Shinco KFR-25GWZ/BM, KFR-35GWZ/BM, KFR-50GWZ/BM, KFR-70GWZ/BM Instruction Manual

Page 1
Split Type Wall-mounted Inverter Room Air Conditioner
Instruction Manual
Thank you for purchasing a Shinco air conditioner.To guarantee safety and best efficiency, please read this manual carefully and keep it for future reference.
Applicable to
KFR-25GWZ/BM KFR-35GWZ/BM KFR-50GWZ/BM KFR-70GWZ/BM
Page 2
To Consumers
1. This air conditioning unit should be installed and repaired by a qualified technician.
2. The air conditioning unit must be grounded reliably during the installation.
3. Please clean the air filter nets 1 to 2 times per month when the air conditioner is being used frequently (details inside).
With the compressor and the micro computer controlling chip, the performance is stable and reliable.
The high-efficiency compressor and heat exchanger guarantee higher efficiency and energy-saving. Quiet running.
Some information included in this manual might be different on the unit if parts
are modified by the manufacturer.
Note:
Features:
1
Page 3
SAFETY PRECAUTIONS
Please read the SAFETY AND OPERATING INSTRUCTIONS carefully before operating the unit. Please respect the following safety precautions when using your air conditioner to preventfire, shock hazard or personal injury.
WARNING CAUTION
This sign warns of risk of death or serious injury. This sign warns of injury or damage to property.
This symbol denotes an action that is PROHIBITED. This symbol denotes an action that is COMPULSORY.
INSTALLATION PRECAUTIONS
WARNING
CAUTION
==
==
=Do not install, remove or re-install, the unit yourself.
Improper installation may cause leakage, electric shock or fire. The unit should be installed by a qualified technician.
==
==
=Please use ground. Improper grounding could cause elec
tric shock. Do not place the ground line near water or gas pipes, elec tric or telephone lines. Improper installation could cause an electric shock.
Do not install the unit in a place where there could be a
gas leak. The unit may catch fire if flammable gas leaks around it.
Please ensure smooth flow of water when installing the
drain hose.
The indoor unit must be installed at least 2.4 meters high
from the floor.
If the fuse on PCB board is blown, please have it
changed by aqualified technician.
2
Page 4
OPERATION PRECAUTIONS
WARNING
CAUTION
Do not operate with wet hands.
Avoid staying directly in front of operating unit.
Do not insert foreign objects into the unit.
Always have the unit repaired by a professional technician -
contact a service center.
Danger of electric shock or fire if used improperly.
Do not use if the power cord is damaged, it could cause an
electric shock or fire.
Do not allow children to operate the air conditioner.
Never sit on the unit.
If you notice an abnormality (burnt smell, etc) please shut
the power off and unplug the unit.
The unit should not be used for any other purpose.
Avoid spilling liquids on the unit.
Do not place the air conditioner close to a heat source, it
could cause a deformation or color fading.
Do not block the air intake and outlet vents.
Do not let the air conditioner function at maximum power for
an extended period of time (close all doors and windows).
Do not operate without the air filter installed or when the
front intake grill has been removed.
Do not place anything on the unit.
Always turn the power off before cleaning the air condi
tionerto avoid any possible accidents.
Please ensure proper ventilation when using the air
conditioner.
3
Page 5
CONTENTS
4
To Consumers .......................................................... 1
SAFETY PRECAUTIONS ........................................ 2
OPERATING PRECAUTIONS ................................. 3
2. Batteries ............................................................................................................................. 7
3-1 Setting the clock ............................................................................................................... 7
3-2 Wind Speed-Wind Direction Adjustment........................................................................... 8
3-3 Timer setting ..................................................................................................................... 8
3-4 Cooling•Heating•Dehumidy mode .................................................................................... 9
3-5 Ventilator mode................................................................................................................. 9
3-6 Drying clothes mode .........................................................................................................9
3-7 Auto running ................................................................................................................... 10
3-8 Powerful mode ................................................................................................................ 10
3-9 Sleeping mode ................................................................................................................ 10
3-10 Switching from Co to F
0
.........................................................................................................................................................................
11
3-11 Sensor Switching mode ................................................................................................ 11
4. Maintenance ..................................................................................................................... 11
5. Efficiency guide................................................................................................................. 12
6. Trouble Shooting............................................................................................................... 13
Part Installation Instruction..........................14
1. Select the location for installation ..................................................................................... 14
2. Installation of Indoor Unit ...............................................................................................15
2-3 Installation of the Power Source ..................................................................................... 16
2-4 Installation of Drain Hose ............................................................................................... 16
2-5 Arrangement of Pipes ..................................................................................................... 17
3. Installation of Outdoor Unit ............................................................................................... 18
3-1 Flared Joint .................................................................................................................... 18
3-2 Pipe Joint ........................................................................................................................ 18
3-3 Drain Hose ...................................................................................................................... 19
3-5 Installation of the exterior draining pipe .......................................................................... 21
4. TEST RUN ........................................................................................................................ 21
4-1 Pipe-cleaning and vacuum verification ........................................................................... 21
4-2 Test Run Procedure ........................................................................................................ 21
4-3 Instructions to Consumers .............................................................................................. 22
Main Specifications .........................................23
Page 6
5
Page 7
6
23456789012345678
9
23456789012345678
9
23456789012345678
9
23456789012345678
9
23456789012345678
9
23456789012345678
9
23456789012345678
9
23456789012345678
9
Page 8
7
Two AAA Size 1.5v batteries
Remove front cover
(Change the batteries)
4. Wind speed display : (Low) (Medium)
(High) (Auto)
5. Present time display:
6. Signal transmitting display:
7. Wind direction display: (Wind direction adjustment)
TIME
Press “SET TIMER”, the minutes indicator will be flashing, then use the arrows to set the minutes (0~59 minutes) press “SET TIMER” again. Do the same thing to set the hour (0~23 hours).
Avoid direct sunshine and other heat resources. If the re­mote control does not function properly, please press the restart button or change the batteries. Remove the front cover of the remote control. Please use two new AAA size 1.5V batteries of the same brand. Be sure to observe polarity. The batteries should be taken out of the unit if it is not used for a long period of time. Never mix new and used batteries.
Directions:
1. Mode display: (Auto) (Cooling) (Dehumidifying) (Heating) (Fan) (Dry clothing)
2. Temperature setting display:
3. The temperature around the remote controller display:
TEMP
2. Batteries
8. Sensor switching display:
9. Sleep timer display:
10. One hour setting display:
11. High power display:
12. Lock display:
13. Timer setting display:
ON
SET
OFF
LOCK
3-1 Setting the clock
1 HR
Page 9
8
3-2 Wind Speed-Wind Direction Adjustment
SET TIMER
TIME
Attention:
The clock can be set even if the unit is closed.
For your comfort, adjust the wind speed and direction correctly. To adjust the wind speed, press on SPEED (see below):
Low
change in turn
Medium High Auto
downward
45°
To adjust the wind direction press DIRECTION (see below) Regulate the horizontal wind direction:
Static Swing up and down
Change in turn
To set the starting time press the TIMER button, when ON displays in the time section on the LCD screen, use the arrows to enter the desired starting time and then press SET TIME again. The unit will start automatically at the time you have set.
To set the stop time press the TIMER button, when OFF displays in the time section on LCD screen, use the arrows to enter the desired stopping time and then press SET TIME again. The unit will stop automatically at the time you have set.
ONSET
3-3 Timer setting
OFFSET
Page 10
9
To cancel time setting press the TIMER button. Nothing will be displayed on the LCD screen.
One hour setting Press the 1HR button, the one hour setting function is on (the unit stops after running for 1 hour). To cancel press the 1HR button again.
Note: the values used to display time are from 00:00 to 23:59.
3-4 Cooling•Heating•Dehumidy mode
Press ON/OFF button. Press MODE button, and choose “Cooling”, “Heating” or “Dehumidify” mode. Press the arrows to regulate temperatures between 16 and 30 degrees Celsius. Press the arrows button once, the temperature changes 1 degree at a time. Press the SPEED button to adjust the air flow. Press the DIRECTION button to adjust the wind direction. Press ON/OFF to close the air conditioner.
Attention: If the unit is closed the LCD screen shows the room temperature. The
green light indicates the unit is in cooling or heating mode. The green light will be flashing when the outside temperature is very cold.
During heating mode, if the exterior temperature is very cold, it is possible that the air flow could be less powerful and the unit could make some noise and the internal ventilator could stop. It is also possible that the exterior unit could stop or that some vapour could evaporate from it, etc. This phenomenon is normal when exterior temperature is very cold.
3-5 Ventilator mode
Press ON/OFF. Press MODE, choose the ventilator mode. Press SPEED, choose the desired speed. Press ON/OFF to stop the unit.
Press the ON/OFF button then press MODE button and choose “Drying Clothes” mode. Press the ON/OFF button to close the air conditioner.
3-6 Drying clothes mode
Page 11
10
Attention:
1. Select the cooling, heating or dehumidify mode according to the room
temperature.
2. If the quantity of clothes to dry is too large or the dehumidify mode is not activated,
then the drying will not be completed.
Choose temperature, wind speed and direction automatically. Press ON/OFF button then press MODE button and choose “Auto“ setting. Press TEMP to select the desired temperature and adjust the wind flow and wind direction.
To close press the ON /OFF button.
3-7 Auto running
Press “POWERFUL” in heating or cooling mode and the symbol will appear on the LCD screen. Press POWERFUL again to cancel.
3-8 Powerful mode
Attention:After operating at maximal power for 15
minutes the unit will automatically stop and then restartat the preset temperature. The symbol will disappear on the LCD screen. The unit will make more noise at maximal power.
Use the SLEEP mode to stay comfortable thru the night, the symbol will appear on the LCD screen. To cancel, press SLEEP again.
In cooling mode: one hour after activating the SLEEP mode the preset temperature increases by one degree automatically, and two hours after the preset temperature in­creases by one degree automatically again.
3-9 Sleeping mode
Page 12
11
In heating mode: one hour after activating the SLEEP mode the preset temperature increases by 2 degrees automatically, and two hours after the preset temperature increases by another 2 degrees automatically again. This function will assure your comfort thru the night.
Press SLEEP button again to cancel the sleep function.
3-10 Switching from Co to F
0
Press 0C / 0F button to switch the display from Celsius to Fahrenheit.
Use this function when the room temperature is uneven. The temperature around the remote control can be transmitted to the unit to adjust the temperature.
Press SENSOR when the unit is in use in heating or cooling mode and this symbol will show on the LCD screen. Press SENSOR again to cancel
.
3-11 Sensor Switching mode
Attention: Always unplug unit before cleaning. Clean the filters every two weeks.
4. Maintenance
Clean with soft cloth
Cleaning of the remote control Clean the intake vent grill
Clean with a damp cloth and dry. If necessary use a gentle soap.
Clean with a damp cloth
Page 13
12
Clean the air filter (once every two weeks)
1. Hold the two ends of the
grill and gently push the filters downward
2. Use vacuum cleaner or water to clean the filters and then dry.
3. To put the filters back into place hold the two ends of the grill and insert the filters.
Intake vent grill
Lift and pull downwards
Raise and insert
When the machine will not be used for a long period of time
Run to dry the inside of the machine=Pull out the power plug Take the batteries out
of the remote control.
5. Efficiency guide
Try to keep windows and doors closed. Avoid direct sunlight to indoor unit. Keep the air filters clean.
Adjust the vertical and horizontal air direction to get a comfortable indoor temperature. Do not place yourself directly in front of the operating unit. Raising the fan speed can enhance the cooling efficiency. In heating operation, the humidity level of the room should be adjusted properly, or the air will be dry and uncomfortable.
Page 14
13
6. Trouble Shooting
Before calling a repair man, please check the followings:
The air conditioner does not work
The unit does not blow warm air in heating mode
Low efficiency of cooling or heating
Noise
Abnormality on the remote con­trol screen
Cold water leaking from the air condi­tioner
Symptom Possible reason
Moisture will occur in the air outlet due to the tempera ture difference.
Batteries need to be replaced.
Batteries are inserted incorrectly. Take the batteries out and insert them again.
The air filters are too dirty.
The intake vent or outlet vent is blocked up.
In heating operation, the ambient temperature is too low.
Defrosting operation may be required.
The compressor is in a delay mode (to protect the
compressor there are several minutes delay for every start) wait a few minutes after starting the unit.
The hot air will be blown out only after the defrosting operation.
Problem with the remote control.
Problem with the voltage. Please shut the power,
wait 3 minutes and restart the unit.
Verify the circuit breaker or fuse.
Water leak noise. It is the sound of the circulation of
refrigerant.
Condensed air leaking out. In heating operation, during the defrosting, it is the sound of the back-flow refrigerant.
Page 15
14
To guarantee the unit it must be installed according to the instructions in this manual.
The air conditioner has to be grounded properly.
Check the connecting cables and pipes carefully, make sure they are correct
and firm before connecting the power of the air conditioner. The maximum length of the connecting pipe between the indoor unit and outdoor unit should be no more than 5 metres (or it will affect the efficiency) .
After installation, the consumer must operate the air conditioner according to
the instructions in this manual.
Caution: The installation must be performed in accordance with the National/ Re-
gional Wiring Standard or Code by a qualified technician.
Caution: The indoor unit must be installed at least 2.4m(8ft) above floor or ground
level.
Warning: Risk of electric shock can cause injury or death: Disconnect all remote electric power supplies before servicing. There must be an air-break switch between indoor and outdoor unit which needs to be installed close to the indoor unit.
Part
Installation Instruction
1. Select the location for installation
1-1 Indoor unit
Must be placed on a rigid wall with no vibrations.
No obstacle in front of air intake and outlet vents, the distance between the top
of the unit and the ceiling should be at least 10cm (4 inches).
Place unit where the cold air can be blown evenly throughout the room.
The maximum distance between the indoor unit and outdoor unit is 5 metres;
the same distance must be respected for the height.
Avoid direct sunlight. Exhaust water must be easily drained.
The air filter must be installed or removed easily (there should be at least 20
cm of free space under the unit).
The distance between the unit and a television or a radio should be more than
1 metre (because the unit can disturb the images of the television and make some noise).
Page 16
15
The unit has to be more than 1 metre away from a fluorescent lamp or other
electric bulbs ( they could interfere with the remote control).
1-2 Outdoor unit
It should be installed in a well ventilated place that is protected from strong
winds.
It should not be exposed to direct sunlight and rain.
It should be installed where the operating noise will not disturb neighbours. It
should be placed on a solid base to avoid vibrations or noise.
Keep away from flammable gas.
If the unit is installed on a raised base make sure it is well secured.
2. Installation of Indoor Unit
As the unit is heavy, the wall should have sufficient strength and durability for operation of the air conditioner, and for prevention of any vibration or noise. If it is weak, reinforce­ment work should be performed prior to installation.
There should be more than 10cm of space all around while installing the indoor unit.
Tie a thin cord in the hole
More than 10 cm
More than 10 cm
More than 10 cm
Installation plate
The level can be obtained easily by aligning the hanging cord with the stripe of middle holes
Fix screw ST4 X 30
2-1Fix the wall-mounted plate
Page 17
16
2-2 Drill a hole in the wall
Select the location.
Drill a hole of approximately 6.5 cm diameter
Insert the wall-through sheath into the hole
Hole thru wall
Thickness of wall
Indoor
Wall-throughSheath
ø6.5 cm
We recommend that you do not use an extension cord or an adapter plug with this appliance. Do not change the plug on the power cord of this appliance.
The specification of the power wires and the connecting wires should respect the relative standards, the AWG size of connection cords between indoor and outdoor unit is 16 and for the power supply cord it is 14.(the one of KFR-70GWZ/BM is 12.)The connection of the wires must be done strictly according to the diagrams and connecting marks. Only the same marks can be connected together. The location of the connecting cables between the indoor unit and outdoor unit must be out of direct sunlight exposure.
2-3 Installation of the Power Source
W arning:
NEVER cut a power wire open. A wrong connection could cause major incidents. Do not use a damaged supply cord, it must be replaced to avoid an electric shock.
2-4 Installation of Drain Hose
Medium power connecting wire
Power bar
Indoor unit
The drain hose should be put below the refrigerant pipe (copper pipe)
Do not bend the drain hose or raise it.
Do not wrap the drain hose too tightly.
Page 18
17
The drain hose must be put below the copper pipe. Put to­gether the refrigerant pipe, drain hose and the connecting wire of indoor and outdoor units. Wrap them with binding belt. The pipes can be arranged towards five directions (back, right, left, down and left-back). Bind the pipes with binding belt from the place closest to the elbow (The overlap of the binding should be 1/2 of the width). Bind the pipes from 1 cm inside of the unit, if you direct the pipes from the left side.
2-5 Arrangement of Pipes
Front
Left
Left back
Down
Back
Right
Cut off this part directing pipes toward left side
1cm
Cut off this part when directing pipes to right side
Cut off this part when directing pipes down ward
Installation of Indoor Unit
Pass the pipes through the wall, hoist the unit on the installation plate and fix the lower part with a hook.
Install the wall-through bushing sheath at suitable place
Wall-through bushing
Attention! Do not raise the drain hose
Installation plate
Page 19
18
The outdoor unit should be installed on a solid base. (Such as concrete) If it is in­stalled against a brick wall, the thickness of the brick wall should be at least 10cm deep. If there is a vibration, please install the protective anti-vibration rubber spacer. Do not install the unit directly on the ground; the base has to be solid and resistant enough to support the weight of the unit. It has to be firmly fixed. The unit should not be installed on an angle greater than 50.
When installing the unit, be sure to leave a space of 50 cm in front, more than 10 cm behind, on top and on the left side of the unit and leave a space of 35 cm on the right side.
3. Installation of Outdoor Unit
3-1 Flared Joint
You will have a flared joint on both units (indoor and outdoor). As indicated on the diagram, the refrigerant pipe is used to connect the indoor unit and the outdoor unit.
Indoor unit
Outdoor unit
Refrigerant verification = If the length of the pipe is more than 5m, please refill the refrigerant (fleon R410A).
Pipe length
less than 5m more than 5m
need not to refill refrigerant need to refill refrigerant 50g/m
One of the major causes for a gas leak is due to a defective flared joint, so please verify the quality of the installation.
3-2 Pipe Joint
Page 20
19
1. pipe cutting Use pipe cutter to cut the copper pipe correctly
qualified
Copper pipe 90
Unqualified
Burr
tilted rugged
Copper pipe
Pipe cutter
2.remove burrs Get rid all the burrs of the pipes section.
Burr
3.install the nut Remove the connecting nut which is installed on the indoor unit and outdoor unit, after rid the pipe of burrs, install it on the pipe again.
Connecting nut
Copper pipe
4. Flare work Use the follow instruments to undertake flare work.
Die
yoke die
Copper pipe
Connecting nut
Tilted
Flare instrumen
5. Check Compare the flare work with the following diagrams. The flared part should be cut off and flared again if there are some deficiencies of the flare work.
Over flared
Even Broken Rugged
Copper pipe
External diameter(mm)
1/4 3/8 1/2 5/8
A(mm)
0.8~1.5
1.2~1.8
1.2~2.0
1.5~2.5
1. Connection of the indoor unit.
Connect the thick and thin pipes to the indoor unit.
Apply a thin coat of refrigerating oil on the pipes joints. When connecting, screw the centre and then screw the first 3-4 turns of the connecting nut by hand. Use the wring torque diagram as the standard of indoor pipe’s connection, use two spanners to tighten them; over-tightening will damage the flared joint
.
External diameter(mm)
1/4 3/8 1/2 5/8
Wring torque(kgfcm)
150~210 380~450 400~460 500~575
2. Connection of outdoor unit.
Proceed the same way as the indoor unit. Connect the pipes with the outdoor unit’s valve. Use a spanner to grip the valve and use the torque spanner to grip the connecting nut. Connect the pipe to outdoor unit with the same wring torque as used for the indoor unit.
Caution: Proper insulation thickness. If the insulation is too thick, it could cause an accumulation of water behind the indoor unit. If the insulation is too thin it could cause moisture and water dripping.
3-3 Drain Hose
To drain the water, please incline the drain hose downwards (diagram 1). Do not install as shown on diagram 2~5.
Page 21
20
3-4 Electric wire connection
L3 L4 S G
Indoor Electric parts
Air-break switch
L3 L4 S G
Outdoor Electric parts
Outdoor Encloser
Intdoor Evaporator
L1 L2 G
Outdoor Electric parts
Air-break switch
Power supply
Outdoor Encloser
The installation must be done as indicated on the diagram, connect the power wires according to the stipulated order and colors. The power wires between the indoor unit and the outdoor unit must be corresponding with each other (colour, order and diameter) The yellow-green wire is the ground­ing wire, it must be connected to an adequate electric power socket or it could cause an incident. After installation, the wires must be pressed tightly with the wire clip. Make sure the wires are attached solidly by pulling gently.
If the connecting wires are not long enough replace them with wires of same diameter and color.
Warning
:
The wires must be connected properly otherwise it could cause a short circuit.
If the drain hose installed on the indoor unit is not long enough, please connect as shown on the dia­gram to your right. If the drain hose needs pass through indoors, please wrap it with heat insulation materials which are avail­able at your local hardware store.
Incline downward
Do not raise the drain hose
Dripping
(1) (2) (3) (4) (5)
Dripping
air
The distance between the hose end and the ground is less than 5cm
The end of the drain hose is dipped into water
Drainage retention
Wave
Dripping
Page 22
21
4. Test Run
Make sure all the pipe joints have been screwed tightly, then clean the pipes and verify the vacuum. Remove the valve core copper caps of the high pressure valve and the low pressure valve. Remove copper cap of refrigerant-adding valve, measure the vacuum with the vacuum pump (value should be less than 10Pa) Close the copper cap of refrigerant-adding valve. Unscrew the high pressure valve and low pressure valve. Use the leakage detector or soapy water to check the system pipe joint and valve cap for leakage.
If there is no leakage, screw tightly the copper caps of valve cores
.
3-5 Installation of the exterior draining pipe
Insert the drainage pipe into the hole of the base, connect an extending pipe to drain the water.
Base hole of the outdoor unit catchment trough
4-1 Pipe-cleaning and vacuum verification
4-2 Test Run Procedure
Before testing, please check all the connecting wires and pipes carefully to see if they are correctly connected, verify if the stop valve is completely opened or closed, and if the air conditioner has been grounded correctly. Connect the air conditioner system to the power source, a “Du” sound emitted by the indoor buzzer should be heard. Turn the air conditioner ON with the remote control. Please choose the “heating” mode and set temperature at 25
0
C to check the heating
function. Please choose the “cooling” mode, set temperature at 16
0
C to check the
cooling function
Page 23
22
4-3 Instructions to Consumers
Remark
Check the following items according to the related contents of this manual.
Indoor unit : Is the noise abnormal? Does every indicating lamp function normally? Does it drain smoothly?
Outdoor unit: Is there abnormal noise or vibration when it is running? Does the noise and water drainage disturb the neighbours? Is there a gas leak?
The remote control: Do all the function keys work normally? When transmitting the signal, does the indoor unit emit a “Du” sound?
After installation, the service technicians are required to: Explain the operation methods, the key functions, and any other information included in this manual. Explain how to remove and install the filters and how to control the wind direction. How to place the batteries in the remote control. Advise the consumers to read this instruction manual carefully before operation, and answer the consumers’ questions.
Page 24
23
The above mentioned cooling and heating capacities are standard and may vary slightly in accordance with the ambient temperature.
Please use the unit for heating when the outdoor temperature ranges from –70C to 430C and for cooling when outdoor temperature ranges from 180C to 430C.
The air conditioner should be connected to its own separate circuit.
No notice will be given if there are changes in the data, please take the data on the unit’s name plate as the standard.
Note:
Data Model
Item
Type Cooling Capacity (Btu/h) Heating Capacity (Btu/h) Rated Voltage (V) Rated Frequency (Hz) Rated Cooling Power Input (W) Rated Heating Power Input (W) Mass:indoor unit/outdoor unit (lbs) Air Flow:indoor unit (m
3
/h) Design Pressure of High Side (PSI) Design Pressure of Low Side (PSI) Refrigerant:type/quantity (lbs)
Main Specifications
KFR-25
GWZ/BM
9000
10400
765 880
24/77
450 500 250
R410A/1.85
KFR-35
GWZ/BM
12000 13650
1075 1160
24/95
500 500 250
R410A/2.1
18000 19100
1670 1720
35/112
800 500 250
R410A/2.9
KFR-50
GWZ/BM
KFR-70
GWZ/BM
Cooling & Heating
230
60
24000 27000
2400 2550
37/150
1200
500 250
R410A/4.2
Page 25
Serial No.: eb45493 Version:090318
Loading...