Shinko BCR2, BCD2, BCS2 Communication Instruction Manual

1
COMMUNICATION INSTRUCTION MANUAL BCD2, BCR2, BCS2 (C5W, C5)
No. BCx2CE5 2018.02
This manual contains instructions for communication functions of the BCD2, BCR2, BCS2.
Serial communication and Console communication cannot be used together. When performing Serial communication, remove the tool cable (CMD-001) from the USB port of the PC and console connector of the BCD2, BCR2, BCS2. When performing Console communication, it is not required to remove the Serial communication cables. However, do not send a command from the master side.
1. System Configuration
1.1 When Using USB Communication Cable CMC-001-1 (sold separately)
(Fig. 1.1-1)
1.2 When Using Communication Converter IF-400 (sold separately)
(Fig. 1.2-1)
USB communication cable
CMC-001-1 (sold separately)
No. 0 No. 1 No. 30
BCS2
Host computer
Communication converter
IF-400 (sold separately)
RS-232C RS-485
No. 0
No. 1
No. 30
BCS2
Host computer
2
2. Wiring
2.1 When Using USB Communication Cable CMC-001-1 (sold separately)
(Fig. 2.1-1)
2.2 When Using Communication Converter IF-400 (sold separately)
(Fig. 2.2-1)
Shield wire
Connect only one end of the shield to the FG terminal to avoid a ground loop. If both ends of the shield wire are connected to the FG terminal, the circuit will be closed, resulting in a ground loop. This may cause noise. Be sure to ground the FG terminal. Recommended cable: OTSC-VB 2PX0.5SQ (made by Onamba Co., Ltd.) or equivalent (Use a twisted pair cable.)
RXD
TXD
DCD
DTR
DSR
RTS
CTS
2
3
5
1
4
6
7
8
GND
RI
9
CDM
FG
FG
FG
YA(-)YB(+)SG
YA(-)YB(+)SG
Shield wire
4 3 1 6
Host computer D-sub 9-pin connector
YA(-)YB(+)SG
Shield wire
Shield wire
Communication converter IF-400 (sold separately)
RS-232C RS-485
BCS2
BCR2
, BCD2
YA(-)YB(+)SG
YA(-)YB(+)SG
YA(-)YB(+)SG
FG
FG
USB communication cable
CMC-001-1 (sold separately)
Host computer USB port
YA(-)YB(+)SG
YA(-)YB(+)SG
YA(-)YB(+)SG
Shield wire
Shield wire
YA(-) YB(+) COM
BCS2 BCR2, BCD2
YA(-)YB(+)SG
YA(-)YB(+)SG
YA(-)YB(+)SG
3
Terminator (Terminal resistor)
Communication converter IF-400 (sold separately) has a built-in terminator. The terminator is mounted at the end of the wire when connecting multiple peripheral devices to a personal computer. The terminator prevents signal reflection and disturbance. Do not connect a terminator to the communication line because each BCD2, BCR2, BCS2 has built-in pull-up and pull-down resistors.
4
3. Setting Communication Parameters
Set communication parameters in Engineering mode 1.
To enter Engineering mode 1, press and hold the and keys (in that order) together for approx. 3 seconds in RUN mode. Use the or key for settings (or making a selection).
To register the set data, use the key.
Set each communication parameter following the procedure below.
RUN mode
PV/SV Display
+ (3 sec)
Engineering mode 1
Set value lock
(Several times)
Communication protocol
Characters,
Factory Default
Setting Item, Function, Setting Range
Communication protocol
• Selects communication protocol.
• Selection item: Shinko protocol
Modbus ASCII
Modbus RTU
Shinko protocol (JC command allocated)
Modbus ASCII (JC command allocated)
Modbus RTU (JC command allocated)
Instrument number
• Sets the instrument number.
The instrument numbers should be set one by one when multiple instruments are connected in Serial communication, otherwise communication is impossible.
• Setting range: 0 to 95
Communication speed
• Selects a communication speed equal to that of the host computer.
• Selection item: 9600 bps
19200 bps
38400 bps
Data bit/Parity
• Selects data bit and parity.
• Selection item: 8 bits/No parity
7 bits/No parity
8 bits/Even
7 bits/Even
8 bits/Odd
7 bits/Odd
5
Characters,
Factory Default
Setting Item, Function, Setting Range
Stop bit
• Selects the stop bit.
• Selection item:
1 bit
2 bits
Response delay time
• Response from the controller can be delayed after receiving command from the host
computer.
• Setting range: 0 to 1000 ms
SVTC bias
• By connecting to Shinko programmable controllers [PC-900 or PCD-33A with the SVTC
(Set value digital transmission) option], digital SV via the SVTC command can be received from programmable controllers. Refer to Section ‘8. Set Value Digital Transmission’ on p.46. SV adds SVTC bias value to the value received by the SVTC command.
• Setting range: 20% of input span
DC voltage, current inputs: 20% of scaling span (*)
Available only when Shinko protocol is selected in [Communication protocol].
(*) The placement of the decimal point follows the selection.
(Multiple times)
RUN mode
PV/SV Display
Now, settings are complete.
6
4. Communication Procedure
Communication starts with command transmission from the host computer (hereafter Master) and ends with the response of the BCx2 (hereafter Slave).
• Response with data
When the master sends the Read command, the slave responds with the corresponding set value or current status.
• Acknowledgement
When the master sends the Write command, the slave responds by sending the acknowledgement after the processing is terminated.
• Negative acknowledgement
When the master sends a non-existent command or value out of the setting range, the slave returns a negative acknowledgement.
• No response
The slave will not respond to the master in the following cases:
• Global address (Shinko protocol) is set.
(Fig. 4-1) • Broadcast address (Modbus protocol) is set.
• Communication error (framing error, parity error)
• Checksum error (Shinko protocol), LRC discrepancy (Modbus ASCII mode), CRC-16 discrepancy (Modbus RTU mode)
Communication timing of the RS-485
Master Side (Take note while programming)
When the master starts transmission through the RS-485 communication line, the master is arranged so as to provide an idle status (mark status) transmission period of 1 or more characters before sending the command to ensure synchronization on the receiving side. Set the program so that the master can disconnect the transmitter from the communication line within a 1 character transmission period after sending the command in preparation for reception of the response from the slave. To avoid collision of transmissions between the master and the slave, send the next command after carefully checking that the master has received the response. If a response to the command is not returned due to communication errors, set the Retry Processing to send the command again. (It is recommended to execute Retry twice or more.)
Slave Side
When the slave starts transmission through the RS-485 communication line, the slave is arranged so as to provide an idle status (mark status) transmission period of 1 ms or more (*) before sending the response to ensure synchronization on the receiving side. The slave is arranged so as to disconnect the transmitter from the communication line within a 1 character transmission period after sending the response.
(*) Can be set in [Response delay time] within a range of 0 to 1000 ms. (See p.5.)
Command
Data
Command
Acknowledgement
Command
Negative
acknowledgement
Command
No response
Master Slave
7
5. Shinko Protocol
5.1 Transmission Mode
Shinko protocol is composed of ASCII. Hexadecimal (0 to 9, A to F), which is divided into high order (4-bit) and low order (4-bit) out of 8-bit binary data in command is transmitted as ASCII characters. Data format Start bit: 1 bit
Data bit: 7 bits (8 bits) Selectable Parity: Even (No parity, Odd) Selectable Stop bit: 1 bit (2 bits) Selectable
Error detection: Checksum
5.2 Command Configuration
All commands are composed of ASCII. The data (set value, decimal number) is represented by a hexadecimal number. The negative numbers are represented in 2's complement. Numerals written below the command represent number of characters.
(1) Write command
• Write a single piece of data
Header
(02H)
Address
Sub
address
(20H)
Command type (50H)
Data
item
Data Checksum
Delimiter
(03H)
1 1 1 1 4 4 2 1
• Write multiple pieces of data
Header
(02H)
Address
Sub
address
(20H)
Command type (54H)
Data
item
Data Checksum
Delimiter
(03H)
1 1 1 1 4 4 x n 2 1
n: Amount of data
(2) Read command
• Read a single piece of data
Header
(02H)
Address
Sub
address
(20H)
Command type (20H)
Data
item
Checksum
Delimiter
(03H)
1 1 1 1 4 2 1
• Read multiple pieces of data
Header
(02H)
Address
Sub
address
(20H)
Command type (24H)
Data
item
Amount of
Read datanChecksum
Delimiter
(03H)
1 1 1 1 4 4 2 1
(3) Response with data
• Response to ‘Read a single piece of data’
Header
(06H)
Address
Sub
address
(20H)
Command type (20H)
Data
item
Data Checksum
Delimiter
(03H)
1 1 1 1 4 4 2 1
• Response to ‘Read multiple pieces of data’
Header
(06H)
Address
Sub
address
(20H)
Command type (24H)
Data
item
Data Checksum
Delimiter
(03H)
1 1 1 1 4 4 x n 2 1
n: Amount of data
(4) Acknowledgement
Header
(06H)
Address Checksum
Delimiter
(03H)
1 1 2 1
8
(5) Negative acknowledgement
Header
(15H)
Address
Error code
Checksum
Delimiter
(03H)
1 1 1 2 1
Header: Control code to represent the beginning of the command or the response.
ASCII is used. Write command, Read command: STX (02H) fixed Response with data, Acknowledgement: ACK (06H) fixed Negative acknowledgement: NAK (15H) fixed
Instrument number (Address): Numbers by which the master discerns each slave.
Instrument number 0 to 94 and Global address 95. ASCII (20H to 7FH) is used by adding 20H to instrument numbers 0 to 95 (00H to 5FH). 95 (7FH) is called Global address, which is used when the same command is sent to all the slaves connected. However, the response is not returned.
Sub address: 20H fixed Command type: Code to discern Write command and Read command.
Command
Type
Contents Description
20H Read a single piece of data Reads a single piece of data.
24H Read multiple pieces of data Reads consecutive multiple pieces
of data. (Amount of data: Max. 100)
50H Write a single piece of data Writes a single piece of data.
54H Write multiple pieces of data Writes consecutive multiple pieces
of data. (Amount of data: Max. 100)
Notes about Reading/Writing multiple pieces of data
When reading/writing multiple pieces of data, as it takes time until slave sends response data, the master determines no response time based on timeout period below after sending a command. Timeout period calculation: 6 ms x Amount of data + Response delay time (*)
(*) Refer to Response delay time on p.5.
Data item: Classification of the command object.
Composed of 4-digit hexadecimal numbers, using ASCII. Refer to ‘7. Communication Command Table’. (pp. 26 to 40)
Data: The contents of data (values) differ depending on the Write command.
Composed of 4-digit hexadecimal numbers, using ASCII. Refer to ‘7. Communication Command Table’. (pp. 26 to 40)
Checksum: 2-character data to detect communication errors.
Refer to 5.3 Checksum Calculation on p.9.
Delimiter: Control code to represent the end of command.
ASCII code ETX (03H) fixed
Error code: Represents an error type using ASCII.
Error Code Contents
1 (31H) Non-existent command
2 (32H) Not used
3 (33H) Value outside the setting range
4 (34H) Status unable to be written (e.g. AT is performing.)
5 (35H) During setting mode by keypad operation
9
5.3 Checksum Calculation
Checksum is used to detect receiving errors in the command or data. Set the program for the master side as well to calculate the checksum of the response data from the slaves so that communication errors can be checked.
The ASCII code (hexadecimal) corresponding to the characters which range from the address to that before the checksum is converted to binary notation, and the total value is calculated. The lower one byte of the total value is converted to 2’s complement, and then to hexadecimal numbers, that is, ASCII code for the checksum.
• 1’s complement: Reverse each binary bit. 0 will become 1 and vice versa.
• 2’s complement: Add 1 to 1’s complement.
[Example of checksum calculation]
SV1 (0001H): 600 (0258H) Address (instrument number): 0 (20H)
(Fig. 5.3-1)
20H 20H 50H 30H 30H 30H 31H 30H 32H 35H 38H
0010 0000 0010 0000 0101 0000 0011 0000 0011 0000 0011 0000 0011 0001 0011 0000 0011 0010 0011 0101 0011 1000
+
10 0010 0000
[Hexadecimal] [Binary]
1101 1111
1
+
1110 0000
E 0
45H
30H
[1's complement]
[2's complement]
[Hexadecimal]
[ASCII]
Checksum
STX ETX
P 0 0 0 1 0 2 5 8
02H 20H 20H 50H 30H 30H 30H 31H 30H 32H 35H 38H 03H
[Characters above are represented in ASCII.]
Checksum
Checksum calculation range
[e.g.]
E
45H 30H
0
10
5.4 Command Example
Numerals written below the command represent number of characters.
(1) Read [Address 1, PV (0100H)]
• Read command from the master Header
(02H)
Address
(21H)
Sub
address
(20H)
Command
type
(20H)
Data item
[0100H]
(30H 31H 30H 30H)
Checksum
(44H 45H)
Delimiter
(03H)
1 1 1 1 4 2 1
• A response from the slave in normal status [When PV=600 (0258H)] Header
(06H)
Address
(21H)
Sub
address
(20H)
Command
type
(20H)
Data item
[0100H]
(30H 31H 30H 30H)
Data
[0258H]
(30H 32H 35H 38H)
Checksum
(30H 46H)
Delimiter
(03H)
1 1 1 1 4 4 2 1
(2) Write [Address 1, SV1 (0001H)]
• Write command from the master [when writing SV1 to 600 (0258H)] Header
(02H)
Address
(21H)
Sub
address
(20H)
Command
type
(50H)
Data item
[0001H]
(30H 30H 30H 31H)
Data
[0258H]
(30H 32H 35H 38H)
Checksum
(44H 46H)
Delimiter
(03H)
1 1 1 1 4 4 2 1
• A response from the slave in normal status Header
(06H)
Address
(21H)
Checksum
(44H 46H)
Delimiter
(03H)
1 1 2 1
(3) Read [Address 1, SV1 (0001H)]
• Read command from the master Header
(02H)
Address
(21H)
Sub
address
(20H)
Command
type
(20H)
Data item
[0001H]
(30H 30H 30H 31H)
Checksum
(44H 45H)
Delimiter
(03H)
1 1 1 1 4 2 1
• A response from the slave in normal status [When SV1=600 (0258H)] Header
(06H)
Address
(21H)
Sub
address
(20H)
Command
type
(20H)
Data item
[0001H]
(30H 30H 30H 31H)
Data
[0258H]
(30H 32H 35H 38H)
Checksum
(30H 46H)
Delimiter
(03H)
1 1 1 1 4 4 2 1
11
Program control starts
1:00
2:00
200
0
0:30
1:00
2:00
300
(4) Write (Address 1, Program pattern data) (Write multiple pieces of data)
Example of program pattern setting
Step 1 2 3 4 5
SV ( ) 200 200 300 300 0
Time 1:00 2:00 0:30 1:00 2:00
Wait value ( ) 10 0 10 0 0
(Fig. 5.4-1)
When writing the above program pattern, Command data in the message becomes as follows.
Data is converted to hexadecimal.
Data Item Data Data (Converted to Hexadecimal)
1000H Step 1 SV 200 00C8H
1001H Step 1 time 60 minutes (1:00) 003CH
1002H Step 1 wait value 10 000AH
1003H Step 2 SV 200 00C8H
1004H Step 2 time 120 minutes (2:00) 0078H
1005H Step 2 wait value 0 0000H
1006H Step 3 SV 300 012CH
1007H Step 3 time 30 minutes (0:30) 001EH
1008H Step 3 wait value 10 000AH
1009H Step 4 SV 300 012CH
100AH Step 4 time 60 minutes (1:00) 003CH
100BH Step 4 wait value 0 0000H
100CH Step 5 SV 0 0000H
100DH Step 5 time 120 minutes (2:00) 0078H
100EH Step 5 wait value 0 0000H
• Write command from the master (When writing the above program pattern data) Header
(02H)
Address
(21H)
Sub
address
(20H)
Command
type
(54H)
Data item
[1000H]
(31H 30H 30H 30H)
1 1 1 1 4
Data
[00C8003C000A00C800780000012C001E000A012C003C0000000000780000H]
(30H 30H 43H 38H 30
H30H 33H 43H
・・・・・・
30H 30H 37H 38H 30H 30H 30H 30H)
60 (4 x 15)
Checksum
(38H 36H)
Delimiter
(03H)
2
1
12
• Response from the slave in normal status Header
(06H)
Address
(21H)
Checksum
(44H 46H)
Delimiter
(03H)
1 1 2 1
(5) Read (Address 1, Program pattern data) (Read multiple pieces of data)
• Read command from the master [Amount of data: 15 (000FH), when reading the program pattern
data on p.11]
Header
(02H)
Address
(21H)
Sub
address
(20H)
Command
type
(24H)
Data item
[1000H]
(31H 30H 30H 30H)
Amount of read data
15 [000FH]
(30H 30H 30H 46H)
Checksum
(30H 34H)
Delimiter
(03H)
1 1 1 1 4 4 2 1
• Response from the slave in normal status Header
(06H)
Address
(21H)
Sub
address
(20H)
Command
type
(24H)
Data item
[1000H]
(31H 30H 30H 30H)
1 1 1 1 4
Data
[00C8003C000A00C800780000012C001E000A012C003C0000000000780000H]
(30H 30H 43H 38H 30H30H 33H 43H
・・・・・・
30H 30H 37H 38H 30H 30H 30H 30H)
60 (4 x 15)
Checksum
(42H 36H)
Delimiter
(03H)
2
1
Response data becomes as follows.
Data Item Data Data (Converted to Hexadecimal)
1000H Step 1 SV 200 00C8H
1001H Step 1 time 60 minutes (1:00) 003CH
1002H Step 1 wait value 10 000AH
1003H Step 2 SV 200 00C8H
1004H Step 2 time 120 minutes (2:00) 0078H
1005H Step 2 wait value 0 0000H
1006H Step 3 SV 300 012CH
1007H Step 3 time 30 minutes (0:30) 001EH
1008H Step 3 wait value 10 000AH
1009H Step 4 SV 300 012CH
100AH Step 4 time 60 minutes (1:00) 003CH
100BH Step 4 wait value 0 0000H
100CH Step 5 SV 0 0000H
100DH Step 5 time 120 minutes (2:00) 0078H
100EH Step 5 wait value 0 0000H
13
6. Modbus Protocol
6.1 Transmission Mode
There are 2 transmission modes (ASCII and RTU) in Modbus protocol.
6.1.1 ASCII Mode
Hexadecimal (0 to 9, A to F), which is divided into high order (4-bit) and low order (4-bit) out of 8-bit binary data in command is transmitted as ASCII characters. Data format Start bit: 1 bit
Data bit: 7 bits (8 bits) (Selectable) Parity: Even (No parity, Odd) (Selectable) Stop bit: 1 bit (2 bits) (Selectable)
Error detection : LRC (Longitudinal Redundancy Check)
6.1.2 RTU Mode
8-bit binary data in command is transmitted as it is. Data format Start bit: 1 bit
Data bit: 8 bits Parity: No parity (Even, Odd) (Selectable) Stop bit: 1 bit (2 bits) (Selectable)
Error detection: CRC-16 (Cyclic Redundancy Check)
6.2 Data Communication Interval
6.2.1 ASCII Mode
No communication interval limit between characters
6.2.2 RTU Mode
1.5 character transmission times or less
(Communication speed 9600 bps, 19200 bps: 1.5 character transmission times, Communication speed 38400 bps: 750 s) To transmit continuously, an interval between characters which consist of one message, must be within 1.5 character transmission times. If an interval lasts longer than 1.5 character transmission times, the BCx2 assumes that transmission from the master is finished, which results in a communication error, and will not return a response.
6.3 Message Configuration
6.3.1 ASCII Mode
ASCII mode message is configured to start by Header [: (colon) (3AH)] and end by Delimiter [CR (carriage return) (0DH) + LF (Line feed) (0AH)]. Data section: Max. 2 x 252 characters
Header
(:)
Slave
address
Function
code
Data
Error check
LRC
Delimiter
(CR)
Delimiter
(LF)
6.3.2 RTU Mode
RTU mode is configured to start after idle time is processed for more than 3.5 character transmissions, and end after idle time is processed for more than 3.5 character transmissions. (Communication speed 9600 bps, 19200 bps: 3.5 character transmission times, Communication speed 38400 bps: 1.75 ms) Data section: Max. 252 bytes
3.5 idle
characters
Slave
address
Function
code
Data
Error check
CRC-16
3.5 idle
characters
14
(1) Slave Address
Slave address is an individual instrument number on the slave side, and is set within the range 0 to 95 (00H to 5FH). The master identifies slaves by the slave address of the requested message. The slave informs the master which slave is responding to the master by placing its own address in the response message. Slave address 0 (00H, Broadcast address) can identify all the slaves connected. However, slaves do not respond.
(2) Function Code
The function code is the command code for the slave to undertake one of the following actions.
Type
Function
Code
Sub-Function
Code
Contents
Data access
03 (03H) Reads a single or multiple piece(s) of data
from slave(s).
04 (04H) Reads information from slave(s).
06 (06H) Writes a single piece of data to slave(s).
16 (10H) Writes multiple pieces of data to slave(s).
Diagnostics
08 (08H) 00 Echoes back the request message.
43 (2BH) 14 Reads device identification information.
The function code is used to discern whether the response is normal (acknowledgement) or if any error (negative acknowledgement) has occurred when the slave returns the response message to the master. When acknowledgement is returned, the slave simply returns the original function code. When negative acknowledgement is returned, the MSB of the original function code is set as 1 for the response. For example, if the master sends request message setting 13H to the function code by mistake, slave returns 93H by setting the MSB to 1, because the former is an illegal function.
For negative acknowledgement, the exception codes below are set to the data of the response message, and returned to the master in order to inform it of what kind of error has occurred.
Exception Code Contents
1 (01H) Illegal function (Non-existent function) 2 (02H) Illegal data address (Non-existent data address) 3 (03H) Illegal data value (Value out of the setting range)
17 (11H)
Shinko protocol error code 4 (Status unable to be written. (e.g.) AT is performing.)
18 (12H) Shinko protocol error code 5
(During setting mode by keypad operation)
(3) Data
Data differs depending on the function code. A request message from the master is composed of a data item, amount of data and setting data. A response message from the slave is composed of the number of bytes, data and exception codes in negative acknowledgements, corresponding to the request message. The effective range of data is -32768 to 32767 (8000H to 7FFFH). Refer to Section “7. Communication Command Table” (pp.26 to 40).
(4) Error Check
ASCII Mode
After calculating LRC (Longitudinal Redundancy Check) from the slave address to the end of data, the calculated 8-bit data is converted to two ASCII characters, and are appended to the end of message.
How to Calculate LRC
1
Create a message in RTU mode.
2
Add all the values from the slave address to the end of data. This is assumed as X.
3
Make a complement for X (bit reverse). This is assumed as X.
15
4
Add a value of 1 to X. This is assumed as X.
5
Set X as an LRC to the end of the message.
6
Convert the whole message to ASCII characters.
RTU Mode
After calculating CRC-16 (Cyclic Redundancy Check) from the slave address to the end of the data, the calculated 16-bit data is appended to the end of message in sequence from low order to high order.
How to calculate CRC-16
In the CRC-16 system, the information is divided by the polynomial series. The remainder is added to the end of the information and transmitted. The generation of a polynomial series is as follows. (Generation of polynomial series: X16+ X15+ X2+ 1)
1
Initialize the CRC-16 data (assumed as X) (FFFFH).
2
Calculate exclusive OR (XOR) with the 1st data and X. This is assumed as X.
3
Shift X one bit to the right. This is assumed as X.
4
When a carry is generated as a result of the shift, XOR is calculated by X of
3
and the
fixed value (A001H). This is assumed as X. If a carry is not generated, go to step5.
5
Repeat steps
3
and4until shifting 8 times.
6
XOR is calculated with the next data and X. This is assumed as X.
7
Repeat steps
3
to5.
8
Repeat steps
3
to5up to the final data.
9
Set X as CRC-16 to the end of message in sequence from low order to high order.
16
6.4 Message Example
6.4.1 ASCII Mode
Numerals written below the command represent the number of characters.
(1) Read [Slave address 1, PV (0100H)]
• A request message from the master Header
(3AH)
Slave
address
(30H 31H)
Function
code
(30H 33H)
Data item
[0100H]
(30H 31H 30H 30H)
Amount of data
[0001H]
(30H 30H 30H 31H)
Error check
LRC
(46H 41H)
Delimiter
CR+LF
(0DH 0AH)
1 2 2 4 4 2 2
• Response message from the slave in normal status [When PV=600 (0258H)]
Header
(3AH)
Slave
address
(30H 31H)
Function
code
(30H 33H)
Number of
response bytes
[02H]
(30H 32H)
Data
[0258H]
(30H 32H 35H 38H)
Error check
LRC
(41H 30H)
Delimiter
CR+LF
(0DH 0AH)
1 2 2 2 4 2 2
(2) Write [Slave address 1, SV1 (0001H)]
• A request message from the master [When writing SV1 to 600 (0258H)] Header
(3AH)
Slave
address
(30H 31H)
Function
code
(30H 36H)
Data item
[0001H]
(30H 30H 30H 31H)
Data
[0258H]
(30H 32H 35H 38H)
Error check
LRC
(39H 45H)
Delimiter
CR+LF
(0DH 0AH)
1 2 2 4 4 2 2
• Response message from the slave in normal status Header
(3AH)
Slave
address
(30H 31H)
Function
code
(30H 36H)
Data item
[0001H]
(30H 30H 30H 31H)
Data
[0258H]
(30H 32H 35H 38H)
Error check
LRC
(39H 45H)
Delimiter
CR+LF
(0DH 0AH)
1 2 2 4 4 2 2
• Response message from the slave in exception (error) status (When a value out of the setting range is set)
The function code MSB is set to 1 for the response message in exception (error) status [86H (38H 36H)]. The exception code 03H (30H 33H: Value out of the setting range) is returned (error).
Header
(3AH)
Slave
address
(30H 31H)
Function
code
(38H 36H)
Exception code
[03H]
(30H 33H)
Error check
LRC
(37H 36H)
Delimiter
CR+LF
(0DH 0AH)
1 2 2 2 2 2
(3) Read [Slave address 1, SV1 (0001H)]
• A request message from the master Header
(3AH)
Slave
address
(30H 31H)
Function
code
(30H 33H)
Data item
[0001H]
(30H 30H 30H 31H)
Amount of data
[0001H]
(30H 30H 30H 31H)
Error check
LRC
(46H 41H)
Delimiter
CR+LF
(0DH 0AH)
1 2 2 4 4 2 2
• Response message from the slave in normal status [When SV1=600 (0258H)]
Header
(3AH)
Slave
address
(30H 31H)
Function
code
(30H 33H)
Number of
response bytes
[02H]
(30H 32H)
Data
[0258H]
(30H 32H 35H 38H)
Error check
LRC
(41H 30H)
Delimiter
CR+LF
(0DH 0AH)
1 2 2 2 4 2 2
• Response message from the slave in exception (error) status (When data item is incorrect)
The function code MSB is set to 1 for the response message in exception (error) status [83H (38H 33H)]. The exception code 02H (30H 32H: Non-existent data address) is returned (error).
Header
(3AH)
Slave
address
(30H 31H)
Function
code
(38H 33H)
Exception code
[02H]
(30H 32H)
Error check
LRC
(37H 41H)
Delimiter
CR+LF
(0DH 0AH)
1 2 2 2 2 2
17
Program control starts
1:00
2:00
200
0
0:30
1:00
2:00
300
(4) Write (Slave address 1, Program pattern data) (Write Multiple pieces of data)
Example of program pattern setting
Step 1 2 3 4 5
SV ( ) 200 200 300 300 0
Time 1:00 2:00 0:30 1:00 2:00
Wait value ( ) 10 0 10 0 0
(Fig. 6.4.1-1)
When writing the above program pattern, Data in the message becomes as follows.
Amount of data: 15 (000FH) Number of bytes: 30 (1EH) Data is converted to hexadecimal.
Data Item Data Data (Converted to Hexadecimal)
1000H Step 1 SV 200 00C8H
1001H Step 1 time 60 minutes (1:00) 003CH
1002H Step 1 wait value 10 000AH
1003H Step 2 SV 200 00C8H
1004H Step 2 time 120 minutes (2:00) 0078H
1005H Step 2 wait value 0 0000H
1006H Step 3 SV 300 012CH
1007H Step 3 time 30 minutes (0:30) 001EH
1008H Step 3 wait value 10 000AH
1009H Step 4 SV 300 012CH
100AH Step 4 time 60 minutes (1:00) 003CH
100BH Step 4 wait value 0 0000H
100CH Step 5 SV 0 0000H
100DH Step 5 time 120 minutes (2:00) 0078H
100EH Step 5 wait value 0 0000H
• A request message from the master (When writing the above program pattern data) Header
(3AH)
Slave
address
(30H 31H)
Function
code
(31H 30H)
Data item
[1000H]
(31H 30H 30H 30H)
1 2 2 4
Data
[000F1E00C8003C000A00C800780000012C001E000A012C003C0000000000780000H]
(30H 30H 30H 46H 31H 45H 30H 30H ・・・・・・30H 30H 37H 38H 30H 30H 30H 30H)
66
Error check
LRC
(32H 45H)
Delimiter
CR+LF
(0DH 0AH)
2 2
18
• A response message from the slave in normal status
Header
(3AH)
Slave
address
(30H 31H)
Function
code
(31H 30H)
Data item
[1000H]
(31H 30H 30H 30H)
Data
[000FH]
(30H 30H 30H 46H)
Error check
LRC
(44H 30H)
Delimiter
CR+LF
(0DH 0AH)
1 2 2 4 4 2 2
(5) Read (Slave address 1, Program pattern data) (Read multiple pieces of data)
• A request message from the master (When reading the program pattern data on p.17) Header
(3AH)
Slave
address
(30H 31H)
Function
code
(30H 33H)
Data item
[1000H]
(31H 30H 30H 30H)
Amount of data
[000FH]
(30H 30H 30H 46H)
Error check
LRC
(44H 44H)
Delimiter
CR+LF
(0DH 0AH)
1 2 2 4 4 2 2
• Response message from the slave in normal status
Header
(3AH)
Slave
address
(30H 31H)
Function
code
(30H 33H)
Number of
response bytes
[1EH]
(31H 45H)
1 2 2 2
Data
[00C8003C000A00C800780000012C001E000A012C003C0000000000780000H]
(30H 30H 43H 38H 30H 30H 33H 43H ・・・・・・30H 30H 37H 38H 30H 30H 30H 30H)
60
Error check
LRC
(35H 41H)
Delimiter
CR+LF
(0DH 0AH)
2 2
Data in the response message becomes as follows.
Data Item Data Data (Converted to Hexadecimal)
1000H Step 1 SV 200 00C8H
1001H Step 1 time 60 minutes (1:00) 003CH
1002H Step 1 wait value 10 000AH
1003H Step 2 SV 200 00C8H
1004H Step 2 time 120 minutes (2:00) 0078H
1005H Step 2 wait value 0 0000H
1006H Step 3 SV 300 012CH
1007H Step 3 time 30 minutes (0:30) 001EH
1008H Step 3 wait value 10 000AH
1009H Step 4 SV 300 012CH
100AH Step 4 time 60 minutes (1:00) 003CH
100BH Step 4 wait value 0 0000H
100CH Step 5 SV 0 0000H
100DH Step 5 time 120 minutes (2:00) 0078H
100EH Step 5 wait value 0 0000H
19
6.4.2 RTU Mode
Numerals written below the command represent number of characters.
(1) Read [Slave address 1, PV (0100H)]
• A request message from the master
3.5 idle
characters
Slave
address
(01H)
Function
code
(03H)
Data item
(0100H)
Amount of data
(0001H)
Error check
CRC-16 (85F6H)
3.5 idle
characters
1 1 2 2 2
• Response message from the slave in normal status [When PV is 600 (0258H)]
3.5 idle
characters
Slave
address
(01H)
Function
code
(03H)
Number of
response bytes
(02H)
Data
(0258H)
Error check
CRC-16
(B8DEH)
3.5 idle
characters
1 1 1 2 2
(2) Write [Slave address 1, SV1 (0001H)]
• A request message from the master [When SV1 is written to 600 (0258H)]
3.5 idle
characters
Slave
address
(01H)
Function
code
(06H)
Data item
(0001H)
Data
(0258H)
Error check
CRC-16
(D890H)
3.5 idle
characters
1 1 2 2 2
• Response message from the slave in normal status
3.5 idle
characters
Slave
address
(01H)
Function
code
(06H)
Data item
(0001H)
Data
(0258H)
Error check
CRC-16
(D890H)
3.5 idle
characters
1 1 2 2 2
• Response message from the slave in exception (error) status (When a value out of the setting range is set) The function code MSB is set to 1 for the response message in exception (error) status, and 86H is returned. The Exception code 03H (Value out of the setting range) is returned (error).
3.5 idle
characters
Slave
address
(01H)
Function
code
(86H)
Exception code
(03H)
Error check
CRC-16 (0261H)
3.5 idle
characters
1 1 1 2
(3) Read [Slave address 1, SV1 (0001H)]
• A request message from the master
3.5 idle
characters
Slave
address
(01H)
Function
code
(03H)
Data item
(0001H)
Data
(0001H)
Error check
CRC-16
(D5CAH)
3.5 idle
characters
1 1 2 2 2
• Response message from the slave in normal status [When SV1 is 600 (0258H)]
3.5 idle
characters
Slave
address
(01H)
Function
code
(03H)
Number of
response bytes
(02H)
Data
(0258H)
Error check
CRC-16
(B8DEH)
3.5 idle
characters
1 1 1 2 2
• Response message from the slave in exception (error) status (When data item is incorrect)
The function code MSB is set to 1 for the response message in exception (error) status, and 83H is returned. The Exception code 02H (Non-existent data address) is returned (error).
3.5 idle
characters
Slave
address
(01H)
Function
code
(83H)
Exception code
(02H)
Error check
CRC-16
(C0F1H)
3.5 idle
characters
1 1 1 2
20
Program control starts
1:00
2:00
200
0
0:30
1:00
2:00
300
(4) Write (Slave address 1, Program pattern data) (Write multiple pieces of data)
Program pattern setting example
Step 1 2 3 4 5
SV ( ) 200 200 300 300 0
Time 1:00 2:00 0:30 1:00 2:00
Wait value ( ) 10 0 10 0 0
(Fig. 6.4.2-1)
When writing the above program pattern, Data in the message becomes as follows.
Amount of data: 15 (000FH) Number of bytes: 30 (1EH) Data is converted to hexadecimal.
Data Item Data Data (Converted to Hexadecimal)
1000H Step 1 SV 200 00C8H
1001H Step 1 time 60 minutes (1:00) 003CH
1002H Step 1 wait value 10 000AH
1003H Step 2 SV 200 00C8H
1004H Step 2 time 120 minutes (2:00) 0078H
1005H Step 2 wait value 0 0000H
1006H Step 3 SV 300 012CH
1007H Step 3 time 30 minutes (0:30) 001EH
1008H Step 3 wait value 10 000AH
1009H Step 4 SV 300 012CH
100AH Step 4 time 60 minutes (1:00) 003CH
100BH Step 4 wait value 0 0000H
100CH Step 5 SV 0 0000H
100DH Step 5 time 120 minutes (2:00) 0078H
100EH Step 5 wait value 0 0000H
• A request message from the master (When writing the above program pattern data)
3.5 idle
characters
Slave
address
(01H)
Function
code
(10H)
Data item
(1000H)
1 1 2
Data
(000F1E00C8003C000A00C800780000012C001E000A012C003C0000000000780000H)
33
Error check
CRC-16
(13EEH)
3.5 idle
characters
2
21
• Response message from the slave in normal status
3.5 idle
characters
Slave
address
(01H)
Function
code
(10H)
Data item
(1000H)
Data
(000FH)
Error check
CRC-16
(84CDH)
3.5 idle
characters
1 1 2 2 2
(5) Read (Slave address 1, Program pattern data) (Read multiple pieces of data)
• A request message from the master (When reading the program pattern data on p.21)
3.5 idle
characters
Slave
address
(01H)
Function
code
(03H)
Data item
(1000H)
Amount of data
(000FH)
Error check
CRC-16 (010EH)
3.5 idle
characters
1 1 2 2 2
• Response message from the slave in normal status
3.5 idle
characters
Slave
address
(01H)
Function
code
(03H)
Number of
response bytes
(1EH)
1 1 1
Data
(00C8003C000A00C800780000012C001E000A012C003C0000000000780000H)
30
Error check
CRC-16
(F340H)
3.5 idle
characters
2
Data in the response message becomes as follows.
Data Item Data Data (Converted to Hexadecimal)
1000H Step 1 SV 200 00C8H
1001H Step 1 time 60 minutes (1:00) 003CH
1002H Step 1 wait value 10 000AH
1003H Step 2 SV 200 00C8H
1004H Step 2 time 120 minutes (2:00) 0078H
1005H Step 2 wait value 0 0000H
1006H Step 3 SV 300 012CH
1007H Step 3 time 30 minutes (0:30) 001EH
1008H Step 3 wait value 10 000AH
1009H Step 4 SV 300 012CH
100AH Step 4 time 60 minutes (1:00) 003CH
100BH Step 4 wait value 0 0000H
100CH Step 5 SV 0 0000H
100DH Step 5 time 120 minutes (2:00) 0078H
100EH Step 5 wait value 0 0000H
22
6.5 Diagnostics Function Modbus protocol has the following diagnostics functions.
• Echoes back the request message.
• Reads device identification information.
6.5.1 Message Configuration ASCII mode
Header
(:)
Slave
address
Function
code
Data
Error check
LRC
Delimiter
(CR)
Delimiter
(LF)
RTU mode
3.5 idle
characters
Slave
address
Function
code
Data
Error check
CRC-16
3.5 idle
characters
(1) Slave address:
Slave address is an individual instrument number on the slave side, and is set within the range 1 to 95 (01H to 5FH). The master identifies slaves by the slave address of the requested message. The slave informs the master which slave is responding to the master by placing its own address in the response message. Diagnostics function is disabled for the Slave address 0 (00H, broadcast address).
(2) Function code:
The function code is the command code for the slave to undertake the following action types.
Type Function Code Sub-function Code
Contents
Diagnostics
08 (08H) 00 (0000H) Echoes back the request message. 43 (2BH) 14 (0EH) Reads device identification information.
Function code is used to discern whether the response is normal (acknowledgement) or if any error (negative acknowledgement) has occurred when the slave returns the response message to the master. When acknowledgement is returned, the slave simply returns the original function code. When negative acknowledgement is returned, the MSB of the original function code is set as 1 for the response. For example, when the master sends request message setting 0FH to the sub-function code by mistake, slave returns ABH by setting the MSB to 1, because the former is a non-existent sub-function code.
For negative acknowledgement, the exception codes below are set to the data of the response message, and returned to the master in order to inform it of what kind of error has occurred.
Exception Code
Contents
1 (01H)
Illegal function (Non-existent function) Sub-function code is not correct.
2 (02H)
Illegal data address (Non-existent data address) For function code 43: Object ID is any value other than 00, 01, 02.
3 (03H)
Illegal data value (Value out of the setting range) For function code 08: Data is less than 1, or has exceeded 100. For function code 43: Read Device ID code is any value other than 01, 04.
(3) Data
Data differs depending on the function code. For the Function code 08 (08H), a request message from the master side is composed of ‘Sub-function code 2 Bytes (0000H)’ and ‘Data n x 2 Bytes’. [n: Amount of data (Max. 100)] In normal status, a response message from the slave side is the same as the request message.
Function code
1 Byte
08H
Sub-function code
1 Byte
0000H fixed
Data n x 2 Bytes Random value (Max. 100)
23
For Function code 43 (2BH), the request message from the master side is composed of Sub-function code 14 (0EH), Read Device ID code and Object ID.
Function code 1 Byte 2BH Sub-function code (MEI type) 1 Byte 0EH Read Device ID code (Corresponds to Basic category)
1 Byte 01H/04H
Object ID 1 Byte 00
Vendor name
SHINKO TECHNOS CO., LTD.
01
Product code (model)
(e.g.) BCS2R00-00
02
Version number (D, T, MP)
(e.g.) Dxx-xxxx-xx, MPxxxx-xx
Response message from the slave is composed of Sub-function code 14 (0EH) (for request), Read Device ID code and Object ID.
Function code 1 Byte 2BH
Sub-function code (MEI type) 1 Byte 0EH
Data Read Device ID code 1 Byte 01H/04H
Conformity level 1 Byte 01H/81H
More Follows 1 Byte 00H/FFH
Next Object ID 1 Byte Object ID number
Number of Objects 1 Byte
List of Object ID 1 Byte
List of Object length 1 Byte
List of Object value Object length
For the response message (negative acknowledgement), an exception code is set and returned.
Function code 1 Byte ABH Exception code 1 Byte 01H/02H/03H
(4) Error check:
16-bit data to detect communication errors.
Refer to Sections ‘6.3 Message Configuration (4) Error Check (pp.14, 15).
6.5.2 Message Example
Message example in RTU mode are shown below. Numerals written below the command represent the number of characters.
(1) Echo back Slave address 1, Request message
• A request message from the master [Test data 200 (00C8H), 60 (003CH), 10 (000AH)]
3.5 idle
characters
Slave
address
(01H)
Function
code
(08H)
Sub-function
code
(0000H)
Data
(00C8003C000AH)
Error check
CRC-16
(E7D9H)
3.5 idle
characters
112nx22
• Response message from the slave in normal status (Echoes back the same message.)
3.5 idle
characters
Slave
address
(01H)
Function
code
(08H)
Sub-function
code
(0000H)
Data
(00C8003C000AH)
Error check
CRC-16
(E7D9H)
3.5 idle
characters
112nx22
24
(2) Read Slave address 1, Device identification information (Vendor name)
• A request message from the master
3.5 idle
characters
Slave
address
(01H)
Function
code
(2BH)
Sub-function
code
(0EH)
Data
(0400H)
Error check
CRC-16
(7327H)
3.5 idle
characters
11122
• Response message from the slave in normal status (SHINKO TECHNOS CO., LTD.)
3.5 idle
characters
Slave
address
(01H)
Function
code
(2BH)
Sub-function
code
(0EH)
111
Data
(048100000100185348494E4B4F20544543484E4F5320434F2E2C204C54442EH)
31
Error check
CRC-16
(1C54H)
3.5 idle
characters
2
Data in the response message becomes as follows.
Data Read Device ID code 1 Byte 04H
Conformity level
1 Byte
81H
More Follows
1 Byte
00H
Next Object ID
1 Byte
00H
Number of Objects
1 Byte
01H
List of Object ID
1 Byte
00H
List of Object length
1 Byte
24(18H)
List of Object value Object length S(53H)
H(48H) I(49H) N(4EH) K(4BH) O(4FH)
(20H) T(54H) E(45H) C(43H) H(48H) N(4EH) O(4FH) S(53H)
(20H) C(43H) O(4FH) .(2EH) ,(2CH)
(20H) L(4CH) T(54H) D(44H) .(2EH)
25
(3) Read Slave address 1, Device identification information (Product code)
• A request message from the master
3.5 idle
characters
Slave
address
(01H)
Function
code
(2BH)
Sub-function
code
(0EH)
Data
(0401
H)
Error check
CRC-16
(B2E7H)
3.5 idle
characters
11122
• Response message from the slave in normal status (BCD2R00-01)
3.5 idle
characters
Slave
address
(01H)
Function
code
(2BH)
Sub-function
code
(0EH)
111
Data
(0481000001010A424344325230302D3031H)
Error check
CRC-16
(FDEEH)
3.5 idle
characters
17 2
Data in the response message becomes as follows.
Data Read Device ID code
1 Byte
04H
Conformity level
1 Byte
81H
More Follows
1 Byte
00H
Next Object ID
1 Byte
00H
Number of Objects
1 Byte
01H
List of Object ID
1 Byte
01H
List of Object length
1 Byte
10(0AH)
List of Object value Object length B(42H)
C(43H) D(44H) 2(32H) R(52H) 0(30H) 0(30H)
-(2DH) 0(30H) 1(31H)
• Response message from the slave in exception (error) status [when Sub-function code (MEI type) is incorrect] The function code MSB is set to 1 for the response message in exception (error) status, and ABH is returned. Exception code 01H (Non-existent function) is returned (error).
3.5 idle
characters
Slave
address
(01H)
Function
code
(ABH)
Exception code
(01H)
Error check
CRC-16
(9EF0H)
3.5 idle
characters
111
2
26
7. Communication Command Table
Communication command can be selected in [Communication protocol]. If (Shinko protocol), (Modbus ASCII) or (Modbus RTU) is selected, communication commands (pp. 26 to 35) can be used.
If (Shinko protocol, JC command allocated), (Modbus ASCII, JC command allocated) or
(Modbus RTU, JC command allocated) is selected, JC command (pp. 36 to 40) can be used.
7.1 Shinko Protocol/Modbus ASCII/Modbus RTU
7.1.1 A Single/Multiple Piece(s) of Data Read/Write Command
(20/24/50/54H: 20H/24H/50H/54H, 03/06/10H: 03H/06H/10H)
Shinko
Command
Type
Modbus
Function
Code
Data Item Data
20/24/50/54H 03/06/10H 0001H SV1 Set value, Decimal point ignored 20/24/50/54H 03/06/10H 0002H Input type
0000H: K -200 to 1370 0001H: K -200.0 to 400.0 0002H: J -200 to 1000 0003H: R 0 to 1760 0004H: S 0 to 1760 0005H: B 0 to 1820 0006H: E -200 to 800 0007H: T -200.0 to 400.0 0008H: N -200 to 1300 0009H: PL- 0 to 1390 000AH: C(W/Re5-26) 0 to 2315 000BH: Pt100 -200.0 to 850.0 000CH: JPt100 -200.0 to 500.0 000DH: Pt100 -200 to 850 000EH: JPt100 -200 to 500 000FH: K -328 to 2498 0010H: K -328.0 to 752.0 0011H: J -328 to 1832 0012H: R 32 to 3200 0013H: S 32 to 3200 0014H: B 32 to 3308 0015H: E -328 to 1472 0016H: T -328.0 to 752.0 0017H: N -328 to 2372 0018H: PL- 32 to 2534 0019H: C(W/Re5-26) 32 to 4199 001AH: Pt100 -328.0 to 1562.0 001BH: JPt100 -328.0 to 932.0 001CH: Pt100 -328 to 1562 001DH: JPt100 -328 to 932 001EH: 4 to 20 mADC -2000 to 10000 001FH: 0 to 20 mA DC -2000 to 10000 0020H: 0 to 1 V DC -2000 to 10000 0021H: 0 to 5 V DC -2000 to 10000 0022H: 1 to 5 V DC -2000 to 10000 0023H: 0 to 10 V DC -2000 to 10000
20/24/50/54H 03/06/10H 0003H
Scaling high limit
Set value, Decimal point ignored
20/24/50/54H 03/06/10H 0004H
Scaling low limit
Set value, Decimal point ignored
20/24/50/54H 03/06/10H 0005H Decimal point place
0000H:
No decimal point
0001H: 1 digit after decimal point 0002H: 2 digits after decimal point 0003H: 3 digits after decimal point
27
Shinko
Command
Type
Modbus
Function
Code
Data Item Data
20/24/50/54H 03/06/10H 0006H Event output EV1
allocation (*1)
0000H: No event 0001H: Alarm output, High limit alarm 0002H: Alarm output, Low limit alarm 0003H: Alarm output, High/Low limits alarm 0004H: Alarm output, High/Low limits
independent alarm
0005H: Alarm output, High/Low limit range
alarm
0006H: Alarm output, High/Low limit range
independent alarm 0007H: Alarm output, Process high alarm 0008H: Alarm output, Process low alarm 0009H: Alarm output, High limit with standby
alarm 000AH: Alarm output, Low limit with standby
alarm 000BH: Alarm output, High/Low limits with
standby alarm 000CH: Alarm output, High/Low limits with
standby independent alarm 000DH: Heater burnout alarm output 000EH: Loop break alarm output 000FH: Time signal output 0010H: Output during AT 0011H: Pattern end output 0012H: Output by communication command
20/24/50/54H 03/06/10H 0007H Event output EV2
allocation (*1)
0000H: No event 0001H: Alarm output, High limit alarm 0002H: Alarm output, Low limit alarm 0003H: Alarm output, High/Low limits alarm 0004H: Alarm output, High/Low limits
independent alarm
0005H: Alarm output, High/Low limit range
alarm
0006H: Alarm output, High/Low limit range
independent alarm 0007H: Alarm output, Process high alarm 0008H: Alarm output, Process low alarm 0009H: Alarm output, High limit with standby
alarm 000AH: Alarm output, Low limit with standby
alarm 000BH: Alarm output, High/Low limits with
standby alarm 000CH: Alarm output, High/Low limits with
standby independent alarm 000DH: Heater burnout alarm output 000EH: Loop break alarm output 000FH: Time signal output 0010H: Output during AT 0011H: Pattern end output 0012H: Output by communication command 0013H: Heating/Cooling control
relay contact output
20/24/50/54H 03/06/10H 0008H Reserved (*2)
: : : :
20/24/50/54H 03/06/10H 000AH Reserved (*2)
28
Shinko
Command
Type
Modbus
Function
Code
Data Item Data
20/24/50/54H 03/06/10H 000BH Transmission output type 0000H: PV transmission
0001H: SV transmission
0002H: MV transmission
0003H: DV transmission
20/24/50/54H 03/06/10H 000CH Transmission output high limit Set value, Decimal point ignored 20/24/50/54H 03/06/10H 000DH Transmission output low limit Set value, Decimal point ignored 20/24/50/54H 03/06/10H 000EH SV1 Set value, Decimal point ignored 20/24/50/54H 03/06/10H 000FH SV2 Set value, Decimal point ignored 20/24/50/54H 03/06/10H 0010H SV3 Set value, Decimal point ignored 20/24/50/54H 03/06/10H 0011H SV4 Set value, Decimal point ignored 20/24/50/54H 03/06/10H 0012H EV1 alarm value (*1) Set value, Decimal point ignored 20/24/50/54H 03/06/10H 0013H EV1 high limit alarm value (*1) Set value, Decimal point ignored 20/24/50/54H 03/06/10H 0014H EV2 alarm value (*1) Set value, Decimal point ignored 20/24/50/54H 03/06/10H 0015H EV2 high limit alarm value (*1) Set value, Decimal point ignored 20/24/50/54H 03/06/10H 0016H Reserved (*2)
: : : : 20/24/50/54H 03/06/10H 001BH Reserved (*2) 20/24/50/54H 03/06/10H 001CH
Heater burnout alarm 1 value
Set value, Decimal point ignored
20/24/50/54H 03/06/10H 001DH
Heater burnout alarm 2 value
Set value, Decimal point ignored
20/24/50/54H 03/06/10H 001EH
Loop break alarm time
Set value
20/24/50/54H 03/06/10H 001FH
Loop break alarm span
Set value, Decimal point ignored
20/24/50/54H 03/06/10H 0020H Event input DI1 allocation 0000H: No event
0001H: Set value memory 0002H: Control ON/OFF 0003H: Direct/Reverse action 0004H: Preset output 1 ON/OFF 0005H: Preset output 2 ON/OFF 0006H: Auto/Manual control 0007H: Remote/Local 0008H: Program control RUN/STOP 0009H: Program control
Holding/Not holding
000AH: Program control
Advance function
000BH: Integral action Holding 20/24/50/54H 03/06/10H 0021H Event input DI2 allocation Same as Event input DI1 allocation 20/24/50/54H 03/06/10H 0022H Reserved (*2) 20/24/50/54H 03/06/10H 0023H Reserved (*2) 20/24/50/54H 03/06/10H 0024H EV1 alarm value 0
Enabled/Disabled
0000H: Disabled
0001H: Enabled 20/24/50/54H 03/06/10H 0025H EV1 alarm hysteresis Set value, Decimal point ignored 20/24/50/54H 03/06/10H 0026H EV1 alarm delay time Set value 20/24/50/54H 03/06/10H 0027H EV1 alarm
Energized/De-energized
0000H: Energized
0001H: De-Energized 20/24/50/54H 03/06/10H 0028H EV2 alarm value 0
Enabled/Disabled
0000H: Disabled
0001H: Enabled 20/24/50/54H 03/06/10H 0029H EV2 alarm hysteresis Set value, Decimal point ignored 20/24/50/54H 03/06/10H 002AH EV2 alarm delay time Set value 20/24/50/54H 03/06/10H 002BH EV2 alarm
Energized/De-energized
0000H: Energized
0001H: De-Energized
29
Shinko
Command
Type
Modbus
Function
Code
Data Item Data
20/24/50/54H 03/06/10H 002CH Reserved (*2)
: : : : 20/24/50/54H 03/06/10H 003BH Reserved (*2) 20/24/50/54H 03/06/10H 003CH OUT1 proportional band Set value, Decimal point ignored 20/24/50/54H 03/06/10H 003DH Integral time
Set value
20/24/50/54H 03/06/10H 003EH Derivative time
Set value
20/24/50/54H 03/06/10H 003FH ARW
Set value 20/24/50/54H 03/06/10H 0040H Manual reset Set value, Decimal point ignored 20/24/50/54H 03/06/10H 0041H OUT1 proportional cycle Set value 20/24/50/54H 03/06/10H 0042H OUT1 ON/OFF hysteresis Set value, Decimal point ignored 20/24/50/54H 03/06/10H 0043H OUT1 high limit
Set value 20/24/50/54H 03/06/10H 0044H OUT1 low limit
Set value 20/24/50/54H 03/06/10H 0045H OUT1 rate-of-change
Set value 20/24/50/54H 03/06/10H 0046H OUT2 cooling method 0000H: Air cooling
0001H: Oil cooling
0002H: Water cooling 20/24/50/54H 03/06/10H 0047H OUT2 proportional band Set value, Decimal point ignored 20/24/50/54H 03/06/10H 0048H OUT2 proportional cycle Set value 20/24/50/54H 03/06/10H 0049H OUT2 ON/OFF hysteresis Set value, Decimal point ignored 20/24/50/54H 03/06/10H 004AH OUT2 high limit Set value 20/24/50/54H 03/06/10H 004BH OUT2 low limit Set value 20/24/50/54H 03/06/10H 004CH Overlap band/Dead band Set value, Decimal point ignored 20/24/50/54H 03/06/10H 004DH Direct/Reverse action 0000H: Reverse (Heating) action
0001H: Direct (Cooling) action 20/24/50/54H 03/06/10H 004EH Set value lock 0000H: Unlock
0001H: Lock 1
0002H: Lock 2
0003H: Lock 3
0004H: Lock 4
0005H: Lock 5 20/24/50/54H 03/06/10H 004FH Sensor correction coefficient Set value, Decimal point ignored 20/24/50/54H 03/06/10H 0050H Sensor correction Set value, Decimal point ignored 20/24/50/54H 03/06/10H 0051H PV filter time constant Set value, Decimal point ignored 20/24/50/54H 03/06/10H 0052H Response delay time Set value 20/24/50/54H 03/06/10H 0053H SVTC bias Set value, Decimal point ignored 20/24/50/54H 03/06/10H 0054H External setting input high limit Set value, Decimal point ignored 20/24/50/54H 03/06/10H 0055H External setting input low limit Set value, Decimal point ignored 20/24/50/54H 03/06/10H 0056H Remote bias Set value, Decimal point ignored 20/24/50/54H 03/06/10H 0057H SV Rise/Fall rate start type 0000H: SV start
0001H: PV start 20/24/50/54H 03/06/10H 0058H SV rise rate Set value, Decimal point ignored 20/24/50/54H 03/06/10H 0059H SV fall rate Set value, Decimal point ignored 20/24/50/54H 03/06/10H 005AH Indication when control output
OFF
0000H: OFF indication
0001H: No indication
0002H: PV indication
0003H: PV indication + Any Alarm
active 20/24/50/54H 03/06/10H 005BH AT bias Set value, Decimal point ignored 20/24/50/54H 03/06/10H 005CH Output status when input
errors occur
0000H: Output OFF 0001H: Output ON
20/24/50/54H 03/06/10H 005DH Auto/Manual after power ON 0000H: Automatic control
0001H: Manual control
30
Shinko
Command
Type
Modbus
Function
Code
Data Item Data
20/24/50/54H 03/06/10H 005EH Indication time Set value 20/24/50/54H 03/06/10H 005FH OUT1 MV preset value Set value, Decimal point ignored 20/24/50/54H 03/06/10H 0060H OUT2 MV preset value Set value, Decimal point ignored 20/24/50/54H 03/06/10H 0061H Reserved (*2)
: : : : 20/24/50/54H 03/06/10H 006CH Reserved (*2) 20/24/50/54H 03/06/10H 006DH Step time unit 0000H: Hours:Minutes
0001H: Minutes:Seconds
20/24/50/54H 03/06/10H 006EH Power restore action 0000H: Stops after power is
restored.
0001H: Continues (resumes) after
power is restored.
0002H: Suspends (on hold) after
power is restored. 20/24/50/54H 03/06/10H 006FH Program start temperature Set value, Decimal point ignored 20/24/50/54H 03/06/10H 0070H Program control start type 0000H: PV start
0001H: PVR start
0002H: SV start 20/24/50/54H 03/06/10H 0071H Number of repetitions Set value 20/24/50/54H 03/06/10H 0072H TS1 output step number Set value 20/24/50/54H 03/06/10H 0073H TS1 OFF time (*12) Set value 20/24/50/54H 03/06/10H 0074H TS1 ON time (*12) Set value 20/24/50/54H 03/06/10H 0075H TS2 output step number Set value 20/24/50/54H 03/06/10H 0076H TS2 OFF time (*12) Set value 20/24/50/54H 03/06/10H 0077H TS2 ON time (*12) Set value 20/24/50/54H 03/06/10H 0078H Reserved (*2)
: : : : 20/24/50/54H 03/06/10H 008CH Reserved (*2) 20/24/50/54H 03/06/10H 008DH Not used (*3)
: : : : 20/24/50/54H 03/06/10H 00DFH Not used (*3)
31
7.1.2 A Single Piece of Data Read/Write Command
Shinko
Command
Type
Modbus
Function
Code
Data Item Data
20H/50H 03H/06H 00E0H OUT/OFF key function 0000H: Control output OFF function
0001H: Auto/Manual control 0002H: Program control
20H/50H 03H/06H 00E1H Remote/Local 0000H: Local
0001H: Remote
20H/50H 03H/06H 00E2H Control output OFF function,
Auto/Manual control, Program control
When control output OFF function is selected:
0000H: Control output ON
0001H: Control output OFF When Auto/Manual control is selected:
0000H: Automatic control
0001H: Manual control When Program control is selected:
0000H: Program control STOP
0001H: Program control RUN
20H/50H 03H/06H 00E3H Program control
Holding/Not holding
0000H: Not holding 0001H: Holding
20H/50H 03H/06H 00E4H Output by communication
command
B0 EV1 output 0 : OFF, 1:ON B1 EV2 output 0 : OFF, 1:ON
20H/50H 03H/06H 00E5H Manual control MV (*4) Set value 20H/50H 03H/06H 00E6H AT/Auto-reset Perform/Cancel 0000H: AT/AT on startup/ Auto-reset
Cancel 0001H: AT/Auto-reset Perform 0002H: AT on Startup Perform
20H/50H 03H/06H 00E7H Controller/Converter 0000H: Controller
0001H: Converter
20H/50H 03H/06H 00E8H AT gain Set value, Decimal point ignored
7.1.3 A Single Piece of Data Write Command
Shinko
Command
Type
Modbus
Function
Code
Data Item Data
50H 06H 00E9H Program control
Advance function (*5)
0001H: Advance Perform
50H 06H 00EAH Not used (*3)
: : : : 50H 06H 00FDH Not used (*3) 50H 06H 00FEH Data clear (*6) 1234H: Clear data 50H 06H 00FFH Key operation change flag
clearing (*7)
0001H: Clear key operation change
flag
32
7.1.4 Read Command
Shinko
Command
Type
Modbus
Function
Code
Data Item Data
20H/24H 03H/04H 0100H PV Read value, Decimal point ignored 20H/24H 03H/04H 0101H OUT1 MV Read value, Decimal point ignored 20H/24H 03H/04H 0102H OUT2 MV Read value, Decimal point ignored 20H/24H 03H/04H 0103H Current SV Read value, Decimal point ignored 20H/24H 03H/04H 0104H Set value memory number Read value 20H/24H 03H/04H 0105H Remaining time when program
control runs
Read value
20H/24H 03H/04H 0106H Reserved (*2) 20H/24H 03H/04H 0107H Step number when program
control runs
Read value
20H/24H 03H/04H 0108H Number of repetitions when
program control runs
Read value
20H/24H 03H/04H 0109H CT1 current value Read value, Decimal point ignored 20H/24H 03H/04H 010AH CT2 current value Read value, Decimal point ignored 20H/24H 03H/04H 010BH Reserved (*2) 20H/24H 03H/04H 010CH Key operation changed item Data item changed by key operation 20H/24H 03H/04H 010DH Status flag 1 B0: OUT1 output 0: OFF 1: ON
B1: OUT2 output 0: OFF 1: ON B2: EV1 output 0: OFF 1: ON B3: EV2 output 0: OFF 1: ON B4: Reserved
: B8: Reserved B9: AT/ Auto-reset, AT on startup Perform/Cancel
0: Cancel 1: Perform
B10: AT/Auto-reset, AT on startup
0: AT/Auto-reset 1: AT on startup B11: Heater burnout alarm (*9) 0: OFF 1: ON B12: Loop break alarm 0: OFF 1: ON B13: Overscale (*9) 0: OFF 1: ON B14: Underscale (*9) 0: OFF 1: ON B15: Change in key operation 0: No 1: Yes
20H/24H 03H/04H 010EH Status flag 2 B0: DI1 input 0: OFF 1: ON
B1: DI2 input 0: OFF 1: ON B2: Reserved B3: Reserved B4: Not used, Always 0 B5: Unit status 1 (Program control)
0: Standby 1: Program control RUN B6: Unit status 2 (Fixed value control)
0: PV/SV Display 1: Setting mode B7: Warm-up 0: Finished 1: Warm-up B8: USB connection
0: Standard connection 1: USB connection B9: Control output OFF (Fixed value control)
0: Control output ON 1: Control output OFF B10: Auto/Manual control 0: Automatic 1: Manual B11: Control mode
0: Fixed value control 1: Program control B12: Program control 0: Standby 1: RUN B13: Wait function 0: OFF 1: ON B14: Hold function 0: OFF 1: ON B15: Pattern end function 0: OFF 1: ON
33
Shinko
Command
Type
Modbus
Function
Code
Data Item Data
20H/24H 03H/04H 010FH Error status
flag 1 (*8)
B0: Error 01 0: OFF 1: ON B1: Error 02 0: OFF 1: ON B2: Reserved B3: Reserved B4: Error 05 0: OFF 1: ON B5: Error 06 0: OFF 1: ON B6: Error 07 0: OFF 1: ON B7: Reserved B8: Reserved B9: Error 10 0: OFF 1: ON B10: Reserved
:
B15: Reserved
20H/24H 03H/04H 0110H Error status
flag 2 (*8)
B0: Reserved B1: Reserved B2: Reserved B3: Error 20 0: OFF 1: ON B4: Reserved
:
B15: Reserved
20H/24H 03H/04H 0112H Unit model
information 1
B0: Event input Enabled/Disabled
0: Disabled 1: Enabled
B1: Event output EV2 Enabled/Disabled
0: Disabled 1: Enabled
B2: Reserved
: B4: Reserved B5: Heater burnout alarm output
Enabled/Disabled
0: Disabled 1: Enabled
B6: Heater burnout alarm output rated current
0: 20.0 A 1: 100.0 A
B7: Serial communication Enabled/Disabled
0: Disabled 1: Enabled
B8: Heating/Cooling control Enabled/Disabled
0: Disabled 1: Enabled
B9: Transmission output Enabled/Disabled
0: Disabled 1: Enabled
B10: External setting input Enabled/Disabled
0: Disabled 1: Enabled
B11: Insulated power output Enabled/Disabled
0: Disabled 1: Enabled
B12 to B15: Not used, Always 0
20H/24H 03H/04H 0113H Unit model
information 2
B0 to B2: Model 0: xxD
1: xxR (Vertical type) 2: xxM 3: xxS 4: xxL 5: xxR (Horizontal type)
B3 to B4: OUT1 output type
0: R (Relay contact) 1: S (Non-contact voltage) 2: A (Direct current)
B5 to B6: OUT2 output type
0: DR (Relay contact) 1: DS (Non-contact voltage) 2: DA (Direct current)
B7 to B15: Not used, Always 0
34
7.1.5 A Single/Multiple Piece(s) of Data Read/Write Command (for Program Control)
(20/24/50/54H: 20H/24H/50H/54H, 03/06/10H: 03H/06H/10H)
Shinko
Command
Type
Modbus
Function
Code
Data Item (*10) Data
20/24/50/54H 03/06/10H 1000H Step 1 SV (*11) Set value, Decimal point ignored 20/24/50/54H 03/06/10H 1001H Step 1 time (*13) Set value, Decimal point ignored 20/24/50/54H 03/06/10H 1002H Step 1 wait value Set value, Decimal point ignored 20/24/50/54H 03/06/10H 1003H Step 2 SV (*12) Set value, Decimal point ignored 20/24/50/54H 03/06/10H 1004H Step 2 time (*13) Set value, Decimal point ignored 20/24/50/54H 03/06/10H 1005H Step 2 wait value Set value, Decimal point ignored 20/24/50/54H 03/06/10H 1006H Step 3 SV (*12) Set value, Decimal point ignored 20/24/50/54H 03/06/10H 1007H Step 3 time (*13) Set value, Decimal point ignored 20/24/50/54H 03/06/10H 1008H Step 3 wait value Set value, Decimal point ignored 20/24/50/54H 03/06/10H 1009H Step 4 SV (*12) Set value, Decimal point ignored 20/24/50/54H 03/06/10H 100AH Step 4 time (*13) Set value, Decimal point ignored 20/24/50/54H 03/06/10H 100BH Step 4 wait value Set value, Decimal point ignored 20/24/50/54H 03/06/10H 100CH Step 5 SV Set value, Decimal point ignored 20/24/50/54H 03/06/10H 100DH Step 5 time (*13) Set value, Decimal point ignored 20/24/50/54H 03/06/10H 100EH Step 5 wait value Set value, Decimal point ignored 20/24/50/54H 03/06/10H 100FH Step 6 SV Set value, Decimal point ignored 20/24/50/54H 03/06/10H 1010H Step 6 time (*13) Set value, Decimal point ignored 20/24/50/54H 03/06/10H 1011H Step 6 wait value Set value, Decimal point ignored 20/24/50/54H 03/06/10H 1012H Step 7 SV Set value, Decimal point ignored 20/24/50/54H 03/06/10H 1013H Step 7 time (*13) Set value, Decimal point ignored 20/24/50/54H 03/06/10H 1014H Step 7 wait value Set value, Decimal point ignored 20/24/50/54H 03/06/10H 1015H Step 8 SV Set value, Decimal point ignored 20/24/50/54H 03/06/10H 1016H Step 8 time (*13) Set value, Decimal point ignored 20/24/50/54H 03/06/10H 1017H Step 8 wait value Set value, Decimal point ignored 20/24/50/54H 03/06/10H 1018H Step 9 SV Set value, Decimal point ignored 20/24/50/54H 03/06/10H 1019H Step 9 time (*13) Set value, Decimal point ignored 20/24/50/54H 03/06/10H 101AH Step 9 wait value Set value, Decimal point ignored 20/24/50/54H 03/06/10H 101BH Reserved (*2)
: : : :
20/24/50/54H 03/06/10H 102FH Reserved (*2)
(*1) If any action is changed at 0006H (Event output EV1 allocation) or 0007H (Event output EV2 allocation), EV1 alarm value, EV2 alarm value, etc.
will revert to factory default value.
For the items to be initialized: Refer to Section ‘7.7 Items to be Initialized by Changing Settings’ (p.44).
(*2) For ‘Reserved’ items, if a single/multiple piece(s) of data Read is/are executed, acknowledgement will be returned (but data is 0).
If a single/multiple piece(s) of data is/are written, data will be discarded, and acknowledgement will be returned.
(*3) For ‘Not used’ items, if a single/multiple piece(s) of data Read/Write is/are executed, Error code 1 (31H, Shinko protocol) or Exception code 2
(02H, Modbus protocol) will be returned.
(*4) For 00E5H (Manual control MV), if the following is written, Error code 3 (33H, Shinko protocol) or Exception code 3 (03H, Modbus protocol)
will be returned.
• When OUT1 is in ON/OFF control, and if any items except OUT1 low limit and OUT1 high limit values are written.
• When Heating side (of Heating/Cooling control) is in ON/OFF control, and if any items – except Heating side OUT1 low limit, OUT1 high limit
value, Cooling side OUT2 low limit and OUT2 high limit value – are written.
• When Cooling side (of Heating/Cooling control) is in ON/OFF control, and if any items – except Heating side OUT1 low limit to OUT1 high limit
value, Cooling side OUT2 low limit and OUT2 high limit value – are written.
(*5) If 00E9H (Program control Advance function) is read, Error code 1 (31H, Shinko protocol) or Exception code 2 (02H, Modbus protocol) will be
returned.
If any value except 0001H (Advance Perform) is written, Error code 3 (33H, Shinko protocol) or Exception code 3 (03H, Modbus protocol) will
be returned.
(*6) If 00FEH (Data clear) is executed, all values will revert to factory default values.
If communicating using parameters which are unequal to the factory default, it will be impossible to communicate. Set the communication
parameters again.
(Refer to Section ‘3. Setting Communication Parameters’.)
If 00FEH (Data clear) is read, Error code 1 (31H, Shinko protocol) or Exception code 2 (02H, Modbus protocol) will be returned.
If any value except 1234H (Clear data) is written, error code 3 (33H, Shinko protocol) or Exception code 3 (03H, Modbus protocol) will be
returned.
35
(*7) If 00FFH (Key operation change flag clearing) is read, Error code 1 (31H, Shinko protocol) or Exception code 2 (02H, Modbus protocol)
will be returned.
If any value except 0001H (Clear key operation change flag) is written, Error code 3 (33H, Shinko protocol) or Exception code 3 (03H, Modbus
protocol) will be returned.
(*8) Contents of error code are shown below.
Error Code Contents
Error 01 Internal non-volatile IC memory is defective.
Error 02 Data writing (in non-volatile IC memory) error when power failure occurs.
Error 05
Overscale. PV has exceeded Input range high limit value (Scaling high limit value for DC voltage, current inputs).
Error 06
Underscale. PV has dropped below Input range low limit value (Scaling low limit value for DC voltage, current inputs).
Error 07
Input burnout or disconnection. Input value is outside of the Indication range and control range.
Error 10 Hardware malfunction
Error 20 AT or AT on startup has not been completed even if approx. 4 hours has elapsed since starting.
For AT on startup, PV slope and delay time cannot be measured normally for P, I, D calculation.
(*9) If B13 or B14 is “1: ON”, B11 will also be “1: ON”.
(*10) Data item
163digit: 0: Fixed value control, 1: Program control
162to 160digits: Data item code (serial number) for each step
(*11) Step 1 SV (1000H) corresponds to SV1 (0001H) and SV1 (000EH).
(*12) Step 2 SV to Step 4 SV (1003H, 1006H, 1009H) correspond to SV2 to SV4 (000FH, 0010H, 0011H).
(*13) For TS1 OFF time (0073H), TS1 ON time (0074H), TS2 OFF time (0076H), TS2 ON time (0077H), and Steps 1 to 9 time (1001H, 1004H,
1007H, 100AH, 100DH, 1010H, 1013H, 1016H, 1019H):
Calculate the step time using the smaller time unit at 006DH (Step time unit), then convert it to hexadecimal numbers.
Use hexadecimal numbers for settings as follows.
Setting range: 00:00 to 99:59 (0 to 5999) (e.g.) When ‘Hours:Minutes’ is selected in [Step time unit].
1:00 1 x 60 + 00=60 003CH
1:30 1 x 60 + 30=90 005AH
FFFFH: The step time is held, and Fixed value control is performed.
36
7.2 JC Command Table
If (Shinko protocol, JC command allocated), (Modbus ASCII, JC command allocated) or
(Modbus RTU, JC command allocated) is selected in [Communication protocol], the following JC
command can be used.
7.2.1 A Single Piece of Data Read/Write Command
Shinko
Command
Type
Modbus
Function
Code
Data Item Data
20H/50H 03H/06H 0001H SV1 Set value, Decimal point ignored 20H/50H 03H/06H 0002H Not used (*1) 20H/50H 03H/06H 0003H AT/Auto-reset Perform/Cancel 0000H: AT/ Auto-reset Cancel
0001H: AT/ Auto-reset Perform
20H/50H 03H/06H 0004H OUT1 proportional band
Set value, Decimal point ignored
20H/50H 03H/06H 0005H OUT2 proportional band (*2)(*3)
Set value, Decimal point ignored
20H/50H 03H/06H 0006H Integral time
Set value
20H/50H 03H/06H 0007H Derivative time
Set value
20H/50H 03H/06H 0008H OUT1 proportional cycle
Set value
20H/50H 03H/06H 0009H OUT2 proportional cycle
Set value 20H/50H 03H/06H 000AH Not used (*1) 20H/50H 03H/06H 000BH EV1 alarm value (*4) Set value, Decimal point ignored 20H/50H 03H/06H 000CH EV2 alarm value (*4) Set value, Decimal point ignored 20H/50H 03H/06H 000DH Not used (*1) 20H/50H 03H/06H 000EH Not used (*1) 20H/50H 03H/06H 000FH Heater burnout alarm value Set value, Decimal point ignored 20H/50H 03H/06H 0010H Loop break alarm time Set value 20H/50H 03H/06H 0011H Loop break alarm span Set value, Decimal point ignored 20H/50H 03H/06H 0012H Set value lock (*2)(*5) 0000H: Unlock
0001H: Lock 1
0002H: Lock 2
0003H: Lock 3 20H/50H 03H/06H 0013H SV high limit (*6)
Set value, Decimal point ignored 20H/50H 03H/06H 0014H SV low limit (*6)
Set value, Decimal point ignored 20H/50H 03H/06H 0015H Sensor correction
Set value, Decimal point ignored 20H/50H 03H/06H 0016H Overlap/Dead band
Set value, Decimal point ignored 20H/50H 03H/06H 0017H Not used (*1) 20H/50H 03H/06H 0018H
Scaling high limit
Set value, Decimal point ignored 20H/50H 03H/06H 0019H
Scaling low limit
Set value, Decimal point ignored 20H/50H 03H/06H 001AH Decimal point place
0000H:
No decimal point
0001H: 1 digit after decimal point
0002H: 2 digits after decimal point
0003H: 3 digits after decimal point 20H/50H 03H/06H 001BH PV filter time constant Set value, Decimal point ignored 20H/50H 03H/06H 001CH OUT1 high limit
Set value 20H/50H 03H/06H 001DH OUT1 low limit
Set value 20H/50H 03H/06H 001EH OUT1 ON/OFF hysteresis Set value, Decimal point ignored 20H/50H 03H/06H 001FH OUT2 cooling method 0000H: Air cooling
0001H: Oil cooling
0002H: Water cooling 20H/50H 03H/06H 0020H OUT2 high limit
Set value 20H/50H 03H/06H 0021H OUT2 low limit
Set value 20H/50H 03H/06H 0022H OUT2 ON/OFF hysteresis Set value, Decimal point ignored
37
Shinko
Command
Type
Modbus
Function
Code
Data Item Data
20H/50H 03H/06H
0023H Event output EV1 allocation
(*2)(*7)
0000H: No event 0001H: Alarm output, High limit alarm 0002H: Alarm output, Low limit alarm 0003H: Alarm output, High/Low limits alarm 0004H: Alarm output, High/Low limit range
alarm 0005H: Alarm output, Process high alarm 0006H: Alarm output, Process low alarm 0007H: Alarm output, High limit with
standby alarm 0008H: Alarm output, Low limit with
standby alarm 0009H: Alarm output, High/Low limits with
standby alarm
20H/50H 03H/06H
0024H Event output EV2 allocation
(*2)(*7)
0000H: No event 0001H: Alarm output, High limit alarm 0002H: Alarm output, Low limit alarm 0003H: Alarm output, High/Low limits alarm 0004H: Alarm output, High/Low limit range
alarm 0005H: Alarm output, Process high alarm 0006H: Alarm output, Process low alarm 0007H: Alarm output, High limit with
standby alarm 0008H: Alarm output, Low limit with
standby alarm 0009H: Alarm output, High/Low limits with
standby alarm
20H/50H 03H/06H
0025H EV1 alarm hysteresis Set value, Decimal point ignored
20H/50H 03H/06H
0026H EV2 alarm hysteresis Set value, Decimal point ignored
20H/50H 03H/06H
0027H Not used (*1)
20H/50H 03H/06H
0028H Not used (*1)
20H/50H 03H/06H
0029H EV1 alarm delay time Set value
20H/50H 03H/06H
002AH EV2 alarm delay time Set value
20H/50H 03H/06H
002BH Not used (*1)
20H/50H 03H/06H
002CH Not used (*1)
20H/50H 03H/06H
002DH Not used (*1)
20H/50H 03H/06H
002EH Not used (*1)
20H/50H 03H/06H
002FH Not used (*1)
20H/50H 03H/06H
0030H Not used (*1)
20H/50H 03H/06H
0031H Not used (*1)
20H/50H 03H/06H
0032H Not used (*1)
20H/50H 03H/06H
0033H Not used (*1)
20H/50H 03H/06H
0034H Not used (*1)
20H/50H 03H/06H
0035H Not used (*1)
20H/50H 03H/06H
0036H Not used (*1)
20H/50H 03H/06H
0037H Control output OFF (*8) 0000H: Control output ON
0001H: Control output OFF
20H/50H 03H/06H
0038H Auto/Manual control (*9) 0000H: Automatic control
0001H: Manual control
20H/50H 03H/06H
0039H Manual control MV (*10) Set value
20H/50H 03H/06H
003AH Not used (*1)
20H/50H 03H/06H
003BH Not used (*1)
20H/50H 03H/06H
003CH Not used (*1)
38
Shinko
Command
Type
Modbus
Function
Code
Data Item Data
20H/50H 03H/06H
003DH Not used (*1)
20H/50H 03H/06H
003EH Not used (*1)
20H/50H 03H/06H
003FH Not used (*1)
20H/50H 03H/06H 0040H
EV1 alarm Energized/De-energized
0000H: Energized 0001H: De-energized
20H/50H 03H/06H 0041H
EV2 alarm Energized/De-energized
0000H: Energized 0001H: De-energized
20H/50H 03H/06H 0042H
Not used (*1) 20H/50H 03H/06H 0043H Not used (*1) 20H/50H 03H/06H 0044H Input type
0000H: K -200 to 1370 0001H: K -200.0 to 400.0 0002H: J -200 to 1000 0003H: R 0 to 1760 0004H: S 0 to 1760 0005H: B 0 to 1820 0006H: E -200 to 800 0007H: T -200.0 to 400.0 0008H: N -200 to 1300 0009H: PL- 0 to 1390 000AH: C(W/Re5-26) 0 to 2315 000BH: Pt100 -200.0 to 850.0 000CH: JPt100 -200.0 to 500.0 000DH: Pt100 -200 to 850 000EH: JPt100 -200 to 500 000FH: K -328 to 2498 0010H: K -328.0 to 752.0 0011H: J -328 to 1832 0012H: R 32 to 3200 0013H: S 32 to 3200 0014H: B 32 to 3308 0015H: E -328 to 1472 0016H: T -328.0 to 752.0 0017H: N -328 to 2372 0018H: PL- 32 to 2534 0019H: C(W/Re5-26) 32 to 4199 001AH: Pt100 -328.0 to 1562.0 001BH: JPt100 -328.0 to 932.0 001CH: Pt100 -328 to 1562 001DH: JPt100 -328 to 932 001EH: 4 to 20 mADC -2000 to 10000 001FH: 0 to 20 mA DC -2000 to 10000 0020H: 0 to 1 V DC -2000 to 10000 0021H: 0 to 5 V DC -2000 to 10000 0022H: 1 to 5 V DC -2000 to 10000 0023H: 0 to 10 V DC -2000 to 10000
20H/50H 03H/06H 0045H Direct/Reverse action
0000H: Reverse action
0001H: Direct action 20H/50H 03H/06H 0046H Not used (*1) 20H/50H 03H/06H 0047H AT bias Set value, Decimal point ignored 20H/50H 03H/06H 0048H ARW Set value 20H/50H 03H/06H 006FH Key lock (*11)
0000H: Key lock Disabled (Front keys
Enabled)
0001H: Key lock Enabled (Front keys
Disabled)
39
7.2.2 A Single Piece of Data Write Command
Shinko
Command
Type
Modbus
Function
Code
Data Item Data
50H 06H 0070H Key operation change flag clearing
(*12)
0001H: Clear key operation
change flag
7.2.3 Read Command
Shinko
Command
Type
Modbus
Function
Code
Data Item Data
20H 03H 0080H PV Read value, Decimal point ignored 20H
03H 0081H OUT1 MV Read value, Decimal point ignored
20H
03H 0082H OUT2 MV Read value, Decimal point ignored
20H
03H 0083H Not used (*1)
20H
03H 0084H Not used (*1)
20H
03H 0085H Status flag
0000 0000 0000 0000
20OUT1 output (*13) 0: OFF 1: ON 21OUT2 output (*13) 0: OFF 1: ON 22EV1 output 0: OFF 1: ON 23EV2 output 0: OFF 1: ON 24Not used, Always 0 25Not used, Always 0 26Heater burnout alarm 0: OFF 1: ON 27Loop break alarm 0: OFF 1: ON 28Overscale 0: OFF 1: ON 29Underscale 0: OFF 1: ON 210Control output OFF function
0: Control output ON 1: Control output OFF
211AT/Auto-reset, Perform/Cancel
0: Cancel 1: Perform
212OUT/OFF key function
0: Control output OFF function
1: Auto/Manual control 213Not used, Always 0 214Auto/Manual control
0: Automatic control 1: Manual control
215Change in key operation 0: No 1: Yes
(*1) For ‘Not used’ items, if a single piece of data Read/Write is executed, Error code 1 (31H, Shinko protocol) or Exception code 2 (02H, Modbus
protocol) will be returned.
(*2) The Read/Write range of setting values is different from that of keypad operation.
(*3) For writing 0005H (OUT2 proportional band), write the multiplied value (0.0 to 10.0) of OUT1 proportional band.
For reading 0005H (OUT2 proportional band), the controller internally calculates the multiplied value using OUT1 and OUT2 proportional
bands, and returns the result as response data.
Even if the multiplied value exceeds 10.0, the exceeding value will be returned as response data.
(*4) If 000BH (EV1 alarm value) or 000CH (EV2 alarm value) is changed, EVT1 high limit alarm value or EVT2 high limit alarm value will be
automatically changed to the same value.
(*5) For 0012H (Set value lock), Lock 4 and Lock 5 can be selected, which is the same as 004EH (Set value lock) of the BCx2 (p.29).
(*6) If 0013H (SV high limit) or 0014H (SV low limit) is changed, Scaling high limit or Scaling low limit will be automatically changed to the same
value.
(*7) If any action is changed at 0023H (Event output EV1 allocation) or at 0024H (Event output EV2 allocation), EV1 alarm value, EV2 alarm
value, etc. will revert to factory default value.
For the items to be initialized, refer to Section “7.7 Items to Be Initialized by Changing Settings” (p.44).
The following items cannot be selected via software communication (They can only be set via the keypad):
High/Low limits independent alarm, High/Low limit range independent alarm, High/Low limits with standby independent alarm,
Loop break alarm output, Time signal output, Output during AT, Pattern end output, Output via communication command,
Heating/Cooling control relay contact output (EV2 only)
(*8) For 0037H (Control output OFF), if Control output OFF function is not selected in [OUT/OFF key function], Error code 1 (31H, Shinko
protocol) or Exception code 2 (02H, Modbus protocol) will be returned.
40
(*9) For 0038H (Auto/Manual control), if Auto/Manual control is not selected in [OUT/OFF key function], Error code 1 (31H, Shinko protocol)
or Exception code 2 (02H, Modbus protocol) will be returned.
(*10) For 0039H (Manual control MV), if Write is executed during automatic control, Error code 1 (31H, Shinko protocol) or Exception code 2
(02H, Modbus protocol) will be returned.
If the following are written, Error code 3 (33H, Shinko protocol) or Exception code 3 (03H, Modbus protocol) will be returned.
• When OUT1 is in ON/OFF control, and if any items except OUT1 low limit and OUT1 high limit values are written.
• When Heating side (of Heating/Cooling control) is in ON/OFF control, and if any items – except Heating side OUT1 low limit, OUT1 high
limit value, Cooling side OUT2 low limit and OUT2 high limit value – are written.
• When Cooling side (of Heating/Cooling control) is in ON/OFF control, and if any items – except Heating side OUT1 low limit to OUT1 high
limit value, Cooling side OUT2 low limit and OUT2 high limit value – are written.
(*11) Key lock Enabled/Disabled can be selected.
If Key lock Enabled (Front keys Disabled) is selected, front keys cannot be used. However, if the power to the BCx2 is turned OFF, then
ON again, the Key lock will be cancelled, and front keys can be used.
(*12) If 0070H (Key operation change flag clearing) is read, Error code 1 (31H, Shinko protocol) or Exception code 2 (02H, Modbus protocol)
will be returned.
If any value except 0001H (Clear key operation change flag) is written, Error code 3 (33H, Shinko protocol) or Exception code 3 (03H,
Modbus protocol) will be returned.
(*13) For direct current output, data is not fixed.
7.3 Data
7.3.1 Notes about Write/Read Command
• The data (set value, decimal) is converted to a hexadecimal number. Negative numbers are represented in 2's complement.
• When connecting multiple slaves, the address (instrument number) must not be duplicated.
• Do not use undefined Data items. If they are used, negative acknowledgement will be returned or a random value will be written or read, resulting in malfunction.
• Modbus protocol uses Holding Register addresses. The Holding Register addresses are created as follows. A Shinko command data item is converted to decimal number, and the offset of 40001 is added. The result is the Holding Register address. Using Data item 0001H (SV1) as an example: Data item in the sending message is 0001H, however, Modbus
protocol Holding Register address is 40002 (1 + 40001).
7.3.2 Write Command
• Up to 1,000,000 (one million) entries can be stored in non-volatile IC memory.
If the number of settings exceeds the limit, the data will not be saved. So, do not change the set values frequently via software communication. (If a value set via software communication is the same as the value before the setting, the value will not be written in non-volatile IC memory.)
• Setting range of each item is the same as that of keypad operation.
• When data (set value) has a decimal point, a whole number (hexadecimal) without a decimal point is used.
• If any action is changed at 0006H (Event output EV1 allocation) or at 0007H (Event output EV2 allocation),
the following values will revert to the factory default value:
EV1 alarm value (0012H), EV2 alarm value (0014H), etc.
For the items to be initialized, refer to Section “7.7 Items to Be Initialized by Changing Settings” (p.44).
• Writings via software communication are possible while in Set value lock status.
• Even if options are not ordered, writing or reading via software communication will be possible.
However, their command contents will not function.
• The Instrument Numbers and Communication Speed of the slave cannot be set by software communication.
They can only be set via the keypad.
• When Write is executed using the Global address [95 (7FH), Shinko protocol] command or Broadcast
address [0 (00H) Modbus protocol] command, the command is sent to all the connected slaves. However, a response is not returned.
7.3.3 Read Command
• When the data (set value) has a decimal point, a whole number (hexadecimal) without a decimal point is
used for a response.
41
7.4 Negative Acknowledgement
7.4.1 Error code 1 (31H, Shinko protocol) or Exception code 2 (02H, Modbus protocol)
The slave will return Error code 1 (31H, Shinko protocol) or Exception code 2 (02H, Modbus protocol) in the following case.
• When non-existent data item is read or written.
7.4.2 Error code 3 (33H, Shinko protocol) or Exception code 3 (03H, Modbus protocol)
The slave will return Error code 3 (33H, Shinko protocol) or Exception code 3 (03H, Modbus protocol) in the following case.
• When a value out of the setting range is written.
7.4.3 Error code 4 (34H, Shinko protocol) or Exception code 17 (11H, Modbus protocol)
The slave will return Error code 4 (34H, Shinko protocol) or Exception code 17 (11H, Modbus protocol) in the following cases.
• When 0001H (AT/Auto-reset Perform) or 0002H (AT on startup Perform) is written at 00E6H (AT/Auto-reset Perform/Cancel) during PI control or ON/OFF control action.
• While AT is performing during Fixed value control, if 0001H (AT/Auto-reset Perform) or 0002H (AT on startup Perform) is written at 00E6H (AT/Auto-reset Perform/Cancel). While AT is performing in Fixed value control, and if 00E0H (OUT/OFF key function) is written.
• While AT is performing during Program control, if 0001H (AT/Auto-reset Perform) or 0002H (AT on startup Perform) is written at 00E6H (AT/Auto-reset Perform/Cancel). While AT is performing during Program control, and if 00E0H (OUT/OFF key function) is written.
• When 00E5H (Manual control MV) is written during automatic control
7.4.4 Error code 5 (35H, Shinko protocol) or Exception code 18 (12H, Modbus protocol)
The slave will return Error code 5 (35H, Shinko protocol) or Exception code 18 (12H, Modbus protocol) in the following case.
• During setting mode by keypad operation
42
7.5 Notes on Programming Monitoring Software
7.5.1 How to Speed up the Scan Time
When monitoring multiple units of the controller, set the program so that the requisite minimum pieces of data such as Data item 0100H (PV), Data item 0101H (OUT1 MV), Data item 010DH (Status flag 1), can be read. For other data, set the program so that they can be read only when their set value has changed. This will speed up the scan time.
7.5.2 How to Read the Set Value Changes Made by Front Keypad Operation
If any set value is changed by the keypad operation, the controller sets the [010DH (Status flag 1) B15: Change in key operation] to 1 (Yes). There are 2 methods of reading the set value changes made by front keypad.
(1) Reading method 1
1
On the monitoring software side, check that [010DH (Status flag 1) B15: Change in key operation] has been set to 1 (Yes), then read all set values.
2
Clear [010DH (Status flag 1) B15: Change in key operation], by writing Data item 00FFH (Key operation change flag clearing) to 0001H (Clear key operation change flag). If 00FFH (Key operation change flag clearing) is written to 0001H (Clear key operation change flag) during the setting mode of the controller, Error code 5 (35H, Shinko protocol) or Exception Code 18 (12H, Modbus protocol) will be returned as a negative acknowledgement. And [010DH (Status flag 1) B15: Change in key
operation] cannot be cleared. Set a program so that all set values can be read when a negative acknowledgement is returned.
3
Read all set values again after acknowledgement is returned.
(2) Reading method 2
1
On the monitoring software side, check that [010DH (Status flag 1) B15: Change in key operation] has been set to 1 (Yes), then write the 00FFH (Key operation change flag clearing) to 0001H (Clear key operation change flag).
2
Set the program depending on the acknowledgement or negative acknowledgement as follows. When acknowledgement is returned;
Consider it as settings completed, and read all set values.
When Error code 5 (35H, Shinko protocol) or Exception code 18 (12H, Modbus protocol) is returned as a negative acknowledgement;
Consider it as still in setting mode, and read the requisite minimum pieces of data such as 0100H (PV) 0101H (OUT1 MV), 010DH (Status flag 1), then return to Step1.
Thus, programs which do not affect the scan time can be created using the methods described above, even if set values on the monitoring software will not be updated until settings are complete.
7.5.3 How to Read PID Parameters after AT or ‘AT on Startup’ Finishes
While AT or ‘AT on startup’ is performing, this controller sets [010DH (Status flag 1) B9: AT/Auto-reset, AT on startup Perform/Cancel] to 1 (Perform). After AT or ‘AT on startup’ is finished, PID parameters are updated. On the monitoring software side, check that [010DH (Status flag 1) B9: AT/Auto-reset, AT on startup Perform/Cancel] has been set to 0 (Cancel), then read parameters such as P, I, D, ARW.
7.5.4 Note When Sending All Set Values Simultaneously
• When changing alarm types at 0006H (Event output EV1 allocation) or at 0007H (Event output EV2 allocation), the following values will revert to 0 (zero).
EV1 alarm value (0012H), EV2 alarm value (0014H) First, send the selected alarm type, then send each alarm value. Refer to Section ‘7.7 Items to be Initialized by Changing Settings’. (p.44)
• When changing input types at 0002H (Input type), values such as SV1, OUT1 proportional band, EV1 Alarm value, etc. will be initialized.
First, send the selected input type, then send other set values.
43
7.6 When Communicating with a PLC
To communicate with a PLC, use a Shinko PLC Interface Unit SIF-600. No programming is needed for connection. Shinko protocol 24H (Multiple pieces of data read command) and 54H (Multiple pieces of data write command) are not available.
PLCs corresponding to the SIF-600, its manufacturer and host link units:
PLC Manufacturer PLC Model, Series Name Host Link Unit Model
Mitsubishi Electric Corp.
MELSEC Q, QnA series (*) AJ71UC24, A1SJ71UC24-R2/R4/PRF
A1SJ71C24-R2/R4/PRF, QJ71C24
MELSEC FX series (*)
Omron Corp.
SYSMAC CJ series CS1W-SCU21-V1
CJ1W-SCU21, CJ1W-SCU41
Keyence Corp.
KV KV-L20V
Yokogawa Electric Corp.
FA-M3 F3LC11-2N, F3LC11-1F, F3LC12-1F
Fuji Electric Co., Ltd.
MICREX-SX series NP1L-RS1, NP1L-RS2, NP1L-RS3
NP1L-RS4
(*) Models with compatible QR/QW communication commands
44
7.7 Items to be Initialized by Changing Settings
7.7.1 Shinko protocol/Modbus ASCII/Modbus RTU
If settings are changed, the following items will be initialized.
: Initialized
X: Not initialized
Setting item to be Item changed to be initialized
Input type
(0002H)
Event output
EV1 allocation
(0006H)
Event output
EV2 allocation
(0007H)
Transmission
output
(000BH)
SV1 to SV9 (1000H to 1018H)
X X X
Steps 1 to 9 wait value (1002H to 101AH)
X X X
AT bias (005BH)
X X X
OUT1 proportional band (003CH)
X X X
Manual reset (0040H)
X X X
SV rise rate (0058H)
X X X
SV fall rate (0059H)
X X X
Scaling high limit (0003H)
X X X
Scaling low limit (0004H)
X X X
Program start temperature (006FH)
X X X
EV1 alarm value (0012H)
X X
EV1 high limit alarm value (0013H)
X X
Loop break alarm time (001EH)
X X X
Loop break alarm span (001FH)
X X X
SVTC bias (0053H)
X X X
Remote bias (0056H)
X X X
EV2 alarm value (0014H)
X X
EV2 high limit alarm value (0015H)
X X
Transmission output high limit (000CH)
X X
Transmission output low limit (000DH)
X X
OUT2 proportional band (0047H)
X X X
EV1 alarm value 0 Enabled/Disabled (0024H)
X X X
EV1 alarm hysteresis (0025H)
X X X
EV1 alarm delay time (0026H)
X X X
EV1 alarm Energized/De-energized (0027H)
X X X
EV2 alarm value 0 Enabled/Disabled (0028H)
X X X
EV2 alarm hysteresis (0029H)
X X X
EV2 alarm delay time (002AH)
X X X
EV2 alarm Energized/De-energized (002BH)
X X X
Sensor correction coefficient (004FH)
X X X
Sensor correction (0050H)
X X X
External setting input high limit (0054H)
X X X
External setting input low limit (0055H)
X X X
45
7.7.2 JC Command
For the JC command, the following items will be initialized when settings are changed.
: Initialized
X: Not initialized
Setting item to be changed Item to be initialized
Input type
(0044H)
Event output
EV1 allocation
(0023H)
Event output
EV2 allocation
(0024H)
SV1 (0001H)
X X
AT bias (0047H)
X X
OUT1 proportional band (0004H)
X X
Scaling high limit (0018H)
X X
Scaling low limit (0019H)
X X
EV1 alarm value (000BH)
X
Loop break alarm time (0010H)
X X
Loop break alarm span (0011H)
X X
EV2 alarm value (000CH)
X
OUT2 proportional band (0005H)
X X
EV1 alarm hysteresis (0025H)
X X
EV1 alarm delay time (0029H)
X X
EV1 alarm Energized/De-energized (0040H)
X X
EV2 alarm hysteresis (0026H)
X X
EV2 alarm delay time (002AH)
X X
EV2 alarm Energized/De-energized (0041H)
X X
Sensor correction (0015H)
X X
46
8. Set Value Digital Transmission
By connecting to Shinko programmable controllers [PC-900 or PCD-33A with the SVTC (Set value digital transmission) option], digital SV via the SVTC command can be received from programmable controllers.
8.1 Wiring
For the PC-900, connect YA (-) to YA (-), YB (+) to YB (+), COM (PC-900) to SG (BCx2) terminal respectively. For the PCD-33A, connect YA (-) to YA (-), YB (+) to YB (+), SG to SG terminal respectively. Up to 31 units of the BCS2/BCR2/BCD2 can be connected. The following shows a connection example of PCD-33A and BCS2/BCR2/BCD2.
(Fig. 8.1-1)
8.2 Setting Method of Programmable Controllers (PC-900, PCD-33A) and BCx2 (1) Setting the PC-900 or PCD-33A
If SVTC option is ordered, none of the settings are required. PC-900: Check that ‘Set value digital transmission ( )’ is selected in [Communication mode, ]. PCD-33A: Check that ‘Set value digital transmission ( )’ is selected in [Communication protocol,
] in Auxiliary function setting mode 1.
(2) Setting the BCx2
Check the following items in Engineering mode 1. Refer to Section ‘3. Setting Communication Parameters’. (pp. 4, 5)
• Shinko protocol has been selected in [Communication protocol].
• Communication speed of the BCx2 is equal to that of the PC-900 or PCD-33A (9600 bps or 19200 bps).
(3) Starting ‘Set value (SV) digital transmission’
Enter the program set values on the PC-900 or PCD-33A. If the program is executed by pressing the Key, Step SV of the PC-900 or PCD-33A will be sent to the BCx2. During program Standby, 0 (zero) will be sent to the BCx2.
FG
FG
FG
YA(-)
YB(+)
SG
Shield
wire
Shield wire
Shield wire
PCD-33A
BCS2
YA(-)YB(+)SG
BCR2, BCD2
YA(-)YB(+)SG
YA(-)YB(+)SG
YA(-)YB(+)SG
YA(-)YB(+)SG
YA(-)YB(+)SG
47
9. Specifications
Cable length 1.2 km (Max.), Cable resistance: Within 50 (Terminators are not necessary,
but if used, use 120 or more on both sides.)
Communication line EIA RS-485
Communication method Half-duplex communication
Communication speed 9600, 19200, 38400 bps (Selectable by keypad)
Synchronization method Start-stop synchronization
Code form ASCII, binary
Data bit/Parity 7, 8/Even, Odd, No parity (Selectable by keypad)
Stop bit 1, 2 (Selectable by keypad)
Communication protocol Shinko protocol, Modbus ASCII, Modbus RTU (Selectable by keypad) Data format
Communication
Protocol
Shinko Protocol Modbus ASCII Modbus RTU
Start bit 1 1 1 Data bit 7 (8)
Selectable
7 (8)
Selectable
8
Parity
Even (No parity,
Odd)
Selectable
Even (No parity,
Odd)
Selectable
No parity (Even,
Odd)
Selectable
Stop bit 1 (2)
Selectable
1 (2)
Selectable
1 (2)
Selectable Number of connectable units Max 31 units to 1 host computer
Error correction Command request repeat system
Error detection Parity, checksum (Shinko protocol), LRC (Modbus ASCII), CRC-16 (Modbus
RTU)
Digital external setting Receives digital SV via the SVTC command from Shinko programmable
controllers (PC-900, PCD-33A with the SVTC option).
48
10. Troubleshooting
Check that power is being supplied to the master and slave that customers use. If communication failure still occurs, check the following.
Problem Possible Cause Solution
Communication failure
Communication cable is not securely connected, or is disconnected/defective.
Check the communication cable and connector.
Incorrect wiring of the communication cable and/or connector
Check the communication cable and connector. Refer to Section ‘2. Wiring’ (pp. 2, 3).
Imperfect contact between the communication cable and the connector, or between the communication connector and instrument port
Check the communication cable and connector.
Communication speed of the slave does not match that of the master.
Set the same communication speed on the master and the slave. Refer to Section ‘3. Setting Communication
Parameters’ (pp. 4, 5). The data bit, parity and stop bit of the master do not correspond to those of the slave.
Set the same data bit, parity and stop bit on
the master and the slave.
Refer to Section ‘3. Setting Communication
Parameters’ (pp. 4, 5). The instrument number (address) of the slave does not correspond to that of the command.
Check the instrument number (address)
of the slave and the command.
Refer to Section ‘3. Setting Communication
Parameters’ (pp. 4, 5).
The instrument numbers (addresses) are duplicated in multiple slaves.
Check that each slave has a different
instrument number (address).
Refer to Section ‘3. Setting Communication
Parameters’ (pp. 4, 5).
Make sure that the program is appropriate for the transmission timing.
Check the program.
Refer to Section ‘4. Communication
Procedure’ (p.6).
Although communication is occurring, the
response is negative acknowledgement.
A non-existent command code has been sent.
Check the command code.
The Write command data exceeds the setting range of the slave.
Check the setting range of the slave.
The controller cannot be written when functions such as AT are performing.
Check the slave status.
The BCx2 is in front keypad operation setting mode.
Return the controller to RUN mode.
For all other malfunctions, please contact our main office or dealers.