
TopPage
Refer to "REFRIGERATING-CYCLE REPAIR MANUAL" for handling this refrigerant.
Refrigerant; R600a
SJF800SPSL
SERVICE MANUAL
No.S2904SE78PTUET
Refrigerator-freezer
MODELS
SJ-F750SP-SL/BK
SJ-F800SP-SL/BK
CONTENTS
CHAPTER 1. ENERGY LABEL/INSTALATION
[1] ENERGY LABEL ...........................................1-1
[2] INSTALATION ............................................... 1-1
CHAPTER 2. SPECIFICATION
CHAPTER 3. FICHE
CHAPTER 4. DESIGNATION OFVARIOUS PARTS
[1] EXTERNAL DESCRIPTION .......................... 4-1
[2] CONSTRUCTIONS ....................................... 4-2
CHAPTER 5. DIMENTIONS
[1] OUTER DIMENTIONS AND CLEARANCE........ 5-1
[2] INNER DIMENTIONS.................................... 5-2
CHAPTER 6. LIST OF ELECTORICAL PARTS
CHAPTER 7. WIRING DIAGRAM
[1] WIRING DIAGRAM ....................................... 7-1
[2] ELECTRIC ACCESSORIES LAYOUT........... 7-2
CHAPTER 8. FAILURE DIAGNOSIS
[1] OUTLINE OF CONTROL .............................. 8-1
[2] WHEN THE DEFROSTING FAILURE IS
DOUBTFUL ...................................................8-1
[3] RE-SETTING OF MICROCOMPUTER AT
POWER FAILURE......................................... 8-1
[4] DIAGNOSIS METHOD OF FAILURE
AROUND PWB .............................................. 8-2
[5] CONVERSION TABLE BETWEEN TEM-
PERATURE AND RESISTANCE VALUE........ 8-3
[6] CIRCUIT DIAGRAM OF MAIN PWB ............. 8-4
[7] CIRCUIT DIAGRAM OF LCD PWB ............... 8-5
CHAPTER 9. SELF-DIAGNOSIS MODE
CHAPTER 10. MODE FOR DISPLAY
CHAPTER 11. DISASSEMBLING/ASSEMBLING
PROCEDURES
[1] REFRIGERATOR COMPARTMENT.............11-1
[2] FREEZER COMPARTMENT ........................11-7
[3] HOW TO REMOVE THE CONTROL BASE.....11-12
[4] DEFROST HEATER ...................................11-13
[5] WHEN LEFT AND RIGHT DOORS ARE
NOT ON THE SAME LEVEL ......................11-15
CHAPTER 12. COOLING UNIT
[1] COOLING UNIT........................................... 12-1
[2] LOCATION................................................... 12-2
Parts Guide
This document has been published to be used for
after sales service only.
The contents are subject to change without notice.

SJF800SPSL
1 – 1
SJF800SPSL
ServiceManual
CHAPTER 1. ENERGY LABEL/INSTALATION
[1] ENERGY LABEL
Usage of "the ENERGY LABEL"
• When displaying this refrigerator in the shop-window, attach the "ENERGY LABEL" to it in the following procedure.
[2] INSTALATION
Free standing type
• To ensure adequate ventilation for this refrigerator, install with 6 cm space at the rear and both sides, with aminimum space of 9 cm above the
refrigerator.
"ENERGY LABEL (DATA)"
(This label is in Operation manual)
"ENERGY LABEL (BASE)"
of each language
Refrigerator
Data part
E
B
A
C
D
E
G
F
G
Fix the data part of
"ENERGY LABEL (DATA)"
on the data part of
"ENERGY LABEL (BASE)"
This refrigerator shall be used under the ordinary place condition between +5 C and +38 C of ambient
temperature, and also not be left under -10 C for long days.
To be used this refrigerator within the range of the rated voltage˴6%

SJF800SPSL
2 – 1
SJF800SPSL
ServiceManual
CHAPTER 2. SPECIFICATION
Items SJ-F750SP SJ-F800SP
Type 4 Door
Outer dimensions Height 1720mm(67.7") 1830mm(72.0")
Width 890mm(35.0") 890mm(35.0")
Depth 770mm(30.3") 770mm(30.3")
Rated storage volume Total 556liter(19.6cu.ft) 605liter(21.4cu.ft)
Freezer 211liter(7.5cu.ft) 211liter(7.5cu.ft)
Refrigerator 345liter(12.1cu.ft) 394liter(13.9cu.ft)
Rated gross volume 602liter(21.3cu.ft) 653liter(23.1cu.ft)
Defrosting System Heater system
Start Automatic
Finish Automatic
Temperature control Automatic (Adjustable)
No-frost freezer Yes
Interior lamp (LED) 36
Plasmacluster light (LED, Blue) 1
Caster 4
Evaporating pan 1 (unremovable)
Refrigerator Compartment R-shelf ass'y 2
V-shelf ass'y 1
Bttl rack ass'y 1
Fruit case ass'y 1
Fresh case ass'y 1
V-case ass'y 1
Door pocket ass'y 3
Btl-pok L ass'y 1
Btl-pok R ass'y 1
U-pok door 1
Utility pok ass'y 1
Egg pok ass'y — 1
Egg tray 1
Freezer Compartment Ice cube maker 1
Quick ice maker 1
Ice storage ass'y 2
F-case S ass'y 3
F-case L ass'y 2
Control panel Plasmacluster Yes
Express Ice making Yes
Express Freezing Yes
Vacation mode Yes
Door alarm Yes
Timer Yes
Temp. control Yes
Child lock Yes
Aluminum panel Yes
Deodorizing unit (Honeycomb type) Yes
RATING
Items SJ-F750SP SJ-F800SP
Rated voltage (V~) 220-240
Rated frequency (Hz) 50
Climate class ST
Rated current (A) 0.8-0.9
Rated input of heating systems (W) 173-206
Defrosting input (W) 173-206
Refrigerant (Charging quantity) [Flammable] R-600a(52g) R-600a(52g)
Insulation blowing gas [Flammable] Cyclo pentane (HC)
Net Weight (kg) 111 114

SJF800SPSL
2 – 2
PLUG TYPE
Plug cord 2 pin + Earth
Plug type CS
Destination mark E
COLOR
Items -SL -BK
Outside color Silver Black
Inside color White White

SJF800SPSL
3 – 1
SJF800SPSL
ServiceManual
CHAPTER 3. FICHE
1
NO.
2
3
4
5
6
8
9
11
12
13
14
Trade mark
Items
Description
Remarks
Model name
Type
Energy efficiency class
Eco-award mark
Energy consumption
(220V 50Hz at 25 C)
Star rating of frozen food
compartment
Temperature rise time
Freezing capacity
Climate class
Noise
10 No frost
7
Net storage volume of frozen
food storage compartment
SJ-F750SP SJ-F800SP
Category; 7
A+
ST ST
38 dB(A)
re1pw
38 dB(A)
re1pw
450
kWh/year
1017
kWh/year
1066
kWh/year
345 L
No frost
11 h
9.5 kg /24h
Net storage volume of fresh
food storage compartment
Category; 7
A+
465
kWh/year
394 L
11 h
9.5 kg /24h
880/92
EN153
86/594/EEC
No frost
THE FICHE (according to ANNEX : 94/2/EC)
15
Maximum allowable electricity
consumption (Emax)
(96/57/EC)
211 L
4-STAR
211 L
4-STAR
E max
(2.92)(2.79) (kWh/day)
fridge / freezer
A++/A+/A~G
at 25
at 25

SJF800SPSL
4 – 1
SJF800SPSL
ServiceManual
CHAPTER 4. DESIGNATION OFVARIOUS PARTS
[1] EXTERNAL DESCRIPTION
The names in parenthesis “[ ]” are the denominations used in the REPLACEMENT PARTS LIST.
25
13
12 14
13
25
15
1
17
18
19
20
22
21
26
23
24
7
8
25
9
10
1
2
3
4
5
6
7
8
25
9
10
11
16
15
16
1
22
17
SJ-F800SP
SJ-F750SP
1. Door pocket [Door pocket ass'y]
2. Refrigerator shelf [R-shelf ass'y]
3. Shelf [V-shelf ass'y]
4. Bottle pocket(left) [Btl-pok L ass'y]
5. Vegetable crisper [V-case ass'y]
6. Quick ice maker [Quick ice maker]
7. Freezer case(small) [F-case S ass'y]
8. Freezer case(large) [F-case L ass'y]
9. Caster
10. Adjustable feet [Adjustable leg ass'y]
11. Foot cover [Base cover]
12. Aluminum panel [AL panel]
13. Refrigerator LED Light
[LED pwb ass'y]
14. Plasmacluster Light [PCI pwb ass’y]
15. Utility pocket cover [U-pok door]
16. Utility pocket [Utility pok ass'y]
17. Egg holder [Egg tray]
18. Egg pocket [Egg pok ass’y]
(Only for SJ-F800SP)
19. Bottle rack [Bttl rack ass'y]
20. Fruit case [Fruit case ass'y]
21. Fresh case [Fresh case ass'y]
22. Bottle pocket(right) [Btl-pok R ass'y]
23. Ice cube maker [Ice cube maker]
24. Ice cube box [Ice storage ass'y]
25. Magnetic door seal [Door packing]
26. Control panel

SJF800SPSL
4 – 2
[2] CONSTRUCTIONS
PWB-s ass'y
Ionizer-K
R-thermistor
R fan motor
Damper ass'y
Compressor
Protector
Starting relay
Sub condenser
Evaporator
Fuse ass'y
F-thermistor
Def-thermistor
F-fan motor
Defrost heater
Reed sw
LCD PWB s ass'y
Control panel
C fan motor
Running capacitor
Evaporating pan
Foot cover
Adjustable feet
Caster
mark : cold air flow

SJF800SPSL
5 – 1
SJF800SPSL
ServiceManual
CHAPTER 5. DIMENTIONS
[1] OUTER DIMENTIONS AND CLEARANCE
1. SJ-F750SP
2. SJ-F800SP
890
50
1180
1500
787
890
60
817
770
890
1180
1500
890
60
50
787
770
817

SJF800SPSL
5 – 2
[2] INNER DIMENTIONS
The dimensions between shelves can be changed by setting the shelves on the other rails.
1. SJ-F750SP
2. SJ-F800SP
186340
77
30
328
328
250
136.5
136.5
136.5
346
260.5
365
365
142.5
142.5
316
316
316
316
316
316
708
708
708
282
217
166
217
320
282
96.5
125.5
308
308
298 298
142.5142.5260.5
260.5
125.5 125.5
80
80
308
142.5
136.5
136.5
191
328
328
250
240
96.5
188
125.5
66
311
406
80
365
346
142.5
260.5
168
66
150150
340 230
708
708
328
328
250
136.5
136.5
136.5
217
166
365
365
142.5
142.5
346
260.5
316
316
316
282
217
320
282
96.5
125.5
316
316
316
316
308
308
142.5142.5260.5
298
168
125.5
66
80
80
125.5
308
142.5
260.5
298
136.5
136.5
136.5
191
328
328
250
240
96.5
188
125.5
311
66
406
80
365
346
142.5
260.5
225345
708
190135345

SJF800SPSL
6 – 1
SJF800SPSL
ServiceManual
CHAPTER 6. LIST OF ELECTORICAL PARTS
“ • “ denotes parts that cannot be replaced or parts that cannot be replaced as an individual unit.
ITEMS TYPE NAME RATING SPECIFICATIONS
R Thermistor — DC 5V R0 = 6.4 kΩ, B(0) = 3811
F Thermistor — DC 5V R0 = 6.4 kΩ, B(0) = 3811
Defrost Themistor — DC 5V R0 = 15 kΩ, B(0) = 3811
• RD Heater (F750SP) — 220-240V 8021Ω 6.6W at 230V
• RD Heater (F800SP) — 220-240V 8365Ω 6.32W at 230V
Thermo. fuse SF70E 250V 10A Working temp. : 70 °C
Defrost heater MM6-4350 220-240V 286Ω 185W at 230V
R-Fan motor D08A-12PM.05(K) DC12V 0.07A —
F-Fan motor FBA12J15VXD DC14.5V 0.28A —
C-Fan motor D09T-12CS307(EX) DC12V 0.09A —
Damper NSBC101FA1 DC12V —
Reed SW MS-332/651 DC5V Magnetic Switch
SW Magnet FM10.9X7X25.4(SR-3) — Magnet Switch
Lamp (Side) FPWB-A617CBKZ DC14.5V 150mA white LED Lamp
Lamp (Top) FPWB-A619CBKZ DC14.5V 75mA white LED Lamp
LCD operation FPWB-A615CBKZ DC14.5V Blue LCD
Ionizer indicator FPWB-A621CBKZ DC14.5V Blue LED
Compressor EGM90CLC 220-240V/50Hz Cooling capacity : 218W (50Hz)
Main coil : 18.40Ω
Aux. coil : 25.50Ω
(at 25 °C)
Starting Relay PTH8M220MD2 — 22Ω (at 25 °C)
Overload Relay (Protector) 4TM189NFBYY-53 — Open/Close : 120/ 61 °C
Running capacitor RC-EZA254CBZZ — 400V 5μF
Ionizer-K (Plasmacluster unit) CKITTA131AKKZ DC15V 4.55kV p-p (Second wave)
Common
Aux. coil
Main coil

SJF800SPSL
7 – 1
SJF800SPSL
ServiceManual
CHAPTER 7. WIRING DIAGRAM
[1] WIRING DIAGRAM
Be sure to replace the electrical parts with specified ones for maintaining the safety and performance of the set.
Fuse1 Fuse3
Fuse2
Relay2
AC/DC
DC
MAIN
PWB
G
B
Br
Relay1
111222333
1234
1234
445
12345
566778
12345678
9
112234
1234
5678
9
101112
8
Compressor
Starting relay
Protector
Fuse
Defrost Heater
Running capacitor
R-door heater
F-reed SW
R-reed SW
Defrost-thermistor
LCD Control
PWB
F-thermistor
Damper
Plasmacluster
R-thermistor
Plasmacluster light
Light
Plug / Cord
LED
LED
LED
LEDLED

SJF800SPSL
7 – 2
[2] ELECTRIC ACCESSORIES LAYOUT

SJF800SPSL
8 – 1
SJF800SPSL
ServiceManual
CHAPTER 8. FAILURE DIAGNOSIS
[1] OUTLINE OF CONTROL
1. ON/OFF Control of Compressor
• ON/OFF of the compressor will be controlled depend on the temperature detected by
the R-thermistor and F-thermistor. (Normal cooling control)
• In case the surrounding temperature is high at the power supply input, the compressor will be ON at once and the normal cooling control will start
after several hours.
• When the rapid ice making or rapid freezing is requested by user during the operation, the compressor will be ON and cooling operation will be
started regardless of the detected temperature by the thermistors. However, if requested during the defrosting operation, the request will be executed after the completion of defrosting and ON of the compressor might be delayed.
• During 5 minutes after the compressor stops, it will not start regardless of the detected temperature by R-thermistor and F-thermistor.
2. Defrosting
Microcomputer calculates the appropriate timing of defrosting and defrosting is made automatically. Therefore no manual operation by user is
required. The cycle of defrosting varies depend on the usage condition of the refrigerator. (Maximum time about 50 hours, minimum time 8 hours)
3. Thermistor
Thermistors are installed in 4 places; in the refrigerator and freezer compartment, and close to the Control panel and Evaporator. (R-thermistor, Fthermistor, Outside temp-thermistor, Def-thermistor)
R-thermistor and F-thermistor detects the temperature in the refrigerator and freezer compartment respectively and controls ON/OFF of compressor.
Def-thermistor detects the temperature around the evaporator and shows the progress of defrosting.
Outside temp-thermistor detects the surrounding temperature of refrigerator. It decides the defrost timing and changes the operation mode when the
outside temperature is high.
[2] WHEN THE DEFROSTING FAILURE IS DOUBTFUL
Execute the Self-Diagnosis Mode. (Refer to the Chapter “SELF-DIAGNOSIS MODE”)
• In case the diagnosis result is “EE03” (Def-thermistor system defect), follow up the flowchart of EE03. (In case of any abnormity in the Def-thermistor, defrosting will not be made for safety reasons.)
• In case the diagnosis result is “EE07” (Defrost defect), follow up the flowchart of EE07.
(This diagnosis result will be displayed when defrosting is made for 120 minutes, the maximum time length. In this case, the defect of PWB itself
and also the breakage of heater and heater circuit (melt down of current fuse and temperature fuse) are considerable.)
[3] RE-SETTING OF MICROCOMPUTER AT POWER FAILURE
• At the power failure for over 0.4 second, the control of the microcomputer will might be reset.
• Microcomputer might continue to operate for approximately 10 seconds maximum at power failure depending on the load at the operation. Approximately 30 seconds is necessary for the definite power OFF condition.
• When the power is re-supplied, the normal cooling will be resumed.(If cold enough in the cabinet, the microcomputer will begin defrosting in 40
minutes according to the condition.)
• The temperature and operation mode set by user will be maintained even if a power failure occurred.
(However defrosting, rapid freezing, rapid ice making, and timer will not be maintained.)
• When the self diagnosis is made, each mode and setting are resumed to the initial condition.

SJF800SPSL
8 – 2
[4] DIAGNOSIS METHOD OF FAILURE AROUND PWB
First of all, check by using the self-diagnosis.
In case that the power supply doesn't enter, check by the following procedure.
1. Disconnect power supply and check the following point.
• Is there any failure portion in inserting connectors?
2. Detach the PWB and check the appearance.
• Is there any burning or abnormal damage?
3. Check the conditions of the fuse and the varistor. (Fuse and varistor are located at the position in the figure.)
• Under the condition of power supply plug connected;
In case of no cooling and no indoor lamp lighting, there might be a possibility of fuse (F1 or F2) melt down.
When the fuse F1 or F2 is melt down, PWB does not operate at all.
When the fuse F3 is melt down, defrosting heater and refrigerator door heater are not electrified. (Defrosting error will be diagnosed as
“Defrosting failure” by the self diagnosis.) In this case, the cooling performance may deteriorate or dew generation may occur on the door,
because the defrosting is not done.
• Melting in the fuse cannot be checked visually (as the safer one than transparent glass tube is used). Be sure to detach the connector “CN1”
before measuring the resistance between the both ends of the fuse by the tester.
• Next, measure the resistance value between the both leads of the varistor.
4. Check whether the temperature (resistance value) shown by R-thermistor is correct or not. (Refer to the table below.)
• Detach the connector “CN4” on the PWB and measure the resistance between 1 and 2 pins of harness side.
5. Check whether the temperature (resistance value) shown by Def-thermistor is correct or not. (Refer to the table below.)
• Detach the connector “CN5” on the PWB and measure the resistance value between 6 and 7 pins of harness side.
6. Check whether the temperature (resistance value) shown by F-thermistor is correct or not. (Refer to the table below.)
• Detach the connector “CN5” on the PWB and measure the resistance value between 4 and 5 pins of harness side.
Var is tor
Normal (over approx.1.5MΩ) Damage
Fuse
Melting
Flow of excessive current is considerable for some reasons.
Check for any portion to cause short circuits especially on
the primary circuit.
There is a possibility of excessive voltage applied from outside with the factor such as thunder etc. When repeated with a
factor other than thunder, there might be the apparatus near
by generating noises.
Conduction
Fuse and varistor are normal.
Possibility to be caused by excessive current or voltage
near the power supply is low. Proceed to the other check
item.
-
Var istor 1
Fuse 2
Fuse 1
Var istor 3
Fuse 3

SJF800SPSL
8 – 3
[5] CONVERSION TABLE BETWEEN TEMPERATURE AND RESISTANCE VALUE
1. R-thermistor
2. Def-thermistor, F-thermistor
Temperature
(°C)
Resistance Value
(KΩ)
Temperature
(°C)
Resistance Value
(KΩ)
Temperature
(°C)
Resistance Value
(KΩ)
-25 26.1 -9 10.3 7 4.52
-24 24.54 -8 9.75 8 4.3
-23 23.08 -7 9.24 9 4.1
-22 21.72 -6 8.76 10 3.91
-21 20.46 -5 8.3 11 3.73
-20 19.27 -4 7.87 12 3.56
-19 18.16 -3 7.47 13 3.4
-18 17.13 -2 7.09 14 3.24
-17 16.16 -1 6.74 15 3.1
-16 15.25 0 6.4 20 2.47
-15 14.4 1 6.08 25 1.99
-14 13.6 2 5.78 30 1.61
-13 12.85 3 5.5 35 1.31
-12 12.15 4 5.23 40 1.08
-11 11.49 5 4.98
-10 10.88 6 4.74
Temperature
(°C)
Resistance Value
(KΩ)
Temperature
(°C)
Resistance Value
(KΩ)
Temperature
(°C)
Resistance Value
(KΩ)
-25 61.17 -9 24.13 7 10.58
-24 57.51 -8 22.85 8 10.09
-23 54.1 -7 21.65 9 9.61
-22 50.92 -6 20.52 10 9.16
-21 47.94 -5 19.46 11 8.74
-20 45.17 -4 18.46 12 8.34
-19 42.57 -3 17.51 13 7.96
-18 40.14 -2 16.63 14 7.6
-17 37.86 -1 15.79 15 7.26
-16 35.74 0 15 20 5.79
-15 33.74 1 14.26 25 4.66
-14 31.87 2 13.55 30 3.77
-13 30.12 3 12.89 35 3.08
-12 28.48 4 12.26 40 2.52
-11 26.94 5 11.67
-10 25.49 6 11.11

SJF800SPSL
8 – 4
[6] CIRCUIT DIAGRAM OF MAIN PWB

SJF800SPSL
8 – 5
[7] CIRCUIT DIAGRAM OF LCD PWB

SJF800SPSL
9 – 1
SJF800SPSL
ServiceManual
CHAPTER 9. SELF-DIAGNOSIS MODE
1. Entering method of the mode
1) Press the [Select] button on the LCD panel over 5 seconds at the opening condition of the
freezer and refrigerating room doors.
2) With a beep sound of buzzer, the self-diagnosis mode is entered. When the self-diagnosis
mode is not entered by the above operation, defect of Reed SW system can be considered.
2. When the self-diagnosis mode is entered, the following movements will be made. Forced release operation is not prepared for the self-diagnosis
mode. It returns to the normal movement after a lapse of 2 minutes.
• During the express ice making, express freezing or timer, the mode is released.
• Plasmacluster will not release the mode, and ON is forced for 2 minutes whether it is ON or OFF.
• When the self-diagnosis mode is entered, beep sound for reminding of closing the door must not be sounded for 20 minutes.
• Defect and various conditions are shown by the beeping buzzer pattern.
• Defect and various conditions are displayed on the LCD panel. In case of plural defects and various conditions, these are displayed one after
another by button operation and all contents are notified.
3. Display of self-diagnosis
• Display example of LCD panel (at the defect of F-thermistor system)
• Buzzer notice example; (at defrost defect, 2 times of 0.5 second ON)
ḥ
EXPRESS
ICE
SELECT BUTTON
SELECT
EXPRESS
ICE
Results of diagnosis
Move to the next display.
Move to the previous display.
SELECT
ON
OFF
3 seconds stop
Repeating
0.5 second stop
3 seconds stop
0.5 second stop
0.5 second 0.5 second 0.5 second 0.5 second
Buzzer

SJF800SPSL
9 – 2
• Buzzer: =0.5 sec ON/0.5 sec OFF, =2 sec ON/0.5 sec OFF
No
.
Status Buzzer LCD
Display
Content
Correspon-
dence
method
- No defects None - - - -
1 F-thermistor system defect EE 01
Defect of each thermistor, short circuit/wire breakage of thermistor wiring and defect of main PWB
→[1]
2 R-thermistor system defect EE 02 →[2]
3 DEF-thermistor system defect EE 03 →[3]
4
Outside temperature-thermistor
system defect
EE 04 →[4]
5 Defrost defect EE 07
Wire breakage of fuse•defrost heater, defect of main PWB
(120-minute defrosting has been occurred continuously 2 times
within the past 48 hours.)
→[5]
6 F fan motor system defect EE 08
Defect of each fan motor, fan-lock and defect of wiring/main
PWB
(When fan motor is ON, over current or no current is detected.)
→[6]
7 C fan motor system defect EE 09 →[7]
8 R fan motor system defect EE 10 →[8]
9
Ionizer (Plasmacluster) system
defect
EE 11 →[9]
10 LCD Display communication defect EE 12
Short circuit/wire breakage of wiring and defect of LCD or main
PWB (Communication with LCD PWB has been abnormal over
3 times within the past 48 hours.)
→[10]
11 F-thermistor system defect history EH 61
Defect of thermistor system has been occurred over 1 minute
continuously within the past 48 hours.
→[1]
12 R-thermistor system defect history EH 62 →[2]
13
DEF-thermistor system defect history
EH 63 →[3]
14
Outside temperature-thermistor
system defect history
EH 64 →[4]
15 F fan motor system defect history EH 66
Defect of fan motor has been occurred over 3 times continuously within the past 48 hours.
→[6]
16 C fan motor system defect history EH 67 →[7]
17 R fan motor system defect history EH 68 →[8]
18
Ionizer (Plasmacluster) electrifying
defect history
EH 72
Defect of Ionizer (Plasmacluster) electrifying has been
occurred over 3 times continuously within the past 48 hours.
→[9]
19 F-room high temperature history EH 76
Temperature of F-thermistor has been reached over -10°C continuously for 6 hours or more within the past 48 hours. (except
right after the installation)
→[1]
20 R-room high temperature history EH 77
Temperature of R-thermistor has been reached over +10°
C
continuously for 6 hours or more within the past 48 hours.
(except right after the installation)
→[2]

SJF800SPSL
9 – 3
Correspondence method
Power OFF Power OFF
Replace F-thermistor.
Replace main PWB.
(F-thermistor system diagnosis) (R-thermistor system diagnosis)
OK
NG
and .
Replace R-thermistor.
Replace main PWB.
Remove 6P connector from R
louver Assy and measure the
thermistor resistance between
and .
EE 01 / EH 61 / EH 76
EE 02 / EH 62 / EH 77
[1]
[2]
Remove 4P connector (flat) from
E.V. cover Assy and measure the
thermistor resistance between
NG
OK
NG
NG
OK
OK
Check the F-thermistor
system wiring
Check the R-thermistor
system wiring