MOD L11: Replacement Procedure Linear ActCont ER 2-Way Gas with Linebreak
05-03-11
Linear Actuator Control – Electric Remote 2-Way with Linebreak Feature
Replacement Procedure on a Linear Actuator with a System using Power Gas
www.ShaferValve.com
MOD L11: Replacement Procedure
Linear ActCont ER 2-Way Gas with Linebreak
05-03-11
The purpose of this procedure is to guide the replacement of an Actuator Control with standard features.
This procedure is to be used in conjunction with the following Maintenance and Service Manuals.
Shafer Linear Actuator Installation and Service Manual Bulletin LSM-01102001
*Schematic Diagram 9608-S-SPECIAL
*Numbers in this document contained in [ ] will correspond to the Item Numbers on Schematic Drawing 9608-S and 9608-S-Special
NOTE: With pressure in the pipeline, installation should be done with the valve in the OPEN
position. With no pressure in the pipeline, installation should be done with the valve in the CLOSE position.
WARNING: 1. Turn power gas off (bleed down the power storage tank if applicable).

Remove the Old Control Box and Hand Pump

1. Remove the piping to the power port and exhaust port (if existing) of the old control block.
2. Remove the two tube lines (OPEN and CLOSE) running from the control block to the top of the gas hydraulic tanks.
3. Remove the tube line going from the power storage tank to the control block, if applicable.
4. This should complete the pipe/tube connections freeing the old control box. Remove the old control box and set the parts aside.
Page 1
MOD L11: Replacement Procedure
Linear ActCont ER 2-Way Gas with Linebreak
05-03-11

Figure 1: Install New Control

Install the New Control Box Assy.

The new control box mounts to the same holes in the bracket on the Actuator, as the old one, using 4" long standoffs. Look the new hardware over to enable identification of the parts.
1. Install the four standoffs to the mounting bracket. (See Figure 1)
2. Choose the mounting holes, in the Control, that will offer the best fit, probably the upper ones, and position the Control on the Standoffs. Fasten with nuts and lock washers. (See Figure 1 and Figure 3)
3. Assemble the dipsticks to the new Diffuser Assemblies. Apply an appropriate pipe sealant and install the Diffuser Assemblies in the top ports of the gas hydraulic tanks.
Page 2
MOD L11: Replacement Procedure
Linear ActCont ER 2-Way Gas with Linebreak
05-03-11

Figure 2: View of the New Control from the Back

4. Install new Swagelok® fittings in the back of the Control, top of the Tanks, Power Storage Tank and ESD valve. Apply Teflon® tape and an appropriate pipe sealant to the threads. (See Figures 2, 3 and 4)
5. Install 1/8 NPTF Nipple and 1/8” Shuttle Valve [31], with two 1/8 NPTF to ¼” tube fittings installed, in pilot port for the Control Close Pilot Piston [14]. (See Figure 2)
6. Run ¼” tube line from the 1/8” Shuttle Valve [31] to the cylinder port of the Close Solenoid Valve [32]. (See Figure
2)
7. Run ¼” tube line from the 1/8” Shuttle Valve to the cylinder port of the ESD Valve [19] mounted on the actuator. (See Figure 2 and Figure 4)

Figure 3: New Control Front View

Page 3
MOD L11: Replacement Procedure
Linear ActCont ER 2-Way Gas with Linebreak
05-03-11
8. Run ¼” tube line from the pilot port for the Control Open Pilot Piston [14] to the cylinder port of the Open Solenoid Valve [33]. (See Figure 2)
9. Run ¼” tube lines connecting power port on the back of the Control to power port of the ESD Valve [19] on the Actuator, the power port of the Close Solenoid Valve [32] and the power port of the Open Solenoid Valve [33]
10. Run ¼” tube line from the cylinder port of the Air Relay Valve [9], on the back of the Control, to the pilot port of the ESD Valve [19]. (See Figure 2)
11. Run ½” tube line from the Close port, on the back of the Control, to the top of the Close Tank [2]. (See Figure 2)
12. Run ½” tube line from the Open port, on the back of the Control, to the top of the Open Tank [1]. (See Figure 2)

Figure 4: ESD Valve Mounted on Actuator

13. Run ½” tube line from the power port, on the back of the Control, to the Power Storage Tank [27], if applicable. (See Figure 2)
14. Run a ¼” tube from the pilot port, on the back of the Control, to the connection on the Reference Tank [20]. (See Figure 2)
15. Re-plumb the customer pilot connection, power connection and re-plumb the exhaust, or install muffler, on the poppet block control valve.
Page 4
MOD L11: Replacement Procedure
MOD L11: Replacement Procedure
Linear ActCont ER 2-Way Gas with Linebreak
Linear ActCont ER 2-Way Gas with Linebreak
05-03-1
05-03-11
Page 5
Page 5
MOD L11: Replacement Procedure
Linear ActCont ER 2-Way Gas with Linebreak
05-03-11
If any further information is required, please feel free to contact:
EMERSON PROCESS MANAGEMENT VALVE AUTOMATION, INC.
2500 Park Avenue West
Mansfield, Ohio 44906
Phone: (419) 529-4311
Fax
(419) 529-3688
Please visit our website for up to date product data. www.shafervalve.com
All Rights Reserved
The contents of this publication are presented for informational purpose only, and while every effort has been made to ensure their accuracy, they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. We reserve the right to modify or improve the designs or specifications of such products at any time with out notice.