Setra Systems SRCM Operation Manuals

Model SRCM
Operation
1
Contents
OPERATION ......................................................................................................................................................................... 4
Condition Banner ................................................................................................................................................... 6
Condition Banner – Touch Screen ...................................................................................................................... 7
Operation ................................................................................................................................................................. 7
Alarms Cause Condition Banner to Turn Red .................................................................................................... 7
Condition Banner Functions ................................................................................................................................. 7
Operating Condition Screen ................................................................................................................................. 8
Pressure Value .........................................................................................................................................................9
Slider Bar and Set Point Values ............................................................................................................................. 9
Slider Bar On/O .................................................................................................................................................... 9
Active and Standby Modes .................................................................................................................................. 10
Menu Screens.........................................................................................................................................................11
SETUP UNIT ...................................................................................................................................................................... 12
Room Parameters .................................................................................................................................................. 13
Analog Inputs ........................................................................................................................................................ 14
Changing Room Name ......................................................................................................................................... 15
SETUP DISPLAY ................................................................................................................................................................16
General Tab — Customizing the Condition Banner ........................................................................................ 16
Advanced Tab– ...................................................................................................................................................... 17
Customizing the Operation Condition Screen ................................................................................................. 17
Display Averaging (tenths of seconds) ............................................................................................................... 17
What Pressure To Display .................................................................................................................................... 17
Pressure Resolution .............................................................................................................................................. 18
Supervisor and Operator Passwords .................................................................................................................. 18
Condition Banner Tab- Customizing Blinking Screens .................................................................................. 19
Full Screen Condition .........................................................................................................................................20
Banner and Active Standby Mode Application ................................................................................................. 20
Set Time & Date Screen .......................................................................................................................................22
SETUP ALARM .................................................................................................................................................................. 22
Alarms Disabled when Door Open & Buzzer for Door .................................................................................24
Warning .................................................................................................................................................................. 24
Alarm Set Point ..................................................................................................................................................... 25
Alarm Matrix ......................................................................................................................................................... 25
CALIBRATION AND SELF TEST ..................................................................................................................................... 27
SYSTEM INFORMATION ................................................................................................................................................. 28
USB CONFIGURATION CLONING .................................................................................................................................29
UPDATING FIRMWARE ...................................................................................................................................................31
NETWORK SETUP ............................................................................................................................................................ 32
EVENT LOG ........................................................................................................................................................................34
FRENCH LANGUAGE SUPPORT ON DEFAULT SCREEN & DATA ENTRY SCREEN ............................................. 35
Default screen for English version. ..................................................................................................................... 35
Default screen for French version. ...................................................................................................................... 35
Data Entry Screen for French Version ............................................................................................................... 36
TROUBLESHOOTING ...................................................................................................................................................... 41
RETURNING PRODUCTS FOR REPAIR ........................................................................................................................ 42
WARRANTY AND LIMITATION OF LIABILITY ........................................................................................................... 42
2
3
Operation
The following pages describe how to operate the SRCM using the touch-screen interface. The screen has two basic functions. The primary mode of operation displays the Home screen, which shows the end-user pressure values, messages, text, and other data intended
for visual pressure verication in the facility. The second mode of operation is the Ad­ministrative Menu screen, which permits setup, conguration, and changes to how the SRCM operates. After changes have been performed on the Menu screen, functions are
saved and operation returns to the Home screen. Note: If there is no user interaction with the touch screen for more than 1 minute, the screen will automatically return to the Home Screen. Many administrative settings can be written over the BACnet MS/TP network.
Home Screen
NOTE: All settings of the SRCM can be password protected.
Menu Screen
4
Home Screen
The default screen now has 2 possible modes. If the user wants to display other room variables in addition to Pressure they can switch to the alternate home screen that shows up to 4 parameters per room. These Parameters can be Pressure, Temperature, Humidity,
and user-dened (ex: CO2). The User switches modes by selecting slider on/slider off on
the bottom of the administrative menu.
The Home screen is the normal continuous operating mode of the SRCM. The Home screen shows a Condition Banner on the left one-third of the screen, and Operating Con­ditions on the right two-thirds of the screen. There are two possible home screens, one
with a pressure only display with a slider bar representing the room pressure with respect to the alarm setpoints. The alternate home screen can be used when there are multiple parameters being measured in addition to pressure, such as temperature, humidity and a
user-dened option.
Condition Banner
Pressure Value
Condition Banner
Pressure Temperature Humidity
User-dened
Home Screen
Room Label
Slider Bar and Setpoint Values
Alternate Home Screen displaying multiple
parameters, in addition to pressure.
Pressure Mode
• Positive
• Negative
• Neutral (span)
• Standby
Operation
• Normal (green)
• Warning (yellow)
• Door (yellow)
• Alarm (red)
Room Label
Pressure Mode
• Positive
• Negative
• Neutral (span)
• Standby
Operation
• Normal (green)
• Warning (yellow)
• Door (yellow)
• Alarm (red)
5
Condition Banner
The Condition Banner is the left 1/3rd portion of the screen that can be congured by the end-user or facility manager to display a message to staff on the oor. The
Condition Banner can be Green, Yellow, Red or Blue, depending on the message desired outside the pressurized space. The Condition Banner is set up in the Setup
Display-Condition Banner tab of the Administrative menu. There is also the op-
tion to display the Condition Banner in full screen.
The Condition Banner will change to red in alarm state regardless of the current
conguration. The banner may be changed manually, as required, by pressing the
touch-screen anywhere within the banner color region.
User dened text
ENTRY PERMITTED
graphic (arrow is not intended to indicate direction of airow)
User dened text
User dened text
STOP graphic
User dened text
User dened text
Warning graphic
User dened text
Green Condition Banner—shows the Entry Permitted graphic, and user de-
ned text above and below the graphic
image. Use the GREEN banner to indi­cate room is safe to enter.
Red Condition Banner—shows
the Stop graphic, and user dened
text above and below graphic im­age. Use the RED banner to indicate room is under critical use and entry is restricted.
Yellow Condition Banner—shows the
Warning graphic, and user dened text
above and below graphic image. Use
the YELLOW banner to indicate room
is under transient use and entry is re­stricted.
User dened text
ENTRY PERMITTED
graphic (arrow is not intended to indicate direction of airow)
User dened text
6
BLUE Condition Banner—shows the Entry Permitted graphic, and
user dened text above and below
graphic image. Use the BLUE ban­ner to indicate room is safe to enter.
Condition Banner –
Touch Screen
Operation
Once the messages of each of the four Condition Banners are dened in the Menu
section, the user can cycle through all four conditions by simply touching anywhere on the left one-third of the screen. If passwords are enabled, the user will be prompted to enter their password before proceeding. Each of the four colored screens can have
a unique message dened. See Section: Setup Display, page 11, for instructions on
how to setup the Condition Banner.
Alarms Cause
Condition Banner to
Turn Red
When the alarm occurs the Condition Banner will behave as follows:
1. Condition Banner will turn Red and Blink, irrespective of the color mode selected
by the user. User congured color mode: “Alarm Blink” & “Blink in Red” in the Setup Display screen will remain same. The operation eld which displays the alarm state of the system will also blink. When the system returns to normal user congured
settings will be retained.
2. The Message text on the bottom of the Condition Banner and User dened text on top of the Condition Banner will be displayed as “ALARM” temporarily.
The Condition Banner can be congured so that any of the Condition Banner colors
can be set to blink when that condition occurs. For example if an alarm occurs, Red color can be made to blink. Similarly, the yellow warning, green, and blue modes can also be set to blink.
Condition Banner
Functions
The Condition Banner conguration on the Display screen will have 3 options: Ac­tive, Standby, and No Action for all four colors (Red, Yellow, Green, and Blue).
• When Active is selected, the Occupancy Status object of the SRCM will be active.
• When STANDBY is selected, then the unit shall be put into STANDBY mode (No
alarms will be generated) when the corresponding color condition is selected
• The No Action mode will do nothing other than to display the Condition Banner screen that has been associated with the No Action mode.
7
Operating
Condition Screen
The Operating Condition screen shows the user the active operating conditions of the
pressurized space.
Room Label
Pressure Mode
• Positive
• Negative
Pressure Value
• Neutral (span)
• Standby
Slider Bar and
Alarm Setpoint
Values
The Room Label at the top of the screen can be dened by the user to ensure the
Operation
• Normal (green)
• Warning (yellow)
• Door (yellow)
• Alarm (red)
viewer understands which room is being monitored by the SRCM. See Changing
Room Name page 10, to enter text for your specic room.
The PRESSURE indication shows the intended direction of airow for the space. POSITIVE for airow out of the space, NEGATIVE for airow into the space, NEUTRAL for airow conditions that may vary, and STANDBY for use when there
is no need to verify the direction of airow (alarms are disabled).
The OPERATION indication shows whether the pressurized space is within normal operating parameters (within alarm thresholds), or whether there is an alarm or warn­ing condition. If operation is within alarm thresholds, a green NORMAL indica­tion is shown. If operation is near either high or low alarm threshold limits, a yellow WARNING indication is shown.
If operation is at or beyond high or low threshold limits, a red ALARM indication is shown. If Audible Alarming is Enabled, a piezo buzzer will sound and a SILENCE menu button will appear. Pressing the SILENCE button will shut off the alarm for
the period of time dened in the alarm conguration. Alarm operation can be cong­ured to blink or sound an audible signal. See Section, Alarm Setup, page 15, for more
about setting up ALARM and WARNING conditions.
In addition to the pressure indication, OPERATION also displays whether a door is open. If a door switch is congured, an open door contact will display a yellow DOOR indication.
8
Pressure Value
A black banner displays the actual pressure reading from the space, in either inches of Water Column (“ WC) or Pascals (Pa). The resolution of display can vary, de­pending on desired conguration; either 2, 3, or 4 signicant digits. The accuracy of
measurement remains the same regardless of the number of digits chosen.
Slider Bar and
Set Point Values
Pressure Value
Slider Bar and Setpoint Values
Slider Bar On/Off
The blue banner below the pressure value shows where the current pressure reading is in relation to alarm setpoints. The value at the left of the blue banner is the low set-
point, and the value on the right is the high setpoint. The middle “I-beam” represents
the current measured pressure value on the setpoint scale.
High alarm setpoint
“Cursor” representing where
the pressure value lies relative to the alarm setpoint
If the user does not wish to see the actual slider bar, it can be turned off using the Menu screen. Operation of the pressure sensing and alarming is unaffected. See set­ting up Menu screen, page 7.
Slider bar is turned off, this dis­plays when four parameters are
congured
Slider bar is turned off, this displays
when no parameters are congured -
Pressure still displays
9
Active and Standby
Modes
By pressing the touch-screen directly on the word POSITIVE (or NEGATIVE, NEUTRAL, or STANDBY), the user is able to change the condition of the room between ACTIVE and STANDBY modes. A pop-up menu appears to en­able selection. If passwords are enabled, the user must rst enter a password to
proceed with the change.
In ACTIVE mode, the full function of the SRCM is active. In STANDBY
mode, the SRCM will perform all functions except that alarming will be dis-
abled (both audible and visual alarms). The STANDBY mode is designed to
put the SRCM into a mode where room pressurization is not critical, such as cleaning, patient transfer, or longer-term unoccupied status. Note that this op-
eration can be password protected so that only an Operator or a Supervisor can make this change. Passwords are set up in Setup Display Advanced tab.
10
Menu Screens
Pressing the MENU button on the Home screen brings up the Administrative Menu. If passwords are enabled, the user is required to enter the correct password before being authorized to make changes. From the Administrative Menu, the user can set all op-
erating parameters of the SRCM. This includes initial setup, commissioning, calibra­tion, Network setup, customizing the displays, and warning and alarm parameters. The
menu structure is setup in such a way that the user can setup the unit by starting with the left column and working down, moving to the next column and working down until all setups have been made.
Setup Unit—for initial unit setup
Setup Display—customizes the display
Setup Alarm—setup the behavior of
how alarms are communicated to the user
Slider ON/OFF—denes whether the
pressure value and alarm setpoints are displayed on the home screen
* Calibration is only required for highly accurate measurement needs such as those
needed to comply with federally mandated regulations. See the SRCM Product Data Sheet for more information.
Upon initial installation, the Setup Unit screen should be used to dene installation parameters specic to the job site.
Calibration*—used to re-zero or calibrate internal sensor
Alarm setpoint values Save Settings and Exit
Room Label that settings
apply to (global unless
Secondary is shown)
Network Setup —congure
parameters to be read from the network
Event Log—Alarm/
Warning History
Serial number and other system information
11
Setup Unit
The SRCM can take as input, the signal from two separate pressure transducers as well
as temperature, humidity, and user dened (ex. CO2) inputs for up to two rooms. These are congured for either Primary Room or Secondary Room (an anteroom is an example
of a secondary room). When two transducers are used, the Home screen display of the SRCM can toggle between each space to indicate the status of each room momentarily
cycling from one to the other. Alternatively, the display can be locked on either of the
two rooms.
*If Ch1 is selected for the Primary room, it will not be an available option for the Sec­ondary room.
Setup selection to
congure either
Primary or Secondary Room
Room label of selected room, either Primary or Secondary
depending on ROOM radio button
Primary Room sensor:
• OnBoard Sensor
• External Ch1
Secondary Room sensor:
• External Ch1*
• External Ch2
Primary room pressure signal
output (AO) scale and units:
• 4-20 mA
• 0-5 Vdc
• 0-10 Vdc
Room - Primary or Secondary
Primary Room Sensor
Secondary Room Sensor
Pressure units, either “ WC or Pa
Full Scale (FS) range of transducer
selected, Primary or Secondary
Use the radio button to select the setup parameters for either the Primary Room or Sec­ondary Room.
It may be necessary to change settings to match the sensor being used. OnBoard is the default, which uses the sensor manufactured on-board the unit. Alternatively, an exter­nal sensor (also known as “external transducer” such as a Setra 264 or Setra 267) may be used. If an external sensor is used, change this selection to ADC Ch1 (Analog Input
1) or ADC Ch-2 (Analog Input 2). The FS output and range of the external sensor will need to be entered. If the OnBoard Sensor is selected, a box is shown displaying the
pressure range and engineering unit.
It may be necessary to change settings to match sensor being used, if there is one pres-
ent. There is no specic sensor listed at the default. An external sensor (Setra 264 or Setra 267) may be used for the secondary room, or anteroom. If an external sensor is used, change this selection to ADC Ch1 or ADC Ch2, which use Analog Input 1 or Analog Input 2, respectively. The FS output and range of the external sensor will need
to be entered.
12
Room Parameters
The SRCM can display up to four (4) parameters for each of 2 rooms. The pa­rameters can be Pressure, Temperature, Humidity, and the fourth user dened (Ex., CO2). Start with the Primary Room and set up the Parameters to be moni­tored and displayed on the default or home screen. As Parameters and inputs
are selected further selection of parameters and inputs will become self limiting
(Ex., If Temperature is selected in Parameter 2, it is not available for selection
in Parameter 3 or 4.)
Start with Parameter 1, this is the Room Pressure. Select the Input Source as
OnBoard, ADC-Ch1 or ADC-CH-2.
Parameter 2, Select None, Temperature, or Humidity. Temperature is suggest-
ed. Select Source as ADC-Ch1, ADC-Ch2, or BACnet.
Parameter 3, Select None, Temperature or Humidity. Humidity is suggested.
Select Source as ADC-Ch1, ADC-Ch2, or BACnet.
Parameter 4 Select None, User Dened.
Label
Primary Analog Output
Engineering Unit
Sensor Range
On the display, touch the label box and using the data entry keypad, input the
Room Label for the Primary Room. This will be displayed at the top of the de­fault screen to identify the room that the parameters refer to. Use the Primary/
Secondary Room radio buttons to select the secondary room (generally an
anteroom) and label that room as desired.
This Analog Output (AO) is used to communicate the value of the differential
pressure of the Primary Room to an external source such as a Building Man-
agement System (BMS). The value is scaled as either 4-20 mA, 0-5 VDC, or 0-10 VDC, selectable. A normalized pressure value is generated once every
100 milliseconds. The analog output is only available for the Primary room.
Units of measurement to show on the Home screen are selectable as either
inches of Water Column ("WC) or Pascals (Pa). The units are factory cali­brated as "WC, but if the unit is changed to Pa, the rang will be change to Pascals (Pa). This is selected from the Parameter 1 tab as it is associated with
the primary room pressure.
The SRCM is manufactured with an on-board differential pressure transducer.
This transducer is manufactured to specications for xed minimum and
maximum pressure measurement, known as the full-scale range of the trans­ducer. When the on-board transducer is used exclusively, these values cannot
change. Alarm setpoints cannot be set above the positive value or below the negative value. If a wider or narrower sensor range is required for the project, an external pressure transducer such as a Setra 264 or Setra 267 may be chosen to match the requirements. See more above under Primary Room or Secondary
Room.
If an external transducer is used, the full-scale values and other parameters
need to be congured into the SRCM so the unit understands the scale of mea­surement being received on the inputs Analog CH1 or Analog CH2.
13
Analog Inputs
The SRCM has 2 Analog Input Channels (ADC-CH1 and ADC-CH2)
Note: If a 4-20 mA transmitter is used as an analog input then a 250 ohm resistor must be eld installed and this will be translated into a 1-5 VDC input at the input
terminals.
This takes an analog input from any transducer or transmitter: pressure, temperature
or humidity. If an external transducer is used, the full scale values and parameters
need to be congured into the SRCM so the unit understands the scale of measure­ment being received on inputs ADC CH-1 or ADC CH-2.
The following is an example using a pressure transducer to measure secondary room
pressures. This is showing a pressure transducer with a range of ±1"WC and output of 4-20 mA over that range.
If selecting Analog Ch1 or Analog Ch2 for
either Primary of Secondary Room, enter full-scale (FS) range that matches the trans­ducer being used
Also enter voltage or milliampere range
that matches the transducer being used
The following is an example using a temperature sensor to measure primary room
temperature. This is showing a temperature range of ±50°C and output of 1-10 VDC
over that range.
Select desired units of measure to display on the Home screen, either “WC or Pa. The unit of measure for the exter­nal transducer must be selected before entering range and
output of the unit. After entering all data the units may be
changed and the range will scale accordingly.
14
The following is an example using a humidity sensor to measure primary room relative humidity. The range is 0-98 %RH with a 0-10 VDC output.
Changing Room Name
Touch anywhere within the Room Name entry box to bring up the on-screen keyboard and enter text.
The room name shown on the top part of the Home screen is changed using the Room Label button. The Room Name entry box appears in the middle of the Setup Unit display. Depending on whether the Primary or Secondary Room radio button is enabled, the matching Room Name entry box appears. The maximum number of characters is 18.
Press anywhere in the Room Name selection box to bring up the on-screen keyboard to enter the desired room label text. It is not necessary to touch the white area next to the Label, simply start entering data using the keyboard en­try. Be sure to press the Save button under the text entered before leaving this screen.
Data Entry screen with QWERTY keyboard
Use CAP-ON button to switch between
lower-case and upper-case lettering and other characters
Press Save after text entry is complete.
When nished with data entry, select Enter to conrm, or ESC to cancel and return to the
previous screen
15
Setup Display
The Setup Display screen permits authorized users (based on password level) to congure Condition Banner messages and other Home screen options. There are four tabs for display customization; General, Advanced, Condition Banner, Set
Time and Date.
General Tab —
Customizing the
Condition Banner
Change color and text of Condition Banner by pressing anywhere in the colored region
The General tab allows the user to dene messages for each Condition Banner
color. Pressing anywhere in the colored region of the Condition Banner changes
each selection between GREEN, YELLOW, RED, and BLUE. By pressing on
the colored region of text, the on-screen keyboard pops up, enabling data entry.
If User Dened Text is Disabled, then data entry on the Condition Banner will not be permitted. Change User Dened Text to enabled to change the text of
each banner.
Congure whether the user can
change the text of the Condition Banner. Enabled or Disabled
Congure if you want to enable
banner
When nished making changes, press Save & Exit to store the modications. Or press Exit to
discard changes and return to the previous screen.
Select Home screen language desired, English or French
In the Setup Display General tab you can congure the text to be displayed above and below the center symbol by enabling the User dened text. If you
want the banner to blink, Enable the Blink selection.
If any alarm occurs, the condition banner will turn to red and text above and
below the center symbol will display ALARM
16
Advanced Tab–
Customizing the Operation
Condition Screen
Primary Pressure Resolution
The number of signicant digits
displayed for the pressure value
(1-4)
The Advanced tab allows the user to make renements in how information is displayed on the Operating Condition section of the Home screen. The Display contrast level is adjusted using Adjust Contrast Level, with selec­tions from 1-4. After modifying this parameter, press Save & Exit to view
the brightness and contrast on the Home screen display. Depending on the
lighting and viewing conditions in the nal space, different contrast levels can
improve readability of the SRCM.
Contrast level of Home
screen. Adjust from 1-4 for
readability in varying lighting conditions
Display Averaging.
Select a value from 1-40
Dene Supervisor and Operator
passwords. Enable or Disable use of passwords
Display Averaging
(tenths of seconds)
What Pressure To Display:
• Primary Only
• Secondary Only
• Toggle
When nished making changes, press Save & Exit to store the modications. Or press Exit to discard changes and return
to the previous screen
This function is used to improve the stability of the pressure value displayed
on the Home screen, so signicant digits do not change rapidly. It is used more often in environments where the user requires higher display resolution (4 digits) but the ambient pressure is unstable. By increasing the number, the
effective number of measured data points is increased and a weighted aver­age is developed. Input the number in tenths of a second for the response time of the display to a pressure change. There is no ratcheting of the display or a deadband. The pressure change is very smooth. For example, entering 10
equates to the display reaching nal value in 1 second. Entering 2 equates to nal value in 2 seconds.
Display Averaging does not affect the Analog Output response time, only the apparent stability of the pressure display. Display Averaging also does not af­fect Alarm Thresholds or Alarm Delay.
What Pressure To
Display
This function denes what pressure value is shown on the Home screen under normal operating conditions. This can be Primary Only, Secondary Only, or Toggle, depending on what room is most important for visual pressure veri-
cation.
If this is set to Primary Only, then the Home screen will show the pressure value read by the primary pressure transducer (either on-board, or the alter­nate primary transducer congured from a separate transducer, if one is used).
If a secondary transducer is in use, and an alarm condition occurs in the sec­ondary room, the display will toggle and remain on the secondary room and pressure value as long as the alarm condition is present in that space.
17
If this is set to Secondary Only, then the Home screen will show the pres­sure value read by the secondary pressure transducer (anteroom for ex-
ample). In this case, if an alarm condition occurs in the primary room, the display will toggle and remain on the primary room and pressure value as long as the alarm condition is present in that space. If no Secondary Room
is congured on the Setup Unit screen, attempts to choose Secondary Only will result in the error “Secondary room source is NONE.”
If the function is set to Toggle, then the Home screen will show the pres­sure value for both rooms, alternating back and forth momentarily (approx­imately 10 seconds apart). If an alarm condition occurs in either room, the display will toggle to the appropriate room and pressure value and remain on that room as long as the alarm condition is present. If both rooms are in alarm, then the alarm condition and pressure values will toggle.
Pressure Resolution
Supervisor and Operator Passwords
This setting shows the number of digits after the decimal point for the default screen pressure displays. This setting affects the primary and secondary room settings.
The password function provides security against changed congurations by
unauthorized users. This is accomplished by using two levels of password protection. These can be enabled or disabled.
The Operator level allows access to change between Active and Standby
room modes, but no other changes.
18
The Operator is the person that has day-to-day interaction with the monitor to change operating modes from Active mode to Standby (where no alarms
are active). the operator can also respond to local audible and visual alarms. This could be a Nurse or a Lab Technician. The SRCM was designed to
make interaction with the unit as easy as possible for the Operator. Chang­es to messages and to the room mode requires simply touching active areas of the display. If Operator Password is enabled then a password will be
needed before the change can be made.
The Supervisor Level allows full access to all levels of the menu structure. This mode is used during initial conguration and follow-on recongura­tion.
NOTE: The master Supervisor password is 351, and will work for any condition where a user may need to reset passwords.
Condition Banner Tab-
Customizing Blinking
The Condition Banner can be used for control function as well as pure communi-
cation. There are three choices for each color: Active, Standby, and No Action.
Screens
Used for setting actions that is associated with each banner color
The Condition Banner tab allows the user to choose whether certain parts of the screen blink or not. Blinking components on the Home screen are intended to
draw more attention to the Condition Banner or the OPERATION indicators. This
is for the purpose of making exception conditions more noticeable to staff con­cerned with room pressurization status.
Alarm Blink
Warning Blink
Blink in Red/Green/Yellow/Blue
Full CB Display
Save & Exit
These apply to the right side of the Home Screen
Denes the behavior of the red ALARM
indicator on the Home screen. Normal
Blink is used for the green NORMAL
indicator.
Applies to the yellow WARNING, DOOR
indicator.
Applies to the Condition Banner messages
and icon on the left one-third of the Home screen.
If this is selected the left 1/3rd of the condition banner will become full screen
after 15 seconds. If an alarm is in progress
or occurs while the Condition Banner is full screen, the standard default screen will display. Touching the display will return it to the 1/3rd, 2/3 standard display mode. This is useful when users want a very simple interface. Touching the screen at any time will momentarily display the Home screen.
Saves the selections made on this screen.
19
Full Screen Condition
Banner and Active Standby
Mode Application
Customers may want a minimal user interface and want to switch be-
tween Active and Standby Modes and clearly convey the status of the
room.
Note: Any color can be associated with any action: Active, Standby, or No Action.
The following example uses GREEN for Active and YELLOW for
Standby.
1. On the setup Display/General tab set User dened Text to Enabled.
2. Tap the condition banner screen until the green screen is displayed. Setup the desired green screen text message to be displayed in the Ac­tive mode. Text can be entered so that it displays in the boxes above
and below the center "Clear to Enter" symbol. Touch the top box and
enter the desired text using the Data Entry keypad. Save by pressing the Enter button when complete. Perform the same steps for the bottom box.
3. Setup the desired yellow screen text message in the Setup Display/ General tab. Text can be entered so that it displays in the boxes above
and below the center "Warning Triangle" symbol. Touch the top box
and enter the desired text using the Data Entry keypad. Save by press­ing the Enter button when complete. Perform the same steps for the bottom box.
20
4. Setup the Condition Banner to display Full Screen rather than 1/3
left of screen display that is the default "as shipped" setup. To do this
go to the Setup Display/Condition Banner tab and set the full Condi­tion Banner Display to Enabled. Press Save and Exit.
5. With this setup the unit is in Active Mode. The Full Screen Display will look like the following with the text that was specied in step 2:
6. If the User changes to Standby by touching the section to the right of the PRESSURE, then the display will show up in yellow with the text that was specied
in step 3.
7. This feature can be combined with password protection
21
Set Time &
Date Screen
The Set Time & Date tab is used for setting the time and date of the SRCM. This time
and date is used to time stamp the event log. See Event Log Section.
Note: If power is lost to the unit, the time, and date need to be reset. If BACnet is used and is connected to the network, the time and date will automatically be retrieved.
The date format is DD-MM-YYYY.
Setup Alarm
The Setup Alarm screen permits authorized users (based on password level) to con­gure alarm behavior, such as the duration of alarms, methods of clearing the alarm
condition, and how alarms are acknowledged. It also sets the room mode to positive, negative or neutral room.
Latch Alarm
Alarm Delay
If enabled, causes the display of red ALARM on the Home screen to remain, even if room pressurization returns to NORMAL. Latch Alarm enabled requires that an alarm event be acknowledged and that
the pressure returns to within the normal range. This is useful because it forces recognition that an alarm event occurred. The alarm will still
be on even if the pressure returns to normal range. Only when the
alarm is acknowledged will alarming cease. When disabled, the alarm will be silenced when the pressure returns to normal range without
requiring acknowledgement. When a Latch Alarm occurs, the Home screen displays a RESET
button to the right of the Menu button. Press the RESET button to
acknowledge and reset the Latch Alarm condition.
Time between when the pressure went outside alarm setpoints and when the unit goes into alarm mode. This is useful in preventing false
alarms. For example, if Alarm Delay is set to 20 seconds, the staff has
20 seconds to open a door, enter the room and close the door before
the alarm sounds (if audible alarms are enabled). Alarm Delay also
applies to alarms annunciated to a remote annunciator via the SRCM
Digital Output (hardware conguration).
Dene which room the Setup Alarm
conditions will apply to
For each room (Primary or Sec­ondary), dene whether the room
pressure will be Positive, Neutral, or Negative
22
Audible Alarm
Mute Time Out
Digital Input (DI)
Deadband
Buzzer Volume
Enables or disables the audible buzzer. Regardless of whether audible
alarming is enabled or disabled, the red ALARM condition will show on the Home screen, annunciate to an SRAN, and propagate to a congured Digital Output. If an alarm occurs and the audible alarm is
enabled, a new SILENCE button will appear on the Home screen so that the operator can silence the audible alarm. The audible alarm is
silenced only for the period of time dened by Mute Time Out.
Sets the time (in seconds) that the alarm will remain silent after press-
ing the SILENCE button before the audible alarm resumes again. This assumes that the room pressure condition is still outside the
normal setpoint operating limits. Mute Time Out can be set from 0 to
9998 seconds. Entering a value of 9999 will silence the audible alarm
“forever,” as long as a new alarm condition does not occur.
Used for monitoring the door status, open or closed. The DI is a Nor-
mally-Closed dry contact. A door jamb or valve pressure switch must
be wired to the terminals labeled DOOR in the rear of the unit. When
the door opens the contact will open, and this will show a yellow
DOOR Warning on the Home screen. The Door Alarm will suppress
alarms if they are generated at the same time that the door is open.
is adjustable from 0 to 10% and represents the region within the
setpoint range where yellow WARNING is displayed on the Home
screen to indicate that the pressure is near ALARM limits. If set to
0, no WARNING will occur, only ALARM when the pressure value
reaches setpoints. If set to any other value, WARNING will be dis-
played if the pressure value reaches that percentage of total pressure
setpoint range.
When the unit goes outside of the deadband range the alarm will oc-
cur. The alarm will remain until the pressure returns within the alarm
limit range (or acknowledged Latch alarm) minus the setpoint.
The buzzer volume can be adjusted from one to four, with four being
the highest sound level. The alarm buzzer is disabled using audible
Audible Alarm disable function.
23
Alarms Disabled when Door Open & Buzzer for Door Warning
The SRCM is able to congure the Room status to disable the Alarms when Door is open. This function is used when there will be high trafc through
the area and the user wants to disable any alarms that are occurring as the result of the door being open. The alarms will be re-enabled once the Door is closed.
In the Alarm Setup screen, select the digital input choice to Door Alarm.
As shown in the screen below, the DOOR indication (to the right of Operation) will be highlighted to indicate that the door is open but that STANDBY (to the right of PRESSURE) will indicate that the room is in STANDBY mode.
24
If the door opens when the unit is in alarm, unit will continue to operate in alarm state instead of clearing the alarm.
Alarm Set Point
For each space, Primary Room or Secondary Room, this screen is used to dene the alarm
setpoints. When the room is then set to Positive, Neutral, or Negative, the setpoints and con-
ditions congured here are in effect for alarm and warning conditions.
Alarm Matrix
The SRCM has a great deal of exibility to dene alarm conditions. Alarms and warnings can be congured for primary and secondary rooms, and for the door. Room display can
toggle between Primary and Secondary. The following table outlines what will occur in terms of priority and display under normal and alarm conditions.
N=Normal; A=Alarm
Toggle High Priority Display
Primary
Pressure
Secondary
Pressure
Text (Maxi-
mum eight
Background Remarks
characters)
Disabled N N Normal Green Displays primary pressure
or secondary pressure based on the selection in the setup
display screen.
Disabled N A Alarm Red Shows Alarm for second-
ary room if secondary room is selected for the display. If the pressure to display is selected as Primary, display switches to the secondary room to show the alarm.
Disabled A N Alarm Red Shows Alarm for primary
room if primary room is selected for display. If the pressure to display is se­lected as secondary, display switches to the primary room to show the alarm.
25
Toggle High Priority Display
Primary Pressure
Secondary
Pressure
Text (Maxi-
mum eight
Background Remarks
characters)
Disabled A N Alarm Red Shows Alarm for second-
ary room if secondary room is selected for display. If the pressure to display is selected as Primary, display switches to the secondary room to show the alarm.
Disabled A A Alarm Red Display toggles between pri-
mary and secondary room.
Disabled A A Alarm Red Display toggles between pri-
mary and secondary room.
Enabled N N Normal Green Toggle between primary and
secondary room.
Enabled N A Alarm Red Shows secondary alarm.
Display stops toggling.
Enabled N A Alarm Red Shows secondary alarm.
Display stops toggling.
Enabled A N Alarm Red Shows primary alarm. Dis-
play stops toggling.
Enabled A N Alarm Red Shows primary alarm. Dis-
play stops toggling.
Enabled A A Alarm Red Display toggles between pri-
mary and secondary room.
Enabled A A Alarm Red Display toggles between pri-
mary and secondary room.
26
Calibration and Self-Test
This page is used for calibration of the internal pressure transducer sensor
and testing operation of hardware circuitry. Calibration is only required for
highly accurate measurement needs such as those needed to comply with federally mandated regulations. Calibration should only be performed by
qualied personnel.
1. Select Primary or Secondary room. When selected, the gray box to the right will indicate if the calibration will be applied to the on-board sensor or
the external sensor (Analog Ch1 or Analog Ch2). The indicated pressure is
shown.
2. Calibration of the on-board sensor requires that the faceplate be removed and the captive screw holding the display cover must be loosened (at the
bottom-center of the display bracket).
3. Lift the cover to expose the clear and red tubing connecting the on-board
sensor to the pressure ttings in the rear of the unit.
4. Remove the tubing from the high and low ports (red and clear tubing).
This disconnects the sensor from the room pressure.
5. After calibration, replace the red and clear tubing.
27
Zero Adjust
Span Adjust
Restore Factory User Zero and User Span
Test
Pressing Zero Adjust button will bring up a “Is zero pressure applied?” message. If yes, press OK. If the zero measure-
ment is within 10% of the factory zero measurement stored in the unit, the zero value will be reset. Note: Zero Adjust
should only be performed after the unit has been operating for 30 minutes in the installed location.
This requires the use of a Pressure Calibrator, such as a Setra Model 869 or equivalent. Connect tubing from the Cali­brator to the low and high ports identied near the PCBA markings. Apply Full Range pressure, for example ± 0.1” WC range, use 0.1” WC. When pressure reaches Full Range pressure, press OK button. The output at Full Range must be within 10% of the factory calibration to allow re-adjustment.
If the unit has been miscalibrated in the eld, the factory
zero and span settings can be restored.
The Buzzer, Relay and Internal Memory checksum can be
tested and veried.
System Information
The System Information screen reports Model Number, Serial Number,
Firmware Revision, Network Status, Last (Factory) Calibration Date and
Technical Support Contact.
Technical Support Any string 30 characters or shorter
can be entered in this eld by press­ing anywhere in the white text entry box to enable the pop-up keyboard. Enter an email address, name, or phone number as needed.
Restore Factory Default
Restores the default settings for all con-
guration and setup screens. All congured
settings, including alarm thresholds and
audible alarming, that were modied after
installation will be lost if this function is used. Primary and Secondary Room Labels will show “???.” Normal operation of pres­sure measurement will not be affected.
28
USB
Conguration
Cloning
The SRCM has a USB port built in for the purpose of duplicating congurations when multiple units are being setup with similar congurations. To use this func­tion, a USB 2.0 thumb drive with 256 megabytes or larger must be used. The thumb drive must have at least 100K or free memory available. The USB port should only be accessed by qualied personnel.
Setra recommends the Kingston DataTraveler 112, 4GB (minimum) ash drive
along with the aid of a short mini-USB adapter cable from Tensility International
Corporation, P/N 10-00003. No PC is required.
Manufacturer Model Size (GB) Comment
Kingston DataTraveler 1 No issue
256 MB No issue
DataTraveler 4 To make Kingston work,
DataTraveler 8
DataTraveler 112
Sandisk Cruzer 2 To make Sandisk work,
4 Passes out of the box with-
4
16
format as:
• Fat 32
• Must have volume label
• Do not use quick format
out formatting
format as:
• Fat 32
• Must have volume label
• Do not use quick format
To access the USB port, rst remove the faceplate cover and set it aside. The USB
port is located on the right side of the touch-screen display driver board, and is ac-
cessed by removing the security screw and ipping up the display housing. A mini­A MICRO USB Host Mode OTG cable (from T& S Electronics, P/N: OTG-SBK6 or from SonoXY, P/N: USB_MIC-OTG) is required to connect a standard USB 2.0
compliant thumb-drive to the SRCM USB port.
To make use of the cloning feature, rst setup one SRCM with a conguration that represents most other SRCM units that will be used during installation. Congure the “master” unit with all parameters needed, including alarm thresholds, condition banners, blinking operations, I/O conguration and so on. Make sure the Save & Exit function is used to properly save your conguration. This “master” setup will
then be downloaded to the thumb drive and for use uploading to other units.
As soon as the thumb drive is connected to the SRCM it will be recognized and
bring up a Drive Connected menu.
29
USB Conguration
Cloning
USB Port
• Select Conguration Write to transfer the master SRCM conguration from the
unit to the thumb drive.
• Select START to initiate the copy operation.
Remove the thumb drive and cable and move to the rst “slave” unit to be cong-
ured. With power applied to that unit, connect the thumb drive and cable. Select
Conguration Read and START to write the master conguration to the new slave
unit.
A Write Process Successful message will appear if the conguration has been
written to memory. Review the various Menu screens of the slave unit and sub-
sequent units to conrm the proper conguration is stored. In most cases the only change that will be required to clone SRCM units is Primary and Secondary Room
labels that match the location of installation.
30
Updating Firmware
Note: Before updating rmware, perform USB Conguration Cloning. Refer to USB Conguration Cloning on previous page.
The USB port can be used for upgrading the SRCM rmware in the eld.
To upgrade the rmware you must rst download the rmware for the lat­est versions of the hex le for the host controller, the USB hex le and the BACnet hex le, these are EMS1009.hex, usb.hex and BACnet.hex. Place the new les on the thumb drive. Plug in the USB adapter cable, shown on previ­ous page, and the ash drive.
The SRCM will automatically detect the USB drive bringing up a window.
1. Press the Change button.
2. Scroll to the Upgrade Host Firmware screen shown here.
3. After the host rmware has been updated, change to the Upgrade Communication Firmware screen and press START.
31
Network Setup
The BACnet setup screen is enabled by pushing position 1 switch (labeled MAC) to the on (right) position. After conguration the switch must be moved to the off (left) position.
Five position dip switch location
The Network Setup screen gives the option for the user to congure the
Network and other parameters which have to be read from the network.
BACnet conguration requires the user to congure the following param­eters.
1. Baud Rate - User can select any one of the 4 standard Baud rates for
RS485 communication from 9600, 19200, 38400 and 76800 by using the change button. Auto baud features is not supported.
2. MAC Address - User can enter Medium Access Control address specic to this device by touching on this eld. The MAC address must be unique
across the network. Valid MS/TP MAC addresses are 0-127 for master de­vices and 0-254 for slave devices.
3. Device Instance - The Device instance number must be unique within a BACnet internetwork to identify each device. Instance numbers are dened
as 22 bit long, in decimal instance number ranges from 0 to 4,194,303. FFFFNDD is the network addressing scheme, here FFFF represents the Fa­cility code. N is the number of the network in the building and DD ranges from 0 to 99 to represent the individual device on the network.
32
4. APDU Timeout - Indicates the amount of time in milliseconds between retrans­missions of the APDU requiring acknowledgement for which no acknowledge-
ment has been received. The default value for this property will be 3,000 ms and
max can be 65535.
Save and Exit to save settings or cancel to cancel setting changes.
Once this is complete disable the BACnet setup by moving the dip switch position 1 to off (left ) position.
Five position dip switch location
Press Save and Exit.
5. After the unit returns to the main menu screen, disconnect the power to the unit and reconnect in order to boot up with the proper MAC address and Device In-
stance. The power can also be cycled by removing Jumper JP1 and then reconnect­ing.
Removing the jumper
causes power loss.
Re-insert the jumper to
restore power.
The unit can also be congured through the BACnet interface as well as through
the Touch Screen User Interface.
33
Event Log
The SRCM can be enabled with an audit trail of changes made to the congurations/ modes of the system by Supervisor and Operator. When the Supervisor / Operator changes any conguration through the menu, the action is captured and stored in a string covering the User prole Screen name where the parameter is changed. There will be 5 such instances stored in non-volatile memory of the unit. Any power failure
in the unit will lose the data and it will be the responsibility of BMS system to log
these strings after polling from the SRCM unit through BACnet. The SRCM unit will store these strings as different instances of Character String Object.
The value to which the parameter is changed will not be logged for parameters like
User Dened Condition Banner text, Room Label, Message Text, etc., which needs more memory. Other parameters whose variables are enumerated, real and integer
will be logged until the value is changed.
The string length of each instance of conguration change will be 50 Bytes in the
data memory area of the controller.
34
French Language Support on Default Screen & Data Entry Screen
The home screen can be setup to show French Language words using the Setup Display Menu
The following screens show the difference between English and French Home screens.
Default screen for English version.
Default screen for French version.
35
On the default screen the following changes will be made for the French version.
PRESSURE PRESSION OPERATION OPĖRATION NEGATIVE NĖGATIVE NEUTRAL NEUTRE STANDBY ATTENTE DOOR PORTE WARNING ALERTE ALARM ALARME TEMPERATURE TĖMPERATURE SILENCE, NORMAL, HUMIDITY, RESET do not change
When the language is selected as French in the setup display screen, French characters entry in the data
screen will be enabled. Whenever user presses N (same for all French characters like A, E, I, O, U, C) a
child screen will pop up which will contain all corresponding French characters. In this case child screen will contain French characters corresponding to N. When user presses any of these characters, that char­acter will be taken as input and the child screen will disappear. If user does not want to enter any charac­ter, child screen will disappear when user presses N in the main screen.
Data Entry Screen for French Version
36
French Version—Letter A
French Version—Letter E
37
French Version—Letter U
French Version—Letter Y
38
French Version—Letter I
French Version—Letter O
39
French Version—Letter C
French Version—Letter N
40
Troubleshooting
Error/Trouble Condition Possible Cause Solution
Display shows: "Factory Calibration
has been lost. Return to Factory for
Calibration".
Display shows: "Setup information
has been lost. Loading Default Values
Please Wait...".
User cannot enter into menus because of password protection.
SRCM does not come online Two or more controllers have the
Non-recoverable EEPROM check­sum error of factory calibration data, ER01.
Recoverable EEPROM checksum er­ror of unit setup conguration, ER02.
User has lost password. Use default password "351".
same MAC address.
The MS/TP network has too many devices.
Too many devices were installed without any repeaters.
The MS/TP cable runs are broken. Locate the break and correct the wir-
MS/TP connections at the module were reversed.
The SRCM does not have power. Apply power to the SRCM.
Return unit to factory for calibration.
Unit will auto recover by rebooting
and then displaying message: "Setup
information has been lost, default
conguration loaded. User should recongure." User should press OK/ Cancel (User Acknowledgement) so
that device enters into default screen.
Modify each duplicate address to a
unique number.
Do not exceed the maximum number of devices and maximum length al-
lowed by the EIA-485 specications.
Repeaters need to be installed as
specied in this document.
ing.
Respect polarity of the wires on a MS/TP network.
41
RETURNING PRODUCTS FOR REPAIR
When returning a product to Setra Systems, the material should be carefully packaged and shipped prepaid to:
Setra Systems, Inc.
159 Swanson Road
Boxborough, MA 01719-1304
Attn: Repair Department To assure prompt handling, please refer to return instructions on our Web site at http://www.setra.com/tra/re­pairs/cal_rep.htm.
WARRANTY AND LIMITATION OF LIABILITY
SETRA warrants its products to be free from defects in materials and workmanship, subject to the following terms and conditions: Without charge, SETRA will repair or replace products found to be defective in materi­als or workmanship within the warranty period; provided that:
a) the product has not been subjected to abuse, neglect, accident, incorrect wiring not our own, improper in­stallation or servicing, or use in violation of instructions furnished by SETRA;
b) the product has not been repaired or altered by anyone except SETRA or its authorized service agencies;
c) the serial number or date code has not been removed, defaced, or otherwise changed; and
d) examination discloses, in the judgment of SETRA, the defect in materials or workmanship developed under normal installation, use and service;
e) SETRA is notied in advance of and the product is returned to SETRA transportation prepaid.
Unless otherwise specied in a manual or warranty card, or agreed to in writing and signed by a SETRA of­cer, SETRA pressure, humidity, and acceleration products shall be warranted for one year from date of sale.
The foregoing warranty is in lieu of all warranties, express, implied or statutory, including but not limited to, any implied warranty of merchantability for a particular purpose.
SETRA’s liability for breach of warranty is limited to repair or replacement, or if the goods cannot be repaired or replaced, to a refund of the purchase price. In no instance shall SETRA be liable for incidental or conse­quential damages arising from a breach of warranty, or from the use or installation of its products. No repre­sentative or person is authorized to give any warranty other than as set out above or to assume for SETRA any
other liability in connection with the sale of its products.
For all CE technical questions, contact Setra Systems, USA. EU customers may contact our EU representative Hengstler GmbH, Uhlandstr 49, 78554 Aldingen, Germany (Tel: +49-7424-890; Fax: +49-7424-89500).
SS-SRCM-OPER Rev E 4/15
42
159 Swanson Road, Boxborough, MA 01719-1304
Tel: 800-257-3872/978-263-1400
Loading...