Shimpo DT-501XD-FVT, DT-501XD, DT-501XD-CPT-FVC, DT-501XD-CPT, DT-501XD-TRT-FVC Instruction Manual

...
98211B
Digital Tachometer
Digital Tachometer/ Elapsed timecounter/ Time width meter/ Flowmeter
Standard input series Dierential input series
DT-501X/ DT-501F
Safety Requirements
Be sure to observe
Before operation, maintenance and inspection, please carefully read this instruction manual and follow it for proper use. Please carefully read all information related to this unit and safety, and precautions before use.
This instruction manual categorizes safety precautions as “DANGER”, “WARNING”, and “CAUTION”. Each of them is an important description related to safety. Be sure to observe.
Instruction Manual
Thank you for purchasing SHIMPO's Digital Tachometer DT-501X/ DT-501F. For instructions on how to use this product properly and optimally for a long period of time, please be sure to read this manual thoroughly before use.
When you purchase the product with optional equipment: Please refer to the operation manual of the optional equipment.
Before operation, maintenance and inspection, please carefully read this instruction manual and follow it for proper use.
After reading, be sure to store this manual in a safe, convenient place where operators can always refer to it easily.
!
CAUTION
Electric Shock. Be sure to turn the power OFF when wiring as well as inspecting the unit.
Failure to do so could result in electric shock.
DO NOT block the ventilation holes on the side of the main unit. DO NOT put any foreign objects or materials inside the unit through these holes.
Failure to follow this could result in abnormal heat generation and/or malfunctions.
DO NOT touch the unit with wet (or sweaty) hands when inspecting or for wiring.
Failure to do this could result in electric shock.
!
Precautions before use
Power
●Be sure to use the unit under the specied voltage (AC power specications: 85 - 264VAC / DC power specications: 10.8 - 25.2VDC).
●Inverter power source cannot be used.
Input signal wire
●Connection wiring from sensors shall not be kept in the same or parallel conduit or cable as the power source, power or high voltage cables. If you fail to separate the wiring, noise may be superimposed on the signal wire, resulting in malfunctions.
Use shielded wire for input power connections with the shortest possible metal conduit.
Terminal
Check that the screws have not come loose due to vibrations after a certain period of time.
Operating environment
●Do not install the unit in the following places or conditions.
●●Places exposed to direct sunlight, or places where the ambient temperature exceeds a range of 0 - 45ºC.
●●Places where the relative humidity percentage exceeds a range of 35 - 85%, or places subject to condensation due to rapid change in humidity.
●●Places subject to corrosive and/or combustible gases.
●●Places subject to a large amount of dust, salinity, and/or ferric substance.
●●Places susceptible to noise (including static electricity).
Improper use by neglecting the following
!
!
!
DANGER
WARNING
CAUTION
precautions may result in the potential for re, serious injuries, and/or death.
Improper use may result in serious injuries.
Improper use may result in minor injuries or property damage.
●Limited Warranty
● We are not responsible for damages resulting from negligence through failure to follow the instructions set out in this manual.
We are not responsible for damages resulting from earthquake and/or re unrelated
to us, actions by third parties, or any other accidents, intentional or through customer negligence, as well as from accidents caused by misuse or improper use under abnormal conditions.
● For information regarding assurance provisions, please read the attached warranty certicate.
INDEX
1. Installation to the Start of Operation
2. Unit Model
3. Specications
4. Component Part Names and Functions
5. External Dimensions
6. Installation to the Panel
7. Wiring to Power Source and Sensors (DT-501XA/DT-501XD)
9. Basic Setting Procedure
10. Keys to be Used for Various Settings and Their Applications
11. Teaching Function Settings
12. About Mode
13.
When You Select Mode 1 (Digital Tachometer Mode) for Measurement
14.
When You Select Mode 2 (Elapsed Timecounter Mode) for Measurement
15.
When You Select Mode 3 (Time Width Meter Mode) for Measurement
16.
When You Select Mode 4 (Flowmeter Mode) for Measurement
17.
Setting Method of Functions (Excluding in the Test Mode, Common in Each Mode)
18. Comparator Function
19. Memory Function
20. Test Mode (Function to Check if the Unit is Operating Normally)
21. Error Display
22. Parameter List
23. Function List
24. Option -FVT/-FVC
25. Option -BCD
26. Option -TRT
27. Option -CPT
28. DT-501X / DT-501F series model list
2
2
3
3
4
4
5
6
6
6
7
8
8
10
12
14
16
17
18
19
19
20
21
23
25
27
27
28
1
●1.
Installation to the Start of Operation
This unit is designed for use according to your measurement purposes. Before use, follow the procedures below from installation to the start of operation.
Check before use
Check before use p.2 - 4
• Unit model
• Specications
• Component part names and functions
• External dimensions
Memory function settings
(1) Press the MEM key once to display the MAX value. (2) Press the MEM key again to display the MIN value. (3) Press the MEM key once again
to display the normal measurement value. *You can use the unit without setting various functions.
p.17 - 19
Installation to the panel
View from the front
(1)
Installation of waterproof gasket
(2) Fixation to the panel
(action conguration)
Function settings
(1) Press and hold the SHIFT + FUNC keys for 5 seconds or more and start setting. (2) Press the
item, and press the ENT key to start changing the setting value. (3) Press the
another digit, and after changing the value using the
s
nish the setting value change. (4) After setting all functions, use the SET key to nish setting.
key to select the
s
key to move to
t
key, use the ENT key to
p.4
Panel
p.8 p.
16 -17
Connection with the power and sensor
View from the back
(1) Connection with the power (2) Connection with various sensors
p.5 - 6
Connecting wires
Parameter settings p.8 - 15
(1) Press and hold the SHIFT + PAR keys for 5 seconds or more and start setting. (2) Press the
item, and press the ENT key to start changing the setting value. (3) Press the key to move to another digit, and after changing the value using the
● key, use the ENT key to nish the setting value change.
(3) After setting all parameters,
use the SET key to nish setting.
key to select the
s
t
(function)
Mode
(1) Press the SHIFT + MOD keys and start setting. (2) Use the
the SET key to nish setting.
settings p.8 - 15
key to set, and use
s
Start of operation
●2.
Unit Model
Please check the model number of the equipment purchased.
501X
DT
501F
Power
Symbol Power
A AC power (85 - 264VAC)
D DC power (10.8 - 25.2VDC)
Input type
Symbol Input type
501X Standard input : Supports the sensor input, including rotary encoders, and magnetic sensors
501F(AC Power only) Dierential input Supports the line driver output, including AC servo motors
Option #2
Option #1
Symbol Output Function
FVT
CPT Relay Output
TRT Transistor Output Open Collector Output. HH, H, LL, L GO and ZERO output.
Teaching function settings
●Parameter settings are not necessary.
Symbol Output Power Source
FVC
Analog Signal Output
BCS Output
BCD
Analog Signal Output
Outputs voltage and current that correspond to displayed value
Open Collector, BCD Output Simple interface with the sequencer
Outputs voltage and current that correspond to displayed value
Relay Changeover contact output. H output, L output, and GO output, against the set value
P7
* HH : High set point 2 output
●●●●●H : High set point 1 output
●●●●● L : Low set point 1 output
●●●● LL : Low set point 2 output
Simple setting
2
●3.
Specications
Unit model DT-501X ● DT-501F
Action mode Digital tachometer mode Flowmeter mode Elapsed timecounter mode Time width meter mode
Display
Display 1
0 - 999999
6 digits
Display 2 -
0:00:00 - 9:59:59
(Hour:Minute:Second / base 60 display)
(Hour:Minute:Second / base 10 display)
0:00 - 999:99
0:00:00 - 0:59:59
(Hour:Minute:Second / base 60 display)
With zero suppression function
Decimal point position 0 to 5 digits after the decimal point(000000 ● 0.00000)
-
Number indicator Red 7 segment LED, Letter height 22mm, 6 digits, - display available
LED lamp 8 (SIG, LL, L, H, HH, MAX, MIN, TEA)
Operation key 5 ●SET/SHIFT ,MEM/TEACH , ● /PARA ,
/FUNC ,ENT/MODE●
Input range 0.0067Hz ● 100kHz 10ms - 3600s
Measurement accuracy ±0.008● ±1digit ±0.1● ±1digit
Filter
Note that you can switch between only 10kHz and 0.02kHz in a magnetic sensor, and its contact is only 0.02kHz.
Switches between 100kHz, 30kHz, 10kHz, and 0.02kHz using the parameter.
Display cycle 0.2, 0.5, 1, 2, 5, 10, 15, 30, 60 sec. (changeable in the parameter settings) Dependent on the input signal
Pre-scale function Parameter setting system using the front panel keys. The teaching (combination) of display values are also available.
Memory function
Comparator function
The maximum/minimum measurement values can be memorized and displayed in the indicator.
The settings of the high set point 1, low set point 1, high set point 2, and low set point 2, and judgment results can
be displayed on the LED lamp. The hysteresis setting of the high and low set point 1 values are also available.
(Switches the display using the MEM key)
Auto zero time 0.1 - 150 sec. 0.1 - 3600 sec.
Pre-arithmetic function Updates the displayed value according to the elapsed time after the pulse stops.
Teaching function
Performs scaling automatically by setting the display value with a certain signal input. (only in the tachometer and owmeter modes)
Insulation resistance 10MΩ or more (at DC500V Mega)
Voltage proof AC1500V or more 1min
Operating temperature 0 - 45ºC(No condensation)
Operating humidity 35 - 85%RH (No condensation)
Operating atmosphere No corrosive gas
Conforming standard RoHS
Protection function Front panel: IP66 (or equivalent), Rear terminal block: IP20
Casing material ABS resin
External dimensions ● 96 × ● 48 × ● 92 ● (DIN)
Weight
*There are the input specications in addition to the above specications. For details, refer to p.5 - 6.
●4.
Component Part Names and Functions
FVT● FVC● TRT● BDC options : + approx. 50g
Approx. 200g
CPT options : + approx. 100g
●Front
●●●●●●●●●●●● ● ●●●●●● ●
●●●●●●●●●●●●●● ●●
●Rear
●Side
Name Function
● SIG lamp Lights up when the sensor signal is input
● LL lamp Lights up when the low set point 2 is judged.
● L lamp Lights up when the low set point 1 is judged.
● H lamp Lights up when the high set point 1 is judged.
● HH lamp Lights up when the high set point 2 is judged.
● MAX amp Lights up when the maximum value is displayed
● MIN lamp Lights up when the minimum value is displayed
● TEA lamp Lights up when the teaching function is set
● PEAK lamp Not used
● BTM lamp Not used
● Unit label space Space for attaching the supplied unit labels
● Main display Displays the measurement value
● SET/SHIFT key
● MEM/TEACH key
● ●(UP)/PARA key
●●(NEXT)/FUNC key
● ENT/MODE key
Finishes the setting in various setting modes Pressing this key with other keys switches to various setting modes
Switches to the memory display Pressing this key with the SET key goes to the teaching setting mode
Changes the selected items in various setting modes, or numerical values Pressing this key with the SET key switches to the parameter setting mode
Changes the selected digit in various setting modes Pressing this key with the SET key switches to the function setting mode
Selects the changed item(s) in various setting modes Pressing this key with the SET key switches to the mode setting mode
● Terminal block
● Rear panel
● Terminal block cover 21
Mounting adapter
Unit label
cm
21
PS
kHz rpm
●:●:●
●:●●●
h
sec min rps Hz h:m:s sec min rps Hz
m●●
mm
●● h
●● s
10
m
min
min
h ℓ
min
r
●s
km h
m:s:●
min
mm min
cm
h
min
mm sℓ
m
km
min
h
PS
kHz rpm
m h
10
s
● h
ℓ min
r min
mm min
FVT CPT TRT FVC TRC
BCD RMT DRT SDT SDC
3
●5.
External Dimensions
●6.
Installation to the Panel
Mount this unit to the panel according to the following procedures. Check that the mounting panel is thick enough (1.0 - 5mm) before mounting operation.
Attach the provided waterproof gasket to the panel surface.
1
* If waterproong is not necessary, skip this step.
(1)
Remove the external frame with the cutting lines(backing paper + waterproof gasket) from the gasket sheet.
(Adhesive paste is applied on the both
of the waterproof gasket.)
sides
External frame (backing paper + waterproof gasket)
Backing paper (side with cutting lines)
Backing paper (side without cutting lines)
(2) Attach the provided waterproof gasket to
the edges of the unit attachment panel and opening, aligning with its left and right sides,
and then peel o the backing paper.
*
At this time, be sure not to displace or wrinkle the waterproof gasket. Also, do not expand the waterproof gasket vertically and/or horizontally past the attachment panel’s edges.
Adhesive part of the waterproof gasket
Unit attachment opening
Backing paper
●mm●
CAUTION
!
About waterproong
● Front panel: IP66 (or equivalent)
● Rear terminal block: IP20 (non-waterproof ) Do not install the unit in the following places or conditions. (1) Places regularly subject directly to water (2) Places subject to oil splashes and/or medical supplies (3) Places subject to water splashes on the rear or side face(s). * The front panel is IP66 (or equivalent) waterproofed, but if water is splashed on the unit, be sure to wipe it o the unit as soon as possible.
Place the unit horizontally, and insert the gasket into
2
the opening of the panel surface.
Push the unit until the waterproof gasket (adhesive part) securely reaches the panel surface of the unit.
Waterproof gasket
Panel
Attach the mounting adapter to the unit.
3
Slide the mounting adapter until it lightly touches the panel surface.
Mounting adapter
4
●7.
Wiring to Power Source and Sensors (DT-501XA/DT-501XD)
Note) In order to prevent electric shock, be sure to turn the power OFF. Be sure to use the unit under the rated voltage (AC power specifications: 85 - 264VAC / DC power specifications: 10.8 - 25.2VDC). The inverter output (output to connect a motor) cannot be used as power. Connection wiring from sensors shall not be kept in the same or parallel conduit or cable as the power source, power or high voltage cables. If you fail to separate the wiring, noise may be superimposed on the signal wire, resulting in malfunctions. Use shielded wire for input power connections with the shortest possible metal conduit.
For DT-501XA/DT-501XD
• Terminal block connection diagram
Sensor
Power 1 Power 2 Earth
power output
+12V
Pull-up
Open
collector
Voltage
input
Magnetic
sensor input
0V
1 2 3 4 5 6 7 8 9 10
NC
● Wiring requirements
●●Use M3 crimp-style terminals with a width of 7 mm or less to connect wires to the terminal block.
● After wire connection to the terminal block is completed, be sure to attach the provided terminal block cover.
PWR1 PWR2 E PU
AC power
85 - 264V
DC power
10.8 - 25.2V
-
+
* Model AC power specications: DT-501XA DC power specications: DT-501XD
+12V
Shield wire
Earth
OC
MG
RE
V
oltage output sensor
NPN open collector sensor
(Adjacent switch, gear sensor, rotary encoder)
DC 2-wire sensor
NPN open collector sensor
●adjacent switch●
GND
Magnetic sensor
Relay switch
CAUTION
!
Be sure to connect the power wires to the 1st and 2nd terminals. Incorrect connection could result in damage and/or burns to the unit.
• Input specications • Connection list with sensors
Item Description
Power
AC (DT-501XA) 85 - 264VAC(50/60Hz)
DC (DT-501XD) 10.8 - 25.2VDC Consumption power 10VA Sensor power output DC+12V Max.100mA
Open collector (NPN) input
Open collector input
LO input
Load capacity 12mA or more
0 - 3V HI input Leakage current 0.5mA or less Maximum frequency
(Minimum pulse width 5micro second●
100kHz For no-voltage contact. Short-circuit ● and ● to use.
Contact input
Contact capacity Voltage 12V, Current 15mA or more Maximum frequency
(Minimum pulse width 25micro second●
20Hz LO input 0 - 1.5V
Voltage input
HI input 4.0 - 30V Input resistance Maximum frequency
10kΩ
30kHz
(Minimum pulse width 17micro second●
Input resistance 10k Ω
1Hz ● 100Hz 0.3 ● 30Vp-p
Magnetic sensor input
Input voltage
● 1kHz 1.5 ● 30Vp-p
● 10kHz 6 ● 30Vp-p
Note) Magnetic sensors cannot be used in the time wide meter mode (mode 3).
Maximum frequency
(Minimum pulse width 50micro second●
10kHz
The table below shows the sensors and connection terminal No. to be applied according to the input signal type.Check using the connection diagram on the left.
Input signal type Sensor
Contact signal Relay switch 5-6-9 Open collector Adjacent switch SE-P12-1 4-6-9
Adjacent switch SE-P12
Square wave
Gear sensor SE-G2
Note 1) Connect sensor wires to the specied terminals, and be sure to leave theother terminals empty. More than one sensor cannot be connected simultaneously. Note 2) When one sensor is connected to more than one tachometer, supply the power for the sensor from one of them.
Our product model
Connection terminal
4-7-9Rotary encoder RE-1-●F
• Input circuit
Open collector sensor
Voltage output sensor
Example of external connection
NPN open collector sensor
Example of external connection
Example of external connection Example of external connection Example of external connection
NPN voltage output sensor
PNP voltage output sensor
DC 2-wire sensor
PNP open collector sensor
Relay switch
Magnetic sensor
5
Example of external connection
Example of external connection
Relay switch
Magnetic sensor
●8.
Wiring to Power Source and Sensors (DT-501FA)
Note) In order to prevent electric shock, be sure to turn the power OFF. Be sure to use the unit under the rated voltage (AC power specifications: 85 - 264VAC). The inverter output (output to connect a motor) cannot be used as power. Connection wiring from sensors shall not be kept in the same or parallel conduit or cable as the power source, power or high voltage cables. If you fail to separate the wiring, noise may be superimposed on the signal wire, resulting in malfunctions. Use shielded wire for input power connections with the shortest possible metal conduit.
For DT-501FA
• Terminal block connection diagram
Sensor
Power 1
Power 2 Ear th
power output
+12V
No connection No connection
Dierential
input +
Dierential
input -
0V
1 2 3 4 5 6 7 8 9 10
No connection
● Wiring requirements
● Use M3 crimp-style terminals with a width of 7 mm or less to connect wires to the terminal block.
● After wire connection to the terminal block is completed, be sure to attach the provided terminal block cover.
PWR1 PWR2 E NC NC
Earth
AC power
85 - 264V
* Model AC power specications: DT-501FA
DIF+
DIF-
Dierential output
NC
GND+12V
• Terminal block connection diagram
Item
Power AC (501FA) 85 - 264VAC(50/60Hz)
Consumption power
Sensor power output
Dierential input
●9.
Basic Setting Procedure
10VA DC+12V Max.100mA
Connection to Dierential line driver AM26LS31 etc.
Dierential input voltage
Maximum frequency
Description
DIF+
DIF
V
DIF-
Maximum voltage±5.5V(15mA)
DIF
V
Minimum voltage
(Minimum pulse width 5micro second●
100kHz
±3.0V
Conduct settings as indicated below based on the intended use.
CAUTION
!
Be sure to connect the power wires to the 1st and 2nd terminals. Incorrect connection could result in damage and/or burns to the unit.
• Line driver input circuit
Example of external connection
Line driver
Parameter settings
2
Mode (function) settings
1
Refer to p.8 - 15.
Refer to p.8 - 15.
Teaching function settings
2
Function (action configuration)
3
settings
Refer to p.16 - 17.
Refer to p.7.
Conduct the comparator function p.17 and memory function settings p.18, if necessary. This unit requires no complicated calculation, and implements the teaching function which enables optional changes of display values and error compensation. (excluding the elapsed timecounter and time wide meter modes)
10.
Keys to be Used for Various Settings and Their Applications
The front panel keys to be used for mode, parameter, and function settings, as well as various settings (teaching function / high and low set point 1 value setting / memory function) are described below.
• Operation during the normal measurement display / memory display
Name Function
SHIFT key MEM key
● TEACH key Pressing and holding this key with the SHIFT key for 5 seconds switches to the teaching setting mode
PARA key
FUNC key
MODE key
Pressing this key with other keys switches to various setting modes Switches to the memory display
Pressing and holding this key with the SHIFT key for 5 seconds switches to the parameter setting mode Pressing and holding with the SHIFT key for 5 seconds switches to the function setting mode Pressing and holding this key with the SHIFT key for 5 seconds switches to the parameter setting mode
• Operation in the various setting modes
Name Function
● ● ● ● ●
● SET key Setting completion key in various setting modes
(UP) key Changes the selected items in various setting modes, or numerical values
s
●(NEXT) key Changes the selected digit in various setting modes
t
● ENT key Selects the changed item in various setting modes
Measurement start
6
●11.
Teaching Function Settings
When you can check (measure) the actual revolution speed, the following simple method (teaching function) can be used. The teaching function requires no complicated calculation.
● The teaching function is supported only in mode 1 and mode 4. Mode 2 and mode 3 have no teaching function.
● Setting method
1 0
SHIFT + MEM keys
5 seconds elapsed
Teaching function setting mode
TEA
When you press the SHIFT + MEM keys simultaneously during the normal measurement display, the main display blinks.
●●●●●●●●●●●●●●●●●●●●●●●●(TEA lamp lights up)
The measurement value which was displayed before is displayed in the main display. In the initial status, the digit on the left blinks. Because the value in the blinking digit can be
0 0 0 0 1 0
Use the
key
to select the digit
TEA
0 1 0 0 1 0
key to
Use the ●
select the value
TEA
0 1 0 0 1 0
Use the SET key to
nish the setting
Returns to the normal measurement display
changed, use the Every time you press the digit”, and “decimal point”, then back to “1st digit”.
After selecting the digit you want to change, use the
When you select the decimal point, use the
When the numerical value setting is complete, press the SET key to finish the teaching setting. The teaching setting result is reflected, and the display returns to the normal measurement display.
key to select the digit in which you want to change the value.
t
key, the digit blinks in the order of “1st digit”, “2nd digit”, ... “6th
t
key to change the value (0 - 9).
s
key to change the decimal point position.
s
0 1 0 0 1 0
● Teaching function details
• Mode 1
The teaching function can be used to automatically change the value of parameter items (P2, P3), and calculate the present measurement value from the teaching setting value as below.
External input pulse (Hz) A
Parameter setting value
Display calculation formula
When the input revolution speed is outside the input revolution speed range, “EE-2” is displayed, and the teaching function cannot be used.
During normal display
P1●Pulse count per revolution B P2●Setting revolution speed (detection section) P3●Value to be displayed D
{ (A/B) * 60 } * (D/C)
Input pulse (Hz) in the teaching setting A Teaching function setting value F
C
Parameter setting value
Display calculation formula
When the teaching function is executed
P1●Pulse count per revolution B P2●Setting revolution speed (detection section) P3●Value to be displayed D = F
{ (A/B) * 60 } * (D/C)
C = A * 60(Hz)/ B
Input revolution speed range : 1rpm ● Input revolution speed* ● 99999rpm
●●●●●●●●●●●●●●●●●●●●●●
* The P2 calculation value is maintained by rounding o fractions after the decimal point.
Depending on input and teaching setting values, the teaching setting value for the input at the time might not be displayed.
*Input revolution speed = A × 60(Hz) / B
• Mode 4
The teaching function can be used to automatically change the value of parameter items (P3, P4), and calculate the present measurement value from the teaching setting value as below.
External input pulse (Hz) A
Parameter setting value
Display calculation formula
When the input frequency is outside the input frequency range, “EE-2” is displayed, and the teaching function cannot be used.
Input frequency range●: 1Hz
*
The P3 scaling value maintains values after decimal point up to 7 digits inside. Note that because the number of digits after decimal point that can be maintained in the parameter setting is up to 5, values in 5 digits or more after decimal point will be rounded o when you enter the value in the parameter setting. * If the P3 calculation value exceeds 999999, the P3 value will be forced to be “999999”.
Mode 4 Display value calculation
Number of blades per
P1
revolution P2 Capacity per sensor blade C P3 Scaling D P4 Decimal point display
●A * B● * C * D
●●●A●●●
Input pulse (Hz) in the teaching setting A Teaching function setting value F
B
Parameter setting value
E
Display calculation formula
99999Hz
Mode 4 Display value calculation
Number of blade per
P1
revolution P2 Capacity per sensor blade C P3 Scaling D = F/ (A * B * C ) P4 Decimal point display Decimal point position of E = F
●A * B● * C * D
B
7
●12.
About Mode
DT-501X/DT-501F have ve modes (functions) which can be selected according to the measurement purpose.
Mode
No.
99 Test Mode Executes the self diagnosis p.19
* The mode 1 (digital tachometer mode) is set in the factory setting.
Mode description Details
1 Digital Tachometer Mode* Digital tachometer / used as speedmeter●Displays the proportional value to the input p.8 - 9 2 Elapsed Timecounter Mode Used as the elapsed time display in a certain period●Displays the inversely proportional value to the input p.10 - 11 3 Time Width Meter Mode Measures time for the period when the signal is ON (or OFF) and displays it p.12 - 13 4 Flowmeter Mode Displays the instantaneous ow amount p.14 - 15
for the setting method
For the lists of parameters and functions to be set in each mode, refer to pages 20 and 21.
Page No.
Setting Method
13.
When You Select Mode 1 (Digital Tachometer Mode) for Measurement
Digital tachometer mode
Set each setting item for mode and parameter according to the following procedures. (For the setting method of functions, refer to pages 16 and 17.)
● Setting example (for measuring the peripheral speed of the roller)
As in the gure on the left, the rotary encoder is connected to the feed roller via coupling in the paper manufacturing process. To display the peripheral speed (m/min.) of the feed roller in DT-501under the following conditions:
[Conditions]
● Servo motor (pulse input)
● Diameter of the feed roller
● Peripheral speed of the roller diameter of 90mm ●
●0.09m×3.14)×500rpm ● 141.3m/min
Circumference
●●●●
of the roller
Revolution speed*
*Suppose that the revolution speed in the detection section is 500rpm because the revolution speed is not instructed.
● Setting method (1) Mode
• When you select mode 1 (digital tachometer mode) for measurement (The digital tachometer mode is set in the factory setting.)
Normal display
The main display shows “0”.
0
Mode setting
Finish setting
Note) If you change the mode settings, each parameter and function setting value will return to the factory default setting value.
Press and hold the SHIFT + MODE keys for 5 seconds or more. The main display shows the current set mode No. after blinking.
* When you are setting for the rst time after the
purchase of this unit, mode 1(digital tachometer
mode) in the factory default setting is displayed.
Press the SET key. The display goes to mode 1 (digital tachometer mode).
- 0 1 -
0
The numerical value does not need to be changed and you can proceed to the next step. * Every time you press the
the mode No. switches.
s
(2) Parameter
Parameter setting items in mode 1 (digital tachometer mode) nd numerical values to be set according to the above example
No. Setting item Setting range
Pulse count per revolution
P1
Revolution speed in the
P2
detection section Value to be displayed
P3
(with decimal point)
P4 Display cycle
P5 Auto zero time 0.1 - 150 sec. _ _ 006.0 6.0 sec. 6 sec. Measure using the default setting value as no special instruction is provided.
P6 Input lter 10/30/100/0.02kHz _ 10_ 10kHz 30kHz As the rotary encoder is used as a sensor, select "30".
* For the description about the parameter functions, refer to page 20.
1 - 9999p/r _ _ 0001 1p/r 600p/r Enter the pulse count of the rotary encoder.
1 - 99999rpm _01000 1000rpm 500rpm Enter some numerical value as the revolution speed is not instructed.
0.00001 - 999999 001000 1000 141.3 Refer to the above "Setting example".
0.2/0.5/1.0/2.0/
5.0/10/15/30/60 sec.
Default setting value
Display Description
_ 1.0 _ 1 sec. 1 sec. Measure using the default setting value as no special instruction is provided.
Numerical value to be set according to the above example
8
key,
● Mode 1 (digital tachometer mode) Display value calculation equation
Mode 1 Display value calculation
External input pulse (Hz) A
P1 Pulse count per revolution B
Parameter setting
Equation ●(A/B)
P2 P3 Value to be displayed D
Revolution speed in the detection section(rpm)
*
*
60)
(D/C)
C
• Start setting according to the setting example on the previous page.
Parameter setting
Press and hold the SHIFT + PARA keys for 5 seconds or more to switch to the parameter setting mode.
0 1 - P 0 1
Parameter 1 setting
Parameter 2 setting
Parameter 3 setting
Parameter 4 setting
Parameter 5 setting
Parameter 6 setting
Press the ENT key and start setting parameters. (The main display shows t merical value of each parameter.)
Every time you press the key, the display switches to the next pa rameter.
Every time you press the ● key, the display switches to the next parameter.
he current set nu
s
0 0 0 1
--
-
0 1 0 0 0
-
-
0 0 1 0 0 0
2. 0-
-
0 1 0. 0
--
0 1 0. 0
Use the key to move to another digit
t
s
Use the key to change the numerical value to “600”. Use the ENT key to nish setting.
Use the
key to move to another digit
t
Use the key to change the numerical value
s
to “500”. Use the ENT key to nish setting.
t
key to move to another digit
Use the
s
Use the key to change the numerical value to “141.3”. Use the ENT key to nish setting. (Use the use the key to change its position.)
Every time you press the ● key, the display switches as below.
Select "1.0" and use the ENT key to nish setting.
Use the key to move to another digit Use the key to change the numerical value to “6.0”. Use the ENT key to nish setting. (Use the use the key to change its position.)
Every time you press the key, the display switches as below.
Select "30" and use the ENT key to nish setting.
key to select the decimal point, and
t
s
0.2 > 0.5 >1.0 >2.0 >5.0 60●<●30●<●15●<●10
t
s
key to select the decimal point, and
t
s
s
●10 > 30 >100 > 0.02
●●●●●●●●●●●●
--
-
-
--
-
0 6 0 0
5 0 0
1 4 1. 3
1. 0-
6. 0
3 0
---
Press the SET key.
Finish setting
*If you enter a value outside the setting range, all the input values will blink, which indicates the setting is disabled.
●When this occurs, you cannot switch to other displays until you enter a value within the setting range.
The display goes to mode 1 (digital tachometer mode).
0. 0
(3) Function (For the setting method, refer to pages 16 and 17.)
• Function setting item in mode 1 (digital tachometer mode)
No. Setting item Setting range Input range Default value
F1 High set point 1 value Sets the high set point 1 value 000000 - 999999 0 F2 Low set point 1 value Sets the high set point 1 value 000000 - 999999 0 F3 High set point 2 value Sets the high set point 2 value 000000 - 999999 0 F4 Low set point 2 value Sets the low set point 2 value 000000 - 999999 0
Hysteresis of the high and
F5
low set point 1 values
Judgment output timer at
F6
startup
F7 Minimum revolution speed Sets the revolution speed to be displayed as zero 000000 - 999999 0
Frequency of the moving
F8
average
F9 Pre-arithmetic function
* For the description of functions, refer to pages 21 and 22.
Sets the hysteresis of the high and low set point 1 values
Sets the time when the comparator judgment is output at startup
Used when variation of the revolution speed is large and a stable display cannot be attained
Promptly performs the deceleration display when the signal is lost
0 - 99 0
0 - 99 sec. 0 sec.
0(disabled)/1(3 times)/2(10 times) 0(disabled)
0(disabled)/1(enabled) 0(disabled)
9
Loading...
+ 19 hidden pages