SGL SDR 63 Operating Instructions Manual

Page 1
OPERATING INSTRUCTIONS
PLASTIC CENTRIFUGAL ROOF MOUNTED FANS
SDR 63.3 SIZES 355 – 710
Page 2
Issued: PA S Operating manual No. 28.95.103 Valid from: Serial No. 29956
Date: 01.03.2001 Plastic Radial Roof Mounted Fans
SDR 63 Sizes 355-710
1. General notes
This operating manual is valid for all plastic centrifugal roof fans of series
SDR 63 Sizes 355 - 710
The instructions must be handed to the user, who has to inform the people responsible for operation, servicing and repair. No liability is accepted for damage resulting from non-observance of the instructions.
The fans supplied by SGL ACOTEC are designed with reference to the order on the basis of flow rate, total pressure differential, medium, operating temperature and installation site. The actual parameters are shown on the machine card or rating plate.
The product supplied must only be used for the application specified in the contract and within the scope of the conversion possibilities listed in this operating manual. Any other use is regarded as not in accordance with the intended purpose. SGL ACOTEC do not accept liability for any damage arising from such a use.
CONTENTS
1. General notes 2
2. Construction and operating principle 2- 3
3. Realization of the safety requirements 4
4. Transport/Storage 4
5. Installation 4
6. Drive 5
7. Installation of the motors 5
8. Commissioning 5
9. Inspection/Maintenance 6
2. Construction and operating principle
SGL ACOTEC Centrifugal Roof Mounted Fans of Series SDR 63 have been designed as vertically discharging, direct-drive feed appliances for corrosive gases and vapours. The medium handled is drawn in axially by the rotating impeller and by deflection downstream of the horizontal impeller outlet again passed axially around the enclosed motor and to the outlet branch.
SDR fans of sizes 355 - 710 are of welded construction and consist of the following sub-assemblies: enclosure, motor support, impeller, air intake and tubular liner. Motor support as well as the top and bottom section of the enclosure are welded together. For Sizes 355 and 400, 450 and 500 as well as 560 and 630, identical enclosures are used respectively. This makes it possible to convert the fans also after delivery and installation by changing the impeller and air intake to the other respective size.
The motor support is designed for the installation of six motor sizes (71 - 132) in the design B5. The motors are screened against the medium; cooling air supply is via ventilation hoses (fig. 1). The impellers used have eight backward curved blades and are balanced electrodyna­mically in two planes. Minimum balancing quality Q 6.3 to ISO 1940.
10. Servicing/Conversion 6
Appendix: Characteristics diagrams 8-11
2
Page 3
Issued: PA S Operating manual No. 28.95.103 Valid from: Serial No. 29956
Date: 01.03.2001 Plastic Radial Roof Mounted Fans
SDR 63 Sizes 355-710
Housing, motor support and impellers are made from thermoplastics. The permissible operating temperatures of the fans are with construction in
PVC 50°C
PP 70°C
and must not be exceeded.
Fig. 1 SGL ACOTEC Centrifugal Roof Fan SDR, flat roof installation
12
10 8
11
6
13
14
7
9
18
2 19 20
3
1
4
21 5
1 – Housing 2 – Motor support 3 – Impeller 4 – Air intake 5 – Liner 6 – Splinter guard 7 – Upper ventilation hose 8 – Lower ventilation hose
9 – Motor 10 – Motor lead 11 – Fan supply cable 12 – Terminal box 13 – Moisture-proof union 14 – Roof mount 15 – Roof covering 16 – Roof penetration 17 – Roof liner 18 – Hitching point 19 – Fixing screw, motor 20 – Fixing screw, motor flange 21 – Fixing screw, fan
16
1715
3
Page 4
Issued: PA S Operating manual No. 28.95.103 Valid from: Serial No. 29956
Date: 01.03.2001 Plastic Radial Roof Mounted Fans
SDR 63 Sizes 355-710
3. Realization of the safety requirements
SGL ACOTEC Centrifugal Roof Mounted Fans Type SDR are manufactured to the latest technological standards and conform to the legal requirements in design, construction and safety measures. If used in accordance with their purpose and in compliance with this operating manual, they are safe and reliable.
• All rotating parts are covered so that they cannot be touched (motor enclosed, impeller screened by a housing).
• On open-inlet fans the air intake is covered by a protec­tive grille.
• The enclosures are radially surrounded by a splinter guard, which if the impeller and/or housing are damaged, prevents flying fragments.
• The enclosures and plastic impellers are welded in accordance with the valid regulations. Welding additives for thermoplastics conform to DVS 22.11.
• All impellers are statically and dynamically balanced in two planes. Balancing quality min. Q 6.3 to ISO 1940.
The user of centrifugal roof fans supplied by SGL ACOTEC has the following obligations:
• The fans must only be operated, serviced, converted and repaired by authorized persons. These must be instructed by the user in accordance with the operating instructions about the correct procedure during the above work and about possible angers.
• The user is obliged to operate the supplied product only in sound condition.
• Unauthorised modifications which affect the function and/ or safety of the fan are not permitted.
• All servicing, inspection, conversion and maintenance operations must only be carried out with the fan at rest and the power supply shut off.
• The removal of information-, instruction- and prohibition plates from the product is not permissible. In all cases, the fan must also be operated in accordance with all local safety and accident prevention regulations.
4. Transport and storage
• The fans must be transported carefully and safely to prevent damage through excessive force. Any impact-, traction- or pressure stress on the plastic housings must be avoided.
• When transported by truck, rail or ship, the fans must be loaded and secured so that slipping, tilting or friction are avoided.
• The fans must be lifted and carried by means of fork-lift truck or crane. When transported by crane, the fans must be attached at the four plastic hitching eyes (fig. 2) provided for that purpose. To prevent damage of the eyes, shackles or fabric attachments must be used. The storage of the fans does not require any special arrangements. They should be stored in rooms or on roofed-over areas. The discharge opening must be covered to prevent objects from dropping into it. The fans must not be stacked.
Fig. 2 SDR crane handling
5. Positioning
The SDR fans are placed on flat or sloping roofs by installation on roof mounts, which are fixed onto the roof covering and sealed with the roof liner (fig. 1).
• The intake-side duct must be connected to the liner passing through the roof penetration and must only be made with flexible connectors (bellows-type expansion joints).
• Drive motor and terminal box at the top section of the
4
Page 5
Issued: PA S Operating manual No. 28.95.103 Valid from: Serial No. 29956
Date: 01.03.2001 Plastic Radial Roof Mounted Fans
SDR 63 Sizes 355-710
housing are ready wired before the fans are dispatched.
• The supply to the fan terminal box must be laid be­tween liner and roof mount and sealed at the wall penetration by means of a heavy-gauge moisture-proof union.
6. Drive
• As standard, the centrifugal roof fans are driven by three­phase a.c. motors to IEC recommendation, type of enclosure IP54 or EExe, design B5.
If required, motors for other voltages and frequencies, pole-reversing or also variable-speed motors are used.
• The centrifugal roof fans are in principle supplied with the drive motor fitted. The test run after final installation confirms the performance and operational safety of the fan.
• If the motor is installed by the customer, the manu­facturer’s product liability does not apply.
7. Installation of the motors
• When installing the electrical wiring for the motors and any necessary switchgear, the VDE (German electrical engineers’ association) regulations and the motor manufacturer’s instructions must be observed.
• The installation is made according to the wiring diagram contained in the terminal box and must only be carried out by appropriately qualified technical personnel. Check voltage, rpm and direction of rotation. Direction of rotation of the motor must conform to the rotation symbol on the fan enclosure.
• When using pole-reversing motors, a further change from high to low speed must be provided. The delayed switching must be bumpless.
• A motor protection facility must be provided on principle. If the fans are installed in positions where the temperature of the cooling air exceeds 40oC, a performance reduction of the motors must be taken into account. Values are shown in the catalogues of the motor manufacturers.
8. Commissioning
Commissioning and operation of the fans must only be carried out by appropriately trained persons who are familiar with the applicable operating and safety regulations. After installation of the fan and connection of the suction-side duct system as in Item 5, the following must be checked or carried out:
• All visible screw connections must be checked for tightness.
• Protective devices must be checked for proper attach­ment (casing splinter protection, with open-inlet fans intake protection grille).
• Check motor venting hoses and the condensate drain bore in the housing base for clear passage.
• Foreign bodies (forgotten tools or installation material etc.) must be removed from the internal spaces of the fan and from the upstream ducts and assemblies.
• All possibly existing regulating elements (gate valves, butterfly valves) must be sufficiently closed before starting so that only approx. 10% of the cross-section remains open.
When starting the fan, proceed as follows:
• Expel unauthorized personnel from the fan area!
• Switch on the main switch and the motor switch (note permissible motor starting frequency).
• After nominal speed has been reached, open any control elements until the required working point establishes itself.
After starting, pay special attention to:
• Power input of the motor
• Quiet running of the fan.
After 12 hours of operation, check all visible screw connections for firm seating and retighten if necessary.
5
Page 6
Issued: PA S Operating manual No. 28.95.103 Valid from: Serial No. 29956
Date: 01.03.2001 Plastic Radial Roof Mounted Fans
SDR 63 Sizes 355-710
9. Inspection / Maintenance
The reliability and service life of the fans depend also on correct inspection and maintenance. Fans in continuous and trouble-free operation must be checked every three months as follows:
• Visual check for cracks and/or fractures in the fan enclo­sure caused by vibration.
• Visual inspection of the impeller for wear and/or caked­ondeposits caused by abrasive media.
• Inspection of the duct connections for tightness.
The inspection of the ventilation orifices and the condensate drain bore as in Item 8, para. 3, should be carried out at fairly short intervals to be determined by the user.
SGL ACOTEC Centrifugal Roof Mounted Fans are maintenance-free, the bearings of the motors are generally permanently lubricated for their nominal service life.
10. Servicing / Conversion
Fans are machines which should be provided with preventive and condition-oriented servicing to avoid breakdowns and lengthy downtimes as far as possible.
The servicing operations must be carried out with reference to the safety instructions as in Item 3 and the applicable operational protection at work instructions, and must only be carried out by authorized and qualified persons who are familiar with this operating manual.
Below, only work is described which must be carried out within the scope of the replacement of original parts (e.g. impeller) or when converting the fan.
Important!
Before starting work, stop the fan, switch off the main switch and secure against unintentional or unauthorized switching on again!
10.1 Removal / installation of the impeller
Removal becomes necessary in case of wear, fracture or imbalance of the impeller as well as during the conversion of a fan size to another one (e.g. SDR 63-355 to SDR 630­400 or vice versa). Specified component numbering acc. to fig. 1.
• Disconnect the supply (11) at the terminal box (12)
• Remove the nuts of the six fixing screws (21) and lift off the fan. Air intake and liner (4, 5) remain in the assembled condition on the roof mount (14).
• Turn the fan and place with the discharge opening downwards.
• After removing the plug and unscrewing the fixing screw, the impeller (3) can extracted from the motor shaft.
• Assembly is in the reverse order.
10.2 Changing impeller and liner
This becomes necessary when converting the fan to a different size, e.g. SDR 63-355 to 400, SDR 63-450 to 500 or vice versa.
• Removal of the impeller as in Item 10.1
• Remove the suction-side duct connection from the liner (5) and remove the air intake with liner (4, 5) from the roof mount (14).
• Assemble the replaced components in reverse order.
6
Page 7
Issued: PA S Operating manual No. 28.95.103 Valid from: Serial No. 29956
Date: 01.03.2001 Plastic Radial Roof Mounted Fans
SDR 63 Sizes 355-710
10.3 Changing the motor
• Remove the impeller as in Item 10.1.
• Disconnect the motor lead (10) at the terminal box (12).
• Remove the six fixing screws (2) and lift the motor (9) out of the motor support (2). After removing the four motor fixing screws (19), the motor (9) can be lifted off the support flange.
• Installation in the reverse order. When positioning the motor (9) in the motor support (2), the motor lead (10) must be passed through the lower fan hose (8).
• All unused motor fixing bores in the support flange must be sealed with PE plugs (GPN 300 V7, V10, V041).
Note!
For conversion of the fans only original components must be used. The selection of the drive motors must be made according to the respective characteristic diagrams. Consultation with the fan manufacturer is recommended prior to each conversion.
11. Wear parts
On SGL ACOTEC Centrifugal Roof Mounted Fans, the impellers are wear parts. Impellers of sizes 355 - 710 are made to order and are therefore not kept in stock. Sufficient delivery periods must be allowed for by the customer for ordering replacements.
7
Page 8
8
Total pressure differential
Noise level [dB]
pt [Pa]
SDR 63 – 355
Characteristics
Total pressure differential
Noise level [dB]
pt [Pa]
Fan speed [rpm]
Motor output [kW]
Circumferential velocity [m/s]
SDR 63 – 400
Characteristics
Fan speed [rpm]
Motor output [kW]
Circumferential velocity [m/s]
Page 9
9
Total pressure differential
Noise level [dB]
pt [Pa]
SDR 63 – 450
Characteristics
Total pressure differential
Noise level [dB]
pt [Pa]
Fan speed [rpm]
Motor output [kW]
Circumferential velocity [m/s]
SDR 63 – 500
Characteristics
Fan speed [rpm]
Motor output [kW]
Circumferential velocity [m/s]
Page 10
10
Total pressure differential
Noise level [dB]
pt [Pa]
SDR 63 – 560
Characteristics
Total pressure differential
Noise level [dB]
Fan speed [rpm]
Motor output [kW]
Circumferential velocity [m/s]
pt [Pa]
SDR 63 – 630
Characteristics
Fan speed [rpm]
Motor output [kW]
Circumferential velocity [m/s]
Page 11
11
Total pressure differential
Noise level [dB]
pt [Pa]
SDR 63 – 710
Characteristics
Fan speed [rpm]
Motor output [kW]
Circumferential velocity [m/s]
Page 12
© SGL ACOTEC GmbH, Siershahn (Germany), 2000 ® registered trademarks of SGL CARBON GROUP
companies
This information is based on our present state of knowledge and is intended to provide general notes on our products and their uses. It should therefore not be construed as guaranteeing specific properties of the products described or their suitability for a particular application. Any, existing industrial property rights must be observed. The quality of our products is guaranteed under our “General Conditions of Sale”.
Corrosion Protection Business Unit
SGL ACOTEC GmbH
Berggarten 1 D-56427 Siershahn Phone +49 (26 23) 6 00-0 Fax +49 (26 23) 6 00-7 91 [email protected] www.sglcarbon.com
Loading...