Sharp R-8470, R-8570 Service Manual

Page 1
Page 2
I--
R-8470 R-8570
Page 3
R-8470 R-8570
OVEN
This Manual has been prepared to provide Sharp Corp. Service
Personnel with complete Operation and Service Information for
the SHARP CONVECTION MICROWAVE ovens, R-8470/
R-8570.
It is recommended that service personnel carefully study
entire text of this manual so they will be qualified to render satisfactory customer service.
Check interlock switches and door seal carefully. Special at-
tention should be given to avoid electrical shock and microwave
radiation hazard.
CAUTION
MICROWAVE RADIATION
Personnel should not be exposed to the microwave energy
which may radiate from the magnetron or other microwave
generating devices if it is improperly used or connected. All input and output microwave connections, waveguides,flanges and gaskets must be secured. Never operate the device without a nicrowave energy absorbing load attached. Never look into
an open waveguide or antenna while the device is energized.
SHARPCORPORATION
OSAKA, JAPAN
PRODUCT
Page 4
Page 5
Page 6
OPERATION
DESCRIPTION OF OPERATING SEQUENCE
I
I
following is a description of component functions
during oven operation.
OFF CONDITION
Closing the
door activates
both door interlock
switches: upper latch switch and lower latch switch.
(In this condition,
the monitor switch contacts are
opened
stop switch is activated (contacts closed) by the
latch head, when the door is closed. When oven is plugged in, the 240 volts A.C. is supplied to the relay unit. (Figure O-l).
display will show flashing To set any program or set the clock, you must first touch the STOP/CLEAR (or STOP/CANCEL) pad.
The display will clear,
and
will appear and
count up every minute.
Note: When the door is opened, the oven lamp comes
on.
2. A signal is input to the control unit, energizing the coil of shut-off relay (RY6).
RY6 contacts close, completing a circuit to the damper motor. The damper motor now operates moving the damper to the open position, thereby closing the contacts of the damper switch inputs a signal to the control unit. The coil of relay RY6 is de-energized, opening its contacts, thereby turning off the damper motor.
COOKING CONDITION
Program desired cooking time and Variable Cooking Control by touching the NUMBER pads and the HIGH pad of the Variable Cooking Control. When the COOK
(or START) pad is touched, the following operations
occur:
1. The contacts of relays are closed and components connected to the relays are turned on as follows.
(For details, refer to Figure O-2)
RELAY CONNECTED COMPONENTS
RY-1 power transformer RY-2
oven lamp/turntable motor
RY-3
convection motor heating element
RY-5
fan motor
RY-6
damper motor
2. The 240 volts A.C. is supplied to the primary wind-
ing of the power transformer and is converted about 3 volts A.C. output on the filament winding, and approximately 2200 volts A.C. on the high voltage winding.
3. The filament winding voltage heats the magnetron filament and the H.V. winding voltage is sent to a voltage doubler circuit.
4. The microwave energy produced by the magnetron
is channeled through the waveguide into the cavity
feed-box, and then into the cavity where the food
is placed to be cooked.
5.
6.
Upon completion of the cooking time, the power
transformer, oven lamp, etc. are turned off, and the
generation of microwave energy is stopped. The oven will revert to the OFF condition.
When the door is opened during a cook cycle,
monitor switch, stop switch, upper latch switch are activated with the following results. The circuits to the turntable motor, the cooling fan motor, and the
high voltage components are deenergized, the oven lamp remains on,
and the digital readout displays
the time still remaining in the cook cycle when the
door was opened.
7.
The monitor switch is electrically monitoring the
operation of the upper latch switch and is mechan­ically associated with the door so that it will func­tion in the following sequence. (1) When the door opens from a closed position,
the upper latch switch opens their contacts, and then the monitor switch contacts close.
(2) When the door is closed from the open posi-
tion, the monitor switch contacts first open, and then the contacts of the upper latch switch close.
the upper latch switch failes with their contacts
closed when the door is opened, the closing of the
monitor switch contacts will form a short circuit through the monitor fuse, upper latch switch , causing the monitor fuse to blow.
When the Variable Cooking is programed, the 240 A.C. voltage
is supplied
to the power transformer intermittently through the contacts of the relay which is operated by the control unit within a 32 second time base. The microwave power operation is as follows:
VARI-MODE
ON TIME OFF TIME
HIGH
32 sec.
0 sec.
(approx. 100% power)
24 sec.
8 sec.
(approx. 70% power) MEDIUM
18 sec.
14 sec.
(approx. 50% power) MED.LOW( DEFROST) 12 sec.
20 sec.
(approx. 30% power) LOW
6 sec. 26 sec.
(approx. 10% power)
Note: The ON/OFF time ratio does not correspond
with the percentage of microwave power, be­cause approx. 2 seconds are needed for heating of the magnetron filament.
CONVECTION COOKING CONDITION
Program desired convection temperature by touching the CONVECTION pad and the temp. pad. When the START pad is touched, the following oper­ations occur:
4
Page 7
1.
2.
3
The coil of shut-off relays (RY2, RY3 and RY5) are
energized, the oven
lamp, cooking fan motor,
turntable motor and convection motor are turned
on.
The coil of relay (RY6) is energized by the control
unit. The damper is moved to the closed position, opening the damper switch contacts.
The opening of the damper switch contacts sends
a signal to the LSI on the control unit
de-energizing the relay (RY6) and opening the circuit to the damper motor. The coil of heater relay (RY4) is energized by the
control unit and the mains supply voltage is added
to the heating element.
When the oven temperature reaches the selected
preheat temperature, the following operations oc-
cur:
4-1.
4-2.
The heater relay is de-energized by the con­trol unit temperature circuit and thermistor,
opening the circuit to the heating element.
The oven will continue to function for
minutes, turning the heater on and off, as
needed to maintain the selected preheat temperature. The oven will shut-down completely after
15 minutes.
When the preheat temperature is reached, a beep signal will sound indicating that the holding temperature has
been reached in the oven cavity. Open the door and place the food to be cooked in the oven. Program desired cooking time and convection temper-
ature by touching the NUMBER pad, CONVECTION
pad and Temperature pad.
When the START pad is touched, the following oper-
ations occur: I.
2.
3.
4.
5.
The numbers of the digital readout start the count
down to zero. The oven lamps, turntable motor, cooking fan mo­tor and convection motor are energized.
Heater relay (RY4) is energized (if the cavity tem-
perature is lower than the selected temperature)
and the mains supply voltage is added to the
heating element to return to the selected cooking temperature.
Upon completion of the cooking time, the audible signal will sound, and oven lamps, turntable motor, cooking fan motor and convection motor are de-energized. At the
the convection cycle,
if the cavity air temperature is above 120
the circuit to RY5 will be maintained (by the thermistor circuit) to continue operation of the cooling fan motor until the temperature drops below 100 at which time the relay will be de-energized, turn-
ing off the fan motor. Relay RY3 will however,
open as soon sa the convection cycle has ended,
turning off the convection fan motor. This will now
cool and allow the damper door to open. At the end of the convection cook cycle, shut-off relay (RY6) is energized turning on the damper motor. The damper is returned to the open position,
closing the damper switch contacts which send a signal to the control unit, de-energizing shut-off relay (RY6).
AUTOMATIC MIX COOKING CONDITION
Program desired cooking time and temperature by
touching the number pads and the LOW MIX/BAKE
or HIGH MIX/ROAST pad
When the START pad is touched, the following oper-
ations occur:
1.
2.
3.
4.
5.
6.
The numbers of the digital readout start the count down to zero. The shut-off relay (RY2, RY3 and RY5) are
gized, turning on the oven lamps, turntable motor, and cooling fan motor.
The shut-off relay (RY6) is energized.
The damper door is closed from the open position.
The heater relay (RY4) is energized, adding the
mains supply voltage to the heating element. Now, the oven is in the convection cooking con­dition. When the oven temperature reaches the selected temperature, the following operations occur: 6-l. The power supply voltages is added to the
heating element and power transformer al­ternately.
6-2. The heating element operates through the
heater relay (RY4) contacts and the power transformer operates through the cook relay
contacts.
6-3. These are operated by the control unit to
supply alternately within a 32 second time base, convection heat and microwave en-
ergy.
The relationship between the convection and micro­wave power operations are as follows.
Note: The ON and OFF time ratio does not correspond
with the percentage of microwave power, be-
cause approx. 2 seconds are needed for heating
of the magnetron filament.
Appmx.
184vc
2oo”c
Note: During alternate Microwave/Convection opera-
tion, the convection heater is energized only if the cavity temperature drops below the set tem­perature.
5
Page 8
SENSOR COOKING CONDITION (R-8570
Using the SENSOR COOK function, the foods are cooked without figuring time, power level or quantity. When the oven senses enough steam from the food, it
relays the information to its microprocessor which will
calculate the remaining cooking time and power level
needed for best results. When the food is cooked, water vapor is developed. The sensor “senses” the vapor and its resistance in-
creases gradually. When the resistance reaches the
value set according to the menu, supplementary cook-
ing is started. The time of supplementary cooking is determined by experiment with each food category and inputted into the LSI.
An example of how sensor works:
1. Broccoli at room temperature. Vapor is emitted very slowly.
2. Heat broccoli. Moisture ‘and humidity is emitted
rapidly. You can smell the aroma as it cooks.
3. Sensor detects moisture and humidity and calcu-
lates cooking time and variable power.
1. Touch SENSOR COOK pad.
NOTE:The oven should not be operated on SEN-
SOR COOK immediately after plugging in the unit. Wait five minutes before cooking on SENSOR COOK.
2. Select desired Sensor setting.
3. Touch START pad.
The coil of shut-off relay (RY-1) is energized, the
oven light and cooling fan motor are turned on, but
the power transformer is not turned on.
4. After about 16 seconds, the cook relay (RY-2) is energized. The power transformer is turned on, microwave energy is produced and first stage is started. The 16 seconds is the cooling time required to re-
move any vapor from the oven cavity and sensor. NOTE: During this first stage, do not open the door
or touch STOP/CLEAR pad.
5.
When the sensor detects the vapor emitted from the food, the display switches over to the remaining cooking time and the timer counts down to zero. At this time, the door may be opened to stir food, turn it or season, etc.
6. When the timer reaches zero, an audible signal sounds.
The shut-offrelay and cook relay are de-energized and the power transformer, oven light, etc. are turned off.
7. Opening the door or touching the STOP/CLEAR pad, the time of day will reappear on the display and the oven will revert to an OFF condition.
COMPUCOOK (R-8570 only)
COMPUCOOK will automatically compute the oven
temperature, microwave power and cooking time for
baking, roasting and broiling. Set the
desired
program by
touching
the
COMPUCOOK pad, and number pad. Enter the weight by touching the Number pads When the START pad is touched, the following oper­ations occur:
1.2.The COOK indicator will light and the Convection Fan Symbol will rot ate.
The cooking time will appear on the display and start counting down to zero. The cooking time is adjusted automatically ac-
cording to the setting quantity or weight of food.
The shut-off relays (RY2, RY3, RY4 and RY5) are
energized, turning on the oven lamp, turntable motor, cooling fan motor and convection motor. The power supplay voltage is added to the heating element.
Now, the oven is in the convection cooking mode. When the oven temperature has reached the pro­grammed convection temperature, the oven goes
into the programmed cooking mode. At the end of the COMPUCOOK cycle, the damper
is returned to the open position and the oven will be off condition. The cooling fan will remain on until the oven has cooled.
3.
4.
5.
6.
COMPU DEFROST COOKING
The COMPU DEFROST key is a special function key to defrost meats and poultry faster and better.
COMPU DEFROST 1 to 5 automatically defrosts roast beef, etc. Each key has 3 defrost stages.
When the desired COMPU DEFROST number is
and the food weight is entered by using
number pad’s, the oven will cook according to
special cooking sequence.
the the
Page 9
R-8470 R-8570
oLL
I
z
a
cu
=
8
6
0
7
cc
0
0
I
.
6
7
Page 10
R-8470
-8570
DESCRIPTION AND FUNCTION OF COMPONENTS
LOWER LATCH
The upper and lower latch switches are activated by the latch heads on the door. When the door is opened, the switches interrupt the circuit to the power trans­former, etc. For detais, refer to Oven Schematic dia­gram. And the switches interrupt the circuit to the heating element for model which is provided the heating ele­ment. A cook cycle cannot take place until the door is firmly closed thereby activating both latch switches.
UPPER
LATCH
normally closed. At this time the upper latch switch are in the OFF condition (contacts open) due to their being normally open contacts switches.
2. As the door goes to a closed position, the monitor switch contacts are first opened and then the upper
latch switch contacts close. (When opening the
door, each of these switches operate inversely.).
3. In the door is opened and the upper latch switch contacts fail to open, the fuse blows simultaneously with the closing of the monitor switch contacts.
CAUTION: BEFORE REPLACING A BLOWN FUSE,
TEST THE MONITOR SWITCH, UPPER
LATCH SWITCH FOR PROPER OPERA­TION. (REFER TO CHAPTER “TEST PRO­CEDURE”)
The door can be opened by grasping the door handle and pulling strong. When the door is pulled, the lower and upper latch
heads mounted in the door are raised up to release them from the latch hooks. The door can now be opened.
LATCH
SWITCH
.
MONITOR SWITCH The monitor switch is activated (the contacts opened) by the upper latch head on the door while the door is closed. This switch is intended to render the oven in­operative by means of blowing the fuse when the contacts of the upper latch switch falles to open when the door is opened. Functions:
1. When the door is opened, the monitor switch con-
tacts close (to ON condition) due to their being
LATCH
LOWER LATCH
HEAD
HEAD
Open
Page 11
-8470
R-8570
Usually, the damper is open position except during the
convection cooking.
Damper position is set automatically by damper motor, damper switch, motor cam and damper shaft. These components are operated according to the signal that judges the microwave cooking or convection cooking operation in the control unit.
Microwave Cooking:
Damper is in the open position, because a portion of cooking air is channeled through the cavity to remove steam and vapors given off from the heating foods.
It is then exhausted at the top of the oven cavity into a condensation compartment.
Convection Cooking:
Damper is in the closed position, so that no hot air will
be allowed to leak out the oven cavity.
Damper Operation
1. When power supply cord is plugged in:
l-l.
1-2.
1-3.
I-4.
l-5.
When power supply cord is plugged in, a sig-
nal is sensed in the control unit, and operates
the shut-off relay (RY6).
Contacts of shut-off relay (RY6) close, then
the damper motor is energized, opening the
damper door.
When damper is moved to the open position
by the damper cam damper switch is closed
(ON position). The signal of damper switch is re-sensed in the control unit and shut-off relay (RY6) is turned off. The 240 volts A.C. to the damper motor is stopped and the motor turns off.
2. When oven is microwave cooking: Damper is in the open position.
3. When oven is convection cooking:
3-l. 3-2.
3-3. 3-4.
Damper motor is energized by touching the convection, temperature and START pads. When damper is in the closed position
(damper switch is OFF), its signal is sensed
by the control unit, and shut-off relay (RY6)
is de-energized. The damper is held in the closed position
during the convection cooking operation.
At the end of the convection cooking, the shut-off relay (RY6) is energized, and damper
is returned to the open position.
DAMPER
DAMPER
DAMPER CAM
MOTOR
D-3.
Page 12
R-8470 R-8570
SERVICING
When troubleshooting the microwave oven, it is
IMPORTANT: If then oven becomes inoperative
cause of a blown monitor fuse in the
forming the checks. Many of the passible causes of
monitor switch and upper latch switch
trouble will require that a specific test be performed.
circuit, check the monitor switch and
These tests are given a procedure letter which will be
upper latch switch before
found in the “Test Procedure”section.
the monitor fuse.
TEST
Home fuse blows when power
Shorted wire in power cord or wire har-
Replase cord or check wiring.
cord is plugged into wall recepta-
ness.
cle.
Monitor fuse blows when power
Shorted wire in power cord or wire har-
Replace power cord or check
cord is plugged into wall recepta-
ness.
and repair harness.
Defective monitor switch.
Procedure F. Check home fuse.
when power cord is first plugged
Blown monitor fuse.
Psocedure G.
into wall outlet.
Blown magnetron temp. fuse.
Psocedure H.
Open wire in power cord, wiring harness,
Replace or repair wiring. or wiring between control panel assembly units.
Defective control unit.
Procedure K. Defective relay unit.
Procedure J.
Display does not operate properly
Defective key unit.
Procedure L.
when
STOP/CLEAR
key is
touched. (Buzze should sound
defective control unit.
Procedure K.
and time of day should appear in
Defective relay unit
Procedure J.
display.)
Defective stop switch
Procedure E.
Oven lamp does not light with No power in home.
Check wall outlet.
door opened.
Open wire in power cord or wire harness.
poplace same or repair wir-
Defective oven lamp.
Replace.
Defective upper latch switch.
Procedure E.
Open or loose wire connection to the Check wiring. above components.
Blow monitor fuse or magnetron temp.
Procedure G or H.
fuse.
10
Page 13
R-8470 R-8570
COOKING CONDITION
Oven lamp does not light in cook
Defective shut-off relay
on relay Procedure J.
cycle.
unit.
(Does light when door is opened)
Defective control unit
Procedure K
Oven lamp does not light at all.
Burned out bulb.
Replace
Open wiring of oven lamp.
Check and repair wiring
Oven lamp lights, but turntable
Open or loose wiring to turntable motor.
Check and repair wiring
motor does not operate.
Defective turntable motor.
Replace
Turntable motor operates normally
Defective cooling fan motor.
Replace.
but cooling fan motor dies not
Defective shut-off relay (RY5) on relay Replace
operate
unit. Open or loose wiring to fan motor
Check and repair wiring
MICROWAVE
Oven des not go into a cook cycle when START pad is touched.
Oven seems to be operating but little or no heat is produced in
oven load. (Food
incompletely cooked or not cooked at all at end of cook cycle.)
Oven does into a cook cycle but extremely
uneven
heating is
produced in oven load(food). Oven does not cook properly
when programed for MEDIUM etc. cooking powers.
(Operates properly on HIGH)
Oven does not cook properly when programed in COMPU DE­FROST cooking mode
Upper and/or lower latch switches
Procedure E.
tive or out of adjustment. Defective cook relay (RYI ) on relay unit.
Procedure J.
Defective control unit.
Procedure K.
Defective key unit.
Procedure L.
Open or loose wiring to above compo-
Check and repair wiring
nents. Defective magnetron.
Procedure A.
Defective cook relay
on relay unit.
Procedure J.
Defective power transformer.
Procedure B.
Defective rectifier.
Procedure C.
Defective high voltage capacitor.
Procedure D.
Defective control unit.
Procedure K.
Open or loose wiring to above compo-
Check and repair wiring nents. Low voltage. Dirty oven cavity.
Turntable motor does not operate. Refer to proceding turntable
motor problem.
Defective control unit.
Procedure K. Defective key unit.
Procedure L. Open or loose wiring to above compo-
Check and repair wiring nents.
Defective COMPU DEFROST function.
Refer to COMPU DEFROST
section on operation manual
and check control unit.
Page 14
CONVECTION
CONV indicator light but oven Defective key unit.
Procedure L
does not go into a cook cycle Defective thermistor.
Porcedure N
when START pad is touched.
Open wiring in circuit to above compo- Check and repair wiring. nents.
CONV indicator lights, but heating
Defective heating element.
Procedure I
element does not heat.
Defective heater relay(RY4) on relay unit.
Porcedure J
Defective control unit.
Procedure K
Open or loose wire connection
to the Check and repair wiring.
above components
Temperature in the oven cavity is
Defective heating element.
Procedure I
lower or higher than preset,
Defective control unit.
Porcedure K
Defective convection mortor.
Replace motor.
Defective thermistor.
Procedure N
Defective cooling fan motor.
Replace
Defective dumper motor
Procedure 0
Defective drive mechanism of convection Check.
fan.
I
SENSOR (R-8570)
Oven is in the sensor cooking AH sensor open and/or short. condition but AH sensor does not
Defective control unit.
Procedure M Procedure K
end stage 1 or does not stop
Open or loose wire connection
to the Check and reapir wiring.
cooking cycle.
above components.
12
Page 15
R-8470 R-8570
TEST
TEST
DISCHARGE THE HIGH VOLTAGE CAPACITOR BEFORE TOUCHING ANY OVEN COMPO­NENTS OR WIRING.
To test for an open filament, isolate the magnetron from the high voltage circuit. A continuity check across the magnetron filament leads should indicate less than 1 ohm.
To test for a shorted magnetron, connect the ohmmeter leads between the magnetron filament
leads and chassis ground.
This test should indicate an infinite resistance. If there is little or no
resistance, the magnetron is grounded and must be replaced.
Power output of the magnetron can be measured by performing a water temperature rise test. This test should only be used if above rests do not indicate a faulty magnetron and there is no defect in the following components or wiring: rectifier, high voltage capacitor, heater transformer and power transformer.
POWER
be measured by using water load how much it can be absorbed by the water load. To measure the microwave output power in the microwave oven, the relation of calorie and watt is used. When P(W) heating works for t(second), approximately P x
calorie is generated. On the
other hand, if the temperature of the water with V(ml) rises AT (
during this microwave
heating period, the calorie of the water is V x AT. The formular is as follows;
P x t
4.2 = V x AT
P (W) = 4.2 x V x AT
t
Our condition for the water load is as follows:
Water load . . .
2000 ml, Heating time
.
seconds (2 minutes)
AT
Measuring method;
1. Put the water load of two (2) litres on the
of the oven shelf. The water load should be arranged in two (2) Pyrex beakers, the size of which is one (1) litre, and be placed at right and left, side by side, on the oven shelf.
2. Measure the temperature of water before heating and also after heating during two minutes by microwave, and calculate the temperature rise.
The temperature rise should be the average
of temperature differences measured in each beaker.
3. The output power should be calculated as follows. In case the measuring result is not satis­factory, execute the measurement several times and judge the result from the synthetic point of view. Microwave output power should be within
5% of the nominal one.
Calculation of output power; Microwave output power . ..P (W) = 70 x AT ( “C)
AT = ( ATL + ATR)
2 : average temperature rise
ATL = (TL2
ATR = (TR2
TL2 : water temperature after heating in left beaker
: water temperature before heating in left beaker
TR2 : water temperature after heating in right beaker
Measuring condition; As the microwave output is affected by several conditions, the measurement should be made carefully with following attentions.
1. Initial temperature of salt water should be 20
1
(The salt water should be contained bon (1) percent of salt.) Well and quickly stir the water and the temperature measurement should be done immediately after heating.
2. The graduation of thermometer should be scaled by 0.1
at minimum and an accurate mer-
cury thermometer is recommended.
13
Page 16
TEST
3. Water container should be one (1) litre beaker made of Pyrex glass and its diameter approxi­mately
cm.
4. Room temperature should be around 20
5. Power supply voltage should be specification voltage.
TEST
DISCHARGE THE HIGH VOLTAGE
BEFORE TOUCHING ANY OVEN COMPO-
NENTS OR WIRING. Disconnect the primary input terminals and measure the resistance of the transformer with an
ohmmeter. Check for continuity of the coils with an ohmmeter. On the R x 1 scale, the resistance of the primary coil should be less than 1 ohm and the resistance of the high voltage coil should be approximately 73 ohms; the resistance of the filament coil should be less than 1 ohm.
(HIGH VOLTAGES ARE PRESENT TO HIGH VOLTAGE TERMINAL, SO DO NOT ATTEMPT TO
MEASURE THE FILAMENT AND HIGH VOLTAGE.)
C
RECTIFIER TEST
DISCHARGE THE HIGH VOLTAGE CAPACITOR BEFORE TOUCHING ANY OVEN COMPO­NENTS OR WIRING.
Isolate the rectifier from the circuit. Using the highest ohm scale of the meter, read the resistance across the terminals and observe, reverse the leads to the rectifier terminals and observe meter reading. If a short is indicated in both directions, or if an infinite resistance is read in both di­rections, the rectifier is orobablv defective and should be replaced.
TEST
DISCHARGE THE HIGH VOLTAGE CAPACITOR BEFORE TOUCHING ANY OVEN COMPO-
NENTS OR WIRING.
If the capacitor is open, no high voltage will be available to the magnetron. Disconnect input leads and check for short or open, between the terminals using an ohmmeter.
Checking with a high ohm scale, if the high voltage capacitor is normal, the meter will indicate continuity for a short time and should indicate an open circuit once the capacitor is charged. If the above is not the case, check the capacitor with the ohmmeter to see if it is short circuited
between the terminals. If it is short circuited, replace the capacitor.
TEST
Isolate the switch and check the connection by using the ohmmeter accord ing to the following table.
If improper operation is indicated, make the necessary switch adjustment or replacement.
Table: Switch Connection
Connection
Common Terminal-Normally Open Terminal
Common Terminal-Normally Close Terminal
Operation
Open circuit
Close circuit
Plunger released Plunger pushed
Closed circuit
Open circuit
TEST
Before performing this test, make sure that the upper latch switch is operating properly referring to the above Switch Test Procedure. Check the monitor switch operation by using the ohmmeter as following figure. When the door is open, the meter should indicate a closed circuit. When the monitor switch lever of the upper latch hook is pushed by a screw driver through the upper latch hole on the front plate of the oven cavity with the door opened (in this condition the plunger of the monitor switch is pushed in), the meter should indicate an open circuit.
If improper operation is indicated, replace the defective switch.
14
Page 17
R-8470
-8570
TEST
LATCH
MONITOR SWITCH LEVER
FUSE
If the monitor fuse in the primary-secondary-monitor switch circuit is blown when the door is opened, check the primary and secondary interlock switches and monitor switch according to the Test Procedure of those switches, before replacing the blown monitor fuse.
If the monitor fuse is blown by improper switch operation, adjust or replace the defective switch and monitor fuse at the same time.
Replace just the monitor fuse if the switches operate normally. CAUTION; REPLACEMENT FUSE MUST BE THE LISTED FUSE IN PARTS LIST.
FUSE TEST
A continuity check across the temp. fuse terminal should indicate a closed circuit. If the temperature of the magnetron reaches 115
temp. fuse opens. If the temp. fuse has opened, replace the fuse. An open temp. fuse indicates overheating of the magnetron assembly. Check for restricted air flow to the magnetron through the opening in the chassis, especially the cooling duct.
TEST
Make sure the heating element is fully cooled and test as follows; a. Disconnect wire leads and measure the resistance with an ohmmeter. On the R x 1 scale, the
resistance between the heating element terminals should be approximately 38.4 ohms.
b. Disconnect wire leads and measure the insulation resistance with 500V
1 OOM
insulation
resistance meter.
The insulation resistance between heating element terminal and cavity should be more than
15
Page 18
R-8470
-8570
TEST
TEST
The relay unit consists of circuits including the shut-off relays, buzzer, transformer, etc.
Plug power cord into wall receptacle “88888” will be flashing in the display. Remove the outer case and check voltage between Pin Nos.
1 and 3 of the
connector
(A) on the relay unit with an A.C. voltmeter. The meter should indicate 240 volts, if not check oven circuit. Shut-off , Cook and Heater Relay Test These relays are operated by D.C. voltage.
Check voltage at the relay coil with a D.C. voltmeter during the microwave or convection cooking operation.
DC. voltage indicated
. . . . . . . . . . Defective
relay.
DC. voltage not indicated
. . . . . . ..Check diode which is connected to the relay coil. If diode is
good, control unit is defective.
RELAY SYMBOL
(COOK) RY2 RY3 RY4 (HEATER) RY5 RY6
OPERATIONAL
VOLTAGE
Approx. 14 V.D.C. Approx. 14 V.D.C. Approx. 14 V.D.C. Approx. 14 V.D.C. Approx. 14 V.D.C. Approx. 14 V.D.C.
CONNECTED COMPONENTS
Power transformer Oven lamp/Turntable motor Convection motor Heating element Cooling fan motor Damper motor
TEST
The touch control panel consists of circuits including semiconductors such as LSI, Therefore, unlike conventional microwave ovens, proper maintenance cannot be performed with
only a voltmeter and ohmmeter.
In this service manual, the touch control panel assembly is di-
vided into three units Control Unit, Key Unit and Relay Unit and troubleshooting by unit re-
placement is described according to the symptoms indicated.
1. Key Unit.
The following symptoms indicate a defective key unit. Replace the key un it.
a) When touching the pads, a certain pad produces no signal at all. b) When touching a number pad, two figures or more are displayed. c) When touching the pads, sometimes a pad produces no signal.
2. Control Unit
The following symptoms indicate a defective control unit. Replace the control unit.
2-l In connection with pads. a) When touching the pads, a certain group of pads do not produce a signal. b) When touching the pads, no pads produce 2-2 In connection with indicators a) At a certain digit, all or some segments do not light up.
b) At a certain digit, brightness is low when it lights-up. c) Only one indicator does not light up. d) The corresponding segments of all digits do not light up; or they continue to light up. e) Wrong figure appears. f) A certain group of indicators do not light up. g) The figure of all digits flicker. 2-3 Other possible troubles caused by defective control unit. a)
Buzzer does not sound or continues to sound.
b) Clock does not operate properly. c) Cooking is not possible. d) Proper temperature measurement is not obtained.
Note: When a defective one or more of three components, the Control Unit, Key Unit or Relay
Unit are replaced, the defective part or parts must be properly packed for return in the shipping carton, with its cushion material, in which the new replacement part was shipped to you.
Page 19
R-8470 R-8570
TEST
TEST
If the indicator does not respond to touching a key Pad use the following matrix and place a
jumper wire between the proper pin connections with the cable connector disconnected from the
control unit.
If the indicator responds and oven goes into operation, the key unit was faulty. If there is no response, replace the control unit.
KEY UNIT
SENSOR TEST
sensor
(1) The oven should be plugged in at least five minutes
sensor cooking. (2) Room temperature should not exceed 35 (3) The unit should not be installed in any area where heart and steam are generated. The unit
should not be installed, for example, next to a conventional surface unit. Refer to the “INSTALLATION Instruction”.
(4) Exhaust vents are providend on the back of the unit for proper cooling and air flow in the
cavity.To permit adequate ventilation,
be sure to install so as not to block these vents.
There should be some space for air circuration.
(5) Be sure the exterior of the cooking container and the interior of the oven arer dry. Wipe
off any moisture with a dry cloth or paper towel.
(6) The Sensor works with food at normal storage temperature.For example, chicken pieces
would be at refrigerator temperature and canned soup at room temperature. (7) Foods weighing less than 3 ounces should be cooked by time and vaiper power. (8) Avoid using aerosol sprays or cleaning solvents near the oven while using Sensor settings.
The sensor will detect the vapor given of by the spray and turn off
food is propary
cooked. (9) After 30 minutes it the sensor has not detected the vapor of the food, ERROR will appear
and the oven will shut off. When cooking bacon, the sensor must detect the vapor within
1-l
minutes before ERROR appeares and oven shuts off.
load
Make sure the oven has been plugged in at least five minutes before checking sensor cook op-
eration. The cabinet should be installed and screws tightened.
(1) Fill approximately 200 milliliters (7.2 oz) of tap water in a 1000 milliliter measuring cup. (2) Place the container on the center of tray in the oven cavity. (3) Close the door. (4) Touch SENSOR COOK pad and number pad 1 .Now, the oven is in the sensor cooking
condition and AS-l will appear in the display.
(5) Touch Start pad.The oven will operate for the first 16 seconds, without generating micro-
wave energy.
When the AH sensor is defective (open or short), ERROR will appear in the display after 16 seconds cooling time.
If ERROR appears check sensor wire connections and/or AH sensor. NOTE: ERROR will appear if the door is opend or STOP/CLEAR pad is touched during first
stage of sensor cooking.
17
Page 20
R-8470 R-8570
TEST
(6) After approximately 16 seconds, microwave energy is produced,oven should turn off when
water is boiling (bubling).
If the oven dose not turn off, replace the AH sensor or check the control unit, refer to expla­nation below:
AH SENSOR
To determine if the sensor is defective, the simplest method is to replace it with a new re­placement sensor.
(1) Disconnect oven from power supply and remove outer case. (2) Discharge the high voltage capacitor. (3) Remove the AH sensor. (4) Install the new AH sensor. (5) Re-install the outer case. (6) Reconnect the oven to the power supply andcheck the sensor cook operation proceed as
follows: 6-l. Touch SENSOR COOK pad and number 1 pad.
6-2. Touch Start pad. The contorol panel is in the automatic Sensor operation. 6-3. The oven will turn off automatically when the water is boiling (bubling).
N
If new sensor dose not operate propaly, the problem is with the contorol unit.
TEST
Disconnect the connector-E from the control unit. Measure the resistance of the thermistor with an ohmmeter. Connect the ohmmeter leads to Pin No’s E-l and E-2.
Room Temp.
Resistance
68 “F(20 86 “F(30 Approx. 350 155k
If the meter does not indicate above resistance, replace the thermistor.
0
TEST
When the power cord is plugged into the wall receptacle, the 240 volts A.C. is supplied to the damper motor and the motor operates until the damper is opened and the damper switch closes. Then the damper motor stops operation.
If the damper motor does not operate, check for input voltage by A.C. volt-meter at the motor.
1. Disconnect the power cord from the wall receptacle.
2. Disconnect the wire loads of motor and connect the meter leads to the wire leads of main wire harness.
3. Reconnect the power cord into the wall receptacle.
If 240 volts A.C. is. indicated at the wire leads, replace the motor. Not indicated, check the wire harness and the relay unit.
TEST
Disconnect the wire leads from the switch terminals and connect the ohmmeter leads to the
common (COM and normaly open (NO) terminal of the switch.
1. When switch actuator is pushed by the damper motor cam, the meter should indicate a closed circuit.
2. When the power cord is plugged into the wall receptacle, the damper motor operates and damper cam rotates. The switch
is released and meter sould indicate an open circuit.
If improper operation is indicated, replace the damper switch.
18
Page 21
R-8470 R-8570
TEST
a
THE
type temperature meter must be used.
A low priced bi-metal type thermometer is not reliable or
accurate.
The temperature should be checked approximately 5 minutes after the preheat temperature is
reached (audible signal sounds four times). The temperature experienced may be approximately 20
more or less than indicated on the display, however, in most cases the food cooking results
will be satisfactory.
Difference in power supply voltage will also affect the oven temperature, The household power supply voltage may sometimes become lower than the rated voltage ( 240 ) and cause under-cooking. If the power supply voltage is 10% lower than the rated voltage, longer cooking
time is required by 10% to 20%.
19
Page 22
R-8470 R-8570
TOUCH CONTROL PANEL ASSEMBLY
OUTLINE OF TOUCH CONTROL PANEL
The touch control section consists of the following
units as shown in the block diagram. (1) Control Unit (2) Key Unit (3) Relay Unit
Exchange of signals between each unit is indicated by
the arrows in the block diagram. The principal func-
tions of these units and the signal communicated among them are explained below.
Relay unit consists of six relays (RYI -RY6), power
source circuit and buzzer circuit.
The key unit is composed of a matrix, signals generated
in the LSI are sent to the key unit through
El 1 -El 3and El 5-E17. When a key pad is touched, a signal is completed through the key unit and passed back to the LSI through
to perform the function that was
requested.
Control unit consists of LSI, power source circuit, synchronizing signal circuit, ACL circuit, buzzer circuit, temperature measurement circuit, absolute humidity sensor circuit and indicator circuit.
This LSI controls the temperature measurement signal, AH sensor signal,key strobe signal relay driving signal for oven function and indicator sig­nal.
Source
This circuit generates voltage necessary in the
control unit. Symbol Voltage Application
VC
-5v
(ICI), ACL circuit and tem-
perature measurement circuit
VP
-15v Buzzzer circuit and IC2 IC2 (R-8570 only)
-34v Fluorescent display tube : Grid
and anode voltage
-25V Filament of fluorescent display
tube
VF2
-28V
VF2 voltage
The power source synchronizing signal is available
in order to compose a basic standard time in the
clock circuit.
It accompanies a very small error because it works on commercial frequency.
Cirucit to generate signals resetting the LSI to the initial state when power is supplied.
The buzzer is responsive to signals from the LSI to emit noticing sounds (key touch sound and
completion sound).
Oven
The temperature in the oven cavity is sensed by the thermistor. The variation of resistance according to sensed temperature is detected by the temperature meas-
urement circuit and the result applied to LSI. The result of detecting is given to LSI controlling the relay and display.
Sensor
The circuit detects absolute humidity of a food
which is under cooking, to allow its automatic
cooking.
to “tell” the LSI if the door is open or
To drive the magnetron, heating element, fan mo­tor, convection motor,damper motor, turntable
motor and light the oven lamp.
Indicator element is a Fluorescent Display.
Basicalloy, a Fluorescent Display is triode having a cathode, a grid and an anode. Usually, the cathode
of a Fluorescent Display is directly heated and the filament serves as cathode. The Fluorescent Display 7-digits, 15-segments are
used for displaying figures.
20
Page 23
-8470
-8570
1
2
3
4
5
6
1
2
3
4
5
6
21
Page 24
R-8470
-8.570
1X2429)
The I/O
I of the LSl(lX2429) is detailed in the following table.
DESCRIPTION OF LSI
PIN NO.
SIGNAL
EO-E5
I
OUT
Refer to the touch control panel circuit about the relation between signals and digits. Normally, one pulse is output in every synchronized signal period, and input to the grid of the fluorescent display.
PIN NO.
7
SIGNAL
E6
I
OUT
signals.
Refer to the touch control panel circuit about the relation between signls and indicators. Normally, one pulse is output in every synchronized signal period, and input to the grid of the fluorescent display.
PIN NO.
8
Signal similar to E6.
SIGNAL
E7
I
OUT
Signal applied to touch-key section. A pulse signal is input to
terminal while one of G-2 line keys on key matrix is touched.
PIN NO.
9
Signal similar to E6.
SIGNAL
E8
I
OUT
Signal applied to touch-key section. A pulse signal is input to
terminal while one of G-3 line keys on key matrix is touched.
PIN NO.
Signal similar to E6.
SIGNAL
I
OUT
PIN NO.
12
SIGNAL
El1
I
OUT
Signal similar to E6.
Signal applied to touch-key section. A pulse signal is input to
terminal while one of G-4 line keys on key matrix is touched.
PIN NO.
13
Signal similar to
SIGNAL
El2
OUT
Signal applied to touch-key section. A pulse signal is input to
terminal while one of G-5 line keys on key matrix is touched.
PIN NO.
14
SIGNAL
El3
OUT
Signal similar to E6. Signal applied to touch-key section.
A pulse signal is input to
terminal while one of G-6 line keys on key matrix is touched,
Page 25
R-8470 R-8570
PIN NO.
15
SIGNAL
El4
data siqnal.
Signal similar to E6.
PIN NO.
16
SIGNAL
El5
OUT
data siqnal.
Signal similar to E6.
siqnal.
Signal applied to touch-key section. A pulse signal is input to
terminal while one of G-7 line keys on key matrix is touched.
17
data siqnal.
Signal similar to E6.
siqnal.
SIGNAL
El6
OUT
Signal applied to touch-key section. A pulse signal is input to
terminal while one of G-8 line keys on key matrix is touched.
PIN NO.
18
SIGNAL
El7
OUT
siqnal.
Signal similar to E6.
siqnal.
Signal applied to touch-key section. A pulse signal is input to
terminal while one of G-9 line keys on key matrix is touched.
PIN NO.
SIGNAL
I
OUT
siqnal.
Signal similar to E6.
PIN NO.
21-24
SIGNAL
E23
I
OUT
R-8470: Terminal not used. Connected to GND.
R-8570:
Used for initial balancing of the bridge circuit(absolute himidity sensor).
PIN NO.
25
SIGNAL
EX
IN
clock
The internal clock frequency is set by inserting the ceramic filter oscillation circuit with respect to X terminal.
PIN NO.
SIGNAL
X
OUT
clock
Output to control oscillation
of EX.
PIN NO.
27
SIGNAL
RESET
IN
Signal is input to reset the LSI to the initial state when power is supplied. Temporarily set to “L” level the moment power is supplied, at this time the LSI is reset. Thereafter set at “H” level.
PIN NO.
data siqnal.
Signal similar to E6.
SIGNAL
SO E24
OUT
23
Page 26
PIN NO. 29
SIGNAL E25
I
OUT
R-8470: Terminal not used. R-8570: Used for initial balancing of the bridge circuit(absolute himidity sensor).
NO.
30
SIGNAL
E26
I
I/O
OUT
sound buzzer.
A: Key touch sound.(0.12 sec.) B: Completion sound. (2.4 sec.) C: When the temperature of the oven cavity reaches the preset temperature in the preheating mode, or when the
preheating hold time (15 minutes) is elapsed. (1.2 sec. ON-l
sec. OFF repeat)
PIN NO. 31
SIGNAL
IRQ E27
IN
This is the basic timing for time processing of LSI.
PIN NO.
32
SIGNAL
Vss
source
VC voltage of power source circuit input.
I
IN
PIN NO.
33
SIGNAL
RO
To turn on and off the cook relay.
I
OUT
In HIGH operation, the signals holds “L” level during microwave cooking and “H” level while not cooking. In other cooking modes (MED. HIGH, MED., MED. LOW, LOW) the signal turns to “H” level and “L” level in repetition according to the power level.
PIN NO.
34
SIGNAL
RI
I
OUT
To turn on and off the control relay. The pulse signai(50Hz) is delivered to the control relay driving circuit and cook relay and heater relay control cir­cuit.
PIN NO.
35
SIGNAL
R2
OUT
To turn on and off the heater relay. “L” level during convection cooking; “H” level otherwise. During convection cooking or mix cooking, the signal becomes “H” level when the temperature of the oven, cavity exceeds the predetermined temperature.
PIN NO.
36
SIGNAL
R3
I
OUT
To turn on and off the cooling fan motor relay.
“L” level during both microwave and convection cooking; “H” level
otherwise.
PIN NO.
37
SIGNAL
R4
OUT
To turn on and off the convection motor.
“L” level during CONVECTION or MIX COOK; “H” level otherwise.
24
Page 27
R-8470 R-8570
PIN NO.
SIGNAL
R5
signal.
To turn on and off the damper motor relay.
I
OUT
PIN NO.
39
signal.
Signal similar to EO.
SIGNAL
R6
OUT
PIN NO.
40
SIGNAL
R7
I
IN
signal
Damper opened; “H” level signal. Damper closed; “L” level signal.
PIN NO.
41
SIGNAL
E37
change
Signal in accordace with the model in operation is applied to set up its function.
IN
PIN NO.
42
SIGNAL
E36
I
IN
signal
LSI.
Door closed; “H” level signal. Door opened;
“L” level signal.
PIN NO.
43
Connected to VC.
SIGNAL
I
IN
PIN NO.
44
SIGNAL
AVR-
A reference voltage applied to the A/D converter in the LSI. The reference voltage is generally maintained at -5V.
IN
PIN NO.
45
SIGNAL
AVR+
I
IN
A reference voltage applied to the A/D converter in the LSI.
PIN NO.
46
Connected to GND.
SIGNAL
IN
PIN NO.
47
SIGNAL
AN7
I
IN
key.
When either one of G-l 3 line keys on key matrix is touched, a corresponding signal out of
-El 3 and
El
will be input into AN7.
When no key is touched, the signal is held at “L” level.
PIN NO.
48
SIGNAL
AN6
I
IN
key.
When either one of G-12 line keys on key matrix is touched, a corresponding signal will be input into AN6.
PIN NO.
SIGNAL
AN5
IN
kev.
When either one of G-l 1 line keys on key matrix is touched, a corresponding signal will be input into AN5.
PIN NO.
50
SIGNAL
AN4
IN
key.
When either one of G-10 line keys on key matrix is touched, a corresponding signal will be input into AN4.
25
Page 28
-8470
R-8570
PIN NO.
51
SIGNAL
AN3
I
I/O
IN
R-8470:
Terminal not used. No connection.
R-8570: Used for initial balancing of the bridge circuit (absolute humidity sensor).
This input is an analog input terminal from the AH sensor
connected to the A/D converter built into the
PIN NO.
52
R-8470:
SIGNAL
AN2
I
IN
Terminal not used. No connection.
R-8570:
sensor
This input is an analog input terminal from the AH sensor circuit,
and connected to the A/D converter built into the
PIN NO.
53
SIGNAL
AN1
IN
By inputting DC voltage corresponding to the temperature detected by the thermistor, this input is converted into
temperature by the A/D converter built into the LSI.
PIN NO.
54
SIGNAL
AN0
IN
Terminal not used. Connected to GND.
PIN NO. 55
SIGNAL
R8
Terminal not used. Connected to VC.
I
OUT
PIN NO.
56-60
Terminal not used.
SIGNAL
I
IN
PIN NO.
61
SIGNAL
Terminal not used. Connected to GND.
IN
PIN NO.
62
SIGNAL
IN
Normally connected to VC.
PIN NO.
63
SIGNAL
NC
Terminal not used. Connected to GND.
I
NC
PIN NO.
64
Connected to GN D.
SIGNAL
Vcc
I
IN
26
Page 29
-8470
R-8570
ABSOLUTE HUMIDITY SENSOR CIRCUIT (R-8570
Sensor
The absolute humidity sensor includes two thermistors as shown in the illustration. One thermister is housed in the closed vessel filled with dry air while another in the open vessel. Each sensor is provided with the protective cover mode of metal mesh to be protected from the external airflow.
Internal Structure of
The figer below shows the basic structure of an absolute humidity sensor.
A bridge circuit is
by two thermistors and two resistors (RI and R2). The output of the bridge circuit is to be amplified by the operational amplifier.
Each thermister is supplied with a current to keep itself heated at about 150
(302 “F) and the re­sultant heat is dissipated in the air and if the two thermistors are placed in different humidity condi­tions they
show different degrees
of heat
leading to potential difference between them causing an output voltage from the bridge circuit, the intensity of which is increased as the absolute humidity of the air increases. Since the output is very minute, it will be amplified by the
operational amplifier.
This detector circuit is used to detect the output voltage of the a absolute humidity circuit to allow the LSI to control the sensor cooking of the unit. When the unit is set in the sensor cooking mode, 16 seconds later the detector circuit starts to func­tion and the LSI observes the initial voltage availabel at its AN2 terminal. With this voltage given, the switches SW1 to SW5 in the LSI are
turned on in such a way as to change the resistance values in parallel with R50.
Changing the resistance values results in that there is the same potential at both F-3 terminal of the absolute humidity sensor and AN3 terminal of the
The voltage of AN2 terminal will indicate
about -2.5V. This initial balancing is set up about
16 seconds after the unit is put in the Sensor Cooking mode. As the sensor cooking proceeds, the food is heated to generate moisture by which the resistance bal­ance of the bridge circuit is deviated to increase the voltage available at AN2 terminal of the LSI. Then the LSI observes that voltage at AN2 terminal and
compares it with its initial value, and when the comparison rate reaches the prest value (fixed for each menu to be cooked), the LSI causes the unit to stop the sensor cooking; thereafter, the unit gets in the next necessary operation automatically.
When the LSI starts to detect the initial voltage at
AN2 terminal 16 seconds after the unit has been put in the Sensor Cooking mode, if it is impossible to take a balance of the bridge circuit due to dis­connection of the absolute humidity sensor, ER-
ROR will reappear on the display and the cooking is stopped.
1 )Absolute humidity sensor circuit
c
I”
. .
23
t
I
,
2)lnternal equivalent circuit of
Top View
27
Page 30
A -8470
-8570
SERVICING
Precautions for Handing Electronic
Components
This unit uses PMOS LSI in the integral part of the
circuits. When handing these parts, the following precautions should be strictly followed.
PMOS LSI have extremely high impedance at its input and output terminals. For this reason, it is easily influenced by the surrounding high voltage power source, static electricity charged in clothes, etc,and sometimes it is not fully protected by the
built-in protection circuit.
In order to protect PMOS LSI.
1) When storing and transporting, throughly wrap them in aluminum foil. Also wrap PW boards containing them in aluminium foil.
2) When soldering,
ground the technician as shown in the figure and use grounded soldering iron and work table.
Touch
Panel
We describe the procedures to permit servicing the touch control panel of the microwave oven and the cautions you must consider when doing so. To carry the servicing, power supply to the touch control panel is available either from the power line of the oven proper itself of from an external power source.
panel
supply
oven proper:
OF
OVEN IS STILL
YOU
SER-
Therefore, when checking the performance of the touch control panel,put the outer cabinet on the oven proper to keep you from touching the high voltage transformer, or unplug the primary terminal (connector) of the high volt­age transformer to turn it off; and the end of such connector shall be insulated with an in­sulating tape. After servicing, be sure to replace
the leads to their original locations.
A. On some models, the power supply cord be-
tween the touch control panel and the oven
proper is so short that they can’t be separated
from each other.
For those models, therefore, check and repair all the controls (with the sensor-related ones included) of the touch control panel while keeping it in contact with the oven proper.
3.
4.
B.
On some models, on the other hand, the power supply cord between the touch control panel and the oven proper is so long that they may
be separated from each other. For those mod­els, therefore, it is allowed to check and repair the controls of the touch control panel while
keeping it apart from the oven proper;in this
case you must short both ends of the stop switch (on PWB) of the touch control panel
with a jumper, which brings about an opera-
tional state that is equivalent to that with the
oven door being closed.
As to the sensor-related controls of the touch
control panel, their checking is allowed if the
dummy resistor(s) whose resistance is equal to
that of those controls is used.
panel
Disconnect the touch control panel completely from the oven proper,and short both ends of the stop switch (on PWB) of the touch control
state that is equivalent that with the oven door
being closed. And connect an external power source to the power input terminal of the touch
control panel, and then it is allowed to check
and repair the controls of the touch control
in the case of (1 )-B above, it is here
also possible to check the sensor-related con­trols of the touch control panel by using the
dummy resistor(s).
Tools
Tools required when serivicing the touch control panel assembly.
1) Soldering:
3ow
(To prevent leaking current, it is recommended to
use a soldering iron with grounding terminal.)
2) Oscilloscope: Single beam, frequency range: DC
type or more ad-
vanced model.
3) Others:
Other tools
1) When turning on the power source of the con-
trol unit, remove the aluminum foil applied for
preventing static electricity.
2) Connect the connectors of the indicator and
key units to the control unit taking care that the lead wires are not twisted.
3)
After aluminum foil is removed, take extra care
that abnormal voltage due to static electricity
etc. is not applied to the input or output termi­nals.
4) Attach connectors, electrolytic capacitors, etc.
to PWB, taking care that all connections are tight.
5) Be sure to use specified components where
high precision is required.
28
Page 31
Page 32
R-8470 R-8570
MAGNETRON ASSEMBLY REMOVAL
Disconnect oven from power supply and remove
6. Lower the magnetron assembly until the tube is
outer case.
clear of the waveguide.
2. Discharge the high voltage capacitor.
7. Remove single (1) screw holding the cooling duct
3. Disconnect wire leads from the magnetron
(B) to the magnetron assembly.
bly.
8. Remove the cooling duct (B) from the magnetron.
4. Release the tab which is provided on cooling duct
CAUTION:
WHEN REPLACING THE MAGNETRON,
(B) to hold cooling duct (A).
BE SURE THE R.F. GASKET IS IN
5. Carefully remove four (4) mounting screws holding
PLACE
AND
THE
MAGNETRON
the magnetron assembly to waveguide while sup-
MOUNTING SCREWS ARE TIGHTENED
porting the magnetron assembly from below.
SECURELY.
CONVECTION MOTOR REMOVAL
1. Disconnect oven from power supply and remove outer case.
2. Disharge the high voltage capacitor.
3. Disconnect wire leads from the convection motor.
4. Remove two (2) screw holding the convection motor assembly to the chassis support and waveguide flange.
The convection motor assembly is now free.
7. Remove the two (2) screw and nuts holding the mounting bracket to the motor
8. Remove the pin and pulley (B) from the motor shaft.
5. Remove the convection fan belt.
6. Lift up the convection motor assembly and remove it from the unit.
9. The convection motor is now free. Note: The motor mounting plate with the convection
motor should be installed in close contact with the waveguide flange. Otherwise, the revolution of the convection fan belt may be disrupted.
COOLING FAN
MOTOR REMOVAL
1. Disconnect oven from power supply and remove outer case.
7. Remove the duct (A) with the cooling fan motor attached from the unit.
2. Discharge the high voltage capacitor.
3. Disconnect wire leads from the cooling fan motor.
4. Remove screw holding the grounding wire to the oven cavity flange.
5. Remove four (4) screw holding the chassis support to rear cabinet, cooling duct (A), convection motor mounting plate and control panel back plate.
6. Release the tab which is provided on
(B) to hold the cooling duct (A).
cooling duct
The cooling fan motor assembly is now free.
8. Remove the fan blade from the cooling fan motor shaft by pulling the fan retainer clip.
9. Remove two (2) screws and nuts holding the cooling fan motor and grounding wire to the cool-
ing duct (A).
The cooling fan motor is now free.
1. Disconnect oven from power supply outer case.
and remove
2. Discharge the high voltage capacitor.
3. Remove the magnetron assembly, refer to “Magnetron Assembly Removal”.
4. Disconnect two (2) connectors for the damper motor from the relay unit.
5. Disconnect two (2) connectors for the stop switch from the relay unit.
DAPMER ASSEMBLY
6. Remove two (2) screw holding the damper duct to oven cavity right-side.
7. Remove single (1) screw holding the damper duct
to rear cabinet.
8. Remove two (2) screws holding the damper duct to top of the oven cavity.
9. Remove the damper assembly from the unit.
30
Page 33
Page 34
UPPER/LOWER LATCH SWITCHES AND MONITOR SWITCH ADJUSTMENT
If the upper and lower latch switches and monitor switch do not operate properly due to a mis-adjustment, the following adjustment should be made.
1. Loosen the one (1) screw holding the upper latch hook to the oven cavity front flange and the one (1) screw holding the lower latch hook to the same
flange.
2. With the door closed, adjust the lower latch hook by moving it back and forward and then adjust the upper latch hook by moving it back and forward, or up and down. In and out play of the door al­lowed by the upper and lower latch hooks should be less than 0.5 mm. The vertical position of the upper latch hook should be placed where the upper latch switch and monitor switch have activated with the door closed. Vertical adjustment of the lower
latch hook is not possible.
3. Secure the screws with washers firmly.
4. Now, make sure of the upper latch switch opera­tion. If the upper latch switch has not activated with the door closed, loose the one (1) screw holding
the upper latch hook to the oven cavity front flange
and adjust the upper latch hook position.
After the adjustment, make sure of the following
points:
1. The in and out play of the door remains less than
0.5 mm at latched position. First check the upper latch hook position, pushing and pulling the upper portion of door toward the oven face. Then check the lower latch hook position, pushing and pulling the lower portion of door toward the oven face.
Both results (plays of the door) should be less than
2. The upper and lower latch switches interrupt the circuit before the door can be opened.
3. The monitor switch contacts close when the door
is opened.
4. Re-install the outer case and check for microwave
leakage around the door with an approved micro­wave survey meter. (Refer to Microwave Measure­ment Procedure.)
Latch
Page 35
Page 36
R-8470 R-8570
MICROWAVE MEASUREMENT
After the adjustment of the door latch switches, moni­tor switch and door are completed individually or col­lectively, the following leakage test must be performed with a survey instrument and it must be confirmed that the result meets the requirements of the performance standard for microwave oven.
The safety switch must prevent microwave radiation emission in excess of 5mW/cm2 at any point 5cm or more from external surface of the oven.
THE
Before beginning the actual test for leakage, proceed
as follows;
Make
test instrument is operating normally as specified in its instruction booklet. Important: Survey instruments that comply with the require­ment for instrumentations prescribed by the per­formance standard for microwave ovens must be used for testing.
Recommended instruments are: NARDA 8100 NARDA 8200 HOLDADYA HI 1500 SIMPSON 3800M
2. Place the turntabel tray into the oven cavity.
3. Place the load of 275
of water initially at
20
in the centre of the oven tray. The water container should be a low form of 600 ml beaker with inside diameter of approx.
and made of an electrically non-conductive material such as glass or plastic.
The placing of this standard load in the oven is im-
portant not only to protect the oven, but also to in-
sure that ny leakage is measured accurately.
4. Close the door and turn the oven ON with the timer set for several minutes. If the water begins to boil
before the survey is completed, replace it with 275ml of the cool water.
5. Move the probe slowly (not faster that 2.5cm/sec.) along the gap.
6. The microwave radiation emission should be meas-
ured at any point of 5cm or more from the external
surface of the oven.
Page 37
R-8470 R-8570
1
2
3
4
5
6
TRAY PACKING FOAM
Not
Items
,
C
D
E
Page 38
D
I
11
a 0
N-A
1
I
PANEL
__
____
__
T
W
D
Page 39
R-8470
R -8470
R-8570
R-8570
1
2
3
4
5
6
7
IN)
r-l
\
I
I
I
Q30 DTA143 A
C81
I
TURNTABLE
MOTOR
OVEN LAMP
FAN MOTOR A-9
A-7
A-5
DAMPER MOTOR
DTA143 A x5
IF NOT SPECIFIED,1/4W 5%
NOT SPECIFIED,
IF NOT SPECIFIED, US1060
R76 lk
R71
R66 lk
R65 130 F
C65
DAMPER
STOP SWITCH
SWITCH
(DOOR SWITCH)
Figure S-2. Contorol Panel Circuit (Mot
1
I
2
I
3 4
5 6
7
Page 40
R-8470 R-8470 R-8570 R-8570
R66
lk
G
130 F
KEY UNIT
1
R97
F
CC.
7
8
9
10
11
12
l
A
C
VP
D
E
OVEN
I Panel Circuit (Model R-8470)
7
8
I
9
I
10
11
12
38
Page 41
R-8470
R-8570
3
I
2
4
5
1
AC240
TURNTABLE
MOTOR
OVEN LAMP
POWER TRANSFORMER
HEATING
ELEMENT
FAN
DAMPER
DTA143 A x!
IF NOT SPECIFIED,1/4W 5%
IF NOT SPECIFIED,
25V
IF NOT SPECIFIED, US1060
I
R76 lk
R75
R52
STOP OVEN
THERMISTOR
1
2
3
4
5
39
Page 42
R-8470
R
-8570
7
8
9
10
11
12
,
NAL
VP
xt
HIGH MEDHIGH
STOP INSTANT TIMER
START
HOLD DEFROST
(KEY UNIT
SENSOR
Circuit
R-8570)
I
7
8
9
10
11
12
40
Page 43
R-8470 R -8570
1
2
3
+
,
I
n
Unit)
B
C
D
E
F
G
H
2
3 4
5 6
I
41
Page 44
PARTS LIST
1
Mains supply cord
I- 2
YBEO
Fuse (Ml OA)
I- 3
Fuse holder
4
QSW- MO1 71 WREO
Upper latch switch (V-l
C25)
I- 5
QSW-
73WRE0
Lower latch switch (V-l
6
QSW- MO1 72WRE0
Monitor switch (V-l
I- 7
Oven lamp
8
QFS-
Temp. fuse
9
RMOTDA021 WREO
Turntable motor
l-10
7WRE0 Fan motor
l-11
Convection motor
1-12 .
8WRE0
Damper motor
1-13
QSW- MO1 74WRE0
Stop switch and damper switch (V-5330DK)
1-14
RHET- A01 1 WREO Heating element
1-15
FH-
Thermistor
l-16
RTRN-
Power transformer
1-17
RC-
33WRE0
High voltage capacitor
1-18
RH-
Rectifier
1-19
RH-
Short protector
l-20
RV-
Magnetron
RTRN-A013DREO
Transformer (for control unit)
l-22
AH sensor: R-8570 only
CABINET PARTS
1 2 3 4 5
6 7 8
9 2-10 2-l 1 2-12 2-l 3 2-l 4 2-l 5 2-16 2-l 7
-
Base cabinet (A)
F
Base cabinet (B) Rear cabinet Foot
53WRR0
Schematic diagram: R-8470
TMAPCAl 54WRR0
Schematic diagram: R-8570 Capacitor holder Cushion Cord holder Outer case cabinet Shading cushion (A) Capacitor mounting bracket
Vibration proof cushion
PCAS-
Plug case Cord mounting bracket Cord bushing Cord anchorage (lower) Cord anchorage (upper)
CONTROL PANEL PARTS
1
1E 1F
c4
c75
C31,
c53,
c75
Cl0
CPWBF21 3SWRK0
Control unit: R-8470
CPWBF21 4SWRK0
Control unit: R-8570
connector (D)
connector (E)
3-pin connector (F),(H): R-8570
connector (G)
QCNCMA047 DREO
2-pin connector (H): R-8470
RV-
Fluorescent display tube
RC-
Capacitor 10
RC-
DREO Capacitor
4.7
RC-
Capacitor
0.015
25V 5ov 25V: R-8470
RC-
Capacitor 0.015
25V: R-8570
RC­RC­RC-
Capacitor Capacitor Capacitor
100
22
47
42
16V 25V 16V
ELECTRICAL
1 1 1 1 1 1 2 1 1 1 1 1 2 1 1 1 1 1 1 1 1 1
1
1 1 4 1 1 1 1
1 1 1 1 1 1
1
1 1 1
1 1 1
1 1 1
2 1 7
9
1 1 1
AR
AE
AF AG AG AG AH AG
AX
AW AW
AR AH
AY
BR
AZ
BL
AW
BB
AR
AU
AV
AB
AC
AB
AB
A0
AB
BA
AA
AC
AA
AD
AC
AB
AC
AC
BV
BU
AD
AC
AB
AE
AB
BC
AB
AB
AA
AA
A0
AB
AB
Page 45
R-8470 R-8570
Note
: The voltage supplied to the parts marked
is greater than
Refer to “REPLACEMENT PARTS LIST” described at after page.
NO.
CODE
D83,
D105
D52,
D83,
Ql 00
R2 R3 R4 R22, R82,
R201
R82, R203
R202 R30 R50 R51
R92,
R65
R71,
R76,
R76,
R201 R67 R70, R75,
R81,
R83 R84
R113 R200 R204
ZD2 ZD30
RC-
04QDRE0 RC­RC-
RCRS­RH-
RH-
Diode (US1 060): R-8570
17 AA
RH- DZAOl 1 DREO RH- DZAOl 1 DREO
RH- i RH- i ZOO21 WREO RH-
RH- TZA042 DREO
Diode (11 ES1 ): R-8470
R-8570
IC (lR94558): R-8570 only
Transistor
R)
Transistor
2
AB
3 AB 1
AV
1
AE
1
AG
3
AB
RH-
Transistor (
R-8570
6 AB
RH-TZA025DREO
RH-
Transistor Transistor
R-8470
1 5
1 1 1 1 1 4
4
3
1 1 1
14
1 4
5
1 3
12
1 1 1 1 1 1 1 1
1 1 1
AB AB
RH- TZA021 DREO
RR- DZ331 NDREO
RR-
51 PDREO
RR-
21 PDREO
RR- DZ271 PDREO
RR-
AC AA AA AA AA AA
RR-
Transistor
OMR) Resistor 330 Resistor
150 Resistor Resistor 270 Resistor 47k
Resistor 47k
Resistor
Resistor 470 Resistor block Resistor
330
Resistor
R-8470
R-8570 AA
RR-
53DDRECI
1
AA
RR- DZ471 NDREO RR­RR- DZ331 PDREO
RR-
03DDRE0
R-8570
AA AA AA AA
RR-
31 NDREO
RR-
02DDRE0
RR-
02DDRE0
RR­RR-
RR-
03DDRE0
RR­RR- DZ222 DREO RR­RR­RR­RR­RR­RR-
NDREO RH­RH- EZA051 DREO RH-
Capacitor
0.1
Capacitor
0.47
Capacitor
3.3
Ceramic filter
Diode (US1 060): R-8470
25V: R-8570 25V
5ov
Resistor
130
Resistor
Resistor
Resistor
5k
Resistor 27k
Resistor
Resistor
Resistor Resistor block (1 Resistor block (27k Resistor block (56k Resistor 56k Resistor
200k
Resistor
200 Zener diode Zener diode (RD5.1 EB3) Zener diode
43
R-8470
R-8570
R-8470
1 l4W: R-8570 only
AB
1
AB
1
AB
1
AF
14 AA
AA AA
AA
AA AA
AA
AA
AA AB AC AD AA AA AA
AB
Page 46
-8470
-8570
Note : The voltage supplied to the parts marked ‘I*” is greater than
Refer to “REPLACEMENT PARTS LIST” described at after page.
Q’TY
CODE
3-2
2A 2c
2D
2E Cl c2
Cl 80 D84, Fl
R21 R40 R41
RY6
3
4
5 6 7
2
3
4
5
6
7
8
9
4-l 0 4-l 1 4-l 2 4-l 3 4-14 4-l 5 4-l 6 4-l 7 4-l 8 4-l 9
4-20 4-21 4-22 4-23 4-24 4-25 4-26
4-27
4-28 4-29 4-30 4-31 4-32 4-33 4-34 4-35 4-36 4-37 4-38 4-39 4-40
4-41
QCNCM231
VW1
042
06n
QFS-
I
VRD-
83J VRD­VRD-
54J VRD-
J RRLY- 21 RALM- 2021YAZZ RH-
WREO
A031 WRRO
59WRJ0
FOVN­NCPL-
NTNT-
X-
5YBE0
PDUC­PDUC-
40WRW0
24WRE0
LANGK031 1 WRFO PDUC-
PDUC-
PDUC-
PDUC­FDUC- 01 91 WRWO
PREFH0031 WRPO
PFPF-
PFPF­PFPF­PDUC­PDUC­FSKR- AOO2WRWO
Relay unit
connector (A)
wire connector
wire connector
8-pin connector (I)
Fuse holder Capacitor
0.1
Capacitor
1000
Capacitor
0.1
Capacitor
10 Diode (11 El ) Diode (US1 060)
5ov 35v 25V 5ov
Fuse Filter coil (22
Transistor
Resistor Resistor Resistor 150k Resistor
470 Relay Buzzer
Varistor
Key unit: R-8470 Key unit: R-8570 Display filter Control panel frame Key unit angle Control panel back plate
OVEN PARTS
Oven cavity Shading cushion (B)
Turntable coupling Turntable tray
Oven lamp glass flange
Waveguide cover
Oven lamp screen glass Oven lamp mounting plate Magnetron cooling duct (A) Magnetron cooling duct (B)
Turntable motor mounting plate
Fan blade assembly Hinge mounting plate Chassis support Upper latch hook Monitor switch lever Lower latch hook
Stop switch lever Steam duct (left): R-8470 Steam duct (left): R-8570 Steam duct (right)
. Steam duct (upper) Steam duct (top) Steam duct cushion (A) Air guide duct Thermal protection plate (left) Thermal protection plate (right) Thermal protection plate (oven cavity top) Thermal protection plate (upper) Thermal protection cover Sensor cover: R-8570 only Steam duct cushion (B) Thermal protection sheet (right) Thermal protection sheet (left)
Thermal protection sheet (upper)
Convection air duct (upper) Convection air duct (left) Convection air guide (left) Convection air guide (upper) Convection fan Convection fan belt Pulley A (for convection fan)
1
BH
1
AD
1
AM
1
AM
1
AC
1
AA
1
AB
1
AH
1
AA
1
5
AB
7
AA
1
AC
1
AC
1 1
AA
2
AA
1
AA
1
AA
6
AN
1
AF
1
AF
1
AY
1
AY
1
AH
1
AU
1
AK
1
AK
1 1 1
1 1
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
1
BR
AA
AF
AU
AK
AG
AF
AF AG AH
AF
AE
AC
AE
AF
AF
AF AC
AE
AE AD AG AH AA
AE AH
AF AN AG
AE AA
AM
AH
AM
AK AK
AG
AF AC
Page 47
R-8470 R-8570
The voltage supplied to the parts marked
is greater than
: Refer to “REPLACEMENT PARTS LIST” described at after page.
NO.
Q’TY
CODE
4-42
NPLYB0031 WRFO
Pulley 0 (for convection motor)
1
4-43
Convection motor mounting plate
1
4-44
WREO
Fan shaft
1
4-45
X-
Shaft mounting plate (A)
1
4-46
Shaft mounting plate
1
4-47
Heating element holder
2
4-48
PDUC- A071 WRWO
Damper duct
1
4-49
PFTA-
Damper
1
4-50
NSFTT0071 WREO
Damper shaft
1
4-51
Damper cushion
1
4-52
1 WREO
Damper cam
1
4-53
PCUSU0471 WRPO
Steam duct cushion (C)
1
4-54
SH0041 WREO
Heating element insulator
1
4-55
Turntable roller assembly
1
5
1 2 3 4 5 6 7 8
9 5-10 5-l 1 5-l 2 5-13 5-14 5-15 5-16 5-17 5-18
5-l 9 5-20 5-21 5-22 5-23
Door assembly, complete: R-8470
1
Door assembly, complete: R-8570
1
Latch plate
1
Joint lever
1
LSTPPAOl
Upper latch head
1
LSTPPAOl
Lower latch head
1
Latch spring
1
Door sash upper
1
Door panel ass’y
1
Door sash (right)
1
Latch cover
1
LX-
Screw (torx); latch cover mtg
3
HDECQA041 WREO
Door sash (lower)
1
Door decoration plate
1
Ferrite
1
Sash mounting plate (upper)
1
Sash mounting plate (lower)
1
FHNG-
Door hinge ass’y
1
Door sash (left)
1
Door glass: R-8470
1
Door glass: R-8570
1
PCUSG021 3WRP0
Door sushion (short)
2
PCUSG021 2WRP0 Door cushion (long)
2
Door ferrite (upper)
2
LX-
7WRE0
Screw; sash mounting plate mtg
6
LX-
Screw; door hinge ass’y mtg
5
1
2
3
4
5
6
7
8
9
6-l 0 6-l 1
6-12 6-13
QW-
QW-
FW-
86WRE0
FW-
85WRE0
TSPCNA31 2WRR0
3WRR0
Ti
69WRR0
Ti
70WRR0
SCREWS, NUTS, WASHERS,
1 LX­ 2
LX-
41 WREO
3 LX-
86WRE0
4 LX-
7WRE0
5 LX-
6 LX-
MISCELLANEOUS
High voltage wire A (Trans.-Capa.) High voltage wire B Main wire harness Thermistor harness Wire holder Wire holder
lock “EXL”) Wire holder (WH-1 Name plate: R-8470 Name plate: R-8570 Caution label Cook book Operation manual: R-8470 Ooeration manual: R-8570
Screw
waveguide cover mtg
Screw
monitor switch lever mtg
Screw ; cord mounting bracket, capacitor mounting bracket,
magnetron cooling duct (B), base cabinet (A) and rectifier
Screw ; convection air guide (upper) mtg Screw ; rear cabinet, base cabinet (A), (B) and control panel
assembly mtg
Screw
upper and lower latch hook mtg
1 1 1 1 1 1
2 1 1 1 1 1 1
AC
AK
AQ
AC AC AL AL
AD
AA AA AC AA
BS
BT
AE AD AC AC AC
AM
BF
AH
AK AA
AM
AF
AF
AS AH
AZ
AZ AA
AE AA AA
AS
AS AD AD
AX
AL AA AA AA AC
AC
BA
AK AN
AA AA AA
AA AA
AA
Page 48
R-8470 R-8570
Note :
is greater than
: Refer to “REPLACEMENT PARTS LIST” described at after page.
Q’TY
CODE
7 8
9 7-10 7-11 7-12 7-13 7-14 7-15 7-16 7-17
7-18 7-19 7-20 7-21 7-22
7-23 7-24 7-25 7-26 7-27 7-28
7-29 7-30
7-32 7-33 7-34 7-35
7-36
7-37 7-38 7-39 7-40 7-41
LX-
Screw ; outer case cabinet mtg
2 AB
Screw ; fuse holder mtg
1
AA
Screw ; damper switch mtg
1
AA
Screw ;
fan motor and convection motor mtg
4 AA
Screw ;
magnetron mtg
3
AA
2KS0 Screw ; magnetron mtg
AA
4KS0 Screw ; power transformer mtg
AA
Screw ;
heating element mtg
2 AA
2000
Screw ; door assembly mtg
4 AA
Screw ;
waveguide cover mtg 3
AA
Screw
damper duct, convection air duct (upper), (left), oven 17
AA
lamp mounting plate and shaft mounting plate mtg
Screw ; thermistor mtg 2
AA Screw ; AH sensor and sensor cover mtg: R-8570 6 AA Screw ;
oven lamp mtg
2
AA
0000 Screw ; damper motor mtg 2
AA Screw ;
damper duct, steam duct (right), (left), (upper), thermal
21
AA
protection plate (right), (left), thermal protection cover, oven lamp mounting plate, sensor cover and air guide duct
X C P S D4 0 P 2 7 0 0 0
Screw ; cord anchorage (upper) mtg 2 AA
oxuo
Screw ;
heating element holder and heating element insulator mtg 4 AA
Screw ; convection motor mounting plate and damper duct mtg
4
AA
0000
Screw ;
cord anchorage (lower) mtg
1
AA
0000
Screw ;
plug case mtg
1
AA
2XS0
Screw ; transformer (for control unit), relay unit and control unit 8 AA
2000
Screw ;
outer case cabinet mtg
8
AA
LX-
Nut ; convection air duct upper, oven lamp mounting plate
9
AA
and convection motor mtg
LX-
Nut
earthing
AA
32000
Nut ; fan motor mtg
AA
32000 Nut ; convection fan mtg
1
AA
05300
Washer ; turntable coupling mtg
1
AA
08000
Washer ; monitor switch lever mtg
1
AA
08000 Washer ; convection fan mtg
1
AA
10000
Washer ; convection fan mtg
1
AA
08000
Washer ; power transformer mtg
000
Pin ; convection fan and pulley (A) mtg
AA
AA
000
Pin ;
pulley (B) mtg
1
AA
04000 Ring ; turntable coupling mtg
1
AA
HOW TO ORDER REPLACEMENT PARTS
To have your order filled promptly and correctly, please furnish the following information.
1. MODEL NUMBER
2. REF. NO.
3. PART NO.
4. DESCRIPTION
46
Page 49
-8470
R-8570
parts
marked parts on
lrst
been prepared
LISTED PART NO
USED PART
by side.
REF. NO.
c4 C5 etc
Cl0
D7 etc
etc
Cl50 etc 080
LISTED PART NO.
USED PART NO.
----
RC-
RC-
E
RC-
DREO
RC-
E
RC-
53N
RC-
RC-
C
RC-
E
RC-
RC-
C
RC-
04QDRE0
RC-
RC-
H
RC-
H
RH-
1
RH-
1 DREO
1 El
1 RH- I ZOO21 WREO RH- I X21 RH-TZ0029DREO
1
RH-TZA022DREO
143-A-l
RH-TZA025DREO
f 1 A
RH-TZA021 DREO
REF. NO.
R22 etc
R30 R55
etc
R84
R200 R204
LISTED PART NO.
USED PART NO.
NDREO
RD-
J
RR
51 PDREO
SD-
51 J
RR-
21 PDREO
RD-
21 J
DZ277 PDREO
J
RR-
53DDRE0
53J
RR- DZ471
RD- ST
J
RR-
D
S
RR-
SERVICE INFORMATION FOR CONTROL UNIT
--
1st
have
and
So, please
LSI,
Remove
and
PWB
open Its pin nos
and 52
LSI.
C65
Page 50
R-8470 R-8570
1
2
3
4
5
6
PARTS
1
I
2 /
3
4
I
5
6
Page 51
R-8470 R-8570
1
2 3 4
5
6
I
E
/
I
2
Page 52
R-8470 R-8570
1
2
3
4
5
1
I
2
3
4
5
6
Page 53
R-8470 R-8570
1
2
3
4
5
6
DOOR
ASSEMBLY
MISCELLANEOUS
6-3
Trans.
I
I
t
Page 54
R-8470 R-8570
General:
Connect:
FIXING PROCEDURE OF CORD ANCHORAGE
As for the above subject, sometime it may cause to have wrong fixing about two pieces of cord anchorage unit. But this cord anchorage is an important part for the safety, therefore it must be fixed correctly and firmly.
1.
The cord anchorage which is used to secure the mains supply cord can be fixed in two different ways.
2.
If you fix them
shown in Figure 2, the mains supply cord will not be secured firmly.
3.
Therefore, make sure to fix them as shown in figure 1.
BFO
SUPPLY
ANCHORAGE
Figure 1. Correct Fixing
2. Wrong Fixing
mm
‘86
SHARP CORP. (9N0.75E) Printed in Japan
Loading...