Sharp AH-PN10, AU-PN10, AH-PN13, AU-PN13, AH-PN10-GY Operation Manual

...
Page 1
OPERATION MANUAL
INDOOR UNIT OUTDOOR UNIT
AH-PN10 AU-PN10 AH-PN10-GY AU-PN10 AH-PN13 AU-PN13 AH-PN13-GY AU-PN13 AH-PN19 AU-PN19 AH-PN24 AU-PN24 AH-L10 AU-L10 AH-L13 AU-L13
CONTENTS Page
IMPORTANT SAFETY INSTRUCTIONS
1
PART NAMES 2
USING THE REMOTE CONTROL
5
AUXILIARY MODE 5
TIPS ON SAVING ENERGY
5
BASIC OPERATION 6
ADJUSTING THE AIR FLOW DIRECTION
7
POWERFUL JET OPERATION
7
GENTLE COOL AIR 8
PLASMACLUSTER OPERATION
8
TIMER OPERATION 9
ONE-HOUR OFF TIMER 10
DISPLAY BUTTON 10
MAINTENANCE 11
OPERATING CONDITION 11
BEFORE CALLING FOR SERVICE
12
INSTALLATION MANUAL 13
AH-PN10, 10GY AH-L10 AH-PN13, 13GY AH-L13
AH-PN19, AH-PN24
INSTALLATION MANUAL
Thank you for purchasing a SHARP air conditioner. Please read this manual carefully before operating the product
OM_AH-PN10 13GY_EN.indd 1OM_AH-PN10 13GY_EN.indd 1 12/22/11 6:30:07 PM12/22/11 6:30:07 PM
Page 2
OM_AH-PN10 13GY_EN.indd 2OM_AH-PN10 13GY_EN.indd 2 12/22/11 6:30:09 PM12/22/11 6:30:09 PM
Page 3
ENG-
E-1
ENGLISH
Please read this manual carefully before using the product. This manual should be kept in a safe place for handy reference.
IMPORTANT SAFETY INSTRUCTIONS
WARNINGS
• Do not pull or deform the power supply cord. Pulling and misuse of the power supply cord can result in damage to the unit and cause electrical shock.
• Be careful not to expose your body directly to the outlet air for a long time. It may affect your physical conditions.
• When using the air conditioner for infants, children, elderly, bedridden, or disabled people make sure the room temperature is suitable for those in the room.
• Never insert objects into the unit. Inserting objects can result in injury due to the high speed rotation of internal fans.
• Ground the air conditioner without fail. Do not connect the grounding wire to gas pipe, water pipe, lightning rod or telephone grounding wire. Incomplete grounding may cause electric shock.
• If anything is abnormal with the air conditioner (ex. a burning smell), stop the operation immediately and turn the circuit breaker OFF.
• The appliance shall be installed in accordance with national wiring regulations. Improper cable connection can cause the power supply cord, plug and the electrical outlet to overheat and cause fire.
• If the supply cord is damaged, it must be replaced by the manufacturer or its service agent or a similarly qualified person in order to avoid a hazard. Use only the manufacture specified power cord for replacement.
• Do not splash or pour water directly on the unit. Water can cause electrical shock or equipment damage.
• Do not attempt to install/remove/repair the unit by yourself. Incorrect work will cause electric shock, water leak, fire etc. Consult your dealer or other qualified service personnel for the installation/removal/repair of the unit.
CAUTIONS
• Open a window or door periodically to ventilate the room, especially when using gas appliances. Insufficient ventilation may cause oxygen shortage.
• Do not operate the buttons with wet hand. It may cause electric shock.
• For safety, turn the circuit breaker off when not using the unit for an extended period of time.
• Check the outdoor unit mounting rack periodically for wear and to make sure it is firmly in place.
• Do not put anything on the outdoor unit nor step on it. The object or the person may fall down or drop, causing injury.
• This unit is designed for residential use. Do not use for other applications such as in a kennel or greenhouse to raise animals or grow plants.
• Do not place a vessel with water on the unit. If water penetrates into the unit, electrical insulations may deteriorate and cause electric shock.
• Do not block the air inlets nor outlets of the unit. It may cause insufficient performance or troubles.
• Be sure to stop the operation and turn the circuit breaker off before performing any maintenance or cleaning. A fan is rotating inside the unit and you may get injured.
• This appliance is not intended for use by young children or infirm persons without supervision. Young children should be supervised to ensure that they do not play with the appliance.
• Make sure to connect the air conditioner to power supply of the rated voltage and fre­quency. Use of a power supply with improper voltage and frequency can result in equipment damage and possible fire.
• Do not install the unit in a place where inflam­mable gas may leak. It may cause fire.
Install the unit in a place with minimal dust,
fumes and moisture in the air.
• Arrange the drain hose to ensure smooth drainage. Insufficient drainage may cause wet­ting of the room, furniture etc.
• Make sure a leak breaker or a circuit breaker is installed, depending on the installation loca­tion, to avoid electrical shock.
OM_AH-PN10 13GY_EN.indd Sec1:1OM_AH-PN10 13GY_EN.indd Sec1:1 12/22/11 6:30:09 PM12/22/11 6:30:09 PM
Page 4
E-2
1
Inlet (Air)
2
Open Panel
3
Air Filter
4
AUX Button
5
Receiver Window
6
Vertical Airflow Louvre
7
Horizontal Airflow Louvre
8
Outlet (Air)
9
OPERATION Lamp (red
)
10
TIMER Lamp (orange
)
11
POWERFUL JET Lamp
(green
)
12
PLASMACLUSTER Lamp
(blue
)
PART NAMES
INDOOR UNIT
OUTDOOR UNIT
1
2
3
4
5
6
7
8
9
10
11
13
14
15
16
13
Inlet (Air)
14
Refrigerant Pipe and
Interconnecting Cord
15
Drainage Hose
16
Outlet (Air)
NOTE:
Actual units might vary slightly from those shown above.
AH-L10 AH-L13
9
10
11
AH-PN10, AH-PN10-GY AH-PN13, AH-PN13-GY
AU-PN10 AU-PN13 AU-L10 AU-L13
12
OM_AH-PN10 13GY_EN.indd Sec1:2OM_AH-PN10 13GY_EN.indd Sec1:2 12/22/11 6:30:10 PM12/22/11 6:30:10 PM
Page 5
ENG-
E-3
1 Inlet (Air)
2 Open Panel
3
Air Filter
4
AUX Button
5 Receiver Window
6 Power Supply Cord
7 Vertical Airflow Louvre
8 Horizontal Airflow Louvre
9 Outlet (Air)
10
PLASMACLUSTER Lamp
(blue
)
11
OPERATION Lamp (red
)
12
TIMER Lamp (orange
)
13
POWERFUL JET Lamp
(blue
)
14
Inlet (Air)
15
Refrigerant Pipe and
Interconnecting Cord
16
Drainage Hose
17
Outlet (Air)
NOTE:
Actual units might vary slightly from those shown above.
INDOOR UNIT
OUTDOOR UNIT
1
2
3
4
5
6
7
8
9
14 15 16
17
14
15
16
17
AU-PN19
AU-PN24
10
11
12
13
AH-PN19, AH-PN24
OM_AH-PN10 13GY_EN.indd Sec1:3OM_AH-PN10 13GY_EN.indd Sec1:3 12/22/11 6:30:11 PM12/22/11 6:30:11 PM
Page 6
E-4
REMOTE CONTROL
1
TRANSMITTER
2
DISPLAY
3
ON/OFF Button
4
THERMOSTAT Button
5
DISPLAY Button
6
ONE-HOUR OFF TIMER Button
7
PLASMACLUSTER Button
8
TIMER ON Button
9
MODE Button
10
TIMER OFF Button
11
FAN Button
12
TIMER CANCEL Button
13
SWING Button
14
Reset Button
15
POWERFUL JET Button
16
GENTLE COOL AIR Button
DISPLAY
17
MODE Symbols
: AUTO : COOL : DRY
18
POWERFUL JET Symbol
19
PLASMACLUSTER Symbol
20
FAN SPEED Symbols
: AUTO
: Manual setting
21
GENTLE COOL AIR Symbol
22
TEMPERATURE AND TIMER COUNT DOWN Indicator
23
TRANSMITTING Symbol
24
TIMER ON / TIMER OFF Indicator
17 18
19
20
21 22
23 24
1
2
3 4
5
6 7 8 9
10
11 12 13 14 15 16
PART NAMES
(AH-PN10, AH-PN10-GY AH-PN13, AH-PN13-GY AH-PN19, AH-PN24 ONLY)
(AH-PN10, AH-PN10-GY AH-PN13, AH-PN13-GY AH-PN19, AH-PN24 ONLY)
OM_AH-PN10 13GY_EN.indd Sec1:4OM_AH-PN10 13GY_EN.indd Sec1:4 12/22/11 6:30:13 PM12/22/11 6:30:13 PM
Page 7
ENG-
E-5
AUX
7 m
18,000/24,000 BTU
AUX
LOADING BATTERIES
1
Remove the battery cover.
2
Insert two batteries.
(AAA(R03))
Make sure the (+) and (-) polarities are correctly aligned.
3
Reinstall the battery cover.
4
Press the RESET button using a
thin stick.
NOTE:
• The battery life is approximately 1 year in normal use.
• When replacing the batteries, always change both and use the same type.
• If you will not be using the unit for a long time, remove the batteries from the remote control.
USING THE REMOTE CONTROL
Battery cover
HOW TO USE THE REMOTE CONTROL
Point the remote control towards the receiver window and press the desired button. The unit generates a beep when it receives the signal.
• Make sure nothing, such as curtains, block the signal receiver window.
• The signal effective distance is 7 m.
CAUTION:
Do not expose the receiver window to direct sunlight. This may adversely affect its operation.
Use of certain fluorescent lamp in the same room may interfere with transmission of the signal.
• Do not leave the remote control in direct sunlight or near a heater. Protect the remote control from moisture and shock.
Use this mode when the remote control is not available.
TO TURN ON Press the AUX button.
The red OPERATION lamp ( ) will light and the unit will start operating in the AUTO mode.
• The fan speed and temperature setting are set to AUTO.
TO TURN OFF Press the AUX button again.
• The red OPERATION lamp ( ) will turn off.
AUXILIARY MODE
TIPS ON SAVING ENERGY
Below are some simple ways to save energy when you use your air conditioner.
Set the proper temperature
• Setting the temperature lower than neces­sary during cooling operation will result in increased power consumption.
Block direct sunlight and prevent drafts
Blocking direct sunlight during cooling operation will reduce power consumption.
• Close the windows and doors during cooling operation.
Keep filter clean to ensure the most efficient operation
Disconnect the power cord or turn off the circuit breaker when the unit is not used for an extended period of time
• The indoor unit still consumes a small amount of power when it is not operating.
Receiver window
RESET button
9,000/12,000 BTU
OM_AH-PN10 13GY_EN.indd Sec1:5OM_AH-PN10 13GY_EN.indd Sec1:5 12/22/11 6:30:14 PM12/22/11 6:30:14 PM
Page 8
E-6
2 3
1 4
1
Press the MODE button to select the
operation mode.
2
Press the ON/OFF button to start
operation.
• The red OPERATION lamp ( ) will light up.
TO TURN OFF
Press the ON/OFF button again.
• The red OPERATION lamp ( ) will turn off.
3
Press the THERMOSTAT button to
set the desired temperature.
(AUTO/DRY mode) The temperature can be changed up to ±2 °C the automatically set of temperature.
(COOL mode) The temperature setting range: 16-30°C.
4
Press the FAN button to set the
desired fan speed.
BASIC OPERATION
AUTO COOL DRY
AUTO SOFT LOW HIGH
NOTE:
AUTO MODE
In the AUTO mode, the temperature setting and mode are automatically selected according to the room temperature when the unit is turned on.
DRY MODE
The fan speed is preset to AUTO and cannot be changed.
WHEN POWER FAILURE OCCURS
This air conditioner has a memory function to store settings when a power failure occurs. After power recovery, the unit will automatically re-start in the same settings which were active before the power failure, except for timer settings.
OM_AH-PN10 13GY_EN.indd Sec1:6OM_AH-PN10 13GY_EN.indd Sec1:6 12/22/11 6:30:16 PM12/22/11 6:30:16 PM
Page 9
ENG-
E-7
The air conditioner works at the maximum power and optimum louvre direction to makes the room cool rapidly.
1
During operation, press the
POWERFUL JET button.
• The remote control will display “ ”.
• The temperature display will go off.
• The green POWERFUL JET lamp (
)
will light up.
• The vertical airflow louvre will be set obliquely downward.
TO CANCEL
Press the POWERFUL JET button again.
• The green POWERFUL JET lamp ( ) will turn off.
• The vertical airflow louvre will return to the original direction.
NOTE:
• The air conditioner will operate at “Extra HIGH” fan speed for 30 minutes, and then shift to “HIGH” fan speed.
• You can not set the temperature or fan speed during the POWERFUL JET operation.
Louvre lever
1 2
1
9,000/12,000 BTU
18,000/24,000 BTU
CAUTION:
Never attempt to adjust the vertical airflow lou­vre manually.
• Manual adjustment of the vertical airflow lou­vre can cause the unit to malfunction.
• When the vertical adjustment louvre is posi­tioned at the lowest position in the COOL or DRY mode for an extended period of time, condensation may result.
VERTICAL AIR FLOW DIRECTION
1
Press the SWING button.
• The vertical airflow louvre will swing.
2
Press the SWING button again
to stop the desired position.
• The adjustment range is narrower the swing range in order to prevent conden­sation from dripping.
ADJUSTING THE AIR FLOW DIRECTION
POWERFUL JET OPERATION
HORIZONTAL AIR FLOW DIRECTION
Hold the horizontal airflow louvre levers and adjust the air flow direction.
Louvre lever
OM_AH-PN10 13GY_EN.indd Sec1:7OM_AH-PN10 13GY_EN.indd Sec1:7 12/22/11 6:30:17 PM12/22/11 6:30:17 PM
Page 10
E-8
The vertical airflow louvre is set obliquely upward to deliver cool air to the ceiling in order to avoid direct airflow.
1
During operation, press the
GENTLE COOL AIR button.
• The remote control will display “ ”.
TO CANCEL
Press the GENTLE COOL AIR button again.
NOTE:
• If you want GENTLE COOL AIR operation in POWERFUL JET mode, press GENTLE COOL AIR button during POWERFUL JET operation.
1
GENTLE COOL AIR
PLASMACLUSTER OPERATION
Plasmacluster ions released into the room will reduce some airborne mold.
1
During operation, press the
PLASMACLUSTER button.
• The remote control will display “ ”.
• The blue PLASMACLUSTER lamp (
)
will light up.
TO CANCEL
Press the PLASMACLUSTER button again.
• The blue PLASMACLUSTER lamp (
)
will turn off.
NOTE:
• Use of the PLASMACLUSTER operation will be memorized, and it will be activated the next time you turn on the unit.
• To perform Plasmacluster operation in FAN only mode, press the PLASMACLUSTER but­ton when the unit is not operating.
The mode symbol of the remote control will go
off and the fan speed cannot be set to AUTO.
1
(AH-PN10, AH-PN10-GY AH-PN13, AH-PN13-GY AH-PN19, AH-PN24 ONLY)
OM_AH-PN10 13GY_EN.indd Sec1:8OM_AH-PN10 13GY_EN.indd Sec1:8 12/22/11 6:30:18 PM12/22/11 6:30:18 PM
Page 11
ENG-
E-9
TIMER ON
1
Press the TIMER ON button and
set the time as desired.
The orange TIMER lamp ( ) will light up.
• The time setting will count down to show the remaining time.
TO CANCEL
Press the CANCEL button.
The orange TIMER lamp ( ) will turn off.
TIMER OPERATION
1
TIMER OFF
1
Press the TIMER OFF button and
set the time as desired.
The orange TIMER lamp ( ) will light up.
• The time setting will count down to show the remaining time.
TO CANCEL
Press the CANCEL button.
• The orange TIMER lamp ( ) will turn off.
0.5h 1.0h 1.5h 10h 11h 12h
0.5h 1.0h 1.5h 10h 11h 12h
CANCEL
1
NOTE:
• Timer duration can be set from a minimum of half an hour to a maximum of 12 hours. Up to 9.5 hours, you can set in half-hour increments, and from 10 to 12 hours, in 1-hour increments.
• The TIMER OFF and TIMER ON can not be set together.
• The ONE-HOUR OFF TIMER operation has priority over TIMER ON and TIMER OFF operations.
• When the temperature is set during timer setting, the temperature will show in the display for 5 seconds and then return to the timer display.
• If a power failure occurs while the TIMER is set, the TIMER setting will be cancelled and will not be retrieved even after the power is restored.
TIMER OFF
• When the TIMER OFF is set, the temperature setting is automatically adjusted to prevent the room from be coming excessively cold while you sleep. (Auto Sleep function) One hour after the time operation begins, the temperature setting rises 1°C higher than the original temperature setting.
TIMER ON
• The unit will turn on prior to the set time to allow the room to reach the desired temperature by the programmed time. (Awaking function)
CANCEL
OM_AH-PN10 13GY_EN.indd Sec1:9OM_AH-PN10 13GY_EN.indd Sec1:9 12/22/11 6:30:20 PM12/22/11 6:30:20 PM
Page 12
E-10
CANCEL
1
1
When the ONE-HOUR OFF TIMER is set, the unit will automatically turn off after one hour.
1
Press the ONE-HOUR OFF TIMER
button.
• The remote control will displays “ ”.
The orange TIMER lamp ( ) will light up.
TO CANCEL
Press the CANCEL button.
• The orange TIMER lamp ( ) will turn off.
NOTE:
• The ONE-HOUR OFF TIMER operation has priority over TIMER ON and TIMER OFF operations.
• If the ONE-HOUR OFF TIMER is set while the unit is not operating, the unit will operate for an hour at the formerly set condition.
• If you wish to operate the unit for another hour before the ONE-HOUR OFF TIMER is activated, press the ONE-HOUR OFF TIMER button again during operation.
ONE-HOUR OFF TIMER
Use when the lamps on the unit are too bright. (The red OPERATION lamp and the orange TIMER lamp cannot be turned off.)
1
During operation, press the
DISPLAY button.
• The blue PLASMACLUSTER lamp ( )
and/or the green POWERFULL JET lamp (
) will turn off.
TO LIGHT UP
Press the DISPLAY button again.
DISPLAY BUTTON
OM_AH-PN10 13GY_EN.indd Sec1:10OM_AH-PN10 13GY_EN.indd Sec1:10 12/22/11 6:30:21 PM12/22/11 6:30:21 PM
Page 13
ENG-
E-11
9,000/12,000 BTU
18,000/24,000 BTU
Be sure to disconnect the power cord from the wall outlet or turn off the circuit breaker before performing any maintenance.
CLEANING THE FILTERS
1
Turn off the unit.
2
Remove the filters.
1
Lift the open panel.
2
Pull the air filters down to remove them.
MAINTENANCE
OPERATING CONDITION
Mode
Indoor Temp.
Outdoor Te mp .
Cooling
Upper limit 32˚C43˚C
Lower limit 21˚C21˚C
• The built-in safety device may prevent the unit from operating when used out of this range.
• Condensation may form on the air outlet if the unit operates continuously in the COOL or DRY mode when humidity is over 80 %.
MAINTENANCE AFTER AIR CONDITIONER SEASON
1
Operate the unit in the COOL mode, temperature setting 30˚C,
to thoroughly dry inside the unit.
2
Stop the operation and unplug the unit. Turn off the circuit breaker,
if you have one exclusively for the air conditioner.
3
Clean the filters, then reinstall them.
MAINTENANCE BEFORE AIR CONDITIONER SEASON
1
Make sure that the air filters are not dirty.
2
Make sure that nothing obstructs the air inlet or outlet.
3
Clean the filters.
Use a vacuum cleaner to remove dust. If the filters are dirty, wash them with warm water and a mild detergent. Dry filters in the shade before reinstalling.
4
Reinstall the filters and close the open panel.
CLEANING THE UNIT AND THE REMOTE CONTROL
• Wipe them with a soft cloth.
• Do not directly splash or pour water on them. It can cause electrical shock or equipment damage.
• Do not use hot water, thinner, abrasive pow­ders or strong solvents.
OM_AH-PN10 13GY_EN.indd Sec1:11OM_AH-PN10 13GY_EN.indd Sec1:11 12/22/11 6:30:22 PM12/22/11 6:30:22 PM
Page 14
E-12
Check the following points before calling for service.
The unit does not operate
• Check if the circuit breaker has tripped or the fuse has blown.
The unit does not cool effectively
Check the filters. If dirty, clean them.
• Check the outdoor unit to make sure nothing is blocking the air inlet or outlet.
• Check the thermostat is proper setting.
• Make sure windows and doors are closed tightly.
The unit does not receive the remote control signal
• Check whether the remote control batteries have become old and weak.
• Try to send the signal again with the remote control pointed properly towards the unit’s signal receiver window.
• Check whether the remote control batteries are installed properly.
Please call for service when OPERATION lamp, TIMER lamp and/or PLASMACLUSTER lamp on the unit blink.
The following conditions do not denote equipment malfunctions
UNIT DOES NOT OPERATE
The unit will not operate if it is turned on im­mediately after it is turned off.
The unit will not
operate immediately
after the mode is changed.
This is to protect the unit.
Wait 3 minutes before
operating the unit.
ODORS
Carpet and furniture odors that entered into theunit may be sent out from the unit.
CRACKING NOISE
This sound is generated by the friction of the unit expanding or connecting due to a tempera­ture change.
SWISHING NOISE
The soft, swishing noise is the sound of the refrigerant flowing inside the unit.
MIST SEEN AT INDOOR AIR OUTLET
In cooling operation,
this is caused by the differ­ence between the room air temperature and the air discharged.
ODOR EMITTED FROM THE PLASMACLUSTER AIR OUTLET
(AH-PN10, AH-PN10-GY AH-PN13, AH-PN13-GY AH-PN19, AH-PN24 ONLY)
This is the smell of ozone generated from the
Plasmacluster Ion generator. The ozone concentration is very small, posing no adverse effect on your health.
The ozone discharged into the air rapidly decomposes, and its density in the room will not increase.
A LOW BUZZING NOISE
(AH-PN10, AH-PN10-GY AH-PN13, AH-PN13-GY AH-PN19, AH-PN24 ONLY)
This is a sound of the unit generating Plasma­cluster ions.
BEFORE CALLING FOR SERVICE
(AH-PN10, AH-PN10-GY AH-PN13, AH-PN13-GY AH-PN19, AH-PN24 ONLY)
OM_AH-PN10 13GY_EN.indd Sec1:12OM_AH-PN10 13GY_EN.indd Sec1:12 12/22/11 6:30:23 PM12/22/11 6:30:23 PM
Page 15
ENG-
E-13
INSTALLATION MANUAL
SAFETY PRECAUTIONS
SPLIT TYPE ROOM AIR CONDITIONER
ACCESSORIES
ITEMS Q’ty ITEMS Q’ty ITEMS Q’ty
1
MOUNTING PLATE
1
3
DRY BATTERY
2
5
CABLE COVER
1
2
REMOTE CONTROL
1
4
REMOTE CONTROL
HOLDER
1
6
OPERATION AND
INSTALLATION MANUAL
1
9K, 12K BTU
18K, 24K BTU
9K, 12K BTU
18K, 24K BTU
Installation must be made in accordance with the installation manual by qualified service personnel.
Incorrect work will cause electric shock, water leak, fire.
Be sure to use the attached accessories parts and specified parts for installation.
Use of other parts will cause electric shock, water leak, fire, the unit falling.
• The appliance shall be installed in accordance with national wiring regulations.
Wrong connection can cause overheating or fire.
After installation has complete, check that there is no leakage of refrigerant gas.
If the refrigerant gas contact with fire, it may generate toxic gas.
• Ventilate the room if refrigerant gas leakes during installation.
If the refrigerant gas contact with fire, it may generate toxic gas.
• Use the specified electrical cable.
Make sure the cable is secured in place and that the terminals are free of any excess force from the cable. Otherwise overheating or fire may result.
Form the cable so that the control box cover, the cord holder and cable holder are not loose.
Otherwise overheating, fire or electric shock may result.
• Tighten the flare nut with a torque wrench according to the specified method.
If the flare nut is tightened too hard, the flare nut may be broken after a long time and cause refrigerant gas leakage.
• When installing the unit, take care not to enter air substance other than the specified refrigerant (R22) in the refrigerant cycle.
Otherwise, it will cause burst and injury as a result of abnormal high pressure in the refrigerant cycle.
• Be sure to connect the refrigerant pipe before running the compressor.
Otherwise, it will cause burst and injury as a result of abnormal high pressure in the refrigerant cycle.
• Earth the unit.
Incomplete earth may cause electrical shock.
• Install an earth leakage breaker to avoid electric shock in case of leak.
Use the current-activated, high-sensitivity, high-speed type breaker with a rated sensitivity current of below 30 mA and an operating time of below 0.1 second.
• Arrange the drain hose to ensure smooth drainage.
Insufficient drainage may cause wetting of the room, furniture etc.
OM_AH-PN10 13GY_EN.indd Sec1:13OM_AH-PN10 13GY_EN.indd Sec1:13 12/22/11 6:30:25 PM12/22/11 6:30:25 PM
Page 16
E-14
NOTES ON LOCATIONS
INDOOR UNIT
1. Keep the air outlet clear of any obstacle so that outgoing air flows smoothly in the entire room.
2. Make a drain hose hole for easy drainage.
3. Provide sufficient space on both sides and above the unit.
4. The air filters should be easily taken in and out.
5. Keep TV set, radio and the like 1 m or more away from the unit and the remote control.
6. Keep the air inlet clear of obstacles that could block incoming air.
7. The remote control may not function properly in a room equipped with an electronic simultane­ous-start or rapid-start fluorescent lighting.
8. Select a location that does not cause loud operation noise and extreme vibrations.
OUTDOOR UNIT
1. Place the outdoor unit on a stable base.
2. Provided sufficient space around the unit. It should also be well ventilated.
3. The unit should not be exposed to strong wind nor splashed with rain water.
4. Water drain from the unit should be let out without problem. Lay a drain hose if required. In cold regions, installation of the drain pipe is not advisable as freezing could result.
5. Keep TV set, radio and the like 1 m or more away from the unit.
6. Avoid locations exposed to machine oil vapor, salty air (facing the seashore, for example), hot spring vapor sulfur gas, etc. Such location can cause breakdown.
7. Avoid locations exposed to muddy water (along a road, for example) or where the unit can be tampered with.
8. Select a location where the outgoing air or operating noise cannot annoy others.
9. Keep the air outlet opening free of any obstacle. This could affect the performance of the unit and create loud noises.
INSTALLATION DIAGRAM
Provide as much installation space as possible for efficient air-conditioning.
50 mm or more 50 mm or more
50 mm or more
70 mm or more
Coating tape (Commercially available)
50 mm or more
200 mm or more
100 mm or more
200 mm or more
Fix the remote control holder to the wall with the short screws.
4
REMOTE CONTROL HOLDER
SHORT SCREW
2
REMOTE CONTROL
Coating tape (Commercially available)
50 mm or more
50 mm or more
70 mm or more
50 mm or more
300 mm
or more
1000 mm or more
400 mm or more
9000/12000 BTU 24000 BTU 18000 BTU
300 mm or more
400 mm or more
300 mm or more
1000 mm or more
300 mm
or more
OM_AH-PN10 13GY_EN.indd Sec1:14OM_AH-PN10 13GY_EN.indd Sec1:14 12/22/11 6:30:27 PM12/22/11 6:30:27 PM
Page 17
ENG-
E-15
INSTALLATION DIMENSION OF INDOOR UNIT
860
108
A
125
J
175
115
I
F
E
D
J
E
A
F
I
D
292
45
30
Length unit: mm
Center of wall hole
Center of wall hole
Outline of indoor unit
(Unit size)
965 (Unit size)
Model
Max. piping
length:A
Max. height
difference:B
Min. piping
length
Additional refrigerant
(piping length exceeds 7.5m)
9K-Btu/h type 10 m 5 m
1 m
15 g/m
12K-Btu/h type 15 m 7 m
10 g/m
18K 24K-Btu/h type
15 m 10 m
• Standard piping length is 7.5m.
• When the outdoor unit is placed at a higher level than the indoor unit, provide a trap near the hose’s lead-in port.
Use the refrigerant pipes shown in the table below.
Pipe size
Pipe
thickness
Thermal insulation
Liquid side 1/4" (ø 6.35 mm)
0.8 mm
Thickness: 6 mm or thicker Material: Polyethylene foam
Gas side
9K-Btu/h type
3/8" (ø 9.52 mm)
12K-Btu/h type
1/2" (ø 12.7 mm)
18K 24K-Btu/h type
5/8" (ø 15.88 mm)
1.0 mm
• The thermal insulation should cover both the gas and liquid pipes.
Trap
PIPES
A
B
B
3 13
05
05
80
A
J
I
80
88 88
F
42
E
E E
C
A
B
J
H
G
F
0
0
I
D
D
Length unit: mm
Center of wall hole
Center of wall hole
Outline of indoor unit
(Unit size)
965 (Unit size)
9000/12000 BTU
18000/24000 BTU
OM_AH-PN10 13GY_EN.indd Sec1:15OM_AH-PN10 13GY_EN.indd Sec1:15 12/22/11 6:30:28 PM12/22/11 6:30:28 PM
Page 18
E-16
Installing the mounting plate
(1) Referring to the “
INSTALLATION DIMEN-
SION OF INDOOR UNIT
”, mark the location
for the fixing holes and the piping hole.
Recommended fixing holes are marked in circle around the hole. (7 points)
• Make sure that the mounting plate is hori­zontally.
(2) Secure the mounting plate to the wall with
the long screws and check the stiffness.
Wall
Making a piping hole
(1)
Drill a piping hole with 70mm diameter concrete drill or a hole saw with a 5mm down ward slant to the outside.
(2) Set the sleeve and caps.
1
MOUNTING PLATE
LONG SCREW
Indoor Outdoor
Cut with a saw.
Cap
5 mm
Sleeve
(Downward to outdoor)
PLACING THE MOUNTING PLATE AND MAKING A PIPING HOLE
LONG SCREW
1
MOUNTING PLATE
SETTING UP THE INDOOR UNIT
1
2
3
4
5
Mounting the indoor unit
For right side piping
(1)
Pass the pipes and the drain hose through the piping hole. (2) Hook the unit onto the mounting plate. (3) Pull the connecting cable into the indoor unit. (4) Push the unit and apply the bottom hooks to the
mounting plate's support. (5) Pull the bottom of the unit to check that the unit is
fixed in place.
For left side piping
(1)
Reverse the positions of the drain hose and drain cap.
Refer to “
Exchange the drain hose
(2)
Connect the pipes and wrap tape around the insula-
tion of the piping joints tightly not to become thick. (3) Bind the pipes and connecting cable with tape. (4) Set the pipes and connecting cable along the back
of the unit, and attach the piping holder. (5) Pass the pipes, connecting cable and the drain
hose through the piping hole. (6) Hook the unit onto the mounting plate. (7) Push the unit and apply the bottom hooks to the
mounting plate's support. (8) Pull the bottom of the unit to check that the unit is
fixed in place.
NOTES:
• Bend the pipes carefully as not to damage them.
• Lay the drain hose below the pipes.
Drain Hose
MOUNTING PLATE
Taping
Drain Cap
Piping route
For directions 1, 2 , 4 and 5, cut out the specific zone without leaving any sharp edge. (Keep the cut-out plate for possible future use.)
PLATE
Cut the plate along notch.
Hook
MOUNTING PLATE
Tape
Pipes
Drain Hose
Insulation
Tape
Model 9000/12000 BTU Model 18000/2400 BTU
Model 9000/12000 BTU
PLATE
PLATE
Piping holder
OM_AH-PN10 13GY_EN.indd Sec1:16OM_AH-PN10 13GY_EN.indd Sec1:16 12/22/11 6:30:29 PM12/22/11 6:30:29 PM
Page 19
ENG-
E-17
1
2
3
4
5
(1)
Remove the screw and pull out the drain hose.
(2) Pull out the drain cap.
(3) Reconnect the drain hose to the right and
insert the drain cap to the left.
• Fully insert the drain hose until it stops and fix the screw removed in (1).
• Insert a hexagon wrench (4 mm diagonal) into the drain cap, and press it fully.
Drain Hose
Hexagon wrench
Drain Cap
Drain Hose
Drain Cap
Screw
Exchange the drain hose
Screw
CONNECTING THE CABLE TO THE INDOOR UNIT
Use a copper cable. (Cross-section area: 2.0 mm2 ) 9,000-12,000-18,000 BTU only Use a cable which is not lighter than polychloroprene sheathed flexible cord (Code designation 60245 IEC 57). Use a copper cable. (Cross-section area: 2.0 mm2) 24,000 BTU only
8
8
40
50
Earth wire
Connecting cable
Length unit: mm
8
8
80
90
8
8
80
90
Drain Hose
MOUNTING PLATE
Taping
Drain Cap
Hook
MOUNTING PLATE
Piping holder
Tape
Pipes
Drain Hose
Insulation
Tape
Earth wire Earth wire
Plate
Cut the plate along notch.
Piping route
For directions 1, 2 , 4 and 5, cut out the specific zone without leaving any sharp edge. (Keep the cut-out plate for possible future use.)
Model 18000/24000 BTU
Model 9000/12000 BTU Model 18000 BTU Model 24000 BTU
Plate
Plate
Plate
WARNING:
After replacing, make sure that both the drain hose and drain cap are firmly inserted.
OM_AH-PN10 13GY_EN.indd Sec1:17OM_AH-PN10 13GY_EN.indd Sec1:17 12/22/11 6:30:32 PM12/22/11 6:30:32 PM
Page 20
E-18
SHORT SCREW
5
CABLE COVER
CAUTIONS:
• Be very careful not to confuse the terminal connections. Wrong cabling may damage the internal control circuit.
• Be sure to connect the cable to match the markings on the indoor unit’s terminal board and those of the outdoor unit.
(1) Process the end of the connecting
cable for the indoor side. (2) Open the open panel. (3) Connect the cable. (4) Fix the cable with the cable cover
and the short screw. (5) Close the open panel.
N1
N1
OUTDOOR UNIT
NL
POWER SUPPLY
NL1
NLL1
OUTDOOR UNIT
NL
POWER SUPPLY
SHORT SCREW
5
CABLE COVER
18K-Btu/h type
24K-Btu/h type
CONNECTING THE DRAIN HOSE
Not running wavy.
Not left in water.
No trap allowed.
Not to rise.
Connecting the drain hose
(1) Connect a drain hose. (2) Tape over the connecting part.
Drain Hose (Commercially available)
ø16 mm
No trap allowed.
NOTE:
• Be sure to lay the drain hose downward for smooth drainflow.
Be careful not to allow the drain hose to rise, form a trap or leave its end in water, as shown below.
• Coil thermal insulation around a drain hose extension, if run­ning in the room.
Checking drainage
(1) Open the open panel. (2) Remove the air filters. (3) Pour some water into the drain pan. (4) Check the water drains smoothly.
Connect to outdoor
Power supply cable
Earth wire
Connect to outdoor
Power supply cable
Cable holder
Cable holder
Model 9000/12000 BTU
Model 18000/24000 BTU
Connecting cable
Earth wire
Power supply cable
Earth wire
OM_AH-PN10 13GY_EN.indd Sec1:18OM_AH-PN10 13GY_EN.indd Sec1:18 12/22/11 6:30:33 PM12/22/11 6:30:33 PM
Page 21
ENG-
E-19
OUTDOOR UNIT INSTALLATION
A
B
Referring to the figure, firmly fasten the outdoor unit with bolts.
ระยะหางของขาตั้งตัวเคร องปรับอากาศ
ระยะหางของขาตั้งตัวเคร องปรับอากาศ
Model A B
9K/12K Btu/h 515 299
18K Btu/h 557 379
24K Btu/h 590 361
Length unit: mm
Unit size
AH-PN10
AH-PN10GY
AH-PN13
AH-PN13GY
AH-L10 AH-L13
AH-PN19 AH-PN24
AU-PN10 AU-PN13
AU-L10 AU-L13
AU-PN19 AU-PN24
WIDTH 223 250 250 330 357
HEIGHT 292 313 540 710 800
DEPTH 860 965 730 850 940
Connecting the refrigerant pipes
Connecting the pipes
Connect the pipes for the indoor unit first and then for the outdoor unit.
(1) Tighten the flare nuts by hand for the first 3-4
turns.
(2) Use a wrench and torque wrench to tighten up
the pipes.
• Do not over tighten the pipes. It may be de formed or damaged.
Flaring the pipe end
(1) Cutting with a pipe cutter. Cut at a right angle.
(2) Deburring.
Allow no cuttings in the pipe.
(3) Putting in the flare nut (4) Flaring the pipe end
Flare processing dimensions (A)
Tool A
R22 tool 0.5 - 1.0 mm
(5) Checking
To be flared perfectly circular.
Flare nut not missing.
90°
A
Flare nut tightening torque
Flare nut
Wrench
Torque wrench
Pipe size Torque
Liquid size 1/4" 16 ± 2 N·m (1.6 ± 0.2 kgf·m)
Gas side 3/8" 9K-Btu/h type 38 ± 4 N·m (3.8 ± 0.4 kgf·m)
1/2"
12K 18K-Btu/h type
55 ± 5 N·m (5.5 ± 0.5 kgf·m)
5/8" 24K-Btu/h type 70 ± 7 N·m (7.0 ± 0.7 kgf·m)
OM_AH-PN10 13GY_EN.indd Sec1:19OM_AH-PN10 13GY_EN.indd Sec1:19 12/22/11 6:30:35 PM12/22/11 6:30:35 PM
Page 22
E-20
CONNECTING THE PIPES TO THE OUTDOOR UNIT
Piping can be made in four directions, choose whichever direction convenient according to unit’s installation condition.
1. Remove 3 screws of service panel. Slide the panel downward and detach it.
Screw
Pipe cover
2. Remove the knock out hole of pipe cover or unit base pan, depending on the piping direction intended. After removing the knock out hole, remove burrs and attach BUSHING B on the knock out hole to protect the edge.
Knock out hole for refrigerant pipe
Knock out hole for refrigerant pipe and cable
3. Remove the pipe cover.
Pipe cover (front)
4. Connect the pipes.
Align the center of the pipes and tighten the flare nuts by hand for the first 3-4 turns. Use two wrenches to tighten up the pipes.
• Take care so that the connecting pipes will not touch the internal refrigerant piping.
• Be sure to cover the pipe connection area thoroughly with pipe thermal insulation.
Slit
6. Fill up the clearance between the knock out hole and the pipes with putty.
Slit
Slit
Pipe cover (rear)
5. Replace the pipe cover. Cut off the remaining portion of the pipe cover slit to widen the pipe opening and replace the pipe cover.
OM_AH-PN10 13GY_EN.indd Sec1:20OM_AH-PN10 13GY_EN.indd Sec1:20 12/22/11 6:30:37 PM12/22/11 6:30:37 PM
Page 23
ENG-
E-21
AIR REMOVAL
Lo Hi
Valve shaft cap tightening torque
Pipe size Torque
รุนเคร องปรับอากาศ
รุนเคร องปรับอากาศ
Liquid side 1/4" 24±3N · m (2.4±0.3 kgf · m) AH/AU-PN10, 13, 19 and 24
AH/AU-L10, 13
Gas side 3/8" 9K-Btu/h type 31±3 N · m (3.1±0.3 kgf · m) AH/AU-PN10 and L10
1/2" 12K 18K-Btu/h type 31±3 N · m (3.1±0.3 kgf · m) AH/AU-PN13, 19 and L13
5/8" 24K-Btu/h type 31±3 N · m (3.1±0.3 kgf · m) AH/AU-PN24
Service port cap tightening torque
Torque
11±1 N · m (1.1±0.1 kgf · m)
(1) Remove both valve shaft caps of the 2 and 3-way valves. (2) Remove the service port cap of the 3-way valve. (3)
Connect the gauge manifold hose to the service port and the vacuum pump. Be sure that the hose end to be connected to the service port has a valve core pusher. (4) Open the gauge manifold low-pressure valve(Lo) and operate the vacuum pump for 10-15 minutes. Make sure the compound gauge reads -0.1 MPa(-76 cmHg). (5) Close the gauge manifold valve. (6) Turn off the vacuum pump. Leave as it for 1-2 minutes and make sure the needle of the compound gauge does not go back. (7)
Open the 2-way valve 90° counterclockwise by turning the hexagon wrench. Close it after 5 second,
and check for gas leakage.* (8) Disconnect the gauge manifold hose from the service port. (9) Fully open the 2-way valve with hexagon wrench. (10)
Fully open the 3-way valve with hexagon wrench.
(11)
Firmly tighten the service port cap and both valve shaft caps with a torque wrench at the specified
tightening torque. *
Check the pipe connections for gas leak using a leakage detector or soapy water.
Gauge manifold
Compound gauge
Vacuum pump
Service port cap
3-way valve
Valve shaft cap
2-way valve
Hexagon wrench (Diagonally 4 mm)
OPEN
Service port
CLOSE
OM_AH-PN10 13GY_EN.indd Sec1:21OM_AH-PN10 13GY_EN.indd Sec1:21 12/22/11 6:30:37 PM12/22/11 6:30:37 PM
Page 24
E-22
CONNECTING THE CABLE TO THE OUTDOOR UNIT
9K 12K-Btu/h type
(1) Process the end of the connecting cable for the
outdoor unit. (2) Remove the control box cover. (3) Connect the cable. (4) Put back the control box cover. (5) Double-check that the cable is securely in place.
N
1
Earth wire
Control box cover
Connecting cable
Terminal board
Cable holder
8
8
40
50
Terminal cover
Earth wire
Length unit: mm
Connecting cable 9K 12K 18K-Btu/h type
18K-Btu/h type
(1) Process the end of the connecting cable for the
outdoor unit. (2) Remove the control box cover and the terminal cover. (3) Remove the cable holder and connect the cable. (4) Fix the cable sheath with the cable holder and the
screw. (5) Double-check that the cable is securely in place. (6) Put back the terminal cover and the control box cover.
24K-Btu/h type
(1)
ถอดรูสําหรับตอสายไฟออก โดยกระแทกที่แผนเหล็กของถอดฝาชุดครอบทอออก
ถอดรูสําหรับตอสายไฟออก โดยกระแทกที่แผนเหล็กของถอดฝาชุดครอบทอออก
(2) ตอสายไฟเขากับชุดควบคุมโดยตอใหตรงกับที่ตอกับชุดภายในบาน
(2) ตอสายไฟเขากับชุดควบคุมโดยตอใหตรงกับที่ตอกับชุดภายในบาน
(3) ยึดสายไฟใหแนนดวยตัวยึดสายไฟ
(3) ยึดสายไฟใหแนนดวยตัวยึดสายไฟ
(4) Double-check that the cable is securely in place. (5)
ปดชองวางระหวางสายไฟและรูของแผนใหหมดเพ อปองกันสิ่งแปลกปลอมเขาไปในตัวเคร อง
ปดชองวางระหวางสายไฟและรูของแผนใหหมดเพ อปองกันสิ่งแปลกปลอมเขาไปในตัวเคร อง
(6)
ประกอบฝาปดเขาที่เดิม
ประกอบฝาปดเขาที่เดิม
45 mm
8 mm
รูสำหรับตอสายไฟ
รูสำหรับตอสายไฟ
รูสำหรับตอสายไฟ
รูสำหรับตอสายไฟ
Cable holder
Terminal cover
CAUTIONS:
• Be sure to put the cable leads deep into the terminal board and tighten up the screws. Poor contact
can cause overheating or fire, or malfunction.
• Be sure to connect the cable to match the markings on the indoor unit’s terminal board and those of
the outdoor unit.
.
24 -Btu/h type
OM_AH-PN10 13GY_EN.indd Sec1:22OM_AH-PN10 13GY_EN.indd Sec1:22 12/22/11 6:30:39 PM12/22/11 6:30:39 PM
Page 25
ENG-
E-23
POWER CABLING
Power supply cable
Blue Brown Green/Yellow-striped
Power supply
Blue Live Green/Yellow-striped
Prepare a dedicated power supply circuit.
9K-Btu/h type 12K-Btu/h type 18K-Btu/h type 24K-Btu/h type
Power supply 220 V - 240 V, single-phase
Circuit breaker 10 A 15 A 20 A 25 A
• Fit a disconnect switch, having a contact separation of at least 3mm in all poles, to the electricity
power line.
TEST RUN
(1) Start the operation with the remote control.
(2) To start test run in cooling, hold down the
AUX button on the unit for over 5 seconds until a beep sound is heard and an operation lamp flashes.
(3) Make sure the system runs well. To stop the operation, press the AUX button
again.
ITEMS TO CHECK
Is the specified power supply voltage used? Is the connecting cable fixed to terminal board firmly? Is the earth wire connected properly arranged? Is the drainage properly? Is the indoor unit hooked to the mounting plate firmly? Is there any gas leakage at the pipe connection?
EXPLANATION TO CUSTOMER
• Explain to the customer how to use and maintain the system, referring to the operation manual.
• Ask the customer to carefully read the operation manual.
• When the system has been set up, hand the installation manual to the customer.
Model 18000/24000 BTUModel 9000/12000 BTU
AUX
AUX
OM_AH-PN10 13GY_EN.indd Sec1:23OM_AH-PN10 13GY_EN.indd Sec1:23 12/22/11 6:30:40 PM12/22/11 6:30:40 PM
Page 26
E-24
DETACHING THE UNIT FROM THE MOUNTING PLATE
“ ” mark.
Push the “
” marks at the bottom of the indoor unit and pull the bottom of the unit. When the hooks are released from the mounting plate, support the bottom of the unit and lift the unit upwards.
PUMP DOWN
Pump down is adopted in the case of unit removal for re-installation, abandonment, repair etc. Pump down is to collect the refrigerant into the outdoor unit.
PROCEDURE USING GAUGE MANIFOLD
(Recommended procedure)
(1) Connect the gauge manifold hose to the service
port of the 3-way valve.
(2) Run the air conditioner at cooling test run mode (Refer to 10 TEST RUN).
(3) After 5-10 minutes, close the 2-way valve.
(4) Close the 3-way valve when the compound gauge
reading becomes almost 0 MPa(0 cmHg).
(5) Stop the test run operation.
(6) Disconnect the gauge manifold hose from the service port.
(7) Disconnect both refrigerant pipes.
PROCEDURE WITHOUT USING GAUGE MANIFOLD
(1) Run the air conditioner at cooling test run mode (Refer to TEST RUN).
(2) After 5-10 minutes, fully close the 2-way valve by turning the hexagon wrench.
(3) After 2-3 minutes, immediately close the 3-way valve fully.
(4) Stop the test run operation.
(5) Disconnect both refrigerant pipes.
CUTIONS:
• Make sure that the compressor is turned off before removing the refrigerant pipes. Otherwise, it will
cause burst and injury.
Do not perform PUMP DOWN when refrigerant is leaking or there is no refrigerant in the refrigerant cycle. Otherwise, it will cause burst and injury.
Lo Hi
Gauge manifold
Compound gauge
3-way valve
2-way valve
Service port
OM_AH-PN10 13GY_EN.indd Sec1:24OM_AH-PN10 13GY_EN.indd Sec1:24 12/22/11 6:30:41 PM12/22/11 6:30:41 PM
Page 27
OM_AH-PN10 13GY_EN.indd Sec1:25OM_AH-PN10 13GY_EN.indd Sec1:25 12/22/11 6:30:42 PM12/22/11 6:30:42 PM
Page 28
Printed in Thailand TINSEA720JBRZ 11M- TH 2
OM_AH-PN10 13GY_EN.indd Sec1:26OM_AH-PN10 13GY_EN.indd Sec1:26 12/22/11 6:30:42 PM12/22/11 6:30:42 PM
Loading...