In the interests of user-safety (Required by safety regulations in some countries) the set
should be restored to its original condition and only parts identical to those specified should
be used.
Parts marked with "" are important for maintaining the safety of the set. Be sure to replace these parts with specified ones for maintaining the
safety and performance of the set.
This document has been published to be used for
after sales service only.
The contents are subject to change without notice.
Page 2
Propeller fan Φ460, 3-wing
13.0 (330)
800
Oil
FV50S ( 350cc )
11
AUX3M24LV
CHAPTER 1. SPECIFICATION
[1] SPECIFICATION
[2] Outdoor
ITEMS
Power supply
Phase
Rated frequency
Reted voltage
System
Indoor units number
Maximum length (per unit)
Maximum height difference
Performance
Capacity (Min.-Max.)
Rated
(Cooling)
Rated
(Heating)
Noise level
Air flow quantity
Fan speed
Compressor system
Compressor
Type
Fan system
Fan motor
Fan
Refrigerant system
Condenser
Refrigerant control
Refrigerant
Refrigerant filling
Connections
Refrigerant coupling
Refrigerant tube size
(A:Gas line,B:Liquid line)
Drain joint
Others
Net dimensions
Net weight
Moisture removal (Liters/h)
Power input
Running current
Capacity (Min.-Max.)
Power input
Running current
INDOOR MODELAE-X15PU
V
Hz60
ft (m)
ft (m)
Btu/h14000(5000 - 14000)
1/h3.2
W1120
A7.5
Btu/h
W
A
Cooling dB(A)
Heating dB(A)
Cooling m3/min
Heating m3/min
Cooling rpm
Heating rpm
Width
Height
Depth
inch(mm)
inch(mm)
inch(mm)
lb (kg)
Single
208/230
65.6 (20)
32.8 (10)
18000(4500 - 20000)
1550
10.0
49
50
42.7
45.8
800
SIAM(13.0cc)SNB130FGBMT
900W
Twin Rotary
CMOTLB537JBEZ
8poles,43W
Louver fin and Grooved tube type
Expansion valve FUJIKOKI Φ1.8
R410A
2.64lb (1200g)
Flare type
A: 1/2" (Flared connection 1/2")
B: 1/4" (Flared connection 1/4")
Connected part O.D.Φ16
33.5 (850)
28.0 (710)
93.7 (42.5)
AE-X18PU
Single
208/230
60
98.4 (30)
49.2 (15)
17000(6000 - 19000)
--
14152440
8.0
21600(5500 - 25000)24000(5500 - 26000)
1920
11.0
5253
42.3
42.3
820
820820
SIAM(13.0cc)SNB130FGBMT
900W
FV50S ( 350cc )
Twin Rotary
CMOTLB537JBEZCMOTLB537JBEZ
8poles,43W8poles,43W
Propeller fan Φ460, 3-wing
Louver fin and Grooved tube type Louver fin and Grooved tube type
This PCB is common for AE-X15PU/X18PU/X24PU, but for AE-X24PU,
there will be a sub-board. Will be released after approval.
2 – 5
Page 10
AE-X15PU
[3] FUNCTION
1. Function
1.1. Restart control
Once the compressor stops operating, it will not restart for 180 seconds to protect the compressor.
Therefore, if the operating compressor is shut down from the remote
control and then turned back on immediately after, the compressor will
restart after a preset delay time.
(The indoor unit will restart operation immediately after the ON switch
is operated on the remote control.)
1.2. Outdoor unit 2-way valve freeze prevention control
If the temperature of the outdoor unit 2-way valve remains below 0°C
for 10 consecutive minutes during cooling or dehumidifying operation,
the compressor operation stops temporarily in order to prevent freezing.
When the temperature of the 2-way valve rises to 10°C or higher after
about 180 seconds, the compressor restarts and resumes normal
operation.
1.3. Outdoor unit overheat prevention control
During cooling operation, if the temperature of the outdoor unit heat
exchanger exceeds the outdoor unit heat exchanger overheat prevention temperature (about 55°C), the operating frequency is decreased
by about 4 to 15 Hz. Then, this operation is repeated every 60 seconds until the temperature of the outdoor unit heat exchanger drops to
about 54
Once the temperature of the outdoor unit
about 54°C or lower, the operating frequency is increased by about 4
to 10 Hz every 60 seconds until the normal operation condition
resumes.
If the temperature of the outdoor unit heat exchanger exceeds the outdoor unit heat exchanger overheat protection temperature for (120
sec. : outdoor temperature ≥ 40°C, 60 sec : outdoor temperature <
40°C) at minimum operating frequency, the compressor stops operat-
ing and then restarts after about 180 seconds, and the above mentioned control is repeated.
°C or lower.
heat exchanger drops to
1.4. Compressor overheat prevention control
If the temperature of the compressor exceeds the compressor overheat prevention temperature (110°C), the operation frequency is
decreased by about 4 to 10 Hz. Then, this operation is repeated every
60
seconds until the temperature of the compressor drops below the
overheat protection temperature (100°C)
Once the temperature of the compressor drops below the overheat
protection temperature, the operating frequency is increased by about
4 to 10 Hz every 60 seconds until the normal operation condition
resumes.
If the temperature of the compressor exceeds the overheat protection
temperature (for 120 seconds in cooling operation or 60 seconds in
heating operation) at minimum operating frequency, the compressor
stops operating and then restarts after about 180 seconds, and the
above mentioned control is repeated.
.
1.5. Peak control
If the current flowing in the air conditioner exceeds the peak control
current (see the table below), the operation frequency is decreased
until the current value drops below the peak control current regardless
of the frequency control demand issued from the indoor unit based on
the room temperature.
The compressor stops immediately after cooling, dehumidifying or
heating operation is shut down, but the outdoor unit fan continues
operation for 50 seconds before it stops.
1.7. Defrosting
1.7.1 Reverse defrosting
The defrost operation starts when the compressor operating time
exceeds 10 minutes during heating operation, as shown below, and
the outside air temperature and the outdoor unit heat exchanger temperature
the indoor unit fan stops. The defrost operation stops when the outdoor unit heat exchanger temperature rises to about 15°C or higher or
the defrosting time exceeds 9 minutes.
1.8.
If a malfunction occurs, LED1 on the outdoor unit flashes in 0.2-seco
When reading the result of self-diagnosis, you shall combine it with indoor
unit indication in order to get a correct conclusion.
For details, please refer to the troubleshooting section.
meet certain conditions. When the defrost operation starts,
10 min or more10 min or more10 min or more
Start of
heating
operation
Defrosting
Max. 9min
Defrosting
Max. 9min
Self-diagnostic malfunction code display of Outdoor unit
nd intervals as shown below.
0 5
2 – 6
Page 11
AE-X15PU
1.9. AUTOMATIC AIR CONDITIONING
In the AUTO mode, the unit will automatically select COOL or HEAT
mode by comparing the room temperature and your desired temperature.
The unit will automatically switch between HEAT and COOL mode to
keep the desired temperature.
COANDA and MULTI SPACE button will be inactivated during AUTO
mode.
Modes and Temperature Settings
the figures in ( ) are temperature settings
During operation, if the outdoor temperature changes, the temperature
settings will automatically slide as shown in the chart.
2. Outline of PAM circuit
1.10. INACTIVATE 5°F(-15°C) AUTO STOP FUNCTION
During the heating operation, the unit will automatically stop when
the outdoor temperature drops below 5°F(-15°C) to prevent the
outdoor unit from the damage caused by the freezing of the drained
water. The unit will stop its operation for 4 hour and then resume
the operation when the outdoor temperature rises above 7°F(-13.9°C).
If the customer do not want to use this function, this function can be
inactivated by cutting JPA on outdoor PWB.
1. Power off.
2. Cut the JPA
cut JPA
2.1. PAM (Pulse Amplitude Modulation)
The PAM circuit varies the compressor drive voltage and controls the rotation speed of the compressor.
The IGBT shown in the block diagram charges the energy (electromotive force) generated by the reactor to the electrolytic capacitor for the inverter
by turning ON and OFF.
208 or
230V
When the IGBT is ON, an electric current flows to the IGBT via
the reactor (L1) and diode bridge (DB2).
When the IGBT turns OFF, the energy stored while the IGBT
was ON is charged to the voltage capacitor via the diode
bridge (DB1).
As such, by varying the ON/OFF duty of the IGBT, the output
voltage is varied.
2 – 7
Page 12
AE-X15PU
2.2. High power factor control circuit
This circuit brings the operating current waveform closer to the waveform of commercial power supply voltage to maintain a high power factor.
Because of the capacitor input, when the PAM circuit is OFF, the phase of the current waveform deviates from the voltage waveform as shown below.
To prevent this deviation, a current is supplied during the periods indicated by "O" in the diagram.
To determine the length of period to supply a current, the zero-cross timing of the AC input voltage is input to the microcomputer via the clock circuit.
The power source frequency is also determined at the same time.
The IGBT turns ON after the time length determined by the zero-cross point to supply a current to the IGBT via the reactor.
This brings the current waveform closer to the voltage waveform in phase.
As descr bed above, the ON/OFF operation of the IGBT controls the increase/decrease of the compressor power supply voltage (DC voltage) to
improve the compressor efficiency and maintain a high power factor by keeping the current phase closer to that of the supply voltage.
2.2.1 Detailed explanation of PAM drive circuit sequence
60
about 9 mS
1300uS
0.004
1.7ms
2.2.2 AC clock (zero-cross) judgment
• The clock circuit determines the time from one rising point of the clock waveform to the next rising point.
The detected clock waveform is used to judge the power source frequency (60Hz).
• The zero-cross of the AC voltage is judged as the rising of the clock waveform, as shown in the diagram above.
2.2.3 IGBT ON start time (delay time B)
• Based on the zero-cross of the AC voltage, the IGBT turns ON after a delay time set according to the power source frequency.
2.2.4 IGBT ON time (C)
• After the above delay time, the IGBT turns ON to supply a current to the reactor.
• The ON time of the IGBT determines the amount of energy (level of DC voltage rise) supplied to the reactor.
DC voltage level in each operation mode (varies depending on external load conditions)
– Cooling operation --- 220 to 290 V
– Heating operation --- 260 to 290 V
2.3. PAM protection circuit
To prevent excessive voltage of PAM output from damaging the IPM and electrolytic capacitor as well as the control printed wiring board (PWB), this
circuit monitors the PAM output voltage and turns off the PAM control signal and PAM drive immediately when an abnormal voltage output is gener-
ted. At the same time, it shuts off the compressor operation.
a
The protection voltage level is as follows.
C9
C8
7
2 – 8
Page 13
AE-X15PU
2.3.1 Details of troubleshooting procedure for PAM
1) PAM shutdown due to error
1) When the DC voltage detection circuit sends a signal exceeding the specified voltage to the microcomputer
DC voltage of 400 V or higher (detection circuit input voltage of about 4.6 V or higher) [IC1 69 pin]
– When an error is detected
• PAM IGBT turns OFF.
• Compressor turns OFF.
• All units shut down completely when the error occurs four times.
2) When the outdoor unit clock waveform differs from the specified value immediately before the PAM IGBT turns ON
When there is no clock waveform input
When a clock signal of other than specified power source frequency (60Hz) is input
– When an error is detected
• PAM IGBT does not turn ON.
• Compressor operates normally.
• Complete shutdown does not occur.
2) PAM error indication
In case of error “1)”
– An error signal is sent to the indoor unit as soon as an error is generated.
• Malfunction No. 14-0 is indicated when the error code is called out by the indoor unit's self-diagnosis function.
– The LED on the outdoor unit flashes 14 times when an error is generated.
• The LED continues flashing in the 14-time cycle even after the compressor stops ope
• The LED turns off (data is deleted from the memory) when the outdoor unit power is turned off.
In case of error “2)”
– An error signal is sent to the indoor unit as soon as an error is judged.
• Malfunction No. 14-1 is indicated when the error code is called out by the indoor unit's self-diagnosis function.
– The LED on the outdoor unit flashes 14 times when an error is judged.
• The LED on the outdoor unit flashes in normal pattern when the compressor stops operating.
(Compressor OFF or Thermostat OFF from remote control)
* When a user complains that the air conditioner does not provide sufficient cool air or warm air
In addition to conventional error-generating reasons, there is a possibility that the PAM IGBT does not turn ON even if the compressor is operating.
In that case, the DC voltage does not rise even though the compressor is operating, and lowers to the 180-VDC level.
– Check items
• Clock circuit check
• PAM IGBT check
rating.
2 – 9
Page 14
AE-X15PU
3. Explanation of IPM drive circuit
The IPM for compressor drive is made by Mitsubishi Electric.
The power supply for the IPM drive, the shunt resistance for over current detection, etc., are provided outside the IPM (control PWB).
3.1. IPM drive power supply circuit
The power supply for the upper-phase IGBT (HU, HV, HW) drive employs a bootstrap system, and provides power to the upper-phase IC.
The 15-V power supply for the lower-phase IC is provided by the control printed wiring board (PWB).
3.1.1 Brief explanation of bootstrap system (single power drive system)
To supply power to the upper-phase IC, the microcomputer (IC1) turns ON the lower-phase IGBT (LU, LV, LW).
This results in a charging current that flows to the electrolytic capacitor of each upper-phase IC input and charges the bootstrap capacitor with a 15V
current.
The power supply for the subsequent stages is charged while the lower-phase IGBT is ON in ordinary compressor drive c
ontrol.
2 – 10
Page 15
AE-X15PU
3.1.2 DC over current detection circuit
When a current of about 20 A or higher flows through the shunt resistance [AE-X15PU(R230~R234), AE-X18PU/AE-X24PU(R230~R235)] on the
control printed wiring board (PWB), the voltage at this resistance is input to IPM CIN pin (15). Then, the gate voltage of the lower-phase IGBT (LU,
LV, LW) inside the IPM turns OFF to cut off the over current. At the same time, an L output of more than 20μs is generated from IPM from pin (14),
and this results in an L input to over current detection input pin (17) of the microcomputer (IC1) and turns OFF the PWM signal output (IC1 pins (20)
through (25)) to the IGBT gate.
AE-X15PU(R230~R234),
AE-X18PU/AE-X24PU(R230~R235)
2 – 11
Page 16
AE-X15PU
4. 180° energizing control
This is the control system to moderate the speed by the current phase difference for higher efficiency and lower noise of the compressor. The current
phase difference control is the control system paid attention to the interrelation between efficiency and phase gap generated by the applied voltage of
motor and current in the coil of motor as shown in the figure below.
This control is the forced magnetization system independent of the location of rotor, detecting the phase difference between driving voltage phase and
line current phase flowing in motor coil, and controls the modulation rate data to get the phase difference at the best efficiency.
2 – 12
Page 17
AE-X15PU
CHAPTER 3. FUNCTION AND OPERATION OF PROTECTIVE PROCEDURES
[1] PROTECTION DEVICE FUNCTIONS AND OPERATIONS
* These models have following thermistors.
INDOOR UNIT
AE-X15PU, AE-X18PU, AE-X24PU
The errors for the thermistors that are not mentioned above are irrelevant.
These indoor units don’t have power relay.
DescriptionDetection periodReset conditionIndoor
1Indoor unit fan lockOperation stops if there is no
Indoor unit fan rotation speed error
22-way valve freeze
prevention
3Outdoor unit heat
exchanger overheat shutdown
4Compressor dis-
charge overheat
shutdown
5Dehumidifying oper-
ation temporary
stop
6DC over current
error
7AC over current
error
8AC over current
error in compressor
OFF status
9AC maximum cur-
rent error
10 AC current defi-
ciency error
input of rotation pulse signal from
indoor unit fan motor for 1 minute.
Operation stops if rotation pulse
signal from indoor unit fan indicates abnormally low speed
(about 300 rpm or slower).
Compressor stops if temperature
of outdoor unit 2-way valve
remains below 0℃ for 10 continuous minutes during cooling or
dehumidifying operation.
Operation frequency lowers if outdoor unit heat exchanger temperature exceeds about 55℃ during
cooling operation.
Compressor stop
heat exchanger temperature
exceeds about 55℃
onds at minimum frequency.
Operating frequency lowers if
temperature of compressor
chamber thermistor (TH1) falls
below about 110℃.
Compressor stops if temperature
of compressor chamber thermistor (TH1) remains at about
110℃ (for 120 seconds in cooling
operation, or 60 seconds in heating operation) at minimum frequency.
Compressor stops if outside air
temperature thermistor is lower
than about 16℃ during dehumidifying operation.
Compressor stops if electric cur-
about 20 A or higher flows
rent of
in IPM.
Operating frequency lowers if
compressor AC current exceeds
peak control current value. Compressor stops if compressor AC
current exceeds peak control current value at minimum frequency.
Indoor and outdoor units stop if
AC current exceeds about 3 A
while compressor is in non-operation status.
Compressor stops if compressor
AC current exceeds 17 A.
Compressor stops if operating
frequency is 50 Hz o
compressor AC current is about
2.0 A or lower.
s if outdoor unit
for 120 sec-
r higher and
When indoor unit fan
is in operation
When indoor unit fan
is in operation
When in cooling or
dehumidifying operation
When in cooling or
dehumidifying operation
When compressor is
in operation
When in dehumidifying operation
When compressor is
in operation
When compressor is
in operation
When compressor is
in non-operation
When compressor is
in operation
When compressor i
in operation
TH1, TH2, TH3, TH4, TH6
unit
error
display
Operation OFF or ON I2YesNone
Operation OFF or ON I2YesNone
Automatic reset when
temperature of 2-way
valve rises above
10℃ .
Automatic reset after
safety period (180
sec).
Automatic reset after
safety period (180
sec).
Automatic reset when
outside air temperature rises above
16℃.
Operation OFF or ON YesI1Yes
Operation OFF or ON YesI1YesYes
Replacement of
defective parts such
as IPM
Operation OFF or ON Yes I1YesYes
s
Operation OFF or ON Yes I1YesYes
NoneYesYes
NoneYesYes
NoneYesYes
NoneYesYes
YesI2YesYes
result display
Indoor
unit
Outdoor
Yes
sisongaid-fleSnoitarepOnoitcnuF
unit
3 – 1
Page 18
AE-X15PU
F
DescriptionDetection periodReset conditionIndoor
11 Thermistor installa-
tion error or 4-way
valve error
12 Compressor high
temperature error
13 Outdoor unit heat
exchanger thermistor short-circuit
error
14 Outdoor unit outside
air temperature
thermistor short-circuit error
15 Outdoor unit suction
thermistor short-circuit error
16 Outdoor unit 2-way
valve thermistor
short-circuit error
17 Outdoor unit heat
exchanger thermistor open-circuit
error
18 Outdoor unit outside
air temperature
thermistor open-cir-
error
cuit
19 Outdoor unit suction
thermistor open-circuit error
20 Outdoor unit 2-way
valve thermistor
open-circuit error
21 Outdoor unit dis-
charge thermistor
open-circuit error
22 Serial signal errorPower relay turns OFF if indoor
23 Compressor star-
tup error
24 Compressor rota-
tion error (at 120°
energizing)
25 Outdoor unit DC fan
error
26 PAM over voltage
error
Compressor stops if high and low
values of temperatures detected
by outdoor unit heat exchanger
thermistor (TH2) and 2-way valve
thermistor (TH5) do not match
operating cycle.
Compressor stops if compressor
chamber thermistor (TH1)
exceeds about 114℃
is short-circuit in TH1.
Compressor stops if there is
short-circuit in outdoor unit heat
exchanger thermistor (TH2).
Compressor stops if there is
short-circuit in outdoor unit outside air temperature thermistor
(TH3).
Compressor stops if there is
short-circuit in outdoor unit suction thermistor (TH4).
Compressor stops if there is
short-circuit in outdoor unit 2-way
valve thermistor (TH5).
Compressor stops if there is
open-circuit in outdoor unit heat
exchanger thermistor (TH2).
Compressor stops if there is
open-circuit in outdoor unit outside air temperature thermist
(TH3).
Compressor stops if there is
open-circuit in outdoor unit suction thermistor (TH4).
Compressor stops if there is
open-circuit in outdoor unit 2-way
valve thermistor (TH5).
Compressor stops if there is
open-circuit in outdoor unit discharge thermistor (TH1).
unit cannot receive serial signal
from outdoor unit for
Compressor stops if outdoor unit
cannot receive serial signal from
indoor unit for 30 seconds.
Compressor stops if compressor
fails to start up.
Compressor stops if there is no
input of position detection signal
from compressor or input is
abnormal.
Operation stops if there is no
input of rotation pulse signal from
outdoor unit fan motor for 30 seconds.
Compressor stops if DC voltage is
350 V or higher.
, or if there
or
8 minutes.
result display
Indoor
unit
error
display
3 minutes after compressor startup
When in operationOperation OFF or ON YesI1YesYes
At compressor startup
At compressor startup
At compressor startup
At compressor startup
At compressor startup
At compressor startup
At compressor startup
At compressor startup
ressor star-
At comp
tup
When in operationOperation OFF or ON
When in operationReset after reception
At compressor startup
Compressor operating at 120° energizing
When outdoor unit
fan is in operation
When in operationOperation OFF or ON Yes I1YesYes
Operation OFF or ON Yes I1YesYes
Operation OFF or ON Yes I1YesYes
Opera
tion OFF or ON YesI1YesYes
Operation OFF or ON Yes I1YesYes
Operation OFF or ON Yes I1YesYes
Operation OFF or ON Yes I1YesYes
Operation OFF or ON Yes I1YesYes
Operation OFF or ON Yes I1YesYes
Operation OFF or ON Yes I1YesYes
Operation OFF or ON YesI1YesYes
(Automatic reset
when less than 8 minutes)
NoneNoneNone
of serial signal
Operation OFF or ON Yes I3YesYes
Operation OFF or ON Yes I3YesYes
Operation OFF or ON Yes I1Ye
unit
YesNone
sYes
Outdoor
sisongaid-fleSnoitarepOnoitcnu
unit
3 – 2
Page 19
DescriptionDetection periodReset co
27 PAM clock errorWhen power source frequency
28 Outdoor unit ther-
mal fuse error in the
Terminal board
I1—The outdoor unit restarts four times before the indoor unit error is displayed (complete shutdown).
I2—A single error judgment results in the display of the indoor unit error (complete shutdown).
I3—The outdoor unit restarts eight times before the indoor unit error is displayed (complete shutdown).
cannot be determined (at startup),
or when power source clock cannot be detected for 1 continuous
second (at startup).
Compressor stops if outdoor unit
cannot receive serial signal from
indoor unit for 30 seconds.
The errors for the thermistors that are not mentioned above are irrelevant.
These indoor units don’t have power relay.
TH1, TH2, TH3, TH4, TH6
nditionIndoor
unit
error
display
NoneYesYes
NoneNoneNone
AE-X15PU
result display
Indoor
unit
sisongaid-fleSnoitarepOnoitcnuF
Outdoor
unit
3 – 3
Page 20
AE-X15PU
1. Outdoor unit
ItemModeControl opera-
Compressor
chamber thermistor (TH1)
Heat exchanger
thermistor (TH2)
Outside air temperature thermistor (TH3)
Suction pipe thermistor (TH4)
2-way valve thermistor (TH5)
Cooling
Dehumidifying
Heating
Cooling
Dehumidifying
HeatingExpansion valve
AutoOperation mode
Cooling
Dehumidifying
HeatingRating control
Cooling
Dehumidifying
HeatingExpansion valve
Cooling
Dehumidifying
HeatingOperation not
Expansion valve
control and compressor protection
Outdoor unit heat
exchanger overheat prevention
control
Defrosting
judgment
Operation not
affected
Defrosting
Expansion valve
control
control
Expansion valve
control
affected
tion
When resistance is low
(temperature
judged higher
than actual)
Compressor
operates, but
room does not
become cool or
warm (expansion
valve is open).
Compressor
operates at low
speed or stops.
Defrosting operation is not activated as needed,
and frost accumulates on outdoor
unit (
expansion
valve is closed).
Cooling mode is
activated even if
room tempera-
ture is low.
Normal operation. Outdoor unit ther-
Defrosting operation is activated
unnecessarily.
Compressor
operates, but
room does not
become cool
(expansion valve
open).
is
Compressor
operates, but
room does not
become warm
(expansion valve
is open).
Frost accumu-
lates on indoor
unit evaporator
and room does
not become cool
(expansion valve
is closed).
Normal operation. Outdoor unit ther-
Short-circuitWhen resis-
Compressor high
temperature error
indication.
Outdoor unit thermistor short-circuit error
indication.
Outdoor unit thermistor short-circuit error
indication.
Outdoor unit thermistor short-circuit error
indication.
mistor short-circuit error
indication.
Outdoor unit thermistor short-circuit error
indication.
Outdoor unit thermistor short-circuit error
indication.
Outdoor unit thermistor short-circuit error
indication.
Outdoor unit thermistor short-circuit error
indication.
mistor short-circuit error
indication.
tance is high
(temperature
judged lower
than actual)
Layer short-circuit or open-circuit may result in
compressor in
normal operation.
Normal operation. Outdoor unit ther-
Defrosting operation is activated
unnecessarily,
and room does
not become warm
(expansion valve
is open).
Heating mode is
activated even if
room temperature is high.
Normal operation. Outdoor unit ther-
Defrosting operation is not activated, and frost
accumulates on
outdoor unit.
Frost accumulates on evapora
tor inlet section,
and room does
not become cool
(expansion valve
is closed).
Frost accumulates on expansion valve outlet
section, and room
does not become
warm (expansion
valve is closed).
Compressor
operates, but
room does not
become cool
(expansion valve
is open).
Normal operation. Outdoor unit ther-
Open-circuit
Outdoor unit thermistor open-circuit error
indication.
mistor open-circuit error
indication.
Outdoor unit thermistor open-circuit error
indication.
Outdoor unit thermistor open-circuit error
indication.
mistor open-circuit error
indication.
Outdoor unit thermistor open-circuit error
indication.
Outdoor unit ther-
-
mistor open-circuit error
indication.
Outdoor unit thermistor open-circuit error
indication.
Outdoor unit thermistor open-circuit error
indication.
mistor open-circuit error
indication.
3 – 4
Page 21
[3] THERMISTOR TEMPERATURE CHARACTERISTICS
he
1. Outdoor unit thermistor temperature characteristics
To measure the resistance, first remove the connector from the board.
To operate the outdoor unit independently, short-circuit the sections indicated by arrows in the diagram below with an adapter, and apply rated VAC
between (L1) and (L2) on the terminal board of the outdoor unit. This allows the outdoor unit to be operated in cooling mode independently.
(Do not operate the outdoor unit in this condition for an extended period of time.)
Soldering Side
C8
L2
L3
these pads are connected and Power is applied to L1 and L2 on terminal board.
n the outdoor unit operate in "TEST COOL 40Hz" mode.
C9
3 – 5
Page 22
AE-X15PU
[5] GENERAL TROUBLESHOOTING CHART
* These models have following thermistors.
INDOOR UNIT
AE-X15PU, AE-X18PU, AE-X24PU
The errors for the thermistors that are not mentioned above are irrelevant.
These indoor units don’t have power relay.
1. Indoor unit does not turn on
Main causeInspection methodNormal value/conditionRemedy
Cracked PWB.
(Cracked pattern)
Open-circuit in FU1 (250 V, 2.5A). Check melting of FU1.There should be no open-circuit.Replace PWB.
Check visually.There should be no cracking in
2. Indoor unit fan does not operate
Main causeInspection methodNormal value/conditionRemedy
Open-circuit in heat exchanger
thermistor (TH2) (in heating operation)
Disconnected heat exchanger
thermistor (TH2) (in heating operation)
Measure thermistor resistance
(dismount for check)
Inspect connector on PWB.
Check thermistor ins
dition.
tallation con-
TH1, TH2, TH3, TH4, TH6
PWB or pattern.
Refer to THERMISTOR TEPERATURE CHARACTERISTICS-1
There should be no open-circuit
or faulty contact.
Thermistor should not be disconnected.
Replace PWB.
Replace thermistor.
Replace thermistor.
Install correctly.
3. Indoor unit fan speed does not change
Main causeInspection methodNormal value/condi
Remote control not designed to
allow fan speed change.
Check operation mode.Fan speed should change except
during dehumidifying operation,
ventilation, light dehumidifying
operation, internally normal operation
tionRemedy
4. Remote control signal is not received
Main causeInspection methodNormal value/conditionRemedy
Batteries at end of service life.Measure battery voltage.2.5 V or higher (two batteries in
series connection)
Batteries installed incorrectly.Check battery direction.As indicated on battery compart-
ment.
Lighting fixture is too close, or fluorescent lamp is burning out.
Use Sevick light (Hitachi).Check if Sevick light (Hitachi) is
Operating position/angle is inappropriate.
Open-circuit or short-circuit in wiring of light receiving section.
Defective light receiving unit.Check signal receiving circuit
w condensation on light receiv-
De
.
ing unit
Turn off light and check.Signal should be received when
light is turned off.
Signal may not be received
used.
Operate within range specified in
manual.
Check if wires of light receiving
section are caught.
(measure voltage between terminals 9 and 10 of connector CN7).
Check for water and rust.Signal should be received within
sometimes due to effect of Sevick
light.
Signal should be received within
range specified in manual.
Wires of light receiving section
should not have any damage
caused by pinching.
Tester indicator should move
when signal is received.
range specified in manual.
Explain to user.
Install new batteries.
Install batteries in indicated direction.
Change light position or install
new fluorescent lamp.
Replace light or change position.
Explain appropriate handling to
user.
Replace wires of light receiving
section.
Replace PWB.
Take moisture-proof measure for
lead wire outlet of light receiving
section.
3 – 6
Page 23
5. Louvers do not move
Main causeInspection methodNormal value/conditionRemedy
Caught in sliding section.Operate to see if louvers are
caught in place.
Disconnected connectorInspect connectors.Connectors or pins should not be
Contact of solder on PWB
(connector section on PWB)
Check visually.There should not be solder con-
Louvers should operate smoothly. Remove or correct catching sec-
disconnected.
tact.
6. There is noise in TV/radio
Main causeInspection methodNormal value/conditionRemedy
Grounding wires not connected
properly.
TV/radio is placed too close to
outdoor unit.
Other than above.Check for radio wave interfer-
Check grounding wire connections.
Check distance between TV/radio
and outdoor unit.
ence.
Grounding wires should be connected properly.
If TV/radio is placed too close, it
may become affected by noise.
7. Malfunction occurs
AE-X15PU
tion.
Install correctly.
Correct contacting section.
Connect grounding wires properly.
Move TV/radio away from outdoor
unit.
Main causeInspection metho
Malfunction caused by noise.Che
ence.
ck for radio wave interfer-
dNormal value/conditionRemedy
8. Compressor does not start
Main causeInspection methodNormal value/conditionRemedy
Erroneous inter-unit connection.Check wiring between indoor and
outdoor units.
Dried-up electrolytic capacitor.Check electrolytle ecalpeR.roticapac ciectrolytic capacitor.
Blown outdoor unit fuse.Check 20-A fuse.Fuse should not be blown.Replace fuse/diode bridge.
Power supply voltage is too low.Measure power supply voltage
during startup.
Compressor lock.Supply current and touch com-
pressor cover (sound absorbing
material) to check if operation
starts.
Terminal board 1-N: 230 VAC, 60
Hz
Terminal board 2: serial signal
230±10 VAC, 60 HzMake sure that power supply volt-
Compressor should start normally.
Correct wiring.
.MPI ecalpeR.ytiunitnoc MPI kcehC.MPI degamaD
Replace fuse.
Replace outdoor unit PWB
assembly.
age is 180 V or higher.
Apply external impact to com-
pressor.
Replace compressor.
9. Operation stops after a few minutes and restarts, and this process repeats
Main causeInspection methodNormal value/conditionRemedy
Dried-up electrolytic capacitor.Measure 290-VDC line voltage.250 V or higher.Replace electrolytic capacitor.
Layer short-circuit in expansion
valve coil.
CAUTION:If fuse FU1/FU5 (outdoor unit control circuit board) is blown, be careful of charging voltage in inverter electrolytic capacitor C8, C9.
To discharge stored electricity, unplug the power cord and connect the plug of a soldering iron (230VAC, 30W) between the positive and
negative terminals of inverter electrolytic capacitor C8, C9.
Measure resistance.46±3Ω in each phase (at 20℃
)Replace coil.
3 – 7
Page 24
AE-X15PU
[6] MALFUNCTION (PARTS) CHECK METHOD
1. Procedure for determining defective outdoor unit IPM/compressor
The following flow chart shows a procedure for locating the cause of a malfunction when the compressor does not start up and a DC overcurrent indication error occurs.
208/
L1L2
2. Diode bridge check method
Turn off the power and let the inverter electrolytic capacitor (C8, C9) discharge completely. Then use a tester and check continuity.
When using a digital tester, the (+) and (-) tester lead wires in the table must be reversed.
Turn off the power, let the inverter electrolytic capacitor (C8, C9) discharge completely, and remove the capacitor from the control printed circuit board
(PWB). First, check the case for cracks, deformation and other damages. Then, using a needle-type tester, check co
Determination of normal condition
The tester needle should move on the scale and slowly returns to the original position. The tester needle should move
in the same way when polarities are reversed. (When measurement is taken with the polarities reversed, the tester
needle exceeds the scale range. Therefore, let the capacitor discharge before measurement.)
ntinuity.
3 – 8
Page 25
AE-X15PU
4. IPM check method
Turn off the power, let the large capacity electrolytic capacitor (C8, C9) discharge completely, and dismount the IPM. Then, using a tester, check leak
current between C and E.
When using a digital tester, the (+) and (-) tester lead wires in the table must be reversed.
Needle-type testerNormal resistance value
(-)(+)
PN
U
V
W
Needle-type testerNormal resistance value
(-)(+)
UN∞
V
W
Values in ( ) are for digital tester.
∞
(several MΩ)
(several MΩ)
[7] OUTDOOR UNIT CHECK METHOD
After repairing the outdoor unit, conduct the following inspection procedures to make sure that it has been repaired completely. Then, operate the
compressor for a final operation check.
1. Checking procedures
No
.
1PreparationDisconnect compressor cords (white,
orange, red: 3 wires) from compressor terminals, and connect simulated
load (lamp used as load).
Operate air conditioner in cooling or
heating test operation mode.
2Inverter DC power supply
voltage check
3IPM circuit checkCheck that 3 lamps (load) light.
Measure DC voltage between IPM
pins (20) and (24).
Check position detection voltage (+15
V, 5 V) on control PWB.
(fo
r each phase of U, V and W).
Use multi-meter o
ble of displaying two digits right of the
decimal point (0.01Ω).
tance.
sor cords to compressor.
Operate air conditioner.
Measure DC voltage between IPM
pins (20) and (24).
r digital tester capa-
ydemeRnoitidnoc/eulav lamroNdohtem kcehCmetI
.BWP lortnoc ecalpeRCDV 023
Replace diode bridge.
Correct soldered section of Fasten tabs (BT1, BT2, BT5,BT6) on
control PWB and IPM (S, C, R).
(Repair solder cracks.)
Each voltage should be normal.
All 3 lamps (load) should light with
same intensity.
Resistance value at 20℃ --- 0.65Ω Correct connections at compres-
Each phase 46±3Ω (at 20℃)Replace expansion valve.
Compressor should operate normally.
200 VDC or higher.
Replace control PWB.
sor terminals.
Replace compressor.
Replace control PWB.
Replace outdoor unit thermistor.
Replace compressor (in case of
compressor lock).
3 – 9
Page 26
AE-X15PU
2. Troubleshooting of outdoor unit electric components
2
3
3
3 – 10
Page 27
AE-X15PU
3. Caution in checking printed wiring boards (PWB)
3.1. Non-insulated control circuit
The GND terminals of the low-voltage circuits (control circuits for microcomputer and thermistors and drive circuits for expansion valve and relays) on
the control printed wiring board (PWB) are connected to the compressor drive power supply (320-VDC negative terminal). Therefore, exercise utmost
caution to prevent electric shock.
If a measuring instrument used for the test is grounded, its chassis (ground) has the same electric potential as the 0-V probe. Since non-insulated circuits have the following voltage potential difference from the ground, connection of the grounding wire results in a short-circuit between the 0-V line
and the ground, thus allowing an excessive current t
the sheaths of the thermistor lead wires or expansion valve lead wires inside the outdoor unit become damaged due to pinching by the front panel
If
or other metal parts or contacting a pipe, a high voltage can flow and destroy the circuits. To prevent these problems, carefully conduct assembly
work.
L1
208/230V
L2
o flow to the tester to cause damage.
3 – 11
Page 28
AE-X15PU
[8] TROUBLESHOOTING GUIDE
1. Self-Diagnosis Function
1.1. Indoor unit
• To display the self-diagnosis, hold down the AUX button for over 5 seconds on the indoor unit when the indoor unit is not operating.
• The operation lamp (green), timer lamp (orange) and Plasmacluster lamp (blue) flash to indicate the information of malfunction.
• If the power cord is unplugged or the circuit breaker is turned off, the self-diagnosis memory is lost.
AUX
Plasmacluster lamp(Blue)
Operation lamp(Green)
Timer lamp(orange)
<Display of self-diagnosis result>
The operation lamp (green) and the Plasmacluster lamp (blue) flash in synchronization with the timer lamp (orange).
Timer lamp (1 cycle)
1st2nd3rd4th5th
1-second
ON
1-second
ON
1-second
ON
1-second
ON
1-second
ON
ON
OFF
1-second
OFF
1-second
OFF
1-second
OFF
1.2. Outdoor unit
• The self-diagnosis is indicated the error information by flashing LED1 on the outdoor unit.
• The self-diagnosis of outdoor unit is displayed for sbout 3-10 minutes.Then ,the LED1 returns to normal display.
1-second
OFF
5-second OFF
3 – 12
Page 29
[9] CHART
<INDOOR UNIT> ○:1-second ON / 1-second OFF
AE-X15PU
Problem
symptom
Normal
condition
Indoor and
outdoor units
do not operate.
Indoor and
outdoor units
do not
operate.
Outdoor
unit
indication
(LED1)
Normal
blinking
1-time
2-time
Indoor unit
→
O O O O O Timer (Orange)
O O O O O Timer (Orange)
O Operation (Green)
O O O O O Timer (Orange)
O Operation (Green)
O Plasmacluster (Blue)
O O O O O Timer (Orange)
O Operation (Green)
OPlasmacluster (Blue)
O O O O O Timer (Orange)
O Operation (Green)
O O Plasmacluster (Blue)
O O O O O Timer (Orange)
OOperation (Green)
LampMain SubMainSub
Operation (Green)
Plasmacluster (Blue)
Plasmacluster (Blue)
Plasmacluster (Blue)
Malfunction
No.*
00 Normal
10 Outdoor unit
1Outdoor temperature
2Suction hermistor
3Suction hermistor
20 Cycle
Content of diagnosisCheck pointAction
thermistor
short-circuit
temperature
Heat exchanger
thermistor short
circuit error
thermistor short
circuit error
short circuit error
(for unit A, B, C)
short circuit error
Compressor high
temperature error
1) Measure the resistance
of the outdoor unit
thermistors.
2) Check the lead wire
of the outdoor unit
thermistor for torn
sheath and shortcircuit.
3) 1) 2):Normal
1) Check the outdoor unit
air outlet for blockage.
2) Check if the power
supply voltage is AC
230V at full power.
3) Check the pipe
connections for
refrigerant leaks.
4) Measure resistance
of the outdoor unit
compressor thermistor.
5) Check the expansion
valve for proper
opera ion.
1) Replace the outdoor
unit thermistor
assembly.
2) Replace the outdoor
unit thermistor
assembly.
3) Replace the outdoor
unit control PCB
assembly.
1) Ensure unobstructed
outdoor unit air
ou let.
2) Connect power
supply of proper
voltage.
amount of refrigerant.
4) Replace he outdoor
unit compressor
thermistor assembly.
5) Replace he expansion valve coil,
expansion valve or
outdoor unit control
PCB assembly.
Indoor unit
operates.
Outdoor
unit does
not operate
temporarily
Indoor and
outdoor
units do not
operate.
Indoor unit
operates.
Outdoor
unit does
not operate
temporarily.
3-time
O O O O O Timer (Orange)1Compressor
OOperation (Green)
O Plasmacluster (Blue)
O O O O O Timer (Orange)2Outdoor unit heat
OOperation (Green)
OPlasmacluster (Blue)
O O O O O Timer (Orange)3Indoor unit heat
OOperation (Green)
O O Plasmacluster (Blue)
O O O O O Timer (Orange)4IPM high
OOperation (Green)
OPlasmacluster (Blue)
O O O O O
O O O O O
Timer (Orange)5IPM high
OOperation (Green)
OO Plasmacluster (Blue)
Timer (Orange)
Operation (Green)
O O
Plasmacluster (Blue)
30
Dry operation
Heat
operation
3 – 13
discharge overheat.
exchanger overheat.
exchanger overheat.
temperature error
temperature error
Temporary stop
due to dehumidifying opera ion
5℉/-15℃
AUTO OFF
(Temporary stop for cycle
protection)
(Temporary stop for cycle
protection)
(Temporary stop for cycle
protection)
Measure resistance of the
heat-sink hermistor.
Replace the outdoor unit
control PCB assembly.
(Temporary stop for
cycle protection)
Measure the resistance
of outdoor temperature
thermister.
-
-
-
-
-
-
Replace the indoor
unit thermister assembly.
Page 30
AE-X15PU
Problem
symptom
Indoor and
outdoor
units do not
operate.
Indoor and
outdoor
units do not
operate.
Indoor and
outdoor
units do not
operate.
Indoor and
outdoor
units do not
operate.
)
)
)
)
)
)
)
)
)
)
)
)
)
Malfunction
No.*
Content of diagnosisCheck pointAction
thermistor
open-circuit
DC Current
AC Current
wire check
Outdoor
unit
indication
(LED1)
5-timeO O O O O Timer (Orange)50 Outdoor unit
O O O O O Timer (Orange)1Outdoor temperature
O O O O O Timer (Orange)2Suction thermistor
O O O O O Timer (Orange)3Suction thermistor
O O O O O Timer (Orange)4Discharge thermistor
O O O O O Timer (Orange)5Heat sink thermistor
6-timeO O O O O Timer (Orange)60Outdoor unit
O O O O O Timer (Orange)1IPM pin level errorCheck the IPM is attached
7-timeO O O O O Timer (Orange)70 Outdoor unit
O O O O O Timer (Orange)1AC current error
O O O O O Timer (Orange)2AC maximum current
O O O O O Timer (Orange)3AC current
8-timeO O O O O Timer (Orange)80 Abnormal
Indoor unit
→
OO Operation (
OO Operation (
O Plasmacluster (Blue)
OO Operation (
OPlasmacluster (Blue)
OO Operation (
O O Plasmacluster (Blue)
OO Operation (
OPlasmacluster (Blue)
OO Operation (
OO Plasmacluster (Blue)
O OOperation (
O OOperation (
O Plasmacluster (Blue)
O O O Operation (
O O O Operation (
O Plasmacluster (Blue)
O O O Operation (
OPlasmacluster (Blue)
O O O Operation (
O O Plasmacluster (Blue)
OOperation (
LampMain SubMainSub
Green
Plasmacluster (Blue)
Green
Green
Green
Green
Green
Green
Plasmacluster (Blue)
Green
Green
Plasmacluster (Blue)
Green
Green
Green
Green
Plasmacluster (Blue)
Heat exchanger
thermistor open
circuit error
thermistor open
circuit error
open circuit error
open circuit error
open circuit error
open circuit error
DC over current
error
AC over current error 1) Ensure unobstructed air
when OFF
error
Abnormal wire check
error
1) Check connector of
outdoor unit thermistor
for secure installa ion.
2) Measure resistance of
outdoor hermistors
3) Check the lead wires
of hermistors on the
outdoor unit control
PCB for open-circuit.
EEPROM data error (EEPROM read data error) Replace the indoor unit
Indoor unit room
temperature
thermistor
Indoor unit pipe
temperature
thermistor
Indoor unit valve
temperature
thermistor
motor for proper rotating operation.
(Check fan lock.)
2) Check the lead wire of
the indoor fan motor for
open-circuit.
3) Check connector ofthe
indoor unit fanmotor for
secureinstallation.
4) 1) 2) 3): Normal
(1)Check connector of
thermistor for
secure installation.
(2)Check the tempera-
ture properties of
the thermistor.
(1)Check connector of
thermistor for
secure installation.
(2)Check the tempera-
ture properties of
the thermistor.
(1)Check connector of
thermistor for
secure installation.
(2)Check the tempera-
ture properties of
the thermistor.
1) Replace the indoor
fan motor.
2) Replace the indoor
fan motor.
3) Correct the installation of the indoor
fan motor connector.
4) Replace the indoorunit control PCB.
control PWB.
(1)Replace the ther-
mistor.
(2)Replace the ther-
mistor.
(1)Replace the ther-
mistor.
(2)Replace the ther-
mistor.
(1)Replace the ther-
mistor.
(2)Replace the ther-
mistor.
*Remark
The malfunction No. is calculated using the following way.
Example)
Lamp CalculationMainSub
Indoor unit lamp
Timer (orange)O O O O O
Operation (Green)OO4+1=55
Plasmacluster (blue)O22
→
16 8 4 21
3 – 17
Page 34
AHXP13MY
CHAPTER 4. REFRIGERATION CYCLE
The content of this section is currently under revision.
Will be released after approval.
[1] SCHEMATIC DIAGRAM
AE-X15PU
Service Manual
Indoorunit
Flare couplingFlare coupling
3-way
valve
Outdoor unit
silencer
Compressor
(4)
Reverse valve
Evaporator
(1)
Condenser
s
(3)
2-way
valve
Strainer
Expansion
valve
Strainer
S
S
(2)
[2] STANDARD CONDITION
Temperature of each part and presure of 3-way valve are acquired in standard condition, and would change with condition
around. The standard condition is as follows:
[4] TEMPERATURE AT EACH PART AND PRESSURE IN 3-WAY VALVE
(AY-XPC15PU / AE-X15PU)
MODE
Hz
No.
Temp. on (1) ℉(℃)165.2 (74)194.5 (90.3)
Temp. on (2)
Temp. on (3)
Temp. on (4)
℉(℃)101.5 (38.6)40.3 (4.6)
℉(℃)49.6 (9.8)124.7 (51.5)
℉(℃)57.6 (14.2)39.7 (4.3)
3-way valve pressure (MPaG)
COOLING
MAX
62 OR MORE 80 OR MORE42 FIXED42 FIXED
0.9193.318
HEATING
MAX
COOLING
TEST RUN
HEATING
TEST RUN
147.6 (64.2)140.0 (60.0)
101.1 (38.4)39.2 (4.0)
55.2 (12.9)99.0 (37.2)
60.4 (15.8)
41.5 (5.3)
1.0412.265
CAUTION: Indoor fan speed is set to [HIGH].
4 – 1
Page 35
AE-X15PU
The content of this page is currently under revision.
Will be released after approval.
(AY-XPC18PU / AE-X18PU)
(AY-XPC18PU / AE-X18PU)
MODE
MODE
Hz
Hz
No.
No.
Temp.on①(℃)70.194.5
Temp. on (1) ℉(℃)
Temp.on②(℃)38.7 5.1
Temp. on (2) ℉(℃)
Temp.on③(℃)9.855.3
Temp. on (3) ℉(℃)
Temp.on④(℃)9.93.6
Temp. on (4) ℉(℃)
Temp.on⑤(℃)
3-way valve pressure (MPaG)
3-wayvalvepressure(MPaG)
CAUTION: Indoor fan speed is set to [HIGH].
(AY-XP24PU / AE-X24PU)
MODE
MODE
Hz
Hz
No.
No.
Temp.on①(℃)70.194.5
Temp. on (1) ℉(℃)
Temp.on②(℃)38.7 5.1
Temp. on (2) ℉(℃)
Temp.on③(℃)9.855.3
Temp. on (3) ℉(℃)
Temp.on④(℃)9.93.6
Temp. on (4) ℉(℃)
Temp.on⑤(℃)
3-way valve pressure (MPaG)
3-wayvalvepressure(MPaG)
CAUTION: Indoor fan speed is set to [HIGH].
COOLING
COOLING
MAX
MAX
65 ORMORE88 ORMORE42FIXED42FIXED
73
OR MORE 88 OR MORE42 FIXED42 FIXED
HEATING
HEATING
MAX
MAX
COOLINGTEST
COOLING
RUNMODE
TEST RUN
HEATINGTEST
HEATING
RUNMODE
TEST RUN
158.9 (70.5)198.0 (92.2)138.9 (59.4)13.4. (56.9)
101.1 (38.4)
49.6 (9.8)
50.9 (10.5)
42.4 (5.8)102.9 (39.4)38.3 (3.5)
94.6 (34.8)55.9 (13.3)
78.1 (25.6)
37.0 (2.8)58.2 (14.6)41.5 (5.3)
0.8763.4491.0562.116
COOLING
COOLING
MAX
MAX
65 ORMORE88 ORMORE42FIXED42FIXED
105 OR MORE 97 OR MORE42 FIXED42 FIXED
165.0 (73.9)
HEATING
HEATING
MAX
MAX
COOLINGTEST
COOLING
RUNMODE
TEST RUN
HEATINGTEST
HEATING
RUNMODE
TEST RUN
169.5 (76.4)137.5 (58.6)125.8 (52.1)
113.2 (45.1)45.5 (7.5)103.3 (39.6)41.0 (5.0)
50.4 (10.2)
41.4 (5.2)
0.770
107.4 (41.9)
35.2 (1.2)
2.8741.073
58.5 (14.7)94.6 (34.8)
60.6 (15.9)
39.0 (3.9)
2.170
“Hz” in the table above is converted by frequency, and has nothing to do with power supply frequency.
Note: For COOLING/HEATING max, please set the temperature to low/high limit (COOLING 61℉[16℃], HEATING 86℉[30℃]).
However, it is possible that the COOLING/HEATING max operation can not be obtained depending on the circumambient
condition.
4 – 2
Page 36
[5] FLOW CHART OF REFRIGERANT CYCLE
AE-X15PU
5-2 HEATING5-1 COOLING & DEFROSTING
[6] CHARACTERISTIC OF COOLING AND HEATING OPERATION
6-1 AY-XPC15PU / AE-X15PU
CAUTION: Indoor fan speed is set to [HIGH].
Airflow direction is initial.
Air inlet temperature of is 80℉ (26.7℃) during COOLING operation, and 70℉ (21.1℃) during HEATING operation.
1300
1200
1100
1000
900
POWER CONSUMPTION (W)
800
65758595105115
17.0
16.0
6-1-1 COOLING6-1-2 HEATING
OUTSIDE TEMPERATURE(℉)
1850
1700
1550
1400
1250
POWER CONSUMPTION (W)
1100
233139475563
OUTSIDE TEMPERATURE(℉)
26.0
22.0
15.0
14.0
13.0
COOLING CAPABILITY (kBTU)
12.0
65758595105115
OUTSIDE TEMPERATURE(℉)OUTSIDE TEMPERATURE(℉)
4 – 3
18.0
14.0
10.0
HEATING CAPABILITY (kBTU)
6.0
182838485868
Page 37
AE-X15PU
6-2 AY-XPC18PU / AE-X18PU
CAUTION: Indoor fan speed is set to [HIGH].
Airflow direction is initial.
Temperature of inlet is 80℉ (26.7℃) during COOLING operation, and 70℉ (21.1℃) during HEATING operation.
1600
1500
1400
1300
1200
POWER CONSUMPTION (W)
1100
65758595105115
20.0
19.0
18.0
17.0
16.0
COOLING CAPABILITY (kBTU)
15.0
65758595105115
6-2-1 COOLING
OUTSIDE TEMPERATURE(℉)
OUTSIDE TEMPERATURE(℉)
6-2-2 HEATING
2300
2120
1940
1760
1580
POWER CONSUMPTION (W)
1400
233139475563
OUTSIDE TEMPERATURE(℉)
30.0
26.0
22.0
18.0
14.0
HEATING CAPABILITY (kBTU)
10.0
233139475563
OUTSIDE TEMPERATURE(℉)
6-3 AY-XP24PU / AE-X24PU
CAUTION: Indoor fan speed is set to [HIGH].
Airflow direction is initial.
Temperature of inlet is 80℉ (26.7℃) during COOLING operation, and 70℉ (21.1℃) during HEATING operation.
6-3-1 COOLING
2800
2600
2400
2200
2000
POWER CONSUMPTION (W)
1800
65758595105115
OUTSIDE TEMPERATURE(℉)
28.0
26.0
24.0
22.0
20.0
COOLING CAPABILITY (kBTU)
18.0
65758595105115
OUTSIDE TEMPERATURE(℉)
2600
2400
2200
2000
1800
POWER CONSUMPTION (W)
1600
233139475563
35.0
30.0
25.0
20.0
15.0
HEATING CAPABILITY (kBTU)
10.0
233139475563
6-3-2 HEATING
OUTSIDE TEMPERATURE(℉)
OUTSIDE TEMPERATURE(℉)
4 – 4
Page 38
CHAPTER 5. DISASSEMBLING PROCEDURE
If, in carrying out repairs and modifications, the work requires the use of arc- and flame-producing apparatus, such as welding, brazing and soldering
equipment, this work shall only be started after the rooms have been thoroughly ventilated. While the work is being carried out, the mechanical ventilation, if any, shall be kept in constant operation and all windows and doors kept open. In the case of repairs to parts of the refrigerant circuit, it may
be necessary that not only the workman but also a second person shall be present for observation and assistance. Necessary protective equipment
shall be available and, in the case of open flames or arcs, fire extinguishing apparatus shall be ready to hand. Welding and brazing shall be carried
out by qualified workmen. Be sure to disconnect the power cord from the AC power outlet before starting the disassembly procedure. When reassem-
the unit after repairing, be sure to install screws to their original positions. The screws used are not the same in specifications such as corrosion-
b
ling
resistant treatment, tip shape and length. After the air conditioner is repaired or parts are replaced, measure insulation resistance of the equipment
using an insulation resistance meter. If the measured resistance is lower than 1 MΩ, inspect parts and repair or replace defective parts.
AE-X15PU
[1] OUTDOOR UNIT
Be sure to disconnect the power cord from the AC power outlet before starting the disassembly procedure. When reassembling the unit after repairing, be sure to install screws to their original positions.
The screws used are not the same in specifications such as corrosion-resistant treatment, tip shape and length.
After the air conditioner is repaired or parts are replaced, measure insulation resistance of the equipment using an insulation resistance meter. If the
measured resistance is lower than 1 MΩ, insp
1. MAIN UNIT
1) Unscrew the 2 screws fixing the control box cover and remove it.
ect parts and repair or replace defective parts.
3) Unscrew 3 screws fixing the cable holder and remove it.
Control box cover
2) Unscrew the 2 screws fixing the valve cover and remove it.
Valve cover
Cable cover
4) Loose the screws fixing the connecting cable and unscrew
the Nut, remove the Wire conduit
Nut
Wire
conduit
5 – 1
Page 39
AE-X15PU
5 – 2
5) Unscrew the 2 screws fixing the cable holdor and remove it
6) Unscrew the 6 screws fixing the top plate and remove it.
7) Unscrew the screw fixing the service panel, then slide the panel
downward and remove it.
8) Unscrew the 4 screws fixing the motor angle T and remove it.
Service panel
Motor angle T
9) Unscrew the 2 screws fixing the angle and remove it.
10) Unscrew the 4 screws fixing the front panel and remove it.
1
2
Angle
11)Disconnect the 4 connectors and the 2 terminals.
Terminal
Connector
12)Cut the fixing band.
Page 40
5 – 3
AE-X15PU
13).Unscrew the 3 screws fixing control unit and remove it.
Contol
unit
14)Remove the 2 compressor covers.
Compressor
cover
15)Unscrew the nut fixing the terminal cover and remove it.
Nut
Terminal
cover
16)Disconnect the 3 terminal connected with the compressor.
17)Unscrew the 2 screws fixing the bu khead and remove it.
18)Unscrew the 2 screws fixing the motor angle and remove it.
19)Unscrew the nut fixing the fan and remove it.
20)Unscrew the 4 screws fixing the motor and cut the fixing band, and
then remove the motor.
Nut
Fixing band
Bulkhead
Page 41
5 – 4
[2] DISASSEMBLY OF CONTROL UNIT
1. Control unit box’s Approach to decomposition
AE-X15PU
5) Unscrew the 4 screws fixing the Heatsink holder and remove it.
6) Remove 1 screw and the 2 metal covers.
7) Unscrew the 4 screws fixing the Heatsink and remove it from
Heatsink holder
Heat sink
holder
Metal cover
control
cover
1) Unscrew the 2 screws and remove the terminal board.
2) Unscrew the 2 screws fixing the terminal angle and remove it.
3) Remove the metal cover.
4) Unscrew the 8 screws fixing the control board unit and remove it
Page 42
PARTS GUIDE
SPLIT TYPE
ROOM AIR CONDITIONER
AE-X15PU
OUTDOOR UNIT
MODEL
[1]OUTDOOR UNIT PARTS
[2]
OUTDOOR UNIT STRUCTURE
AND CYCLE PARTS
AE-X15PU
AE-X18PU
AE-X24PU
In the interests of user-safety (Required by safety regulations in some countries) the set should
be restored to its original condi ion and only parts identical to those specified should be used.
CONTENTS
[3]OTHER OUTDOOR UNIT
ELECTRIC PARTS
[4]OUTDOOR PACKING PARTS
To have your order filled promptly and correctly, please furnish the
following information.
1. MODEL NUMBER 2. REF. No.
3. PART NO. 4. DESCRIPTION
★ MARK: SPARE PARTS-DELIVERY SECTION
Parts marked with "" are important for maintaining the safety of the set. Be sure to replace these
parts with specified ones for maintaining the safety and performance of the set.
“HOW TO ORDER REPLACEMENT PARTS”
This document has been published to be used
for after sales service only.
The contents are subject to change without notice.
Page 43
AE-X15PU
[1] OUTDOOR UNIT PARTS FOR AE-X15PU, AE-X18PU, AE-X24PU
2
Page 44
AE-X15PU
RANK
MARK
RANK
CMOTLB537JBEZNFAN MOTOR1
MOTOR ANGLE T1
MOTOR ANGLE1
FAN MOTOR ANGLE SUB2
FRONT PANEL L1
FAN GUARD1
FRONT PANEL R ASS'Y1
FRONT PANEL R1
HANDLE1
IIR SHEET A1
NPROPELLER FAN1
SIDE CABINET L1
IIR SHEET1
IIR SHEET B1
SIDE CABINET R SEAL1
SPRING2
THERMISTOR SPRING1
CABLE HOLDER1
CABLE COVER1
PCOV-B981JBFANSIDE COVER 21
PSEL-E389JBEZNSIDE COVER SEAL1
PCOV-C030JBFANVALVE COVER1
TOP PLATE ASS'Y1
TOP PLATE1
TOP PLATE SEAL A1
TOP PLATE SEAL B1
TOP PLATE SEAL C1
TOP PLATE SEAL E1
BULKHEAD ASS'Y1
BULKHEAD1
BULKHEAD SEAL1
BULKHEAD SEAL A1
BULKHEAD SEAL B1
BULKHEAD SEAL C1
ANGLE ASS'Y1
BASE PAN ASS'Y1
BASE PAN SUB ASS'Y1
BASE PAN SEAL C1
FLARE COUPLING BASE1
SPECIAL NUT1
THERMISTOR HOLDER1
MOTOR ANGLE T SEAL1
TLAB-F617JBRANENERGY LABEL1
TLAB-F696JBRZNCAUTION LABEL UL1
TLAB-F748JBRZNUL COPPER WIRE LABEL1
[2] OUTDOOR UNIT STRUCTURE AND CYCLE PARTS(AE-X15PU,AE-X18PU,AE-X24PU)