Shenzhen 1106, 1106L, 1110, 1110L, 3110L User Manual

...
Page 1
XPC series 6-20KVA online UPS
Shenzhen JFY Tech Co.,Ltd
Page 2
Page 3
Thank you for using JFY product
Page 4
Safety notes
Operating safety
1. Read safety notes carefully and thoroughly before operation, ensure the
proper usage and save this manual properly.
2. Pay attention to alarm table on the UPS and operate following it.
3. Avoid installing the UPS near water or in excessive humidity.
4. Avoid installing the UPS where it would be exposed to direct sunlight or
nearby heater.
5. The UPS must be stored in a location with good ventilation and ensure
enough space on each side for ventilation.
6. No liquid or spray detergent to clean the UPS.
7. Use powder fire extinguisher in the event of fire occurring in the vicinity. Liquid fire extinguishing agents may causes electric shock.
Electric safety
1. UPS has provided earthed terminal, in the final installed system
configuration, equipotential earth bonding to the external UPS battery cabinets, connect the earth before connecting to the building wiring terminal.
2. Before moving or re-wiring the UPS, please disc onnect the ma ins source and
make sure the UPS is completely shut down. If not, the o utput terminal may be electrically live that may causes electric shock.
3. Please use fitting and accessories appointed by JFY.
4. To meet the requirement of EMC, the length of output line should be less
than 40m distance.
Battery safety
1. B attery should be replaced periodically to ensure normal UPS operation and
adequate autonomy time because of high ambient temperature shortening the battery lifetimes.
2. Battery should be managed by professional personnel.
3. Do use the same type and same number of batteries in replacement.
4. In ca se of electrical shock and high short circuit current, please observe the
precaution as follows:
A. Remove watches, rings, or other metal object from the hands; B. Use tools with insulated handles; C. Wear rubber gloves and boots; D. Do not lay tools or metal parts on top of batteries; E. Disconnect the load before operate the terminal of battery.
5. Do not attempt to dispose of batteries by burning them. This could cause
battery explosion. The batteries must be rightly deposed according to local
Page 5
regulation.
6. Do not open or destroy batteries. Escaping electrolyte can cause injury to the
skin and eyes. It may be toxic. If electrolyte comes into contacting with the skin, wash the affected area with plenty of clean water immediately and go to the hospital for a check.
7. Do not make the positive and negative terminals of the battery short circuit;
otherwise it may cause electric shock or fire.
Maintenance
The operating environment and storage method are two key factors affecting the lifetime and reliability of the UPS. Hence, it is advisable not using the device in the following environments:
1 Where the temperature and relative humidity are outside the
specifications (temperature: 0-40, relative humidity: 20-90%).
2 Where vibrations or shocks are existing. 3 Dust, corrosive agents or salts or inflammable gas are present.
If the UPS will remain idle for a long period, it must be stored in a dry environment. The storage temperature should range from -25-55 (without battery). Before power on the UPS, set the ambient temperature over 0 and keep more than 2 hours.
Page 6
Safety notes
1 Introduction…………………………………………………………………………… 1
1.1 Sign explain ………………………………………………………………… 1
1.2
Front view……………………………………………………………………… 2
1.3
Back view…………………………………………………………………… 2
1.4
Technical data ………………………………………… ……… …………… 4
2 Installation …………………………………………………………………………… 5
2.1
Unpacking and check ……………………………………………………… 5
2.2
Cable list ……………………………………………………………… 6
2.3
UPS Connecting …………………………………………………………… 6
2.4 Installation for long backup model ………………………………… 8
2.5 Connect to the RS232 communication port ……………………… 9
2.6
Parallel card (Optional)……………………………………………… 9
2.7
Installation of the intelligent card …………………………………… 13
2.8
EPO ……………………………………………………………………………… 14
2.9 Maintenance switch ……………………………………………………… 15
2.10
Dust-proof net (Optional) ……………………………………………… 16
2.11
Isolation transformation box (Optional) ………………………… 16
3 Control Panel ……………………………………………………………………… 16 4 Operation ………………………………………………………………………… 17
4.1 Start up ……………………………………………………………………… 17
4.2
Shut down …………………………………………………………………… 21
5 Battery Maintenance. …………………………………………………………… 23 6 Trouble Shooting………………………………………………………………… 24 7 Signification of Fault code ……………………………………… 26 8 JFY-tech Contact Information ……………………………………………… 27
- 5 -
Page 7
1 Introduction
This series UPS is a advanced on-line sine wave uninterruptible power system with parallel redunda ncy function and t he maintenance swi tch is optional. Pr ovide a high quality AC power for your precision equipment with a wide range of application. It’s ideally suited for computer equipment, communication system, industry automatic control equipment. Because of the on-line design, the input voltage always would be adjusted and filtered differing from backup UPS. When power outage, battery will supply the load without transfer time. When over load or
fault of inverterUPS will turn t o bypass mode and supplied by the utility power. At the time of eliminating over loadUPS will automatically turn to supplied by
the inverter. This manual is suitable for XPC series produces as follows:
1106inner battery normal model 1106Lexternal battery long backup model 1110inner battery normal model 1110L:external battery long backup model 3110L3 phase in, 1phase out, external battery long backup model 3115L3 phase in, 1phase out, external battery long backup model
3120L3 phase in, 1phase out, external battery long backup model
Meanwhile each model can be divided into normal and professional version for user choice. Professional version is added with EPO switch and manual
maintenance switch, please check 2.8, 2.9 section
1.1 Sign explain
Sign Meaning
Equipment grounding conductor
Attention
Danger
AC DC
Do not dispose of unsorted waste
- 1 -
Grounding (Earth )
Recycling
Over load
Battery
ON/OFF button
Page 8
1.2 Front view
1106L/ 1110L
1106/ 1110/ 3110L/ 3115L/ 3120L
1.3 Back view
1106
1110
- 2 -
Page 9
1106L
1110L
RS232 communication port
Intelligent slot Direct current fan
3310L
Parallel port covered (optional)
3315L/ 3320L
Input circuit breaker Maintenance switch covered (only available for professional model) Input/Output terminal covered Cable shelf EPO (only available for professional model)
Notice: the views are available for the normal and professional model.
- 3 -
Page 10
1.4 Technical data
Model 1106 1106L 1110 1110L 3110L 3115L 3120L
Size(W×L×H)
mm
WeightKg
Power
Rated capacity
Input
Voltage Range
*Max Current
Frequency 46Hz~54Hz
Power factor 0.99 0.95
Output
Rated voltage
Current 27A 45A 68A 91A
Frequency
Power factor 0.8
248× 500×
616
57 20 59 21 27 35 35
6KVA
4.8KW
33A 37A 55A 59A 86A 112A
240× 500×
460
6KVA
4.8KW
46Hz~54Hz(On line modefollow ut ility power )
248× 500×
616
10KVA
8KW
120VAC275VAC
220VAC×1±1%
50Hz×(1±0.1%)(Battery mode)
240× 500×
460
10KVA
8KW
10KVA
8KW
248× 500×
616
15KVA
12KW
20KVA
16KW
Over load
ability
Peak Factor 3:1
THD THD<2% (linear load)
Battery(High ambient temperature and deep discharge will shorten the battery life
Backup time
Charge time
105%125%, After 1 minutes turn to bypass mode, After 30 minutes turn
off output; 125%135%, After 30s turn to bypass mode. After 1 minutes
turn off output; >135%, After 0.1s turn to bypass mode
4 minutes (full load)
7 hours
charge to
90%
Depend on
external
battery
Depend on
external
battery
4 minutes (full load)
7 hours
charge to
90%
Depend on external battery
Depend on external battery
* Max current is when the UPS working with 187V DC input, full load output, full load charge.
- 4 -
Page 11
Model
EMC
ESD IEC61000-4-2 Level 4
RS IEC61000-4-3 Level 3
EFT IEC61000-4-4 Level 4
Surge IEC61000-4-5 Level 4
Operation
temperature
Storage
temperature
Humidity 20%-90% (non condensation)
Altitude <1000m
Height (m) 1000 1500 2000 2500 3000 3500 4000 4500 5000
Capacity rate 100% 95% 91% 86% 82% 78% 74% 70% 67%
1106 1110 1110L 3110L 3115L 3120L
0-40
-25-55
Attention: when UPS worked in the height over 1000m, the output rated power
must be decrease progressively referring to the above table.
2Installation
Danger: Be careful when installation before cutting off AC power switch or
cutting of the battery input for long backup model.
Attention: >> Installation and wiring must be performed in accordance with the
local electric laws/regulations and execute by professional personnel.
>> Advise to be used on ground
2.1 Unpacking and check
Accessorya. One user manual b. Terminal
NOTE: Before installation, please inspect the unit. Be sure that nothing inside the package is damaged during transportation. Do not turn on the unit and notify the carrier and dealer immediately if there is any damage or lacking of some parts.
Recycling: please save the original package for future use.
- 5 -
Page 12
2.2 Cable list
Attention: Cable’s diameter and wire’s CSA depend on UPS rated power.
In the following chart, L means L1, L2, L3 for the 3 phase model.
MODEL
IN PUT
G N L
BATTERY
+
- G
OUT PUT
L N G
1106 1106L 1110 1110L 3110L 3115L 3120L
10AWG
2
(6mm
)
10AWG
2
(6mm
)
10AWG
2
(6mm
)
10AWG
2
(6mm
)
10AWG
2
(6mm
)
10AWG
2
(6mm
)
10AWG
2
(6mm
)
10AWG
2
(6mm
)
10AWG
2
(6mm
)
10AWG
(6mm
2
)
10AWG
(6mm
2
)
10AWG
(6mm
2
)
10AWG
(6mm
2
)
10AWG
(6mm
2
)
10AWG
(6mm
2
)
10AWG
(6mm
2
)
10AWG
(6mm
2
)
10AWG
(6mm
2
)
8AWG
(10mm
8AWG
(10mm
8AWG
(10mm
8AWG
(10mm
8AWG
(10mm
8AWG
(10mm
8AWG
(10mm
8AWG
(10mm
8AWG
(10mm
2
)
2
)
2
)
2
)
2
)
2
)
2
)
2
)
2
)
8AWG
(10mm2)
8AWG
(10mm2)
8AWG
(10mm2)
8AWG
(10mm2)
8AWG
(10mm2)
8AWG
(10mm2)
8AWG
(10mm2)
8AWG
(10mm2)
8AWG
(10mm2)
8AWG
(10mm2)
8AWG
(10mm2)
8AWG
(10mm2)
8AWG
(10mm2)
8AWG
(10mm2)
8AWG
(10mm2)
8AWG
(10mm2)
8AWG
(10mm2)
8AWG
(10mm2)
6AWG
(25mm
6AWG
(25mm
6AWG
(25mm
6AWG
(25mm
6AWG
(25mm
6AWG
(25mm
6AWG
(25mm
6AWG
(25mm
6AWG
(25mm
2
)
2
)
2
)
2
)
2
)
2
)
2
)
2
)
2
)
6AWG
(25mm
6AWG
(25mm
6AWG
(25mm
6AWG
(25mm
6AWG
(25mm
6AWG
(25mm
6AWG
(25mm
6AWG
(25mm
6AWG
(25mm
2
)
2
)
2
)
2
)
2
)
2
)
2
)
2
)
2
)
2.3 UPS Connecting
- 6 -
Page 13
Danger: Ensure the power cable with circuit breaker protection, and pay attention to
the capacity, if not, may destroy AC switch. (MAX input current refer to 1.4 technical data)
Please refer to 2.2 cable list to choose the fit input & output cable Remove the cover plate of terminal tierConnect output cable to the output terminal
Connect input cable to the input terminal Connect battery to the battery terminal (only for long-backup model)
Use tie across truss rope shelfUse tie truss input, output, battery input cable Put back t h e cover pl ate
Make sure connection be correctthen switch on AC powerPut UPS input
switch “ON”then UPS work normally
Danger:Please ensure the fastness of connection.
Input & Output terminal for single phase model:
1106/1110 1106L/ 1110L
Input & Output terminal for three phase model:
3110L/ 3115L/ 3120L
- 7 -
Page 14
g
2.4 Installation for long backup model
The long backup model (except for special model with 20pcs battery) with battery voltage 192VDC can be connected with 16sets battery, battery can be paralleled with many groups; Special model with battery voltage 240VDC can be co nnected with 20sets battery, batt ery can be paralle led with many groups. In case of electric shock, please observe strictly the following procedure:
1) Turn off battery switch “OFF”, with suitable series battery.
2) Choose the fit battery cable to connect battery and UPS (refer to 2.2 Cable list).
Between UPS and battery must ha ve a DC breaker, whose voltage and current must be in th e range of UPS as follows:
16 pcs battery 192VDC
MODEL
Bat voltage Bat current
20 pcs battery 240VDC
MODEL
Bat volta
Bat current
3) Before connecting to the UPS, Ensure no load connected. After connection turn on battery switch “ON”, switch on AC, the UPS begin to charge for battery.
e
DangerDo not connect the cable to the UPS first. Otherwise, it maybe causes the
hazard of electric shock.
1106(L)
192VDC
34A. max
1106(L)
240VDC 240VDC 240VDC
27A. max 45A. max 45A. max 68A. max 91A. max
192VDC 192VDC
1110(L) 3110L 3115L
192VDC
3120L
192VDC
56A. max 56A. max 83A.max 112A. max
1110(L) 3110L 3115L
240VDC
3120L
240VDC
Attention: the battery ground with logo is on the right side of main case terminal
tier
.
- 8 -
Page 15
2.5 Connect to the RS232 communication port
RS232 communication port: connect the UPS and the monitor The RS232 communication cable conncet to the serial port of the computer The RS232 communication cable conncet to the RS232 communication port of
UPS.
The DIN configuration of the RS232 interface port on UPS is as following
2.6 Parallel card(Optional)
Redundancy ntroduce
N+X is the now dependable power supply structure. N is indicate the least number of UPS all the load need; X is indicate the redundancy number of UPS that can be suppoted by the system. More bigger of X, more dependable of the system. N+X is the best solution for the high dependable situation. Just with parallel card and data line, it can be paralleled with maximum 3 UPS.
Parallel installation
Parallel function is optional. You can buy parallel fittings by yourself (including parallel card and data line) . customer service staff will install to ups, The max number of parallel is 3, Parallel UPS must have independent batt ery.
- 9 -
Page 16
Remove the cover plate of parallel , install data line
1) Parallel card is between of ups`s communication port,with parall el ca rd,use
the data Line successively connection
2) All of UPS output cable connect to a connection tray, Then use the connection
tray to load
Attention: Output cable require:
If the distance between ups to load less then 20m, require every UPS output cable length disparity under 20%; If the distance between ups to load over then 20m, require every UPS output cable length disparity under 10%.
3) Parallel UPS terminal tier input, output connection, as under picture, input,
output cable follow single UPS match cable require.
- 10 -
Page 17
- 11 -
Page 18
p
p
p
p
p
Ground
Output
Battery3#
Battery 2#
Battery 1#
ut GND
In
ut N
In
ut L3 phaseInput L3 phase
In
ut L2 phase
In In
ut L1 phase
- 12 -
Page 19
4) operation explain
General operation must follow the one of single upsParallel UPS with AC turn on: switch on AC, only press anyone of ups, the
other UPS will turn on at the same time, Then UPS turn to bypass model; Battery mode turn on: Firstly short press every ups on/off button, UPS start building assist power supply, Then long press anyone of ups, The other UPS will turn on at the same time, all ups will work on battery mode.
Par allel ups turn off: press and hol d on/off button of anyone ups more t han 4S
(the buzzer will beep twic e), then parallel ups shut down; press and hold on/off button of anyone ups button more than 1S, less than 4S (the buzzer will beep twice), then single ups shut down.
Attention: long press is more than 1s, short press is less than 0.5S.
2.7 Installation of the intelligent card
You don’t need to stop the UPS during the installation of communication card.
1) Remove the cover plate of slot
2) Insert the intelligent card into the slot
3) Secure the intelligent card wi th two screws.
SNMP card (Optional)
Be located of back panel intelligent card slot, Supply the SNMP allow data
- 13 -
Page 20
AS400 card (Optional)
Only need Insert AS400 (Optional) card into the intelligent card slot, Immediately realize use AS400 system monitoring UPS, manage the power supply. PIN explain:
PIN Meaning
PIN1 PIN2 PIN3 PIN4 PIN5 PIN6 PIN7
PIN8
PIN9
Conduction: UPS breakdown Conduction: warning Ground connection (Ground)
Remote shut down Public point none conduction: UP S work Conduction: bypass action Conduction: battery low voltage Conduction: UPS Work
none conduction: bypass work Conduction: AC cut off
2.8 EPO
EPO (Emergent Power Off) is located of UPS back panel, green terminal, Use EPO function shut down ups with Emergent circumstance, Two ways connection:
Connect 1
1-2 conduction, UPS execute shut down 3-4 free
Emergent Power Off
- 14 -
Page 21
g
Connect 2
Emer
ent Power Off
User switch
1-2 with lead c onnect 3-4 if switch offUPS execute shut down
2.9 Maintenance switch
The UPS can be maintained on-line with maintenance switch. No matter in AC model, battery model or bypass model, electric exist inside of UPS. But with Maintenance switch, UPS can be separated from utility power supply and ensure the safety of maintaining on-line.
Maintenance switch
- 15 -
Page 22
2.10 Dust-proof net (Optional)
Fully protect the UPS from the dust going inside, it's necessary in much dust and smoke circumstance. The dust- proof net is arranged in the inner of the front panel. Specific installation steps please check the installation manual of dust-proof net.
2.11 Isolation transformation box (Optional)
Isolation transformation with the properties of filter out clutter & the current balance, can protect th e load from the effect of other devices. And output isol ation transformation can be optional. Specific installation steps please check the installation manual of Isolation transformation.
3 Control Panel
3.1 Function instruction
Part Function
ON/OFF button
SELECT button
LCD panel Show the UPS working st atus and the warning message.
Press and hold the button more than 1s to turn on/off the UPS.Mute the alarm in bypass/ battery mode: press and hold the
button 2-10s in bypass/ battery mode. Reset once again.
Mute all the alarm: press and hold the button more than 10s in
AC/ bypass/ battery/ stanby/ inverter mode. Reset once again.
Battery test: Press and hold the button 2-10s in AC mode.
Green LED Inverter status Yellow LED Invert er status in bypass/ battery mode or warning message. Red LED Fault. The fault me ssage ca n be showed on LCD.
- 16 -
Page 23
3.2 LCD display:
The LCD has six parts as following:
Numerical display: show voltage, frequency, battery capacity, load capacit y and
fault code
Configuration: show the connection configuration of part
Load capacity icon: show the level of the load capacity Battery capacity icon: show the level of the battery capacity
④ ⑤
Alarm icon: when the UPS is abnormal the icon appearance
Display area: display UPS work mode area, "on line" while in AC mode, "on
batt" while in battery mode , "on bps" while in bypass mode.
4 Operation
4.1 Start up
Attention: The battery is fully charged before delivery. However storage and
transportation will inevitably cause some charge loss. Therefore, it's advisable to charge the battery for 10 hours before using it, to ensure adequate battery autonomy.
Note: means LED lighting, and means LED is faded.
Turn on the UPS with utility power supply (in AC mode)
After power supply is connected correctly, set the input breaker at "ON" position.
Then press and hold the "ON" button more than 2s to turn on the UPS, at this time self-test is running (If the UPS is in normal operation, it will show full screens one by one). The basic information of UPS can be showed on LCD panel.
- 17 -
Page 24
Work status showed on LCD panel as follwing (in AC mode):
Attention: If the utility power is abnormal, the UPS will operate in Battery mode
without interruption.
Turn on the UPS without utility power supply (in Battery mode)
Press down the “ON” button over 2 s to start the UPS (connect the external battery first for the long backup time models).
1) UPS start up in battery mode, LCD shows the main message in battery mode
UPS power to the load by battery.
2) While in battery mode, the buzzer will beep every 4s. Mote the alarm referring
to Function of SELECT button.
- 18 -
Page 25
LCD display after turning on the UPS
With the down button, input & output and other me ssage ca n be showe d on LCD. Shows while in AC mode as following:
- 19 -
Page 26
XPC11 series only display INPUT as following:
- 20 -
Page 27
4.2 Shut down
Press and hold the "OFF" button over 2s, t h e UPS woul d be shut down.
After shutting down, the UPS is still in bypass mode and the Yellow LED is
lighting.
While in bypass mode, the buzzer will beep every 2 minutes. Please press TEST
button more than 2 seconds.
Cut off AC power, then the UPS will be without output.
4.3 Charge current setting (only for long backup model)
Connect to the AC Power, turn on breaker, then press and hold the "ON"
button more than 2s to start the UPS. UPS work on line mode and the LCD display as following:
At the same time press the SELECT and down/up button and hold more
than 2s, the settings will be displayed on LCD panel.
- 21 -
Page 28
1) The first row is battery capacity with six types: 33AH, 45AH, 55AH, 65AH,
70AH and 100AH. Select with up/down button and choice the similar if there is no your type. Choice 100AH when wit h the capacity of battery over 100AH.
2) After selection of suitable capacity, press and hold SELECT button more
than 3s to exit out of the setting interface. At the same time, the charging is according to the set methods. Press the SELECT button to flip through parameters, and the current charging current and voltage will be showe d as follows:
Interface of charging current
22
Page 29
Interface of charging voltage
3) Press and hold on/off button more than 2s, the UPS shut down and save the
settings. When power on UPS next time, UPS will charge the battery according to the last time saved settings.
4) The setting interface is available in AC mode, battery mode, bypass mode.
5 Battery Maintenance
The UPS requires very little maintenance. Built-in batteries are sealed,
maintenance-free and just always be charging for the expected life. When connecting to the utility powe r, regardless of whether the UPS is on, the batteries are charged all the time with protection for overcharge and over discharge by the UPS.
If the UPS will remain idle for a long period, it should be charged every 4-6
months; When in high temperature, the batteries should be charged and discharged every 2 months, and the charging time should be more than 12 hours.
Normally, the serve time of batteries is 3-5 years. Should you detect a
problem, it’s demand for an early replacement and the replacement may be carried out only by professional personnel.
When replace the batteries, install the same number and same type of batteries. The replacement of single battery is deprecated. The whole replacement
should be observed the supplier’s instruction.
Normally (supplied by t h e batteries rarely), the batteries should be charged
and discharged every 4-6 months. Keep to be charge d when discharged to shout down of UPS and the standard charging time should be mor e than 12 hours.
23
Page 30
6 Trouble Shooting
If the Alarm icon is on and the LCD shows fault code, it indicate that the operation is abnormal. Please follow the troubleshooting table to eliminate the trouble. Fault menu as follows:
According to the above message, the UPS is in fault status turn to bypass mode.
If the UPS system does not operate correctly, please solve the problem by using the table below.
Fault Cause Correction
Fault code: 23, Alarm beeps continuously
Fault code: 9, Alarm beeps continuously
“INPUT” flash on LCD display
Fault code: 22, Alarm beeps continuously
“CHG ERR” flash on LCD display “FAN ERR” flash on LCD display
Capacity of battery flash on LCD display
Over temperature inside of UPS
Short circuit occurs on the UPS output
Mains voltage and frequency go out of input range Over load/ load fault
Charger failure Notify the dealer.
Fan failure
Battery low
Check over-load, fans, room temperature. Notify dealer when shuting down for 10 minutes doesn’t work. Check output wiring and if connected devices are in short circuit status. Notify the dealer. In battery mode now, save the data and close the application, check the input voltage and input frequency. Remove excess loads from UPS output. Check if the load is normal.
Check if the fan is stuck. Clean up dust. Check if the batteries are normal, replace when the batteries destroy. Check if the battery switch “ON”.
24
Page 31
AC can’t go to UPS Input switch “OFF” Set the input switch “ON”
Charge the batteries at least 10 hours and then check capacity. If the problem still persists, consult your dealer.
Press and hold the on/off button more than 2s.
Connect the batteries and charge batteries with low voltage before power on.
Battery backup time is shorter than nominal value
UPS could not started
Batteries are not fully charged
UPS over load Remove excess loads from UPS output. Batteries defect Contact your dealer to replace the battery. Too short time for holding the button Disconnect the batteries/ start with load and low battery voltage Failure Notify the dealer.
Attention: Fault code please refer to “Signification of Fault code”.
Maintenance service should be provided with the following information:
1) UPS MODEL NO.
2) UPS SERIAL NO.
3) The date fault occurs
4) The explanation of the fault ( display of LCD/ LED, voice, electric power,
load and batteries for long backup model)
25
Page 32
7 Signification of Fault code
Fault
code
1 BUS soft start error Please notify the dealer. 2 BUS high voltage Please notify the dealer. 3 BUS low voltage Please notify the dealer. 4 BUS imbalance Please notify the dealer. 5 Bus short circuit Please notify the dealer. 6 Inverter soft start over time Please notify the dealer. 7 Inverter high voltage Please notify the dealer. 8 Inverter low voltage Please notify the dealer.
9 Output short circuit Please notify the dealer. 17 Output negative power Please notify the dealer. 21 Current imbalance Please notify the dealer.
22 Over load
23 Over temperature
24 Inverter and relay can’t be closed Check if short circuit and notify the dealer. 25 Inverter and relay can’t be separated Check if short circuit and notify the dealer. 26 Utility power SCR fault Please notify the dealer. 29 Rectifier fault Please notify the dealer.
32 34 CAN communication fault Please notify the dealer.
35 Synchronization signal fault Please notify the dealer. 36 Auxiliary power fault Please notify the dealer. 42 Input fuse open Please notify the dealer. 55 NTC fault Please notify the dealer. 57 Battery fault Please notify the dealer. 59 Battery over charge fault Please notify the dealer.
Disconnection of parallel­communication
Signification Correction
Remove excess loads from UPS output. Check if the load is norma l. Check over-load, fans, room temperature. Notify dealer when shuting down for 10 minutes doesn’t work.
Check the line of communication.
- 26 -