Shinko DCL-33A Communication Instruction Manual

1
COMMUNICATION INSTRUCTION MANUAL DCL-33A (C5)
No.DCL32CE1 2016.06 This manual contains instructions for the communication functions, operations and notes when operating the DCL-33A. To prevent accidents arising from the misuse of this controller, please ensure the operator receives this manual.
Warning
1. System Configuration
1.1 When Using USB Communication Cable CMC-001-3 (Sold Separately)
(Fig. 1.1-1)
1.2 When Using Communication Converter IF-400 (Sold Separately)
(Fig. 1.2-1)
USB communication
cable CMC-001-3
(sold separately)
Host computer
DCL-33A
No. 0
DCL-33A
No. 1
DCL-33A
No. 30
DCL-33A
No. 0
DCL-33A
No. 1
DCL-33A
No.-30
Communication converter
IF-400 (sold separately)
RS-232C RS-485
Host computer
Regulatory temperatury na szynę DIN z serii DCL-33A
http://acse.pl
2
USB communication
cable CMC-001-3
(sold separately)
Host computer USB port
2. Wiring
2.1 When Using USB Communication Cable CMC-001-3 (Sold Separately)
(Fig. 2.1-1)
2.2 When Using Communication Converter IF-400 (Sold Separately)
D-sub 9-pin connector
(Fig. 2.2-1)
DCL-33A bottom
CMC-001-3
CDD or CPP (sold separately)
DCL-33A (Max. 31 units)
Host computer
D-sub 9-pin computer
DCL-33A (Max. 31 units)
IF-400
(sold separately)
CDD or CPP (sold separately)
Bottom of IF-400, DCL-33A
Shield wire
FG
3
Shield wire
Be sure to ground only one end of the shield wire to avoid a ground loop. If both ends of the shield wire are grounded, the circuit will be closed, resulting in a ground loop. This may cause noise. Recommended cable: OTSC-VB 2PX0.5SQ (made by Onamba Co., Ltd.) or equivalent
(Use a twisted pair cable.)
Terminator (Terminal resistor)
The terminator is mounted at the end of the wire when connecting multiple peripheral devices to a personal computer. The terminator prevents signal reflection and disturbance. Do not connect a terminator to the communication line because each DCL-33A has built-in pull-up and pull-down resistors.
3. Setting Method for Communication
Press and hold the and keys (in that order) together for approx. 3 seconds in the PV/SV Display. The unit enters Auxiliary function setting mode 1. Press the key twice. “Communication protocol” will appear. Use the or key for settings or selections, and register them by pressing the key.
Characters,
Factory Default
Setting Item, Function, Setting Range (Selection item)
Communication protocol
• Selects the communication protocol.
: Shinko protocol : Modbus ASCII mode : Modbus RTU mode : Shinko protocol (Block read) : Modbus ASCII mode (Block read) : Modbus RTU mode (Block read)
Instrument number
• Sets the instrument number.
The instrument numbers should be set one by one when multiple instruments are connected in Serial communication, otherwise communication is impossible.
• Setting range: 0 to 95
Communication speed
• Selects a communication speed equal to that of the host computer.
: 2400 bps
: 4800 bps : 9600 bps : 19200 bps : 38400 bps
Parity
• Selects the parity.
• Not available if Shinko protocol or Shinko protocol (Block read) is selected in
[Communication protocol].
: No parity
: Even : Odd
Stop bit
• Selects the stop bit.
• Not available if Shinko protocol or Shinko protocol (Block read) is selected in
[Communication protocol].
: 1 bit
: 2 bits
Press the key. The unit reverts to the PV/SV Display.
Now settings are complete.
4
4. Communication Procedure
Communication starts with command transmission from the host computer (hereafter Master), and ends with the response of the DCL-33A (hereafter Slave).
• Response with data
When the master sends the Read command, the slave responds with the corresponding set value or current status.
• Acknowledgement
When the master sends the Write command, the slave responds by sending the acknowledgement after the processing is terminated.
• Negative acknowledgement
When the master sends a non-existent command or value out of the setting range, the slave returns a negative acknowledgement.
• No response
The slave will not respond to the master in the following cases:
• Global address (Shinko protocol) is set.
(Fig. 4-1) • Broadcast address (Modbus protocol) is set.
• Communication error (framing error, parity error)
• Checksum error (Shinko protocol), LRC discrepancy (Modbus ASCII mode), CRC-16 discrepancy (Modbus RTU mode)
Communication timing between the master and slave
Master Side (Take note while programming)
When the master starts transmission through the RS-485 communication line, the master is arranged so as to provide an idle status (mark status) transmission period of 1 or more characters before sending the command to ensure synchronization on the receiving side. Set the program so that the master can disconnect the transmitter from the communication line within a 1 character transmission period after sending the command in preparation for reception of the response from the slave. To avoid collision of transmissions between the master and the slave, send the next command after carefully checking that the master has received the response. If a response to the command is not returned due to communication errors, set the Retry Processing to send the command again. (It is recommended to execute Retry twice or more.)
Slave Side
When the slave starts transmission through the RS-485 communication line, the slave is arranged so as to provide an idle status (mark status) transmission period of 1 or more characters before sending the response to ensure synchronization on the receiving side. The slave is arranged so as to disconnect the transmitter from the communication line within a 1 character transmission period after sending the response.
Command
Data
Command
Acknowledgement
Command
Negative
acknowledgement
Command
No response
Master Slave
5
5. Shinko Protocol
5.1 Transmission Mode
Shinko protocol is composed of ASCII. Hexadecimal (0 to 9, A to F), which is divided into high order (4-bit) and low order (4-bit) out of 8-bit binary data in command is transmitted as ASCII characters. Data format Start bit: 1 bit
Data bit: 7 bits Selectable Parity: Even Selectable Stop bit: 1 bit Selectable
Error detection: Checksum
5.2 Command Configuration
All commands are composed of ASCII. The data (set value, decimal number) is represented by a hexadecimal number. The negative numbers are represented in 2's complement. Numerals written below the command represent number of characters.
(1) Write command
• Write a single piece of data
Header
(02H)
Address
Sub
address
(20H)
Command type (50H)
Data
item
Data Checksum
Delimiter
(03H)
1 1 1 1 4 4 2 1
• Write multiple pieces of data
Header
(02H)
Address
Sub
address
(20H)
Command
type
(54H)
Data
item
1 1 1 1 4
Data Checksum
Delimiter
(03H)
4 x n 2 1
n: Amount of data
(2) Read command
• Read a single piece of data
Header
(02H)
Address
Sub
address
(20H)
Command
type
(20H)
Data
item
Checksum
Delimiter
(03H)
1 1 1 1 4 2 1
• Read multiple pieces of data
Header
(02H)
Address
Sub
address
(20H)
Command
type
(24H)
Data
item
Amount of
read datanChecksum
Delimiter
(03H)
1 1 1 1 4 4 2 1
(3) Response with data
• Response to ‘Read a single piece of data’
Header
(06H)
Address
Sub
address
(20H)
Command
type
(20H)
Data
item
Data Checksum
Delimiter
(03H)
1 1 1 1 4 4 2 1
6
• Response to ‘Read multiple pieces of data’
Header
(06H)
Address
Sub
address
(20H)
Command
type
(24H)
Data
item
1 1 1 1 4
Data Checksum
Delimiter
(03H)
4 x n 2 1
n: Amount of data
(4) Acknowledgement
Header
(06H)
Address Checksum
Delimiter
(03H)
1 1 2 1
(5) Negative acknowledgement
Header
(15H)
Address
Error code
Checksum
Delimiter
(03H)
1 1 1 2 1
Header: Control code to represent the beginning of the command or the response.
ASCII is used. Write command, Read command: STX (02H) fixed Response with data, Acknowledgement: ACK (06H) fixed Negative acknowledgement: NAK (15H) fixed
Instrument number (Address): Numbers by which the master discerns each slave.
Instrument number 0 to 94 and Global address 95. ASCII (20H to 7FH) is used by adding 20H to instrument numbers 0 to 95 (00H to 5FH). 95 (7FH) is called Global address, which is used when the same command is sent to all the slaves connected. However, the response is not returned.
Sub address: 20H fixed
Command type: Codes for Write command and Read command.
Command
Type
Contents Description
20H Read (A single piece of data) Reads a single piece of data.
24H Read (Multiple pieces of data) Reads consecutive multiple pieces
of data. (Amount of data: Max. 100)
50H Write (A single piece of data) Writes a single piece of data.
54H Write (Multiple pieces of data) Writes consecutive multiple pieces
of data. (Amount of data: Max. 100)
Notes about Read/Write multiple pieces of data
When reading or writing multiple pieces of data, as it takes time until slave sends response data, the master determines no response based on the timeout period below after sending a command.
Timeout period calculation: 6 ms x Amount of data
Data item: Classification of the command object.
Composed of 4-digit hexadecimal numbers, using ASCII. Refer to Section ‘7. Communication Command Table’ (pp.23 - 38).
Data: The contents of data (values) differ depending on the Write command.
Composed of 4-digit hexadecimal numbers, using ASCII. Refer to Section ‘7. Communication Command Table’ (pp.23 - 38).
Checksum: 2-character data to detect communication errors.
7
Delimiter: Control code to represent the end of command.
ASCII code ETX (03H) fixed
Error code: Represents an error type using ASCII.
Error Code Contents
1 (31H) Non-existent command
2 (32H) Not used
3 (33H) Setting outside the setting range
4 (34H) Status unable to be written (e.g. AT is performing.)
5 (35H) During setting mode by keypad operation
5.3 Checksum Calculation
Checksum is used to detect receiving errors in the command or data. Set the program for the master side as well to calculate the checksum of the response data from the slaves so that communication errors can be checked.
The ASCII code (hexadecimal) corresponding to the characters which range from the address to that before the checksum is converted to binary notation, and the total value is calculated. The lower one byte of the total value is converted to 2’s complement, and then to hexadecimal numbers, that is, ASCII code for the checksum.
• 1’s complement: Reverse each binary bit. 0 will become 1 and vice versa.
• 2’s complement: Add 1 to 1’s complement.
[Example of checksum calculation]
Write SV1 (0001H) to 600 (0258H). See (Fig. 5.3-1). Address (instrument number): 0 (20H)
(Fig. 5.3-1)
20H 20H 50H 30H 30H 30H 31H 30H 32H 35H 38H
0010 0000 0010 0000 0101 0000 0011 0000 0011 0000 0011 0000 0011 0001 0011 0000 0011 0010 0011 0101 0011 1000
+
10 0010 0000
[Hexadecimal] [Binary]
1101 1111
1
+
1110 0000
E 0
45H
30H
[1's complement]
[2's complement]
[Hexadecimal]
[ASCII]
Checksum
STX ETX
P 0 0 0 1 0 2 5 8
02H 20H 20H 50H 30H 30H 30H 31H 30H 32H 35H 38H 03H
[Characters above are represented in ASCII.]
Checksum
Checksum calculation range
[e.g.]
E
45H 30H
0
8
5.4 Command Example
Numerals written below the command represent number of characters.
(1) Read [Address 1, PV]
• Read command from the master
Header
(02H)
Address
(21H)
Sub
address
(20H)
Command
type
(20H)
Data item
[0080H]
(30H 30H 38H 30H)
Checksum
(44H 37H)
Delimiter
(03H)
1 1 1 1 4 2 1
• A response from the slave in normal status [When PV=25 (0019H)]
Header
(06H)
Address
(21H)
Sub
address
(20H)
Command
type
(20H)
Data item
[0080H]
(30H 30H 38H 30H)
Data
[0019H]
(30H 30H 31H 39H)
Checksum
(30H 44H)
Delimiter
(03H)
1 1 1 1 4 4 2 1
(2) Read [Address 1, SV1]
• Read command from the master
Header
(02H)
Address
(21H)
Sub
address
(20H)
Command
type
(20H)
Data item
[0001H]
(30H 30H 30H 31H)
Checksum
(44H 45H)
Delimiter
(03H)
1 1 1 1 4 2 1
• A response from the slave in normal status [When SV1=600 (0258H)]
Header
(06H)
Address
(21H)
Sub
address
(20H)
Command
type
(20H)
Data item
[0001H]
(30H 30H 30H 31H)
Data
[0258H]
(30H 32H 35H 38H)
Checksum
(30H 46H)
Delimiter
(03H)
1 1 1 1 4 4 2 1
(3) Write [Address 1, SV1 600 (0258H)]
• Write command from the master
Header
(02H)
Address
(21H)
Sub
address
(20H)
Command
type
(50H)
Data item
[0001H]
(30H 30H 30H 31H)
Data
[0258H]
(30H 32H 35H 38H)
Checksum
(44H 46H)
Delimiter
(03H)
1 1 1 1 4 4 2 1
• A response from the slave in normal status
Header
(06H)
Address
(21H)
Checksum
(44H 46H)
Delimiter
(03H)
1 1 2 1
9
(4) Read [Address 1, 25 commands from SV1]
• Read command from the master
Header
(02H)
Address
(21H)
Sub
address
(20H)
Command
type
(24H)
Data item
[0001H]
(30H 30H 30H 31H)
Amount of read data
25 [0019H]
(30H 30H 31H 39H)
Checksum
(31H 30H)
Delimiter
(03H)
1 1 1 1 4 4 2 1
• A response from the slave in normal status
Header
(06H)
Address
(21H)
Sub
address
(20H)
Command
type
(24H)
Data item
[0001H]
(30H 30H 30H 31H)
1 1 1 1 4
Data
[00000000055A
• • •
0000]
(
30H 30H 30H 30H 30H 30H 30H 30H 30H 35H 35H 41H • • • 30H 30H 30H 30H)
Checksum
(43H 38H)
Delimiter
(03H)
100 (4 x 25) 2 1
Response data becomes as follows.
Data Item Data
Data
(Converted to Hexadecimal)
0001H SV1 0 0000H 0002H Input type K [-200 to 1370 ] 0000H 0003H Scaling high limit 1370 055AH 0004H Scaling low limit -200 FF38H 0005H Decimal point place No decimal point 0000H 0006H A1 type No alarm action 0000H 0007H A2 type
No alarm action
0000H
0008H A3 type
No alarm action
0000H
0009H A4 type
No alarm action
0000H
000AH
Reserved
0 0000H
000BH
Reserved
0 0000H
000CH
Reserved
0 0000H
000DH
Reserved
0 0000H 000EH SV1 0 0000H 000FH SV2 0 0000H 0010H
Reserved
0 0000H 0011H
Reserved
0 0000H 0012H A1 value 0 0000H 0013H A1 high limit alarm value 0 0000H 0014H A2 value 0 0000H 0015H A2 high limit alarm value 0 0000H 0016H A3 value 0 0000H 0017H A3 high limit alarm value 0 0000H 0018H A4 value 0 0000H 0019H A4 high limit alarm value 0 0000H
10
(5) Write [Address 1, 25 commands from SV1]
(e.g.) The data (25 commands from SV1) is shown below.
Data Item Data
Data
(Converted to Hexadecimal)
0001H SV1 2000 07D0H 0002H Input type K [-199.9 to 400.0 ] 0001H 0003H Scaling high limit 4000 0FA0H 0004H Scaling low limit 0 0000H 0005H Decimal point place XXX.X (1 digit after
decimal point)
0001H
0006H A1 type
High/Low limits
independent alarm
000AH
0007H A2 type High limit alarm 0001H 0008H A3 type Low limit alarm 0002H 0009H A4 type No alarm action 0000H 000AH
Reserved
0 0000H 000BH
Reserved
0 0000H 000CH
Reserved
0 0000H 000DH
Reserved
0 0000H 000EH SV1 2000 07D0H 000FH SV2 0 0000H 0010H
Reserved
0 0000H 0011H
Reserved
0 0000H 0012H A1 value 1000 03E8H 0013H A1 high limit alarm value 500 01F4H 0014H A2 value 1000 03E8H 0015H A2 high limit alarm value 0 0000H 0016H A3 value -1500 FA24H 0017H A3 high limit alarm value 0 0000H 0018H A4 value 0 0000H 0019H A4 high limit alarm value 0 0000H
• Write command from the master (When writing the above data)
Header
(02H)
Address
(21H)
Sub
address
(20H)
Command
type
(54H)
Data item
[0001H]
(30H 30H 30H 31H)
1 1 1 1 4
Data
[07D000010FA0 • • • 0000]
(30H 37H 44H 30H 30H 30H 30H 31H 30H 46H 41H 30H • • • 30H 30H 30H 30H)
Checksum
(45H 46H)
Delimiter
(03H)
100 (4 x 25) 2 1
• Response from the slave in normal status
Header
(06H)
Address
(21H)
Checksum
(44H 46H)
Delimiter
(03H)
1 1 2 1
11
6. Modbus Protocol
6.1 Transmission Mode
There are 2 transmission modes (ASCII and RTU) in Modbus protocol.
6.1.1 ASCII Mode
Hexadecimal (0 to 9, A to F), which is divided into high order (4-bit) and low order (4-bit) out of 8-bit binary data in command is transmitted as ASCII characters. Data format Start bit: 1 bit
Data bit: 7 bits (Selectable) Parity: Even (No parity, Odd) (Selectable)
Stop bit: 1 bit (2 bits) (Selectable) Error detection : LRC (Longitudinal Redundancy Check) Data communication interval: 1 second or less
6.1.2 RTU Mode
8-bit binary data in command is transmitted as it is. Data format Start bit: 1 bit
Data bit: 8 bits Parity: No parity (Even, Odd) (Selectable) Stop bit: 1 bit (2 bits) (Selectable)
Error detection: CRC-16 (Cyclic Redundancy Check)
6.2 Data Communication Interval
6.2.1 ASCII Mode
No communication interval limit between characters
6.2.2 RTU Mode
1.5 character transmission times or less (Communication speed 2400, 4800, 9600, 19200 bps: 1.5 character transmission times, Communication speed 38400 bps: 750 s) To transmit continuously, an interval between characters which consist of one message, must be within 1.5 character transmission times. If an interval lasts longer than 1.5 character transmission times, the DCL-33A assumes that transmission from the master is finished, which results in a communication error, and will not return a response.
6.3 Message Configuration
6.3.1 ASCII Mode
ASCII mode message is configured to start by Header [: (colon) (3AH)] and end by Delimiter [CR (carriage return) (0DH) + LF (Line feed) (0AH)]. Data section: Max. 2 x 252 characters
Header
(:)
Slave
address
Function
code
Data
Error check
LRC
Delimiter
(CR)
Delimiter
(LF)
6.3.2 RTU Mode
RTU mode is configured to start after idle time is processed for more than 3.5 character transmissions, and end after idle time is processed for more than 3.5 character transmissions. (Communication speed 2400, 4800, 9600, 19200 bps: 3.5 character transmission times, Communication speed 38400 bps: 1.75 ms) Data section: Max. 252 bytes
3.5 idle
characters
Slave
address
Function
code
Data
Error check
CRC-16
3.5 idle
characters
12
(1) Slave Address
Slave address is an individual instrument number on the slave side, and is set within the range 0 to 95 (00H to 5FH). The master identifies slaves by the slave address of the requested message. The slave informs the master which slave is responding to the master by placing its own address in the response message. Slave address 0 (00H, Broadcast address) can identify all the slaves connected. However, slaves do not respond.
(2) Function Code
The function code is the command code for the slave to undertake one of the following actions. (Table 6.3-1)
Type Function Code Sub-Function Code Contents
03 (03H)
Reads a single or multiple piece(s) of
data from slave(s). 04 (04H) Reads information from slave(s).
06 (06H) Writes a single piece of data to slave(s).
Data access
16 (10H) Writes multiple pieces of data to slave(s).
08 (08H) 00 Echoes back the request message.
Diagnostics
43 (2BH) 14 Reads device identification information.
The function code is used to discern whether the response is normal (acknowledgement) or if any error (negative acknowledgement) has occurred when the slave returns the response message to the master. When acknowledgement is returned, the slave simply returns the original function code.
When negative acknowledgement is returned, the MSB of the original function code is set as 1 for the response.
For example, if the master sends request message setting 10H to the function code by mistake, slave returns 90H by setting the MSB to 1, because the former is an illegal function. For negative acknowledgement, the exception codes below (Table 6.3-2) are set to the data of the response message, and returned to the master in order to inform it of what kind of error has occurred. (Table 6.3-2)
Exception Code Contents
1 (01H) Illegal function (Non-existent function) 2 (02H) Illegal data address (Non-existent data address) 3 (03H) Illegal data value (Value out of the setting range)
17 (11H)
Shinko protocol error code 4 (Status unable to be written. (e.g.) AT is performing.)
18 (12H)
Shinko protocol error code 5 (During setting mode by keypad operation)
(3) Data
Data differs depending on the function code. A request message from the master is composed of a data item, amount of data and setting data. A response message from the slave is composed of the number of bytes, data and exception codes in negative acknowledgements, corresponding to the request message. The effective range of data is -32768 to 32767 (8000H to 7FFFH). Refer to Section “7. Communication Command Table” (pp.23 - 38).
(4) Error Check
ASCII Mode
A
fter calculating LRC (Longitudinal Redundancy Check) from the slave address to the end of data,
the calculated 8-bit data is converted to two ASCII characters, and are appended to the end of message.
How to Calculate LRC
1
Create a message in RTU mode.
2
Add all the values from the slave address to the end of data. This is assumed as X.
3
Make a complement for X (bit reverse). This is assumed as X.
4
Add a value of 1 to X. This is assumed as X.
5
Set X as an LRC to the end of the message.
6
Convert the whole message to ASCII characters.
13
RTU Mode
After calculating CRC-16 (Cyclic Redundancy Check) from the slave address to the end of the data, the calculated 16-bit data is appended to the end of message in sequence from low order to high order.
How to calculate CRC-16
In the CRC-16 system, the information is divided by the polynomial series. The remainder is added to the end of the information and transmitted. The generation of a polynomial series is as follows. (Generation of polynomial series: X16+ X15+ X2+ 1)
1
Initialize the CRC-16 data (assumed as X) (FFFFH).
2
Calculate exclusive OR (XOR) with the 1st data and X. This is assumed as X.
3
Shift X one bit to the right. This is assumed as X.
4
When a carry is generated as a result of the shift, XOR is calculated by X of
3
and the
fixed value (A001H). This is assumed as X. If a carry is not generated, go to step5.
5
Repeat steps3and4until shifting 8 times.
6
XOR is calculated with the next data and X. This is assumed as X.
7
Repeat steps3to5.
8
Repeat steps3to
5
up to the final data.
9
Set X as CRC-16 to the end of message in sequence from low order to high order.
6.4 Message Example
6.4.1 ASCII Mode
Numerals written below the command represent the number of characters.
(1) Read [Slave address 1, PV (0100H)]
• A request message from the master
Header
(3AH)
Slave
address
(30H 31H)
Function
code
(30H 33H)
Data item
[0100H]
(30H 31H 30H 30H)
Amount of data
[0001H]
(30H 30H 30H 31H)
Error check
LRC
(46H 41H)
Delimiter
CR+LF
(0DH 0AH)
1 2 2 4 4 2 2
• Response message from the slave in normal status [When PV=600 (0258H)]
Header
(3AH)
Slave
address
(30H 31H)
Function
code
(30H 33H)
Number of
response bytes
[02H]
(30H 32H)
Data
[0258H]
(30H 32H 35H 38H)
Error check
LRC
(41H 30H)
Delimiter
CR+LF
(0DH 0AH)
1 2 2 2 4 2 2
(2) Write [Slave address 1, SV1 (0001H)]
• A request message from the master [When writing SV1 to 600 (0258H)]
Header
(3AH)
Slave
address
(30H 31H)
Function
code
(30H 36H)
Data item
[0001H]
(30H 30H 30H 31H)
Data
[0258H]
(30H 32H 35H 38H)
Error check
LRC
(39H 45H)
Delimiter
CR+LF
(0DH 0AH)
1 2 2 4 4 2 2
• Response message from the slave in normal status
Header
(3AH)
Slave
address
(30H 31H)
Function
code
(30H 36H)
Data item
[0001H]
(30H 30H 30H 31H)
Data
[0258H]
(30H 32H 35H 38H)
Error check
LRC
(39H 45H)
Delimiter
CR+LF
(0DH 0AH)
1 2 2 4 4 2 2
• Response message from the slave in exception (error) status (When a value out of the setting range is written) The function code MSB is set to 1 for the response message in exception (error) status [86H (38H 36H)]. The exception code 03H (30H 33H: Value out of the setting range) is returned (error).
Header
(3AH)
Slave
address
(30H 31H)
Function
code
(38H 36H)
Exception code
[03H]
(30H 33H)
Error check
LRC
(37H 36H)
Delimiter
CR+LF
(0DH 0AH)
1 2 2 2 2 2
14
(3) Read [Slave address 1, SV1 (0001H)]
• A request message from the master
Header
(3AH)
Slave
address
(30H 31H)
Function
code
(30H 33H)
Data item
[0001H]
(30H 30H 30H 31H)
Amount of data
[0001H]
(30H 30H 30H 31H)
Error check
LRC
(46H 41H)
Delimiter
CR+LF
(0DH 0AH)
1 2 2 4 4 2 2
• Response message from the slave in normal status [When SV1=600 (0258H)]
Header
(3AH)
Slave
address
(30H 31H)
Function
code
(30H 33H)
Number of
response bytes
[02H]
(30H 32H)
Data
[0258H]
(30H 32H 35H 38H)
Error check
LRC
(41H 30H)
Delimiter
CR+LF
(0DH 0AH)
1 2 2 2 4 2 2
• Response message from the slave in exception (error) status (When data item is incorrect) The function code MSB is set to 1 for the response message in exception (error) status [83H (38H 33H)]. The exception code 02H (30H 32H: Non-existent data address) is returned (error).
Header
(3AH)
Slave
address
(30H 31H)
Function
code
(38H 33H)
Exception code
[02H]
(30H 32H)
Error check
LRC
(37H 41H)
Delimiter
CR+LF
(0DH 0AH)
1 2 2 2 2 2
(4) Read [Slave address 1, 25 commands from SV1]
• A request message from the master
Header
(3AH)
Slave
address
(30H 31H)
Function
code
(30H 33H)
Data item
[0001H]
(30H 30H 30H 31H)
Amount of data
[0019H]
(30H 30H 31H 39H)
Error check
LRC
(45H 32H)
Delimiter
CR+LF
(0DH 0AH)
1 2 2 4 4 2 2
• Response message from the slave in normal status
Header
(3AH)
Slave
address
(30H 31H)
Function
code
(30H 33H)
Number of
response bytes
[32H]
(33H 32H)
1 2 2 2
Data
[00000000055A • • • 0000]
(30H 30H 30H 30H 30H 30H 30H 30H 30H 35H 35H 41H • • • 30H 30H 30H 30H)
Error check
LRC
(33H 34H)
Delimiter
CR+LF
(0DH 0AH)
100 (4 x 25) 2 2
Response data section is shown below.
Data Item Data
Data
(Converted to Hexadecimal)
0001H SV1 0 0000H 0002H Input type K [-200 to 1370 ] 0000H 0003H Scaling high limit 1370 055AH 0004H Scaling low limit -200 FF38H 0005H Decimal point place No decimal point 0000H 0006H A1 type No alarm action 0000H 0007H A2 type
No alarm action
0000H
0008H A3 type
No alarm action
0000H
0009H A4 type
No alarm action
0000H
000AH
Reserved
0 0000H
000BH
Reserved
0 0000H
000CH
Reserved
0 0000H
000DH
Reserved
0 0000H 000EH SV1 0 0000H 000FH SV2 0 0000H
15
0010H
Reserved
0 0000H 0011H
Reserved
0 0000H 0012H A1 value 0 0000H 0013H A1 high limit alarm value 0 0000H 0014H A2 value 0 0000H 0015H A2 high limit alarm value 0 0000H 0016H A3 value 0 0000H 0017H A3 high limit alarm value 0 0000H 0018H A4 value 0 0000H 0019H A4 high limit alarm value 0 0000H
(5) Write (Slave address 1, 25 commands from SV1)
(e.g.) The data (25 commands from SV1) is shown below.
Data Item Data
Data
(Converted to Hexadecimal)
0001H SV1 2000 07D0H 0002H Input type K [-199.9 to 400.0 ] 0001H 0003H Scaling high limit 4000 0FA0H 0004H Scaling low limit 0 0000H 0005H Decimal point place XXX.X (1 digit after
decimal point)
0001H
0006H A1 type
High/Low limits
independent alarm
000AH
0007H A2 type High limit alarm 0001H 0008H A3 type Low limit alarm 0002H 0009H A4 type No alarm action 0000H 000AH
Reserved
0 0000H 000BH
Reserved
0 0000H 000CH
Reserved
0 0000H 000DH
Reserved
0 0000H 000EH SV1 2000 07D0H 000FH SV2 0 0000H 0010H
Reserved
0 0000H 0011H
Reserved
0 0000H 0012H A1 value 1000 03E8H 0013H A1 high limit alarm value 500 01F4H 0014H A2 value 1000 03E8H 0015H A2 high limit alarm value 0 0000H 0016H A3 value -1500 FA24H 0017H A3 high limit alarm value 0 0000H 0018H A4 value 0 0000H 0019H A4 high limit alarm value 0 0000H
• A request message from the master (when writing the above data)
Header
(3AH)
Slave
address
(30H 31H)
Function
code
(31H 30H)
Data item
[0001H]
(30H 30H 30H 31H)
Amount of data
[0019H]
(30H 30H 31H 39H)
Number of bytes
[32H]
(33H 32H)
1 2 2 4 4 2
Data
[07D00001
• • •
0000
(30H 37H 44H 30H 30H 30H 30H 31H
• • •
30H 30H 30H 30H)
Error check
LRC
(34H 45H)
Delimiter
CR+LF
(0DH 0AH)
100 (4 x 25) 2 2
• Response message from the slave in normal status
Header
(3AH)
Slave
address
(30H 31H)
Function
code
(31H 30H)
Data item
[0001H]
(30H 30H 30H 31H)
Amount of data
[0019H]
(30H 30H 31H 39H)
Error check
LRC
(44H 35H)
Delimiter
CR+LF
(0DH 0AH)
1 2 2 4 4 2 2
16
6.4.2 RTU Mode
Numerals written below the command represent number of characters.
(1) Read [Slave address 1, PV (0100H)]
• A request message from the master
3.5 idle
characters
Slave
address
(01H)
Function
code
(03H)
Data item
(0100H)
Amount of data
(0001H)
Error check
CRC-16 (85F6H)
3.5 idle
characters
1 1 2 2 2
• Response message from the slave in normal status [When PV is 600 (0258H)]
3.5 idle
characters
Slave
address
(01H)
Function
code
(03H)
Number of
response bytes
(02H)
Data
(0258H)
Error check
CRC-16
(B8DEH)
3.5 idle
characters
1 1 1 2 2
(2) Write [Slave address 1, SV1 (0001H)]
• A request message from the master [When 600 (0258H) is written to SV1]
3.5 idle
characters
Slave
address
(01H)
Function
code
(06H)
Data item
(0001H)
Data
(0258H)
Error check
CRC-16
(D890H)
3.5 idle
characters
1 1 2 2 2
• Response message from the slave in normal status
3.5 idle
characters
Slave
address
(01H)
Function
code
(06H)
Data item
(0001H)
Data
(0258H)
Error check
CRC-16
(D890H)
3.5 idle
characters
1 1 2 2 2
• Response message from the slave in exception (error) status (When a value out of the setting range is set) The function code MSB is set to 1 for the response message in exception (error) status, and 86H is returned. The Exception code 03H (Value out of the setting range) is returned (error).
3.5 idle
characters
Slave
address
(01H)
Function
code
(86H)
Exception code
(03H)
Error check
CRC-16 (0261H)
3.5 idle
characters
1 1 1 2
(3) Read [Slave address 1, SV1 (0001H)]
• A request message from the master
3.5 idle
characters
Slave
address
(01H)
Function
code
(03H)
Data item
(0001H)
Data
(0001H)
Error check
CRC-16
(D5CAH)
3.5 idle
characters
1 1 2 2 2
• Response message from the slave in normal status [When SV1 is 600 (0258H)]
3.5 idle
characters
Slave
address
(01H)
Function
code
(03H)
Number of
response bytes
(02H)
Data
(0258H)
Error check
CRC-16
(B8DEH)
3.5 idle
characters
1 1 1 2 2
• Response message from the slave in exception (error) status (When data item is incorrect) The function code MSB is set to 1 for the response message in exception (error) status, and 83H is returned. The Exception code 02H (Non-existent data address) is returned (error).
3.5 idle
characters
Slave
address
(01H)
Function
code
(83H)
Exception code
(02H)
Error check
CRC-16
(C0F1H)
3.5 idle
characters
1 1 1 2
17
(4) Read [Slave address 1, 25 commands from SV1]
• A request message from the master
3.5 idle
characters
Slave
address
(01H)
Function
code
(03H)
Data item
(0001H)
A
mount of
data
(0019H)
Error check
CRC-16
(D5C0H)
3.5 idle
characters
1 1 2 2 2
• Response message from the slave in normal status
3.5 idle
characters
Slave
address
(01H)
Function
code
(03H)
Number of
response byte
(32H)
Data
(00000000055A
• • •
0000H)
Error check
CRC-16
(60D9H)
3.5 idle
characters
1 1 1 50 (2 x 25) 2
Response data section is shown below.
Data Item Data
Data
(Converted to Hexadecimal)
0001H SV1 0 0000H 0002H Input type K [-200 to 1370 ] 0000H 0003H Scaling high limit 1370 055AH 0004H Scaling low limit -200 FF38H 0005H Decimal point place No decimal point 0000H 0006H A1 type No alarm action 0000H 0007H A2 type
No alarm action
0000H
0008H A3 type
No alarm action
0000H
0009H A4 type
No alarm action
0000H
000AH
Reserved
0 0000H
000BH
Reserved
0 0000H
000CH
Reserved
0 0000H
000DH
Reserved
0 0000H 000EH SV1 0 0000H 000FH SV2 0 0000H 0010H
Reserved
0 0000H 0011H
Reserved
0 0000H 0012H A1 value 0 0000H 0013H A1 high limit alarm value 0 0000H 0014H A2 value 0 0000H 0015H A2 high limit alarm value 0 0000H 0016H A3 value 0 0000H 0017H A3 high limit alarm value 0 0000H 0018H A4 value 0 0000H 0019H A4 high limit alarm value 0 0000H
18
(5) Write [Slave address 1, 25 commands from SV1]
(e.g.) The data (25 commands from SV1) is shown below.
Data Item Data
Data
(Converted to Hexadecimal)
0001H SV1 2000 07D0H 0002H Input type K [-199.9 to 400.0 ] 0001H 0003H Scaling high limit 4000 0FA0H 0004H Scaling low limit 0 0000H 0005H Decimal point place XXX.X (1 digit after
decimal point)
0001H
0006H A1 type
High/Low limits
independent alarm
000AH
0007H A2 type High limit alarm 0001H 0008H A3 type Low limit alarm 0002H 0009H A4 type No alarm action 0000H 000AH
Reserved
0 0000H 000BH
Reserved
0 0000H 000CH
Reserved
0 0000H 000DH
Reserved
0 0000H 000EH SV1 2000 07D0H 000FH SV2 0 0000H 0010H
Reserved
0 0000H 0011H
Reserved
0 0000H 0012H A1 value 1000 03E8H 0013H A1 high limit alarm value 500 01F4H 0014H A2 value 1000 03E8H 0015H A2 high limit alarm value 0 0000H 0016H A3 value -1500 FA24H 0017H A3 high limit alarm value 0 0000H 0018H A4 value 0 0000H 0019H A4 high limit alarm value 0 0000H
• A request message from the master (When writing the above data)
3.5 idle
characters
Slave
address
(01H)
Function
code
(10H)
Data item
(0001H)
Amount of
data
(0019H)
Number of bytes
(32H)
1 1 2 2 1
Data
(07D000010FA0
• • •
0000H)
Error check
CRC-16
(5C89H)
3.5 idle
characters
50 (2 x 25) 2
• Response message from the slave in normal status
3.5 idle
characters
Slave
address
(01H)
Function
code
(10H)
Data item
(0001H)
Amount of
data
(0019H)
Error check
CRC-16 (5003H)
3.5 idle
characters
1 1 2 2 2
19
6.5 Diagnostics Function Modbus protocol has the following diagnostics functions.
• Echoes back the request message.
• Reads device identification information.
6.5.1 Message Configuration ASCII mode
Header
(:)
Slave
address
Function
code
Data
Error check
LRC
Delimiter
(CR)
Delimiter
(LF)
RTU mode
3.5 idle
characters
Slave
address
Function
code
Data
Error check
CRC-16
3.5 idle
characters
(1) Slave address
Slave address is an individual instrument number on the slave side, and is set within the range 1 to 95 (01H to 5FH). The master identifies slaves by the slave address of the requested message. The slave informs the master which slave is responding to the master by placing its own address in the response message. Diagnostics function is disabled for the Slave address 0 (00H, broadcast address).
(2) Function code
The function code is the command code for the slave to undertake the following action types.
Type Function Code Sub-Function Code
Contents
08 (08H) 00 (0000H) Echoes back the request message.
Diagnostics
43 (2BH) 14 (0EH) Reads device identification information.
Function code is used to discern whether the response is normal (acknowledgement) or if any error (negative acknowledgement) has occurred when the slave returns the response message to the
master. When acknowledgement is returned, the slave simply returns the original function code. When negative acknowledgement is returned, the MSB of the original function code is set as 1 for the response. For example, when the master sends request message setting 0FH to the sub-function code by mistake, slave returns ABH by setting the MSB to 1, because the former is a non-existent
sub-function code. For negative acknowledgement, the exception codes below are set to the data of the response message, and returned to the master in order to inform it of what kind of error has occurred.
Exception Code Contents
1 (01H)
Illegal function (Non-existent function) Sub-function code is not correct.
2 (02H)
Illegal data address (Non-existent data address) For function code 43: Object ID is any value other than 00, 01, 02.
3 (03H)
Illegal data value (Value out of the setting range) For function code 08: Data is less than 1, or has exceeded 100. For function code 43: Read Device ID code is any value other than 01, 04.
(3) Data
Data differs depending on the function code. For the Function code 08 (08H), a request message from the master side is composed of ‘Sub-function code 2 Bytes (0000H)’ and ‘Data n x 2 Bytes’. [n: Amount of data (Max. 100)] In normal status, a response message from the slave side is the same as the request message.
Function code
1 Byte
08H
Sub-function code
1 Byte
0000H fixed
Data n x 2 Bytes Random value (Max. 100)
20
For Function code 43 (2BH), the request message from the master side is composed of Sub-function code 14 (0EH), Read Device ID code and Object ID.
Function code 1 Byte 2BH Sub-function code (MEI type) 1 Byte 0EH Read Device ID code (Corresponds to Basic category)
1 Byte 01H/04H
Object ID 1 Byte 00
Vendor name
SHINKO TECHNOS CO., LTD.
01
Product code (model)
(e.g.) DCL-33A-R/M
02
Version number (D, T, MP)
(e.g.) Dxx-xxxx-xx, MPxxxx-xx
Response message from the slave is composed of Sub-function code 14 (0EH) (for request), Read Device ID code and Object ID.
Function code 1 Byte 2BH
Sub-function code (MEI type) 1 Byte 0EH
Data Read Device ID code 1 Byte 01H/04H
Conformity level 1 Byte 01H/81H
More Follows 1 Byte 00H/FFH
Next Object ID 1 Byte Object ID number
Number of Objects 1 Byte
List of Object ID 1 Byte
List of Object length 1 Byte
List of Object value Object length
For the response message (negative acknowledgement), an exception code is set and returned.
Function code 1 Byte ABH Exception code 1 Byte 01H/02H/03H
(4) Error check
16-bit data to detect communication errors.
Refer to Section ‘6.3 Message Configuration (4) Error Check (pp.12, 13).
6.5.2 Message Example
Message example in RTU mode are shown below. Numerals written below the command represent the number of characters.
(1) Echo back Slave address 1, Request message
• A request message from the master [Test data 200 (00C8H), 60 (003CH), 10 (000AH)]
3.5 idle
characters
Slave
address
(01H)
Function
code
(08H)
Sub-function
code
(0000H)
Data
(00C8003C000AH)
Error check
CRC-16
(E7D9H)
3.5 idle
characters
1 1 2 n x 2 2
• Response message from the slave in normal status (Echoes back the same message.)
3.5 idle
characters
Slave
address
(01H)
Function
code
(08H)
Sub-function
code
(0000H)
Data
(00C8003C000AH)
Error check
CRC-16
(E7D9H)
3.5 idle
characters
1 1 2 n x 2 2
21
(2) Read Slave address 1, Device identification information (Vendor name)
• A request message from the master
3.5 idle
characters
Slave
address
(01H)
Function
code
(2BH)
Sub-function
code
(0EH)
Data
(0400H)
Error check
CRC-16 (7327H)
3.5 idle
characters
1 1 1 2 2
• Response message from the slave in normal status (SHINKO TECHNOS CO., LTD.)
3.5 idle
characters
Slave
address
(01H)
Function
code
(2BH)
Sub-function
code
(0EH)
1 1 1
Data
(048100000100185348494E4B4F20544543484E4F5320434F2E2C204C54442EH)
31
Error check
CRC-16
(1C54H)
3.5 idle
characters
2
Data in the response message becomes as follows.
Data Read Device ID code 1 Byte 04H
Conformity level
1 Byte
81H
More Follows
1 Byte
00H
Next Object ID
1 Byte
00H
Number of Objects
1 Byte
01H
List of Object ID
1 Byte
00H
List of Object length
1 Byte
24(18H)
List of Object value Object length S(53H)
H(48H) I(49H) N(4EH) K(4BH) O(4FH)
(20H) T(54H) E(45H) C(43H) H(48H) N(4EH) O(4FH) S(53H)
(20H) C(43H) O(4FH) .(2EH) ,(2CH)
(20H) L(4CH) T(54H) D(44H) .(2EH)
22
(3) Read Slave address 1, Device identification information (Product code)
• A request message from the master
3.5 idle
characters
Slave
address
(01H)
Function
code
(2BH)
Sub-function
code
(0EH)
Data
(0401H)
Error check
CRC-16
(B2E7H)
3.5 idle
characters
1 1 1 2 2
• Response message from the slave in normal status (DCL-33A-R/M)
3.5 idle
characters
Slave
address
(01H)
Function
code
(2BH)
Sub-function
code
(0EH)
1 1 1
Data
(0481000001010B44434C2D3333412D522F4DH)
Error check
CRC-16
(8EF3H)
3.5 idle
characters
18 2
Data in the response message becomes as follows.
Data Read Device ID code
1 Byte
04H
Conformity level
1 Byte
81H
More Follows
1 Byte
00H
Next Object ID
1 Byte
00H
Number of Objects
1 Byte
01H
List of Object ID
1 Byte
01H
List of Object length
1 Byte
11(0BH)
List of Object value Object length D(44H)
C(43H) L(4CH)
-(2DH) 3(33H) 3(33H) A(41H)
-(2DH) R(52H) /(2FH) M(4DH)
• Response message from the slave in exception (error) status [when Sub-function code (MEI type) is incorrect] The function code MSB is set to 1 for the response message in exception (error) status, and ABH is returned. Exception code 01H (Non-existent function) is returned (error).
3.5 idle
characters
Slave
address
(01H)
Function
code
(ABH)
Exception code
(01H)
Error check
CRC-16 (9EF0H)
3.5 idle
characters
1 1 1 2
23
7. Communication Command Table
7.1 Shinko Protocol, Modbus ASCII Mode, Modbus RTU Mode Commands
7.1.1 A Single Piece of Data Read/Write Command Shinko
Command
Type
Modbus
Function
Code
Data Item Data
20H/50H 03H/06H 0001H SV1 Set value 20H/50H 03H/06H 0003H AT Perform/Cancel 0000H: AT Cancel
0001H: AT Perform 20H/50H 03H/06H 0004H OUT1 proportional band Set value 20H/50H 03H/06H 0005H OUT2 proportional band Set value 20H/50H 03H/06H 0006H
Integral time
Set value 20H/50H 03H/06H 0007H
Derivative time
Set value 20H/50H 03H/06H 0008H OUT1 proportional cycle Set value 20H/50H 03H/06H 0009H OUT2 proportional cycle Set value 20H/50H 03H/06H 000AH Manual reset Set value 20H/50H 03H/06H 000BH A1 value Set value 20H/50H 03H/06H 000FH
Heater burnout alarm
Set value 20H/50H 03H/06H 0010H
Loop break alarm time
Set value 20H/50H 03H/06H 0011H
Loop break alarm span
Set value 20H/50H 03H/06H 0012H Set value lock
0000H: Unlock
0001H: Lock 1
0002H: Lock 2
0003H: Lock 3 20H/50H 03H/06H 0015H Sensor correction Set value 20H/50H 03H/06H 0016H Overlap/Dead band Set value 20H/50H 03H/06H 0018H Scaling high limit Set value 20H/50H 03H/06H 0019H Scaling low limit Set value 20H/50H 03H/06H 001AH Decimal point place
0000H: XXXX (No decimal point)
0001H: XXX.X (1 digit after decimal point)
0002H: XX.XX (2 digits after decimal point)
0003H: X.XXX (3 digits after decimal point) 20H/50H 03H/06H 001BH PV filter time constant Set value 20H/50H 03H/06H 001CH OUT1 high limit Set value 20H/50H 03H/06H 001DH OUT1 low limit Set value 20H/50H 03H/06H 001EH OUT1 ON/OFF hysteresis Set value 20H/50H 03H/06H 001FH OUT2 cooling method 0000H: Air cooling (Linear
characteristic)
0001H: Oil cooling (1.5th power of
the linear characteristic)
0002H: Water cooling (2nd power
of the linear characteristic) 20H/50H 03H/06H 0020H OUT2 high limit Set value 20H/50H 03H/06H 0021H OUT2 low limit Set value 20H/50H 03H/06H 0022H OUT2 ON/OFF hysteresis Set value 20H/50H 03H/06H 0023H A1 type
0000H: No alarm action 0001H: High limit alarm 0002H: Low limit alarm 0003H: High/Low limits alarm 0004H: High/Low limit range alarm 0005H: Process high alarm 0006H: Process low alarm 0007H: High limit with standby alarm 0008H: Low limit with standby alarm 0009H: High/Low limits with standby
24
Shinko
Command
Type
Modbus
Function
Code
Data Item Data
20H/50H 03H/06H 0023H A1 type 000AH: High/Low limits independent
000BH: High/Low limit range
independent
000CH:High/Low limits with standby
independent 20H/50H 03H/06H 0025H A1 hysteresis Set value 20H/50H 03H/06H 0029H A1 delay time Set value 20H/50H 03H/06H 0040H A1 Energized/De-energized 0000H: Energized
0001H: De-energized
20H/50H 03H/06H 0042H A1 HOLD function 0000H: Not holding
0001H: Holding
20H/50H 03H/06H 0044H Input type 0000H: K [-200 to 1370 ]
0001H: K [-199.9 to 400.0 ] 0002H: J [-200 to 1000 ] 0003H: R [0 to 1760 ] 0004H: S [0 to 1760 ] 0005H: B [0 to 1820 ] 0006H: E [-200 to 800 ] 0007H: T [-199.9 to 400.0 ] 0008H: N [-200 to 1300 ] 0009H: PL- [0 to 1390 ] 000AH: C (W/Re5-26) [0 to 2315 ] 000BH: Pt100 [-199.9 to 850.0 ] 000CH: JPt100 [-199.9 to 500.0 ] 000DH: Pt100 [-200 to 850 ] 000EH: JPt100 [-200 to 500 ] 000FH: K [-320 to 2500 ] 0010H: K [-199.9 to 750.0 ] 0011H: J [-320 to 1800 ] 0012H: R [0 to 3200 ] 0013H: S [0 to 3200 ] 0014H: B [0 to 3300 ] 0015H: E [-320 to 1500 ] 0016H: T [-199.9 to 750.0 ] 0017H: N [-320 to 2300 ] 0018H: PL- [0 to 2500 ] 0019H: C (W/Re5-26) [0 to 4200 ] 001AH: Pt100 [-199.9 to 999.9 ] 001BH: JPt100 [-199.9 to 900.0 ] 001CH: Pt100 [-300 to 1500 ] 001DH: JPt100 [-300 to 900 ] 001EH: 4 to 20 mA DC [-1999 to 9999]
(Shunt resistor externally connected)
001FH: 0 to 20mA DC [-1999 to 9999]
(Shunt resistor externally connected) 0020H: 0 to 1 V DC [-1999 to 9999] 0021H: 0 to 5 V DC [-1999 to 9999] 0022H: 1 to 5 V DC [-1999 to 9999] 0023H: 0 to 10 V DC [-1999 to 9999] 0024H: 0 to 20 mA DC [-1999 to 9999]
(Built-in shunt resistor)
0025H: 0 to 20mA DC [-1999 to 9999]
(Built-in shunt resistor)
20H/50H 03H/06H 0045H Direct/Reverse action 0000H: Heating (Reverse action)
0001H: Cooling (Direct action)
20H/50H 03H/06H 0047H AT bias Set value 20H/50H 03H/06H 0048H ARW Set value 20H/50H 03H/06H 006FH Key lock 0000H: Key Enabled
0001H: Key Locked
25
7.1.2 A Single Piece of Data Write Command Shinko
Command
Type
Modbus
Function
Code
Data Item Data
50H 06H 0070H
Key operation change flag clearing
0000H: No action 0001H: Clear key operation change
flag
7.1.3 A Single Piece of Data Read Command Shinko
Command
Type
Modbus
Function
Code
Data Item Data
20H 03H 0080H PV PV (Process variable) 20H 03H 0081H OUT1 MV (MV1) Current OUT1 MV (MV1) 20H 03H 0082H OUT2 MV (MV2) Current OUT2 MV (MV2) 20H 03H 0085H Status flag 0000 0000 0000 0000
2
15
to 2
0
20digit: OUT1
0: OFF 1: ON 21digit: Not used (Always 0) 22digit: A1 output
0: OFF 1: ON 23to 25digits: Not used (Always 0) 26digit: Heater burnout alarm output
0: OFF 1: ON
(For sensor burnout, 0: OFF) 27digit: Loop break alarm output
0: OFF 1: ON 28digit: Overscale
0: OFF 1: ON 29digit: Underscale
0: OFF 1: ON 210digit: Not used (Always 0) 211digit: During AT
0: OFF 1: During AT 212digit: Not used (Always 0) 213digit: Controller/Converter
0: Controller 1: Converter 214digit: Not used (Always 0) 215digit: Change in key operation
0: No 1: Yes
26
7.2 Shinko Protocol (Block Read), Modbus ASCI Mode (Block Read), Modbus RTU Mode (Block Read) Commands
7.2.1 A Single/Multiple Piece(s) of Data Read/Write Command Shinko
Command Type
Modbus
Function Code
Data Item Data
20H/24H/50H/54H 03H/06H/10H 0001H SV1 Set value 20H/24H/50H/54H 03H/06H/10H 0002H Input type
0000H: K [-200 to 1370 ] 0001H: K [-199.9 to 400.0 ] 0002H: J [-200 to 1000 ] 0003H: R [0 to 1760 ] 0004H: S [0 to 1760 ] 0005H: B [0 to 1820 ] 0006H: E [-200 to 800 ] 0007H: T [-199.9 to 400.0 ] 0008H: N [-200 to 1300 ] 0009H: PL- [0 to 1390 ] 000AH: C (W/Re5-26) [0 to 2315 ] 000BH: Pt100 [-199.9 to 850.0 ] 000CH: JPt100 [-199.9 to 500.0 ] 000DH: Pt100 [-200 to 850 ] 000EH: JPt100 [-200 to 500 ] 000FH: K [-320 to 2500 ] 0010H: K [-199.9 to 750.0 ] 0011H: J [-320 to 1800 ] 0012H: R [0 to 3200 ] 0013H: S [0 to 3200 ] 0014H: B [0 to 3300 ] 0015H: E [-320 to 1500 ] 0016H: T [-199.9 to 750.0 ] 0017H: N [-320 to 2300 ] 0018H: PL- [0 to 2500 ] 0019H: C (W/Re5-26) [0 to 4200 ] 001AH: Pt100 [-199.9 to 999.9 ] 001BH: JPt100 [-199.9 to 900.0 ] 001CH: Pt100 [-300 to 1500 ] 001DH: JPt100 [-300 to 900 ] 001EH: 4 to 20 mA DC [-1999 to 9999]
(Shunt resistor externally connected)
001FH: 0 to 20 mA DC [-1999 to 9999]
(Shunt resistor externally connected) 0020H: 0 to 1 V DC [-1999 to 9999] 0021H: 0 to 5 V DC [-1999 to 9999] 0022H: 1 to 5 V DC [-1999 to 9999] 0023H: 0 to 10 V DC [-1999 to 9999] 0024H: 0 to 20 mA DC [-1999 to 9999]
(Built-in shunt resistor)
0025H: 0 to 20 mA DC [-1999 to 9999]
(Built-in shunt resistor)
20H/24H/50H/54H 03H/06H/10H 0003H Scaling high limit
Set value
20H/24H/50H/54H 03H/06H/10H 0004H Scaling low limit
Set value
20H/24H/50H/54H 03H/06H/10H 0005H Decimal point place
0000H: XXXX (No decimal point) 0001H: XXX.X (1 digit after decimal
point)
0002H: XX.XX (2 digits after decimal
point)
0003H: X.XXX (3 digits after decimal
point)
27
Shinko
Command Type
Modbus
Function Code
Data Item Data
20H/24H/50H/54H 03H/06H/10H 0006H A1 type
0000H: No alarm action 0001H: High limit alarm 0002H: Low limit alarm 0003H: High/Low limits alarm 0004H: High/Low limit range alarm 0005H: Process high alarm 0006H: Process low alarm 0007H: High limit with standby alarm 0008H: Low limit with standby alarm 0009H: High/Low limits with standby 000AH: High/Low limits independent 000BH: High/Low limit range
independent
000CH: High/Low limits with standby
independent
20H/24H/50H/54H 03H/06H/10H 0007H A2 type
0000H: No alarm action 0001H: High limit alarm 0002H: Low limit alarm 0003H: High/Low limits alarm 0004H: High/Low limit range alarm 0005H: Process high alarm 0006H: Process low alarm 0007H: High limit with standby alarm 0008H: Low limit with standby alarm 0009H: High/Low limits with standby 000AH: High/Low limits independent 000BH: High/Low limit range
independent
000CH: High/Low limits with standby
independent
20H/24H/50H/54H 03H/06H/10H 0008H A3 type
0000H: No alarm action 0001H: High limit alarm 0002H: Low limit alarm 0003H: High/Low limits alarm 0004H: High/Low limit range alarm 0005H: Process high alarm 0006H: Process low alarm 0007H: High limit with standby alarm 0008H: Low limit with standby alarm 0009H: High/Low limits with standby 000AH: High/Low limits independent 000BH: High/Low limit range
independent
000CH: High/Low limits with standby
independent
20H/24H/50H/54H 03H/06H/10H 0009H A4 type
0000H: No alarm action 0001H: High limit alarm 0002H: Low limit alarm 0003H: High/Low limits alarm 0004H: High/Low limit range alarm 0005H: Process high alarm 0006H: Process low alarm 0007H: High limit with standby alarm 0008H: Low limit with standby alarm 0009H: High/Low limits with standby 000AH: High/Low limits independent 000BH: High/Low limit range
independent
000CH: High/Low limits with standby
independent
20H/24H/50H/54H 03H/06H/10H 000AH Reserved (*1)
28
Shinko
Command Type
Modbus
Function Code
Data Item Data
20H/24H/50H/54H 03H/06H/10H 000BH Reserved (*1) 20H/24H/50H/54H 03H/06H/10H 000CH Reserved (*1) 20H/24H/50H/54H 03H/06H/10H 000DH Reserved (*1) 20H/24H/50H/54H 03H/06H/10H 000EH SV1
Set value
20H/24H/50H/54H 03H/06H/10H 000FH SV2
Set value
20H/24H/50H/54H 03H/06H/10H 0010H Reserved (*1) 20H/24H/50H/54H 03H/06H/10H 0011H Reserved (*1) 20H/24H/50H/54H 03H/06H/10H 0012H A1 value Set value 20H/24H/50H/54H 03H/06H/10H 0013H A1 high limit alarm
value
Set value
20H/24H/50H/54H 03H/06H/10H 0014H A2 value Set value 20H/24H/50H/54H 03H/06H/10H 0015H A2 high limit alarm
value
Set value
20H/24H/50H/54H 03H/06H/10H 0016H A3 value Set value 20H/24H/50H/54H 03H/06H/10H 0017H A3 high limit alarm
value
Set value
20H/24H/50H/54H 03H/06H/10H 0018H A4 value Set value 20H/24H/50H/54H 03H/06H/10H 0019H A4 high limit alarm
value
Set value
20H/24H/50H/54H 03H/06H/10H 001AH Reserved (*1) 20H/24H/50H/54H 03H/06H/10H 001BH Reserved (*1) 20H/24H/50H/54H 03H/06H/10H 001CH Heater burnout
alarm
Set value
20H/24H/50H/54H 03H/06H/10H 001DH Reserved (*1) 20H/24H/50H/54H 03H/06H/10H 001EH Loop break alarm
time
Set value
20H/24H/50H/54H 03H/06H/10H 001FH Loop break alarm
span
Set value
20H/24H/50H/54H 03H/06H/10H 0020H Event input DI
allocation
0000H: No event 0001H: Set value memory 0002H: Control ON/OFF 0003H: Direct/Reverse action 0004H: Preset output 1 ON/OFF 0005H: Preset output 2 ON/OFF 0006H: Auto/Manual control 0007H: Integral action Holding 0008H: Set value memory 0009H: Control ON/OFF 000AH: Direct/Reverse action 000BH: Preset output 1 ON/OFF 000CH: Preset output 2 ON/OFF 000DH: Auto/Manual control 000EH: Integral action Holding
20H/24H/50H/54H 03H/06H/10H 0021H Reserved (*1) 20H/24H/50H/54H 03H/06H/10H 0022H Reserved (*1) 20H/24H/50H/54H 03H/06H/10H 0023H Reserved (*1)
29
Shinko
Command Type
Modbus
Function Code
Data Item Data
20H/24H/50H/54H 03H/06H/10H 0024H A1 value 0
Enabled/Disabled
0000H: Disabled 0001H: Enabled
20H/24H/50H/54H 03H/06H/10H 0025H A1 hysteresis Set value 20H/24H/50H/54H 03H/06H/10H 0026H A1 delay time Set value 20H/24H/50H/54H 03H/06H/10H 0027H A1 Energized/
De-energized
0000H: Energized 0001H: De-energized
20H/24H/50H/54H 03H/06H/10H 0028H A2 value 0
Enabled/Disabled
0000H: Disabled 0001H: Enabled
20H/24H/50H/54H 03H/06H/10H 0029H A2 hysteresis Set value 20H/24H/50H/54H 03H/06H/10H 002AH A2 delay time Set value 20H/24H/50H/54H 03H/06H/10H 002BH A2 Energized/
De-energized
0000H: Energized 0001H: De-energized
20H/24H/50H/54H 03H/06H/10H 002CH A3 value 0
Enabled/Disabled
0000H: Disabled 0001H: Enabled
20H/24H/50H/54H 03H/06H/10H 002DH A3 hysteresis Set value 20H/24H/50H/54H 03H/06H/10H 002EH A3 delay time Set value 20H/24H/50H/54H 03H/06H/10H 002FH A3 Energized/
De-energized
0000H: Energized 0001H: De-energized
20H/24H/50H/54H 03H/06H/10H 0030H A4 value 0
Enabled/Disabled
0000H: Disabled 0001H: Enabled
20H/24H/50H/54H 03H/06H/10H 0031H A4 hysteresis Set value 20H/24H/50H/54H 03H/06H/10H 0032H A4 delay time Set value 20H/24H/50H/54H 03H/06H/10H 0033H A4 Energized/
De-energized
0000H: Energized 0001H: De-energized
20H/24H/50H/54H 03H/06H/10H 0034H Reserved (*1) 20H/24H/50H/54H 03H/06H/10H 0035H Reserved (*1) 20H/24H/50H/54H 03H/06H/10H 0036H Reserved (*1) 20H/24H/50H/54H 03H/06H/10H 0037H Reserved (*1) 20H/24H/50H/54H 03H/06H/10H 0038H Reserved (*1) 20H/24H/50H/54H 03H/06H/10H 0039H Reserved (*1) 20H/24H/50H/54H 03H/06H/10H 003AH Reserved (*1) 20H/24H/50H/54H 03H/06H/10H 003BH Reserved (*1) 20H/24H/50H/54H 03H/06H/10H 003CH OUT1 proportional
band
Set value
20H/24H/50H/54H 03H/06H/10H 003DH Integral time Set value 20H/24H/50H/54H 03H/06H/10H 003EH Derivative time Set value 20H/24H/50H/54H 03H/06H/10H 003FH ARW Set value 20H/24H/50H/54H 03H/06H/10H 0040H Manual reset Set value 20H/24H/50H/54H 03H/06H/10H 0041H OUT1 proportional
cycle
Set value
20H/24H/50H/54H 03H/06H/10H 0042H OUT1 ON/OFF
hysteresis
Set value
20H/24H/50H/54H 03H/06H/10H 0043H OUT1 high limit Set value 20H/24H/50H/54H 03H/06H/10H 0044H OUT1 low limit Set value 20H/24H/50H/54H 03H/06H/10H 0045H Reserved (*1)
30
Shinko
Command Type
Modbus
Function Code
Data Item Data
20H/24H/50H/54H 03H/06H/10H 0046H OUT2 cooling
method
0000H: Air cooling (Linear
characteristic)
0001H: Oil cooling (1.5thpower of the
linear characteristic)
0002H: Water cooling (2ndpower of
the linear characteristic)
20H/24H/50H/54H 03H/06H/10H 0047H OUT2 proportional
band
Set value
20H/24H/50H/54H 03H/06H/10H 0048H OUT2 proportional
cycle
Set value
20H/24H/50H/54H 03H/06H/10H 0049H OUT2 ON/OFF
hysteresis
Set value
20H/24H/50H/54H 03H/06H/10H 004AH OUT2 high limit Set value 20H/24H/50H/54H 03H/06H/10H 004BH OUT2 low limit Set value 20H/24H/50H/54H 03H/06H/10H 004CH Overlap/Dead band Set value 20H/24H/50H/54H 03H/06H/10H 004DH Direct/Reverse
action
0000H: Heating (Reverse action) 0001H: Cooling (Direct action)
20H/24H/50H/54H 03H/06H/10H 004EH Set value lock 0000H: Unlock
0001H: Lock 1 0002H: Lock 2 0003H: Lock 3
20H/24H/50H/54H 03H/06H/10H 004FH Reserved (*1) 20H/24H/50H/54H 03H/06H/10H 0050H Sensor correction Set value 20H/24H/50H/54H 03H/06H/10H 0051H PV filter time
constant
Set value
20H/24H/50H/54H 03H/06H/10H 0052H Reserved (*1) 20H/24H/50H/54H 03H/06H/10H 0053H SVTC bias Set value 20H/24H/50H/54H 03H/06H/10H 0054H External setting
input high limit
Set value
20H/24H/50H/54H 03H/06H/10H 0055H External setting
input low limit
Set value
20H/24H/50H/54H 03H/06H/10H 0056H Remote bias Set value 20H/24H/50H/54H 03H/06H/10H 0057H SV Rise/Fall rate
start type
0000H: SV start 0001H: PV start
20H/24H/50H/54H 03H/06H/10H 0058H SV rise rate Set value 20H/24H/50H/54H 03H/06H/10H 0059H SV fall rate Set value 20H/24H/50H/54H 03H/06H/10H 005AH Reserved (*1) 20H/24H/50H/54H 03H/06H/10H 005BH AT bias Set value 20H/24H/50H/54H 03H/06H/10H 005CH Output status when
input errors occur
0000H: Output OFF 0001H: Output ON
20H/24H/50H/54H 03H/06H/10H 005DH Auto/Manual
after power ON
0000H: Automatic control 0001H: Manual control
20H/24H/50H/54H 03H/06H/10H 005EH Reserved (*1) 20H/24H/50H/54H 03H/06H/10H 005FH OUT1 MV preset
value
Set value
20H/24H/50H/54H 03H/06H/10H 0060H OUT2 MV preset
value
Set value
20H/24H/50H/54H 03H/06H/10H 0061H A1 HOLD function 0000H: Not holding
0001H: Holding
20H/24H/50H/54H 03H/06H/10H 0062H A2 HOLD function 0000H: Not holding
0001H: Holding
31
Shinko
Command Type
Modbus
Function Code
Data Item Data
20H/24H/50H/54H 03H/06H/10H 0063H A3 HOLD function 0000H: Not holding
0001H: Holding
20H/24H/50H/54H 03H/06H/10H 0064H A4 HOLD function 0000H: Not holding
0001H: Holding
20H/24H/50H/54H 03H/06H/10H 0065H Reserved (*1)
: : : : 20H/24H/50H/54H 03H/06H/10H 008CH Reserved (*1) 20H/24H/50H/54H 03H/06H/10H 008DH Not used (*2)
: : : : 20H/24H/50H/54H 03H/06H/10H 00DFH Not used (*2)
32
7.2.2 A Single Piece of Data Read/Write Command
Shinko
Command
Type
Modbus
Function
Code
Data Item Data
20H/50H 03H/06H 00E0H SUB-MODE key function 0000H: Control output OFF function
0001H: Auto/Manual control 0002H: Alarm HOLD cancel
20H/50H 03H/06H 00E1H Remote/Local 0000H: Local
0001H: Remote
20H/50H 03H/06H 00E2H Control output OFF function
Auto/Manual control, or Alarm HOLD cancel
Control output OFF function
0000H: Control output ON 0001H: Control output OFF
Auto/Manual control
0000H: Automatic control 0001H: Manual control
Alarm HOLD cancel
0000H: No action
0001H: Alarm HOLD cancel 20H/50H 03H/06H 00E3H Reserved (*1) 20H/50H 03H/06H 00E4H Reserved (*1) 20H/50H 03H/06H 00E5H Manual control MV (*3) Set value 20H/50H 03H/06H 00E6H AT Perform/Cancel 0000H: AT Cancel
0001H: AT Perform
20H/50H 03H/06H 00E7H Controller/Converter 0000H: Controller
0001H: Converter 20H/50H 03H/06H 00E8H Reserved (*1) 20H/50H 03H/06H 00E9H Reserved (*1) 20H/50H 03H/06H 00EAH Control output OUT1/EVT 0000H: OUT1
0001H: EVT 20H/50H 03H/06H 00EBH Heater burnout alarm output
Enabled/Disabled
0000H: Disabled
0001H: Enabled 20H/50H 03H/06H 00ECH Loop break alarm output
Enabled/Disabled
0000H: Disabled
0001H: Enabled 20H/50H 03H/06H 00EDH A1 output Enabled/Disabled 0000H: Disabled
0001H: Enabled 20H/50H 03H/06H 00EEH A2 output Enabled/Disabled 0000H: Disabled
0001H: Enabled 20H/50H 03H/06H 00EFH A3 output Enabled/Disabled 0000H: Disabled
0001H: Enabled 20H/50H 03H/06H 00F0H A4 output Enabled/Disabled 0000H: Disabled
0001H: Enabled 20H/50H 03H/06H 00F1H Not used (*2)
: : : : 20H/50H 03H/06H 00FDH Not used (*2) 20H/50H 03H/06H 00FEH Reserved (*1)
7.2.3 A Single Piece of Data Write Command Shinko
Command
Type
Modbus
Function
Code
Data Item Data
50H 06H 00FFH Key operation
change flag clearing (*4)
0000H: No action 0001H: Clear key operation change flag
33
7.2.4 A Single/Multiple Piece(s) of Data Read Command Shinko
Command
Type
Modbus
Function
Code
Data Item Data
20H/24H 03H/04H 0100H PV PV (Process variable) 20H/24H 03H/04H 0101H OUT1 MV (MV1) Current OUT1 MV (MV1) 20H/24H 03H/04H 0102H OUT2 MV (MV2) Current OUT2 MV (MV2) 20H/24H 03H/04H 0103H Current SV Current SV (desired value) 20H/24H 03H/04H 0104H Reserved (*1) 20H/24H 03H/04H 0105H Reserved (*1) 20H/24H 03H/04H 0106H Reserved (*1) 20H/24H 03H/04H 0107H Reserved (*1) 20H/24H 03H/04H 0108H Reserved (*1) 20H/24H 03H/04H 0109H CT1 current value CT1 current value (current value when
OUT1 is ON) 20H/24H 03H/04H 010AH Reserved (*1) 20H/24H 03H/04H 010BH Reserved (*1) 20H/24H 03H/04H 010CH Reserved (*1) 20H/24H 03H/04H 010DH Status flag 1 0000 0000 0000 0000
2
15
to 2
0
20digit: OUT1
0: OFF 1: ON (Current output: Unfixed)
21digit: OUT2
0: OFF 1: ON (Current output: Unfixed)
22digit: A1 output
0: OFF 1: ON
23digit: A2 output
0: OFF 1: ON
24digit: A3 output
0: OFF 1: ON
25digit: A4 output
0: OFF 1: ON
26digit: Heater burnout alarm output
0: OFF 1: ON (When sensor burnout, 0: OFF)
27digit: Loop break alarm output
0: OFF 1: ON
28digit: Oversclae
0: OFF 1: ON
29digit: Underscale
0: OFF 1: ON 210digit: Not used (Always 0) 211digit: During AT
0: OFF 1: During AT 212digit: Not used (Always 0) 213digit: Controller/Converter
0: Controller 1: Converter 214digit: Not used (Always 0) 215digit: Change in key operation
0: No 1: Yes
34
Shinko
Command
Type
Modbus
Function
Code
Data Item Data
20H/24H 03H/04H 010EH Status flag 2 0000 0000 0000 0000
2
15
to 2
0
20digit: Event input DI1
0: OFF 1: ON 21to 25digits: Reserved 26digit: Unit status
0: PV/SV Display mode
1: Setting mode 27digit: Warm-up
0: Finished 1: Warm-up 28to 29digits: Reserved 210digit: Auto/Manual control
0: Automatic 1: Manual 211to 215digits: Reserved
20H/24H 03H/04H 010FH Reserved (*1) 20H/24H 03H/04H 0110H Reserved (*1) 20H/24H 03H/04H 0111H Software version Software version No. 20H/24H 03H/04H 0112H Unit model information 1 0000 0000 0000 0000
2
15
to 2
0
20digit: Event input DI1 Enabled/Disabled
0: Disabled 1: Enabled 21digit: External setting input
Enabled/Disabled
0: Disabled 1: Enabled 22digit: A1 function Enabled/Disabled
0: Disabled 1: Enabled 23digit: A2 function Enabled/Disabled
0: Disabled 1: Enabled 24digit: A3 function Enabled/Disabled
0: Disabled 1: Enabled 25digit: A4 function Enabled/Disabled
0: Disabled 1: Enabled 26digit: Heater burnout alarm output
Enabled/Disabled
0: Disabled 1: Enabled 27digit: Loop break alarm output
Enabled/Disabled
0: Disabled 1: Enabled 28digit: Heater burnout alarm output
rated current (5A)
0: 10A, 20A, 50A 1: 5A 29digit: Heater burnout alarm output
rated current (10A)
0: 5A, 20A, 50A 1: 10A 210digit: Heater burnout alarm output
rated current (20A)
0: 5A, 10A, 50A 1: 20A 211digit: Heater burnout alarm output
rated current (50A)
0: 5A, 10A, 20A 1: 50A 212to 215digits: Not used (Always 0)
35
Shinko
Command
Type
Modbus
Function
Code
Data Item Data
20H/24H 03H/04H 0113H Unit model information 2 0000 0000 0000 0000
2
15
to 2
0
20to 22digits: Model
0: xxD 1: xxR (Vertical type) 2: xxM 3: xxS 4: xxL 5: xxR (Horizontal type)
23to 24digits: OUT1 output type
0: R/M (Relay contact) 1: S/M (Non-contact voltage) 2: A/M (Direct current)
25to 215digits: Not used (Always 0)
(*1) For ‘Reserved’ items, if a Single/Multiple piece(s) of data Read is/are executed, acknowledgement
will be returned (but data is 0).
If a Single/Multiple piece(s) of data Write is/are executed, acknowledgement will be returned, and
data will be discarded.
(*2) For ‘Not used’ items, if a Single/Multiple piece(s) of data Read/Write is executed, Error code 1 (31H,
Shinko protocol) or Exception code 2 (02H, Modbus protocol) will be returned.
(*3) For 00E5H (Manual control MV), if Write is executed for the following, Error code 3 (33H, Shinko
protocol) or Exception code 3 (03H, Modbus protocol) will be returned:
• For ON/OFF control action, if Write is executed for any value other than OUT1 low limit value, OUT1 high limit value
• When Heating side (in Heating/Cooling control) is ON/OFF control, and
if Write is executed for any value other than OUT1 low limit value, OUT1 high limit value on Heating side, or if Write is executed for any value other than OUT2 low limit value, OUT2 high limit value on Cooling side
• When Cooling side (in Heating/Cooling control) is ON/OFF control, and
if Write is executed for any value other than [from OUT1 low limit value to OUT1 high limit value] on Heating side, or if Write is executed for any value other than OUT2 low limit value, OUT2 high limit value on Cooling side
(*4) For 00FFH (Key operation change flag clearing), if Read is executed, Error code 1 (31H, Shinko
protocol) or Exception code 2 (02H, Modbus protocol) will be returned. For any value other than 0001H (Clear key operation change flag), if Write is executed, Error code 3 (33H, Shinko protocol) or Exception code 3 (03H, Modbus protocol) will be returned.
36
7.3 Data
7.3.1 Notes about Write/Read Command
• The data (set value, decimal) is converted to a hexadecimal number. Negative numbers are represented in 2's complement.
• When connecting multiple slaves, the address (instrument number) must not be duplicated.
• Do not use undefined Data items. If they are used, negative acknowledgement will be returned or a random value will be written or read, resulting in malfunction.
• Modbus protocol uses Holding Register addresses. The Holding Register addresses are created as follows. A Shinko command Data item is converted to decimal number, and the offset of 40001 is added. The result is the Holding Register address. Using Data item 0001H (SV1) as an example: Data item in the sending message is 0001H, however, Modbus protocol Holding Register address is 40002 (1 + 40001).
7.3.2 Write Command
• Setting range of each item is the same as that of keypad operation.
When data (set value) has a decimal point, a whole number (hexadecimal) without a decimal point is used.
• Writing via software communication will be possible even in the set value lock status.
• If Lock 3 is selected in [Set value lock], the written data will not be saved in the non-volatile IC memory. Therefore if the power is turned off, they will revert to their value before Lock 3.
• If an alarm type is changed in [Alarm type] (0023H, 0006H, 0007H, 0008H, 0009H), the alarm value (000BH, 0012H, 0014H, 0016H, 0018H) will default to 0 (zero). Alarm output status will also be initialized.
• Even if options are not ordered, writing via software communication will be possible. However, their command contents will not function.
• The Communication protocol, Instrument Numbers, Communication Speed, Parity and Stop bit of the slave cannot be written by software communication. They can only be set via the keypad.
• When writing a command by Global address [95 (7FH), Shinko protocol] or Broadcast address [0
(00H) Modbus protocol], the same command is sent to all the slaves connected. However, the response is not returned.
• Up to 1,000,000 (one million) entries can be stored in non-volatile IC memory.
If the number of writings exceeds the limit, the data will not be saved. So, do not change the set values frequently via communication. (If a value written via software communication is the same as the value before writing, the value will not be written in non-volatile IC memory.)
7.3.3 Read Command
• When the data (set value) has a decimal point, a whole number (hexadecimal) without a decimal point is used for a response.
7.4 Negative Acknowledgement
The slave will return Error code 1 (31H, Shinko protocol) or Exception code 2 (02H, Modbus protocol) in the following case:
• When non-existent data item is read or written.
The slave will return Error code 3 (33H, Shinko protocol) or Exception code 3 (03H, Modbus protocol) in the following case:
• When a value out of the setting range is written.
The slave will return Error code 4 (34H, Shinko protocol) or Exception code 17 (11H, Modbus protocol) in the following cases:
• When 0001H (AT Perform) is written for 0003H or 00E6H (AT Perform/Cancel) during PI control or ON/OFF control action
• While AT is performing, and if 0001H (AT Perform) is written for 0003H or 00E6H (AT Perform/Cancel)
• When Write is executed for Manual control MV (00E5H) during automatic control
The slave will return Error code 5 (35H, Shinko protocol) or Exception code 18 (12H, Modbus protocol) in the following case:
• During setting mode by keypad operation
37
7.5 Notes on Programming Monitoring Software
7.5.1 How to Speed up the Scan Time
When monitoring multiple units of the controller, set the program so that the requisite minimum pieces of data such as Data item 0080H or 0100H (PV), Data item 0081H or 0101H (OUT1 MV), Data item 0082H or 0102H (OUT2 MV), Data item 0085H (Status flag), Data item 010DH (Status flag 1), can be read. For other data, set the program so that they can be read only when their set value has changed. This will speed up the scan time.
7.5.2 How to Read the Set Value Changes Made by Front Keypad Operation
If any set value is changed by the keypad operation, the controller sets 0085H (Status flag) or 010DH (Status flag 1, 215: Change in key operation) to “1 (Yes)”. There are 2 methods of reading the set value changes made by front keypad.
(1) Reading method 1
1
On the monitoring software side, check that 0085H (Status flag) or 010DH (Status flag 1, 215:
Change in key operation) has been set to “1 (Yes)”, then read all set values.
2
Clear 0085H (Status flag) or 010DH (Status flag 1, 215: Change in key operation), by writing 0001H (Clear key operation change flag) for Data item 0070H or 00FFH (Key operation change flag clearing). If 0001H (Clear key operation change flag) is written for 0070H or 00FFH (Key operation change flag clearing) during the setting mode of the controller, Error code 5 (35H, Shinko protocol) or Exception Code 18 (12H, Modbus protocol) will be returned as a negative acknowledgement. And 0085H (Status flag) or 010DH (Status flag 1, 215: Change in key operation) cannot be cleared. Set a program so that all set values can be read when a negative acknowledgement is returned.
3
Read all set values again after acknowledgement is returned.
(2) Reading method 2
1
On the monitoring software side, check that 0085H (Status flag) or 010DH (Status flag 1, 215:
Change in key operation) has been set to “1 (Yes)”, then write 0001H (Clear key operation change flag) for 0070H or 00FFH (Key operation change flag clearing).
2
Set the program depending on the acknowledgement or negative acknowledgement as follows. When acknowledgement is returned;
Consider it as settings completed, and read all set values. When Error code 5 (35H, Shinko protocol) or Exception code 18 (12H, Modbus protocol) is returned as a negative acknowledgement;
Consider it as still in setting mode, and read the requisite minimum pieces of data such as
0080H or 0100H (PV), 0081H or 0101H (OUT1 MV), 0082H or 0102H (OUT2 MV), 0085H
(Status flag), 010DH (Status flag 1), then return to Step1.
Thus, programs which do not affect the scan time can be created using the methods described above, even if set values on the monitoring software will not be updated until settings are complete.
7.5.3 How to Read PID Parameters after AT Finishes
While AT is performing, this controller sets 0085H (Status flag) or 010DH (Status flag 1, 211: During AT) to “1 (During AT)”. After AT is finished, PID parameters are updated. On the monitoring software side, check that 0085H (Status flag) or 010DH (Status flag 1, 211: During AT) has been set to “0 (OFF)”, then read parameters such as P, I, D, ARW.
7.5.4 Note When Sending All Set Values Simultaneously
• When changing alarm types at 0023H, 0006H, 0007H, 0008H or 0009H (Alarm type), the alarm values will default to 0 (zero).
First, send the selected alarm type, then send each alarm value.
• When changing input types at 0044H or 0002H (Input type), the set values such as SV1, OUT1
proportional band, Alarm value, etc. will be initialized. First, send the selected input type, then send other set values.
38
7.6 When Communicating with a PLC
To communicate with a PLC, use the SIF-600, Shinko PLC Interface Unit. No programming is needed for connection. However, Shinko protocol Multiple pieces of data Read (24H) and Multiple pieces of data Write (54H) are not available.
PLCs corresponding to the SIF-600, its manufacturer and host link units:
PLC manufacturer PLC model Host link unit model
MELSEC Q, QnA series (*)
AJ71UC24, A1SJ71UC24-R2/R4/PRF A1SJ71C24-R2/R4/PRF, QJ71C24
Mitsubishi Electric Corp.
MELSEC FX series (*)
Omron Corp. SYSMAC CJ series
CS1W-SCU21-V1 CJ1W-SCU21, CJ1W-SCU41
Keyence Corp.
KV KV-L20V
Yokogawa Electric Corp.
FA-M3 F3LC11-2N, F3LC11-1F, F3LC12-1F
Fuji Electric Co., Ltd.
MICREX-SX series
NP1L-RS1, NP1L-RS2, NP1L-RS3, NP1L-RS4
(*) Models with compatible QR/QW communication commands.
39
8. Set Value Digital Transmission
By connecting to Shinko programmable controllers [PC-900 or PCD-33A with the SVTC (Set value digital transmission) option], SV can be received from programmable controllers.
8.1 Wiring
When connecting to the PCD-33A, connect YA (-) to YA (-), YB (+) to YB (+), SG (PCD-33A) to COM (DCL-33A) respectively. Up to 31 units of the DCL-33A can be connected. The following shows a connection example of PCD-33A and DCL-33A (Fig. 8.1-1).
(Fig. 8.1-1)
8.2 Setting Method of Controllers (1) Setting the PCD-33A
If the SVTC option is added, it is not necessary to set any item. Check if Set value digital transmission [ ] is selected in [Communication protocol ( )] in Auxiliary function setting mode 1.
(2) Setting the DCL-33A
Check the following settings. (Refer to the Instruction manual for the DCL-33A.)
• Shinko protocol has been selected in [Communication protocol].
• Communication speed of the DCL-33A is identical with that of PCD-33A.
(3) The Set Value Digital Transmission starts.
Enter the SV for the program on the PCD-33A. If the program is initiated by pressing the key, SV of the PCD-33A will be transmitted to the DCL-33A. During program standby mode, 0 (zero) is sent to the DCL-33A.
11 YA(
-
)
14 YB(+)
17 SG
CDM (Sold separately) CDD or CPP (Sold separately)
PCD
-
33A
DCL-33A (Max. 31 units)
40
9. Specifications
Cable length: 1.2 km (Max.) Cable resistance: Within 50 (Terminators are not necessary, but
if used, use 120 or more on one side.) Communication line: EIA RS-485 Communication method: Half-duplex communication Communication speed: 2400/4800/9600/19200/38400 bps (Selectable by keypad) (Default: 9600 bps) Synchronization method: Start-stop synchronization Code form: ASCII, binary Communication protocol: Shinko protocol/Modbus ASCII/Modbus RTU (Selectable by keypad)
(Default: Shinko protocol) Data format:
Communication protocol Shinko protocol Modbus ASCII Modbus RTU Start bit 1 1 1 Data bit 7 7 8 Parity Even Even (No parity, Odd)
Selectable
No parity (Even, Odd) Selectable
Stop bit 1 1 (or 2)
Selectable
1 (or 2) Selectable
Error correction: Command request repeat system Error detection: Parity check, checksum (Shinko protocol), LRC (Modbus ASCII), CRC-16 (Modbus RTU)
10. Troubleshooting
Check that power is being supplied to the master and slave that customers use. If communication failure still occurs, check the following.
• Problem: Communication failure Check if any of the following have occurred.
Imperfect contact between the communication cable and the connector, or between the communication connector and instrument port
Incorrect wiring of the communication cable and/or connector. Communication speed of the slave does not match that of the master. The data bit, parity and stop bit of the master do not correspond to those of the slave. The instrument number (address) of the slave does not correspond to that of the command. The instrument numbers (addresses) are duplicated in multiple slaves. Make sure that the program is appropriate for the transmission timing.
Problem: Although communication is occurring, the response is negative acknowledgement.
Check if any of the following have occurred.
A non-existent command code has been sent. The Write command data exceeds the setting range of the slave. The DCL-33A cannot be set when functions such as AT are performing. The DCL-33A is in front keypad operation setting mode.
For all other malfunctions, please contact our main office or dealers.
SHINKO TECHNOS CO., LTD.
OVERSEAS DIVISION
:Head Office
URL: E-mail:
2-5-1, Senbahigashi, Minoo, Osaka, Japan
http://www.shinko-technos.co.jp
overseas@shinko-technos.co.jp
Tel : Fax:
+81-72-727-6100 +81-72-727-7006
Loading...