions.
:
A
1
output terminals 9 and 10 are closed or opened.
:
A
1
output terminals 9 and 10 are opened.
Page 47
47
10 Control Actions
10.1 Fuzzy Self-tuning
Fuzzy self-tuning is a function that performs fine adjustment of PID values automatically. Stable control can be carried out even if the conditions of the production process are changed due to various external factors (types and rates of production).
(1) When using the controller for the first time, perform the AT (auto-tuning) or set the
proper PID values by keypad operation.
(2) When control initiates, the controller performs this function by the previously adjusted
PID values.
(3) When control result is disordered by disturbance or a change in the process, the
controller checks the convergence status, and performs a fine adjustment of PID values if necessary.
The instrument is constantly in self-tuning status, and when deviation occurs, the tuning starts.
• If the convergence is performed smoothly, the PID values are not changed.
• If the convergent speed is slow, the controller corrects the PID values to accelerate the
convergence.
• When overshoot is generated during the convergence, the controller changes the PID
values to correct this.
• When hunting occurs, the controller checks its waveform and performs a fine adjustment
of PID values.
Even in Fuzzy self-tuning status, when very large hunting occurs and the control is not stabilized, AT automatically starts. When the AT “Perform” is selected by the keypad, AT initiates, and when the control is stabilized, the AT is released and the controller returns to self-tuning status.
When lock mode [
] or [ ] is selected, Fuzzy self-tuning or A T doe s not work .
For a control system in which load fluctuation periodically occurs, the Fuzzy self-tuning PID control may malfunction. In such a case, use the controller with the PID control.
10.2 PID (1) Proportional ban d (P )
Proportional action is the action which the control output varies in proportion to the deviation between the SV (desired value) and the processing temperature (PV). If the proportional band is narrowed, even if the output changes by a slight variation of the processing temperature, and better control res ults can be obtained as the offset decreases. However, if the proportional band is narrowed too much, even slight disturbances may cause variation in the processing temperat ure, and control action changes to ON/OFF control action and the so-called hunting phenomenon occurs. Therefore, when the processing temperature comes to the balanced position near the SV and a constant temperature is maintained, the most suitable value is selected by gradually narrowing the proportional band while observing the control results.
(2) Integral time (I )
Integral action is used to eliminate offset. When the integral time is shortened, the returning speed to the setting point is accelerated. However, the cycle of oscillation is also accelerated and control becomes unstable.
(3) Derivative time (D)
Derivative action is used to restore th e change in the processing temp erature according to the rate-of-change. It reduces the amp litude of ov ersh oo t and unde r shoot wi dth. If the derivative time is shortened, the restoring value becomes small, and if the derivative time is extended, an excessive returning phenomeno n may o ccur and the contro l sy stem may oscillate.
Page 48
48
10.3 AT of This Controller
In order to set each value of P, I and D automatically, the AT process has been made to fluctuate in order to achieve an optimal value.
Sometimes the AT process will not fluctuate if AT is performed at or near room temperature. Therefore AT may not finish normally.
(A) I f there is a large diffe r e n c e betwe e n the SV a n d P V as the temperature is rising
The AT process will fluctuate at the temperature 1.5% of input span lower than the SV. (DC input: 1.5% of scaling span)
(1) Calculating PID
constant
(2) PID constant
calculated (3) Controlled by the PID constant set by A T. (4) 1.5% of input span
(Fig. 10.3-1)
(B) When the control is stable or when PV is within SV
(1.5% of input span).
The AT process will fluctuate around the SV. [DC input:
(1.5% of scaling span)]
(1) Calculating PID
constant (2) PID constant
calculated (3) Controlled by the PID constant set by AT.
(Fig. 10.3-2)
(C) When the PV is 1.5% of input span higher than the SV
The AT process will fluctuate at the temperature 1.5% of input span higher than the SV. (DC input: 1.5% of scaling span)
(1) Calculating PID
constant
(2) PID constant
calculated (3) Controlled by the PID constant set by AT. (4) 1.5% of input span
(Fig. 10.3-3)
(1)
(2) (3)
(4)
AT starting point
SV
Temperature
Time
1.5% of input span lower than the SV
AT starting point
(1)
(2)
(3)
Temperature
SV
Time
1.5% of input span higher than the SV
AT starting point
(1)
(2) (3)
(4)
Temperature
SV
Time
Page 49
49
11 Specifications
11.1 Standard Specifications
Mounting: Flush
Mountable panel thickness: 1 to 3mm [If Soft front cover (FC-R-S) is used, 1 to 2.5mm]
Setting: Input system using membrane sheet key
Display:
PV display: Red LED, 4 digits, character size, 8(H) x 4(W)mm SV/MV/TIME display: Green LED, 4 digits, character size, 8(H) x 4(W)mm MEMO display (Set value memory number):
Yellow LED, 1 digit, character size, 8(H) x 4(W)mm
Accuracy (Indication, setting)
Thermocouple: Within
0.2% of each input span 1 digit
K, J, T inputs, range less than 0
(32 ):
Within
0.4% of each input span 1 digit
R, S inputs, range 0 to 200
(0 to 400 ): Within 4 (8 )
B input, range 0 to 300
(0 to 600 ): Accuracy is not guaranteed. Cold junction temperature compensation accuracy:
1 (at 0 to 50 ) RTD: Within 0.2% of each input span 1 digit Direct current: Within
0.2% of each input span 1 digit
DC voltage: Within
0.2% of each input span 1 digit
Input sampling period: 125ms
(When EA, EV or W, W3 option is ordered: 500ms)
Input
Thermocouple: K, J, R, S, B, E, T, N, PL-
, C (W/Re5-26)
External resistance, 100
or less When input is burnt out, Overscale RTD: Pt100, JPt100, 3-wire system Allowable input lead wire resistance: 10
or less per wire When input is burnt out, Overscale Direct current: 0 to 20mA DC, 4 to 20mA DC
Input impedance, 50 Allowable input current, 100mA or less When input is disconnected: 0 to 20mA: The same as 0mA
4 to 20mA: Underscale
DC voltage: 0 to 1V DC
Input impedance, 1M
or more Allowable input voltage, 5V or less Allowable signal source resistance, 2k
or less
When input is disconnected, Overscale
OUT1 (Control output 1)
Relay contact: 1a1b Control capacity: 3A 250V AC (resistive load) 1A 250V AC (inductive load cos
=0.4) Electrical life: 100,000 cycles Non-contact voltage: For SSR drive 12
+2
, 0V DC maximum 40mA DC (short circuit protected) Direct current: 4 to 20mA DC (Isolated type) Load resistance, maximum 550
Page 50
50
Alarm 1 output
The alarm action point is set by the
deviation from the SV (except Process al ar m ).
[When A1 action Energized is selected]
When the input goes outside the range, the output turns ON or OFF (in the case of High/Low limit range alarm).
[When A1 action De-energized is selected]
The output acts conversely.
An alarm can be selected by Rotary switch and DIP switch from 13 types of alarm (including No alarm) plus Pattern end output: High limit alarm, Low limit alarm, High/Low limits alarm, High/Low limit range alarm, Process high alarm and Process low alarm, the standby function which is applied to them respectively, as well as Pattern end output. [See Section 9.6 Alarm 1 (A1), Alarm 2 (A2) Action.]
Setting accuracy: Within
0.2% of each input span 1 digit Action: ON/OFF action Hysteresis: Thermocouple, RTD inputs: 0.1 to 100.0
( ) DC input: 1 to 1000 (The placement of the decimal point follows the selection.)
Output: Relay contact 1a
Control capacity: 3A 250V AC (resistive load)
1A 250V AC (inductive load cos
=0.4)
Electrical life: 100,000 cycles
Pattern end output (A1 output)
If the Pattern end output [Rotary switch A1 (SW302) No.7] is selected, and the program control is performed, the Pattern end output is turned ON when the program is completed. The Pattern end output can be turned OFF by pressing the
key.
(See Section 9.4 Pattern End Action.)
Controlling action
The fuzzy self-tuning PID, PID, PD or ON/OFF control is selectable by DIP switch.
Fuzzy self-tuning PID control OUT1 proportional band (P): Automatic
Integral time (I): Automatic
Derivative time (D): Automatic Anti-reset windup (ARW): Automatic OUT1 proportional cycle: 1 to 120 sec OUT1 high/low limit: 0 to 100% (Direct current output: –5 to 105%)
PID control (with AT function) OUT1 proportional band (P): 0.1 to 999.9%
Integral time (I): 0 to 3600 sec (off when set to 0)
Derivative time (D): 0 to 3600 sec (off when set to 0) Anti-reset windup (ARW): Automatic OUT1 proportional cycle: 1 to 120 sec OUT1 high/low limit: 0 to 100% (Direct current output, –5 to 105%)
PD control OUT1 proportional band (P): 0.1 to 999.9% Derivative time (D): 0 to 3600 sec (off when set to 0) OUT1 proportional cycle: 1 to 120 sec
Reset:
Proportional band converted value
Thermocouple, RTD input: –199.9 to 999.9
( )
DC input: –1999 to 9999 (The placement of the
decimal point follows the selection.)
OUT1 high/low limit: 0 to 100% (Direct current output: –5 to 105%)
Page 51
51
Insulated
Power source
OUT1
A1 output
HB output
A
(*1)
B
CPU
Input
CT input
C
D
E
G
F
Ground terminal
Insulated
Non-insulated Non-insulated
Insulated
Insulated
Communication (*2)
Insulated
Transmission
output
Set value memory
number external
selection (*2)
Insulated Insulated
Insulated
Insulated
Insulated
External setting input
OUT2, A2,
LA or P24
output
ON/OFF control
OUT1 ON/OFF hysteresis: Thermocouple, RTD input: 0.1 to 100.0
( )
DC input: 1 to 1000 (The placement of the decimal
point follows the selection.)
Supply voltage: 100 to 240V AC, 50/60Hz, 24V AC/DC, 50/60Hz Allowable voltage fluctuation: 100 to 240V AC: 85 to 264V AC
24V AC/DC: 20 to 28V AC/DC
Ambient temperature: 0 to 50
(32 to 122 )
Ambient humidity: 35 to 85%RH (non-condensing) Power consumption: Approx. 15VA
Circuit insulation configuration:
(*1) When both OUT1 and OUT2 are Direct current output type or Non-contact voltage
output type, A is not electrically insulated from B.
( * 2) When OUT1 is Direct current o ut pu t t yp e or No n- c o ntact vol tage o ut put t y pe,
A is not electrically insulated from F, and A is not electrically insulated from G. When OUT2 is Direct current output type or Non-contact voltage output type,
B is not elec t r ic a l l y i ns u la t e d fr om F, and B is no t el e ctrically in s u l at e d f r om G.
Insulation resistance
10M
or more, at 500V DC Insulation test must not be carried out between A-B in the case of (*1) above, and between A-F, A-G, B-F, B-G, C-D-E and F-G in the case of (*2) above because they are not insulated from each other.
Dielectric strength
Between input terminal and ground terminal: 1.5kV AC for 1 minute Between input terminal and power terminal: 1.5kV AC for 1 minute Between output terminal and ground terminal: 1.5kV AC for 1 minute Between output terminal and power terminal: 1.5kV AC for 1 minute Between power terminal and ground terminal: 1.5kV AC for 1 minute
Weight: Approx. 320g
External dimensions: 48 x 96 x 100mm (W x H x D)
Material: Case, Front panel: Flame-resistant resin Color: Case, Front panel: Light gray
Page 52
52
Attached functions: [Control output OFF function], [Set value lock], [SV high/low limit]
[Sensor correction], [Multi-range], [Multi-function], [Simplified programmable controller] [Burnout]
When the thermocouple or RTD input is burnt out, OUT1 and OUT2 are turned off (for Direct current output type, OUT1, OUT2 low limit value), and the PV displ ay flas hes “
”. For manual control, the preset MV is outputted. When DC input is disconnected, the PV display flashes “
” for 4 to 20mA DC
input, and “
” for 0 to 1V DC input.
For 0 to 20mA DC, the PV display indicates the value corresponding with 0mA input.
[Input error indication]
Output status
when input
error (*1)
Contents and
indication
Output status
OUT1 OUT2
Direct action Reverse action Direct action Reverse action
Overscale Measured value has exceeded indication range high limit value.
"
" flashes.
ON (20mA)
or OUT1 high
limit
value (*2)
OFF (4mA) or OUT1 low limit value
OFF (4mA) or OUT2 low limit value
ON (20mA)
or OUT2 high
limit
value (*2) OFF (4mA) or OUT1 low limit value
OFF (4mA)
or OUT2 low
limit value
Underscale Measured value has dropped
below indication range low limit value. "
" flashes.
OFF (4mA) or OUT1 low limit value
ON (20mA) or OUT1 high limit value(*2)
ON (20mA) or OUT2 high limit value(*2)
OFF (4mA) or OUT2 low limit value
OFF (4mA) or OUT1 low limit value
OFF (4mA) or OUT2 low limit value
(*1) This is available only for DC input.
For manual control, the preset MV is outputted.
(*2) Outputs a value between OFF (4mA) and ON (20mA) or between OUT1 (or OUT2)
low limit value and OUT1 (or OUT2) high limit value, depending on deviation.
TC, RTD inputs
Input Input range Indication range Control range
T
–199.9 to 400.0
–199.9 to 405.0 –205.0 to 405.0
–199.9 to 750.0 –199.9 to 759.0 –209.0 to 759.0
Pt100
–199.9 to 850.0
–199.9 to 860.0 –210.0 to 860.0 –200 to 850 –210 to 860 –210 to 860 –199.9 to 999.9 –199.9 to 999.9 –211.0 to 1010.9 –320 to 1560 –338 to 1578 –338 to 1578
JPt100
–199.9 to 500.0
–199.9 to 506.0 –206.0 to 506.0 –199.9 to 900.0 –199.9 to 910.9 –211.0 to 910.9
Indication range and Control range for thermocouple inputs other than the above: [Input range low limit value – Input span x 1%] to [Input range high limit value + Input span x 1%]
DC input Indication range: [Scaling low limit value – Scaling span x 1%] to [Scaling high
limit value + Scaling span x 10%] However, if the input value is out of the range –1999 to 9999, the PV display flashes “
” or “ ”.
Control range: [Scaling low limit value – Scaling span x 1%] to [Scaling high
limit value + Scaling span x 10%]
Page 53
53
[Self-diagnosis]
The CPU is monitored by a watchdog timer, and when an abnormal status is found on the CPU, the controller is switched to warm-up status.
[Automatic cold junction temperature compensation] (Thermocouple input type)
This detects the temperature at the connecting terminal between thermocouple and the instrument, and always maintains it at the same status as if the reference junction temperature was at 0
(32 ).
[Warm-up indication]
For approximately 2 seconds after power-on, the input type and the temperature unit are indicated on the PV display, and the input range high limit value (for DC input, scaling high limit value) is indicated on the SV/MV/TIME display.
[SV ramp function]
When the SV is adjusted, it approaches the new SV by the preset rate-of-change (Rising/Falling value per minute). When the power is turned on, the control starts from the PV and approaches the SV by the rate-of-change. For the program control, this function will not work.
Accessories:
One-touch type mounting brackets: 1 set
Instruction manual: 1 copy Unit label: 1 label Current transformer (CT): 1 piece (CTL-6S) (When W (20A) option is ordered.) (CTL-12-S36-10L1U) (When W (50A) option is ordered.) Current transformer (CT): 2 pieces (CTL-6S) (When W3 (20A) option is ordered.) (CTL-12-S36-10L1U) (When W3 (50A) option is ordered.)
Wire harness: 3m (When the W/W3, TA/TV or EA/EV option is
ordered.)
Screw type mounting brackets: 1 set (When the BL option is ordered.) Gasket: 1 piece (When the IP option is ordered.)
Terminal cover: 1 piece (When the TC option is ordered.)
Page 54
54
11.2 Optional Specifications Alarm 2 (Option code: A2)
The alarm action point is set by the
deviation from the SV (except Process alarm).
[When A2 action Energized is selected]
When the input goes outside the range, the output turns ON or OFF (in the case of High/Low limit range alarm).
[When A2 action De-energized is selected]
The output acts conversely.
One alarm can be sele cte d by Ro tary switch and DIP switch from 13 types of alarm (including No alarm) and Pattern end output: High limit alarm, Low limit alarm, High/Low limits alarm, High/Low limit range alarm, Process high alarm and Process low alarm, the standby function which is applied to them respectively, as well as Pattern end output.
• When Alarm 2 (A2 option) and Loop break alarm (LA option) are ordered together, they utilize common out put termi nal s.
• If Alarm 2 (A2 option) is ordered, Heating/Cooling control (DR, DS, DA option) or
Insulated power output (P24 option) cannot be ordered. Setting accuracy: Within
0.2% of each input span 1 digit
Action: ON/OFF action
Hysteresis: Thermocouple, RTD inputs: 0.1 to 100.0
( ) DC input: 1 to 1000 (The placement of the decimal point follows the selection.)
Output: Relay contact, 1a Control capacity: 3A 250V AC (resistive load) 1A 250V AC (inductive load cos
=0.4)
Electrical life: 100,000 cycles
Heating/Cooling control (Option code: DR, DS, DA)
If this option is ordered, Alarm 2 (A2 option), Loop break alarm (LA option) or Insulated power output (P24 option) cannot be ordered.
OUT2 proportional band: 0.0 to 10.0 times OUT1 proportional band
(ON/OFF control action when setting the value to 0.0.)
OUT2 integral time: The same as OUT1 integral time OUT2 derivative time: The same as OUT1 derivative time OUT2 proportional cycle: 1 to 120 sec Overlap/Dead band:
OUT1 proportional band converted value
Thermocouple, RTD inputs: –199.9 to 999.9
( )
DC input: –1999 to 9999 (The placement of the decimal point follows the
selection.) OUT2 ON/OFF hysteresis:
Thermocouple, RTD inputs: 0.1 to 100.0
( )
DC input: 1 to 1000 (The placement of t he decimal po int follows the selection. )
Output [DR] Relay contact, 1a Control capacity: 3A 250V AC (resistive load) 1A 250V AC (inductive load cos
=0.4) Electrical life: 100,000 cycles [DS] Non-contact voltage (for SSR drive)
12
+2
,
0
V DC Maximum 40mA DC (short circuit protected) [DA] Direct current: 4 to 20mA DC (Isolated type) Load resistance: Maximum 550
OUT2 high/low limit: 0 to 100% (Direct current output: -5 to 105%)
OUT2 action mode: Selectable by keypad Air cooling (Linear characteristic), Oil cooling (1.5th power of the linear characteristic), Water cooling (2nd power of the linear characterist ic ).
Page 55
55
Transmission output (Option code: TA, TV)
Converting the value (PV transmission, SV transmission, MV transmission) to
analog signal every 125ms, outputs the value in current or voltage.
One transmission output (PV, SV, MV) can be selected by keypad. Resolution: 1/10000 Current (TA): 4 to 20mA DC (load resistance maximum 500
)
Voltage (TV): 0 to 1V DC (load resistance minimum 100k
)
Output accuracy: Within
0.3% of Transmission output span
Serial communication (Option code: C5, C)
The following operations can be executed from an external computer.
(1) Reading and setting of the SV, PID values and various set values.
(2) Reading of the PV and action status.
(3) Function change Communication line: EIA RS-485 (C5 option) EIA RS-232C (C option) Communication method: Half-duplex communication Synchronization method: Start-stop synchronization Communication speed: 2400, 4800, 9600, 19200bps (Selectable by keypad) Data format Start bit: 1 Data bit: 7 Parity: Even parity Stop bit: 1
Communication protocol: Shinko protocol, Modbus ASCII (Selectable by keypad)
(When Modbus protocol is selected, the Digital external
setting can not be used.) Digital external setting: Receives digital set value from Shinko Programmable controller PC-900, PCD-33A (with SVTC option).
Set value memory number external selection (Option code: SM)
Selects the Set value memory number from 7 files (the below-mentioned data as one file) by external terminals:
SV, OUT1 proportional band, Integral time, Derivative time, OUT2 proportional band, A1 value, A2 value, Overlap/Dead band, OUT1 high limit value, OUT1 low
limit value, OUT2 high limit value, OUT2 low limit value Memory number: 1 to 7 (7 files) Data: 12
External setting input (Option code: EA, EV)
SV can be set by External analog signal.
Setting signal : Direct current [EA] 0 to 20mA DC, 4 to 20mA DC Allowable input current: 100mA DC or less Input impedance, 50
(non-isolated from input) : DC voltage [EV] 0 to 1V DC, 1 to 5V DC Allowable input voltage: 0 to 1V DC: 5V DC or less Input impedance, 100k
(non-isolated from input) Setting signal sampling period: 500ms (If this External setting input is ordered, the input sampling period also changes to 500ms.)
Heater burnout alarm (Option code: W, W3)
Watches the heater current with CT (current transformer), and detects the burnout.
• For the direct current output type, this option cannot be ordered.
• If this option is ordered, the input sampling period also changes to 500ms.
Rated current: 20A [W (20A), W3 (20A) option] or
50A [W (50A), W3 (50A) option] Must be specified
Page 56
56
Setting ra n ge : 2 0A : 0.0 to 20.0A (Indication: 0.0 to 50.0), 50A: 0.0 to 50.0A The alarm will be disabled when set to 0.0.
Setting accuracy: Within
5% of heater rated current Action: ON/OFF action Output: Relay contact, 1a Control capacity: 3A 250V AC (resistive load)
1A 250V AC (inductive load, cos
=0.4)
Electrical life: 100,000 cycles
Loop break alarm (Option code: LA)
Detects the breaking status on the loop such as heater burnout, sensor burnout or actuator trouble.
• When this option and Alarm 2 (A2) option are ordered together, they utilize common output terminals.
• If this option is ordered, Heating/Cooling control (DR, DS, DA option) or Insulated
power output (P24 option) cannot be ordered.
Output: Relay contact, 1a Control capacity: 3A 250V AC (resistive load) 1A 250V AC (inductive load, cos
=0.4)
Electrical life: 100,000 cycles
Insulated power output (Option code: P24)
Can be used as a small capacity power source for each sensor and converter.
If this option is ordered, Alarm 2 (A2 option), Heating/Cooling control (DR, DS, DA
option) or Loop break alarm (LA option) cannot be ordered.
Output voltage: 24
3V DC (when the load current is 30mA.) Ripple voltage: Within 200mV DC (when the load current is 30mA DC.) Max load current: 30mA DC
Screw-type mounting brackets (Option code: BL)
Mountable panel thickness: 1 to 8mm (When soft front cover FC-R-S is used: 1 to 7.5mm)
Color black (Option code: BK)
Front panel: Dark gray, Case: Black
Drip-proof/Dust-proof (IP54) (Option code: IP)
Effective only for front panel surface, case section is excluded. Mount the controller vertically to the flat, rigid panel to ensure it adheres to the Drip-proof/Dust-proof specification. The front cover (soft type, FC-R-S, sold separately) is recommended for comprehensive Drip-proof/Dust-proof protection.
Terminal cover (Option code: TC)
Electrical shock pr ot ect i on t e rm i nal c over
User specified
Input, Scale range: Shipped as specified range. Alarm type: Shipped as specified alarm type [A1, A2 (A2 is optional)]. Control action: Shipped as specified control action. OUT2 action mode: Shipped as specified cooling action mode (DR, DS, DA option). Transmission output: Shipped as specified output (TA, TV option). External setting input: Shipped as specified input (EA, EV option). Transmission output scaling: Shipped as specified scaling range.
Page 57
57
12 Troubleshooting
If any malfunctions occur, refe r to th e fol l ow i ng items after ch eck i ng t h e p owe r a n d the wiring.
Warning
Turn the power supply to the instrument off before wiring or checking. Working on or touching the terminal with the power switched on may result in severe injury or death due to electric shock.
<Indication>
Problem Possible Cause and Solution
The PV display is indicating [ ], no indication or only PV .
• Control output OFF function is working. To release the function, press the key for approx. 1 sec.
The PV display is flashing [
].
• Thermocouple or RTD is burnt out.
Change each sensor.
[Thermocouple]
If the input terminals of the instrument are shorted, and if a value around room temperature is indicated, the instrument is likely to be operating normally, however, the sensor may be burnt out.
[RTD]
If approximate 100
of resistance is connected to the input terminals between A-B of the instrument and between B-B is shorted, and if a value around 0
(32 ) is indicated, the instrument is likely to be operating normally, however, the sensor may be burnt out.
• Check whether the lead wire of thermocouple or RTD is securely mounted to the instrument input terminals.
The PV display is flashing [
].
• Check if polarity of thermocouple or compensating lead wire
is correct.
• Check whethe r codes (A, B, B) of RTD agree with the
instrument terminals. The indication of the PV display is irregular or unstable.
• Suitable sensor input has not been selected. Set the sensor input properly using the Rotary switch (SW303) and DIP switch (SW304).
• Temperature unit (
or ) is not correct.
Set it to a suitable unit with the DIP switch (SW304).
• Sensor correction value is not suitable.
Set it to a suitable value.
• Specification of thermocouple or RTD is improper.
• AC leaks into the thermocouple or RTD circuit. Use an ungrounded type sensor.
• There may be equipment that interferes with, or makes noise near the controller.
Keep equipment that interferes with or makes noise away
from the controller.
Page 58
58
<Key operation>
Problem Possible Cause and Solution
The setting mode cannot be selected.
• Manual control is selected. Change the mode to Automatic control.
• Unable to set the SV, P, I, D, OUT1 proportional cycle, alarm value, etc.
• The values do not change by the
,
keys.
• Set value lock (Lock 1 or Lock 2) is selected. Release the lock selection.
• AT (Auto-tuning) is performing. Cancel AT.
The setting indication does not change within the input range even if the
, keys are pre s se d , and new values are unable to be set.
• SV high limit or SV low limit in Auxiliary function setting mode 1 may be set at the point where the value does not change. Set it to a suitable value in Auxiliary function setting mode 1.
Program control does not start even if the
key is pressed
in the Program mode.
• Step time has not been set. Set the step time.
<Control>
Problem Possible Cause and Solution
PV does not rise. • Thermocouple or RTD is burnt out.
Replace the sensor.
• Check whether the sensor or control output terminals are securely mounted to the instrument terminals.
• Check whether the wiring of sensor or control output
terminals is correct. Control is not performing. (Only PV display is indicated)
• Control output OFF function is working. Press the
key to cancel Control output OFF function.
• Program mode is selected.
To start Program control, press the
key.
To perform Fixed value control, press the
key for
approx. 3 sec while holding down the
key. OUT1 or OUT2 remains in an ON status.
• OUT1 low limit value or OUT2 low limit value is set to 100% or higher in Auxiliary function setting mode 2. Set it to a suitable value.
OUT1 or OUT2 remains in an OFF status.
• OUT1 high limit value or OUT2 high limit value is set to 0% or less in Auxiliary function setting mode 2. Set it to a suitable value.
For all other malfunctions, please contact our main office or dealers.
Page 59
59
13 Character Table
<Main setting mode>
Character Item Default Data
SV
0
<Sub setting mode>
Character Item Default Data
Set value memory number 1 AT Perform/Cancel Cancel OUT1 proportional band 2.5%
OUT2 proportional band 1.0 times Integral time 200 sec Derivative time 50 sec OUT1 proportional cycle R/M: 30 sec
S/M: 3 sec
OUT2 proportional cycle DR: 30 sec
DS: 3 sec
Manual reset 0.0 Alarm 1 value 0 Alarm 2 value 0
xx.x
xx.x:
Heater
current value
Heater burnout alarm value 0.0A
Loop break alarm time 0 minutes
Loop break alarm span 0
<Auxiliary function setting mode 1>
Characte
r
Item Default Data
Set value lock Unlock SV high limit 400 SV low limit 0 Sensor correction 0.0 Overlap/Dead band 0.0
Remote/Local setting Local
Instrument number 0
Communication speed 9600bps
Communication protocol Shinko protocol
<Auxiliary function setting mode 2>
Character Item Default Data
Scaling high limit value 1370
Scaling low limit value -200 Decimal point place No decimal point
PV filter time constant 0.0 sec
OUT1 high limit value 100%
OUT1 low limit value 0%
OUT1 ON/OFF hysteresis 1.0
OUT2 action mode Air cooling
OUT2 high limit value 100%
OUT2 low limit value 0%
OUT2 ON/OFF hysteresis 1.0
Alarm 1 action Energized/De-energized Energized Alarm 2 action Energized/De-energized Energized
Page 60
Alarm 1 hysteresis 1.0 Alarm 2 hysteresis 1.0 Alarm 1 delay time 0 sec
Alarm 2 delay time 0 sec External setting input high limit 400 External setting input low limit 0 Transmission output PV transmission Transmission output high limit 400 Transmission output low limit 0 Indication when control output OFF
OFF on the PV display
SV rise rate 0 /minute SV fall rate 0 /minute Output status when input error Outputs OFF(4mA)
or OUT1(OUT2) lowlimitvalue.
<Program mode>
Characte
r
Item Default Data
Fixed value control/Program control Fixed value
control Step 1 time 00.00 Step 2 time 00.00 Step 3 time 00.00 Step 4 time 00.00 Step 5 time 00.00 Step 6 time 00.00 Step 7 time 00.00
***** Inquiries *****
For any inquiries about this unit, please contact the vendor where you purchased the unit after checking the following.
[Example]
• Model --------------------------- FCR -13A-R/M
Input type ---------------------- K
• Option --------------------------- A2, TV, C5, W (20A)
Serial number ----------------- No. 123F05000 In addition to the above, please let us know the details of the malfunction, if any, and the operating conditions.
No. FCR11E15 2012.10
SHINKO TECHNOS CO., LTD.
OVERSEAS DIVISION
Head Office:
URL: E-mail:
2-5-1, Senbahigashi, Minoo, Osaka, Japan http://www.shinko-technos.co.jp
overseas@shinko-technos.co.jp
Tel :
Fax:
81-72-727-6100 81-72-727-7006
Loading...