Pressure Value .........................................................................................................................................................9
Slider Bar and Set Point Values ............................................................................................................................. 9
Slider Bar On/O .................................................................................................................................................... 9
Active and Standby Modes .................................................................................................................................. 10
Menu Screens.........................................................................................................................................................11
SETUP UNIT ...................................................................................................................................................................... 12
Analog Inputs ........................................................................................................................................................ 14
Changing Room Name ......................................................................................................................................... 15
Customizing the Operation Condition Screen ................................................................................................. 17
Display Averaging (tenths of seconds) ............................................................................................................... 17
What Pressure To Display .................................................................................................................................... 17
Full Screen Condition .........................................................................................................................................20
Banner and Active Standby Mode Application ................................................................................................. 20
Set Time & Date Screen .......................................................................................................................................22
Alarm Set Point ..................................................................................................................................................... 25
CALIBRATION AND SELF TEST ..................................................................................................................................... 27
SYSTEM INFORMATION ................................................................................................................................................. 28
USB CONFIGURATION CLONING .................................................................................................................................29
FRENCH LANGUAGE SUPPORT ON DEFAULT SCREEN & DATA ENTRY SCREEN ............................................. 35
Default screen for English version. ..................................................................................................................... 35
Default screen for French version. ...................................................................................................................... 35
Data Entry Screen for French Version ............................................................................................................... 36
RETURNING PRODUCTS FOR REPAIR ........................................................................................................................ 42
WARRANTY AND LIMITATION OF LIABILITY ........................................................................................................... 42
2
3
Operation
The following pages describe how to operate the SRCM using the touch-screen interface.
The screen has two basic functions. The primary mode of operation displays the Home
screen, which shows the end-user pressure values, messages, text, and other data intended
for visual pressure verication in the facility. The second mode of operation is the Administrative Menu screen, which permits setup, conguration, and changes to how the
SRCM operates. After changes have been performed on the Menu screen, functions are
saved and operation returns to the Home screen. Note: If there is no user interaction with
the touch screen for more than 1 minute, the screen will automatically return to the Home
Screen. Many administrative settings can be written over the BACnet MS/TP network.
Home Screen
NOTE: All settings of the SRCM can be password protected.
Menu Screen
4
Home Screen
The default screen now has 2 possible modes. If the user wants to display other room
variables in addition to Pressure they can switch to the alternate home screen that shows
up to 4 parameters per room. These Parameters can be Pressure, Temperature, Humidity,
and user-dened (ex: CO2). The User switches modes by selecting slider on/slider off on
the bottom of the administrative menu.
The Home screen is the normal continuous operating mode of the SRCM. The Home
screen shows a Condition Banner on the left one-third of the screen, and Operating Conditions on the right two-thirds of the screen. There are two possible home screens, one
with a pressure only display with a slider bar representing the room pressure with respect
to the alarm setpoints. The alternate home screen can be used when there are multiple
parameters being measured in addition to pressure, such as temperature, humidity and a
user-dened option.
Condition Banner
Pressure Value
Condition Banner
Pressure
Temperature
Humidity
User-dened
Home Screen
Room Label
Slider Bar and Setpoint Values
Alternate Home Screen displaying multiple
parameters, in addition to pressure.
Pressure Mode
• Positive
• Negative
• Neutral (span)
• Standby
Operation
• Normal (green)
• Warning (yellow)
• Door (yellow)
• Alarm (red)
Room Label
Pressure Mode
• Positive
• Negative
• Neutral (span)
• Standby
Operation
• Normal (green)
• Warning (yellow)
• Door (yellow)
• Alarm (red)
5
Condition Banner
The Condition Banner is the left 1/3rd portion of the screen that can be congured
by the end-user or facility manager to display a message to staff on the oor. The
Condition Banner can be Green, Yellow, Red or Blue, depending on the message
desired outside the pressurized space. The Condition Banner is set up in the Setup
Display-Condition Banner tab of the Administrative menu. There is also the op-
tion to display the Condition Banner in full screen.
The Condition Banner will change to red in alarm state regardless of the current
conguration. The banner may be changed manually, as required, by pressing the
touch-screen anywhere within the banner color region.
User dened text
ENTRY PERMITTED
graphic (arrow is not intended
to indicate direction of airow)
User dened text
User dened text
STOP graphic
User dened text
User dened text
Warning graphic
User dened text
Green Condition Banner—shows the
Entry Permitted graphic, and user de-
ned text above and below the graphic
image. Use the GREEN banner to indicate room is safe to enter.
Red Condition Banner—shows
the Stop graphic, and user dened
text above and below graphic image. Use the RED banner to indicate
room is under critical use and entry
is restricted.
Yellow Condition Banner—shows the
Warning graphic, and user dened text
above and below graphic image. Use
the YELLOW banner to indicate room
is under transient use and entry is restricted.
User dened text
ENTRY PERMITTED
graphic (arrow is not intended
to indicate direction of airow)
User dened text
6
BLUE Condition Banner—shows
the Entry Permitted graphic, and
user dened text above and below
graphic image. Use the BLUE banner to indicate room is safe to enter.
Condition Banner –
Touch Screen
Operation
Once the messages of each of the four Condition Banners are dened in the Menu
section, the user can cycle through all four conditions by simply touching anywhere
on the left one-third of the screen. If passwords are enabled, the user will be prompted
to enter their password before proceeding. Each of the four colored screens can have
a unique message dened. See Section: Setup Display, page 11, for instructions on
how to setup the Condition Banner.
Alarms Cause
Condition Banner to
Turn Red
When the alarm occurs the Condition Banner will behave as follows:
1. Condition Banner will turn Red and Blink, irrespective of the color mode selected
by the user. User congured color mode: “Alarm Blink” & “Blink in Red” in the
Setup Display screen will remain same. The operation eld which displays the alarm
state of the system will also blink. When the system returns to normal user congured
settings will be retained.
2. The Message text on the bottom of the Condition Banner and User dened text on
top of the Condition Banner will be displayed as “ALARM” temporarily.
The Condition Banner can be congured so that any of the Condition Banner colors
can be set to blink when that condition occurs. For example if an alarm occurs, Red
color can be made to blink. Similarly, the yellow warning, green, and blue modes can
also be set to blink.
Condition Banner
Functions
The Condition Banner conguration on the Display screen will have 3 options: Active, Standby, and No Action for all four colors (Red, Yellow, Green, and Blue).
• When Active is selected, the Occupancy Status object of the SRCM will be active.
• When STANDBY is selected, then the unit shall be put into STANDBY mode (No
alarms will be generated) when the corresponding color condition is selected
• The No Action mode will do nothing other than to display the Condition Banner
screen that has been associated with the No Action mode.
7
Operating
Condition Screen
The Operating Condition screen shows the user the active operating conditions of the
pressurized space.
Room Label
Pressure Mode
• Positive
• Negative
Pressure Value
• Neutral (span)
• Standby
Slider Bar and
Alarm Setpoint
Values
The Room Label at the top of the screen can be dened by the user to ensure the
Operation
• Normal (green)
• Warning (yellow)
• Door (yellow)
• Alarm (red)
viewer understands which room is being monitored by the SRCM. See Changing
Room Name page 10, to enter text for your specic room.
The PRESSURE indication shows the intended direction of airow for the space.
POSITIVE for airow out of the space, NEGATIVE for airow into the space,
NEUTRAL for airow conditions that may vary, and STANDBY for use when there
is no need to verify the direction of airow (alarms are disabled).
The OPERATION indication shows whether the pressurized space is within normal operating parameters (within alarm thresholds), or whether there is an alarm or warning condition. If operation is within alarm thresholds, a green NORMAL indication is shown. If operation is near either high or low alarm threshold limits, a yellow
WARNING indication is shown.
If operation is at or beyond high or low threshold limits, a red ALARM indication is
shown. If Audible Alarming is Enabled, a piezo buzzer will sound and a SILENCE
menu button will appear. Pressing the SILENCE button will shut off the alarm for
the period of time dened in the alarm conguration. Alarm operation can be congured to blink or sound an audible signal. See Section, Alarm Setup, page 15, for more
about setting up ALARM and WARNING conditions.
In addition to the pressure indication, OPERATION also displays whether a door
is open. If a door switch is congured, an open door contact will display a yellow
DOOR indication.
8
Pressure Value
A black banner displays the actual pressure reading from the space, in either inches
of Water Column (“ WC) or Pascals (Pa). The resolution of display can vary, depending on desired conguration; either 2, 3, or 4 signicant digits. The accuracy of
measurement remains the same regardless of the number of digits chosen.
Slider Bar and
Set Point Values
Pressure Value
Slider Bar and
Setpoint Values
Slider Bar On/Off
The blue banner below the pressure value shows where the current pressure reading
is in relation to alarm setpoints. The value at the left of the blue banner is the low set-
point, and the value on the right is the high setpoint. The middle “I-beam” represents
the current measured pressure value on the setpoint scale.
High alarm setpoint
“Cursor” representing where
the pressure value lies relative
to the alarm setpoint
If the user does not wish to see the actual slider bar, it can be turned off using the
Menu screen. Operation of the pressure sensing and alarming is unaffected. See setting up Menu screen, page 7.
Slider bar is turned off, this displays when four parameters are
congured
Slider bar is turned off, this displays
when no parameters are congured -
Pressure still displays
9
Active and Standby
Modes
By pressing the touch-screen directly on the word POSITIVE (or NEGATIVE,
NEUTRAL, or STANDBY), the user is able to change the condition of the
room between ACTIVE and STANDBY modes. A pop-up menu appears to enable selection. If passwords are enabled, the user must rst enter a password to
proceed with the change.
In ACTIVE mode, the full function of the SRCM is active. In STANDBY
mode, the SRCM will perform all functions except that alarming will be dis-
abled (both audible and visual alarms). The STANDBY mode is designed to
put the SRCM into a mode where room pressurization is not critical, such as
cleaning, patient transfer, or longer-term unoccupied status. Note that this op-
eration can be password protected so that only an Operator or a Supervisor can
make this change. Passwords are set up in Setup Display Advanced tab.
10
Menu Screens
Pressing the MENU button on the Home screen brings up the Administrative Menu. If
passwords are enabled, the user is required to enter the correct password before being
authorized to make changes. From the Administrative Menu, the user can set all op-
erating parameters of the SRCM. This includes initial setup, commissioning, calibration, Network setup, customizing the displays, and warning and alarm parameters. The
menu structure is setup in such a way that the user can setup the unit by starting with
the left column and working down, moving to the next column and working down until
all setups have been made.
Setup Unit—for initial unit setup
Setup Display—customizes the display
Setup Alarm—setup the behavior of
how alarms are communicated to the
user
Slider ON/OFF—denes whether the
pressure value and alarm setpoints are
displayed on the home screen
* Calibration is only required for highly accurate measurement needs such as those
needed to comply with federally mandated regulations. See the SRCM Product Data
Sheet for more information.
Upon initial installation, the Setup Unit screen should be used to dene installation
parameters specic to the job site.
Calibration*—used to re-zero or
calibrate internal sensor
Alarm setpoint valuesSave Settings and Exit
Room Label that settings
apply to (global unless
Secondary is shown)
Network Setup —congure
parameters to be read from
the network
Event Log—Alarm/
Warning History
Serial number and other
system information
11
Setup Unit
The SRCM can take as input, the signal from two separate pressure transducers as well
as temperature, humidity, and user dened (ex. CO2) inputs for up to two rooms. These
are congured for either Primary Room or Secondary Room (an anteroom is an example
of a secondary room). When two transducers are used, the Home screen display of the
SRCM can toggle between each space to indicate the status of each room momentarily
cycling from one to the other. Alternatively, the display can be locked on either of the
two rooms.
*If Ch1 is selected for the Primary room, it will not be an available option for the Secondary room.
Setup selection to
congure either
Primary or
Secondary Room
Room label of selected room,
either Primary or Secondary
depending on ROOM radio button
Primary Room sensor:
• OnBoard Sensor
• External Ch1
Secondary Room sensor:
• External Ch1*
• External Ch2
Primary room pressure signal
output (AO) scale and units:
• 4-20 mA
• 0-5 Vdc
• 0-10 Vdc
Room - Primary or
Secondary
Primary Room
Sensor
Secondary Room
Sensor
Pressure units, either “ WC or Pa
Full Scale (FS) range of transducer
selected, Primary or Secondary
Use the radio button to select the setup parameters for either the Primary Room or Secondary Room.
It may be necessary to change settings to match the sensor being used. OnBoard is the
default, which uses the sensor manufactured on-board the unit. Alternatively, an external sensor (also known as “external transducer” such as a Setra 264 or Setra 267) may
be used. If an external sensor is used, change this selection to ADC Ch1 (Analog Input
1) or ADC Ch-2 (Analog Input 2). The FS output and range of the external sensor will
need to be entered. If the OnBoard Sensor is selected, a box is shown displaying the
pressure range and engineering unit.
It may be necessary to change settings to match sensor being used, if there is one pres-
ent. There is no specic sensor listed at the default. An external sensor (Setra 264 or
Setra 267) may be used for the secondary room, or anteroom. If an external sensor is
used, change this selection to ADC Ch1 or ADC Ch2, which use Analog Input 1 or
Analog Input 2, respectively. The FS output and range of the external sensor will need
to be entered.
12
Room Parameters
The SRCM can display up to four (4) parameters for each of 2 rooms. The parameters can be Pressure, Temperature, Humidity, and the fourth user dened
(Ex., CO2). Start with the Primary Room and set up the Parameters to be monitored and displayed on the default or home screen. As Parameters and inputs
are selected further selection of parameters and inputs will become self limiting
(Ex., If Temperature is selected in Parameter 2, it is not available for selection
in Parameter 3 or 4.)
Start with Parameter 1, this is the Room Pressure. Select the Input Source as
OnBoard, ADC-Ch1 or ADC-CH-2.
Parameter 2, Select None, Temperature, or Humidity. Temperature is suggest-
ed. Select Source as ADC-Ch1, ADC-Ch2, or BACnet.
Parameter 3, Select None, Temperature or Humidity. Humidity is suggested.
Select Source as ADC-Ch1, ADC-Ch2, or BACnet.
Parameter 4 Select None, User Dened.
Label
Primary Analog
Output
Engineering Unit
Sensor Range
On the display, touch the label box and using the data entry keypad, input the
Room Label for the Primary Room. This will be displayed at the top of the default screen to identify the room that the parameters refer to. Use the Primary/
Secondary Room radio buttons to select the secondary room (generally an
anteroom) and label that room as desired.
This Analog Output (AO) is used to communicate the value of the differential
pressure of the Primary Room to an external source such as a Building Man-
agement System (BMS). The value is scaled as either 4-20 mA, 0-5 VDC, or
0-10 VDC, selectable. A normalized pressure value is generated once every
100 milliseconds. The analog output is only available for the Primary room.
Units of measurement to show on the Home screen are selectable as either
inches of Water Column ("WC) or Pascals (Pa). The units are factory calibrated as "WC, but if the unit is changed to Pa, the rang will be change to
Pascals (Pa). This is selected from the Parameter 1 tab as it is associated with
the primary room pressure.
The SRCM is manufactured with an on-board differential pressure transducer.
This transducer is manufactured to specications for xed minimum and
maximum pressure measurement, known as the full-scale range of the transducer. When the on-board transducer is used exclusively, these values cannot
change. Alarm setpoints cannot be set above the positive value or below the
negative value. If a wider or narrower sensor range is required for the project,
an external pressure transducer such as a Setra 264 or Setra 267 may be chosen
to match the requirements. See more above under Primary Room or Secondary
Room.
If an external transducer is used, the full-scale values and other parameters
need to be congured into the SRCM so the unit understands the scale of measurement being received on the inputs Analog CH1 or Analog CH2.
13
Analog Inputs
The SRCM has 2 Analog Input Channels (ADC-CH1 and ADC-CH2)
Note: If a 4-20 mA transmitter is used as an analog input then a 250 ohm resistor
must be eld installed and this will be translated into a 1-5 VDC input at the input
terminals.
This takes an analog input from any transducer or transmitter: pressure, temperature
or humidity. If an external transducer is used, the full scale values and parameters
need to be congured into the SRCM so the unit understands the scale of measurement being received on inputs ADC CH-1 or ADC CH-2.
The following is an example using a pressure transducer to measure secondary room
pressures. This is showing a pressure transducer with a range of ±1"WC and output
of 4-20 mA over that range.
If selecting Analog Ch1 or Analog Ch2 for
either Primary of Secondary Room, enter
full-scale (FS) range that matches the transducer being used
Also enter voltage or milliampere range
that matches the transducer being used
The following is an example using a temperature sensor to measure primary room
temperature. This is showing a temperature range of ±50°C and output of 1-10 VDC
over that range.
Select desired units of measure to display on the Home
screen, either “WC or Pa. The unit of measure for the external transducer must be selected before entering range and
output of the unit. After entering all data the units may be
changed and the range will scale accordingly.
14
The following is an example using a humidity sensor to measure primary room
relative humidity. The range is 0-98 %RH with a 0-10 VDC output.
Changing Room Name
Touch anywhere within the
Room Name entry box to bring
up the on-screen keyboard and
enter text.
The room name shown on the top part of the Home screen is changed using the
Room Label button. The Room Name entry box appears in the middle of the
Setup Unit display. Depending on whether the Primary or Secondary Room
radio button is enabled, the matching Room Name entry box appears. The
maximum number of characters is 18.
Press anywhere in the Room Name selection box to bring up the on-screen
keyboard to enter the desired room label text. It is not necessary to touch the
white area next to the Label, simply start entering data using the keyboard entry. Be sure to press the Save button under the text entered before leaving this
screen.
Data Entry screen with
QWERTY keyboard
Use CAP-ON button to switch between
lower-case and upper-case lettering and
other characters
Press Save after text entry is
complete.
When nished with data entry, select Enter to
conrm, or ESC to cancel and return to the
previous screen
15
Setup Display
The Setup Display screen permits authorized users (based on password level) to
congure Condition Banner messages and other Home screen options. There are
four tabs for display customization; General, Advanced, Condition Banner, Set
Time and Date.
General Tab —
Customizing the
Condition Banner
Change color and text of
Condition Banner by pressing
anywhere in the colored region
The General tab allows the user to dene messages for each Condition Banner
color. Pressing anywhere in the colored region of the Condition Banner changes
each selection between GREEN, YELLOW, RED, and BLUE. By pressing on
the colored region of text, the on-screen keyboard pops up, enabling data entry.
If User Dened Text is Disabled, then data entry on the Condition Banner will
not be permitted. Change User Dened Text to enabled to change the text of
each banner.
Congure whether the user can
change the text of the Condition
Banner. Enabled or Disabled
Congure if you want to enable
banner
When nished making changes,
press Save & Exit to store the
modications. Or press Exit to
discard changes and return to
the previous screen.
Select Home screen language
desired, English or French
In the Setup Display General tab you can congure the text to be displayed
above and below the center symbol by enabling the User dened text. If you
want the banner to blink, Enable the Blink selection.
If any alarm occurs, the condition banner will turn to red and text above and
below the center symbol will display ALARM
16
Advanced Tab–
Customizing the Operation
Condition Screen
Primary Pressure Resolution
The number of signicant digits
displayed for the pressure value
(1-4)
The Advanced tab allows the user to make renements in how information
is displayed on the Operating Condition section of the Home screen. The
Display contrast level is adjusted using Adjust Contrast Level, with selections from 1-4. After modifying this parameter, press Save & Exit to view
the brightness and contrast on the Home screen display. Depending on the
lighting and viewing conditions in the nal space, different contrast levels can
improve readability of the SRCM.
Contrast level of Home
screen. Adjust from 1-4 for
readability in varying
lighting conditions
Display Averaging.
Select a value from 1-40
Dene Supervisor and Operator
passwords. Enable or Disable use of
passwords
Display Averaging
(tenths of seconds)
What Pressure To Display:
• Primary Only
• Secondary Only
• Toggle
When nished making changes, press Save & Exit to store
the modications. Or press Exit to discard changes and return
to the previous screen
This function is used to improve the stability of the pressure value displayed
on the Home screen, so signicant digits do not change rapidly. It is used
more often in environments where the user requires higher display resolution
(4 digits) but the ambient pressure is unstable. By increasing the number, the
effective number of measured data points is increased and a weighted average is developed. Input the number in tenths of a second for the response time
of the display to a pressure change. There is no ratcheting of the display or
a deadband. The pressure change is very smooth. For example, entering 10
equates to the display reaching nal value in 1 second. Entering 2 equates to
nal value in 2 seconds.
Display Averaging does not affect the Analog Output response time, only the
apparent stability of the pressure display. Display Averaging also does not affect Alarm Thresholds or Alarm Delay.
What Pressure To
Display
This function denes what pressure value is shown on the Home screen under
normal operating conditions. This can be Primary Only, Secondary Only, or
Toggle, depending on what room is most important for visual pressure veri-
cation.
If this is set to Primary Only, then the Home screen will show the pressure
value read by the primary pressure transducer (either on-board, or the alternate primary transducer congured from a separate transducer, if one is used).
If a secondary transducer is in use, and an alarm condition occurs in the secondary room, the display will toggle and remain on the secondary room and
pressure value as long as the alarm condition is present in that space.
17
If this is set to Secondary Only, then the Home screen will show the pressure value read by the secondary pressure transducer (anteroom for ex-
ample). In this case, if an alarm condition occurs in the primary room, the
display will toggle and remain on the primary room and pressure value as
long as the alarm condition is present in that space. If no Secondary Room
is congured on the Setup Unit screen, attempts to choose Secondary Only
will result in the error “Secondary room source is NONE.”
If the function is set to Toggle, then the Home screen will show the pressure value for both rooms, alternating back and forth momentarily (approximately 10 seconds apart). If an alarm condition occurs in either room, the
display will toggle to the appropriate room and pressure value and remain
on that room as long as the alarm condition is present. If both rooms are in
alarm, then the alarm condition and pressure values will toggle.
Pressure Resolution
Supervisor and
Operator Passwords
This setting shows the number of digits after the decimal point
for the default screen pressure displays. This setting affects the
primary and secondary room settings.
The password function provides security against changed congurations by
unauthorized users. This is accomplished by using two levels of password
protection. These can be enabled or disabled.
The Operator level allows access to change between Active and Standby
room modes, but no other changes.
18
The Operator is the person that has day-to-day interaction with the monitor
to change operating modes from Active mode to Standby (where no alarms
are active). the operator can also respond to local audible and visual alarms.
This could be a Nurse or a Lab Technician. The SRCM was designed to
make interaction with the unit as easy as possible for the Operator. Changes to messages and to the room mode requires simply touching active areas
of the display. If Operator Password is enabled then a password will be
needed before the change can be made.
The Supervisor Level allows full access to all levels of the menu structure.
This mode is used during initial conguration and follow-on reconguration.
NOTE: The master Supervisor password is 351, and will work for any
condition where a user may need to reset passwords.
Condition Banner Tab-
Customizing Blinking
The Condition Banner can be used for control function as well as pure communi-
cation. There are three choices for each color: Active, Standby, and No Action.
Screens
Used for setting
actions that is
associated with
each banner color
The Condition Banner tab allows the user to choose whether certain parts of the
screen blink or not. Blinking components on the Home screen are intended to
draw more attention to the Condition Banner or the OPERATION indicators. This
is for the purpose of making exception conditions more noticeable to staff concerned with room pressurization status.
Alarm Blink
Warning Blink
Blink in Red/Green/Yellow/Blue
Full CB Display
Save & Exit
These apply to the right
side of the Home Screen
Denes the behavior of the red ALARM
indicator on the Home screen. Normal
Blink is used for the green NORMAL
indicator.
Applies to the yellow WARNING, DOOR
indicator.
Applies to the Condition Banner messages
and icon on the left one-third of the Home
screen.
If this is selected the left 1/3rd of the
condition banner will become full screen
after 15 seconds. If an alarm is in progress
or occurs while the Condition Banner is
full screen, the standard default screen
will display. Touching the display will
return it to the 1/3rd, 2/3 standard display
mode. This is useful when users want a
very simple interface. Touching the screen
at any time will momentarily display the
Home screen.
Saves the selections made on this screen.
19
Full Screen Condition
Banner and Active Standby
Mode Application
Customers may want a minimal user interface and want to switch be-
tween Active and Standby Modes and clearly convey the status of the
room.
Note: Any color can be associated with any action: Active, Standby, or
No Action.
The following example uses GREEN for Active and YELLOW for
Standby.
1. On the setup Display/General tab set User dened Text to Enabled.
2. Tap the condition banner screen until the green screen is displayed.
Setup the desired green screen text message to be displayed in the Active mode. Text can be entered so that it displays in the boxes above
and below the center "Clear to Enter" symbol. Touch the top box and
enter the desired text using the Data Entry keypad. Save by pressing
the Enter button when complete. Perform the same steps for the bottom
box.
3. Setup the desired yellow screen text message in the Setup Display/
General tab. Text can be entered so that it displays in the boxes above
and below the center "Warning Triangle" symbol. Touch the top box
and enter the desired text using the Data Entry keypad. Save by pressing the Enter button when complete. Perform the same steps for the
bottom box.
20
4. Setup the Condition Banner to display Full Screen rather than 1/3
left of screen display that is the default "as shipped" setup. To do this
go to the Setup Display/Condition Banner tab and set the full Condition Banner Display to Enabled. Press Save and Exit.
5. With this setup the unit is in Active Mode. The Full Screen Display will look like
the following with the text that was specied in step 2:
6. If the User changes to Standby by touching the section to the right of the
PRESSURE, then the display will show up in yellow with the text that was specied
in step 3.
7. This feature can be combined with password protection
21
Set Time &
Date Screen
The Set Time & Date tab is used for setting the time and date of the SRCM. This time
and date is used to time stamp the event log. See Event Log Section.
Note: If power is lost to the unit, the time, and date need to be reset. If BACnet is used and is connected
to the network, the time and date will automatically be retrieved.
The date format is DD-MM-YYYY.
Setup Alarm
The Setup Alarm screen permits authorized users (based on password level) to congure alarm behavior, such as the duration of alarms, methods of clearing the alarm
condition, and how alarms are acknowledged. It also sets the room mode to positive,
negative or neutral room.
Latch Alarm
Alarm Delay
If enabled, causes the display of red ALARM on the Home screen
to remain, even if room pressurization returns to NORMAL. Latch
Alarm enabled requires that an alarm event be acknowledged and that
the pressure returns to within the normal range. This is useful because
it forces recognition that an alarm event occurred. The alarm will still
be on even if the pressure returns to normal range. Only when the
alarm is acknowledged will alarming cease. When disabled, the alarm
will be silenced when the pressure returns to normal range without
requiring acknowledgement.
When a Latch Alarm occurs, the Home screen displays a RESET
button to the right of the Menu button. Press the RESET button to
acknowledge and reset the Latch Alarm condition.
Time between when the pressure went outside alarm setpoints and
when the unit goes into alarm mode. This is useful in preventing false
alarms. For example, if Alarm Delay is set to 20 seconds, the staff has
20 seconds to open a door, enter the room and close the door before
the alarm sounds (if audible alarms are enabled). Alarm Delay also
applies to alarms annunciated to a remote annunciator via the SRCM
Digital Output (hardware conguration).
Dene which room the Setup Alarm
conditions will apply to
For each room (Primary or Secondary), dene whether the room
pressure will be Positive, Neutral,
or Negative
22
Audible Alarm
Mute Time Out
Digital Input (DI)
Deadband
Buzzer Volume
Enables or disables the audible buzzer. Regardless of whether audible
alarming is enabled or disabled, the red ALARM condition will show
on the Home screen, annunciate to an SRAN, and propagate to a
congured Digital Output. If an alarm occurs and the audible alarm is
enabled, a new SILENCE button will appear on the Home screen so
that the operator can silence the audible alarm. The audible alarm is
silenced only for the period of time dened by Mute Time Out.
Sets the time (in seconds) that the alarm will remain silent after press-
ing the SILENCE button before the audible alarm resumes again.
This assumes that the room pressure condition is still outside the
normal setpoint operating limits. Mute Time Out can be set from 0 to
9998 seconds. Entering a value of 9999 will silence the audible alarm
“forever,” as long as a new alarm condition does not occur.
Used for monitoring the door status, open or closed. The DI is a Nor-
mally-Closed dry contact. A door jamb or valve pressure switch must
be wired to the terminals labeled DOOR in the rear of the unit. When
the door opens the contact will open, and this will show a yellow
DOOR Warning on the Home screen. The Door Alarm will suppress
alarms if they are generated at the same time that the door is open.
is adjustable from 0 to 10% and represents the region within the
setpoint range where yellow WARNING is displayed on the Home
screen to indicate that the pressure is near ALARM limits. If set to
0, no WARNING will occur, only ALARM when the pressure value
reaches setpoints. If set to any other value, WARNING will be dis-
played if the pressure value reaches that percentage of total pressure
setpoint range.
When the unit goes outside of the deadband range the alarm will oc-
cur. The alarm will remain until the pressure returns within the alarm
limit range (or acknowledged Latch alarm) minus the setpoint.
The buzzer volume can be adjusted from one to four, with four being
the highest sound level. The alarm buzzer is disabled using audible
Audible Alarm disable function.
23
Alarms Disabled when Door
Open & Buzzer for Door
Warning
The SRCM is able to congure the Room status to disable the Alarms when
Door is open. This function is used when there will be high trafc through
the area and the user wants to disable any alarms that are occurring as the
result of the door being open. The alarms will be re-enabled once the Door
is closed.
In the Alarm Setup screen, select the digital input choice to Door Alarm.
As shown in the screen below, the DOOR indication (to the right of
Operation) will be highlighted to indicate that the door is open but that
STANDBY (to the right of PRESSURE) will indicate that the room is in
STANDBY mode.
24
If the door opens when the unit is in alarm, unit will continue to operate in
alarm state instead of clearing the alarm.
Alarm Set Point
For each space, Primary Room or Secondary Room, this screen is used to dene the alarm
setpoints. When the room is then set to Positive, Neutral, or Negative, the setpoints and con-
ditions congured here are in effect for alarm and warning conditions.
Alarm Matrix
The SRCM has a great deal of exibility to dene alarm conditions. Alarms and warnings
can be congured for primary and secondary rooms, and for the door. Room display can
toggle between Primary and Secondary. The following table outlines what will occur in
terms of priority and display under normal and alarm conditions.
N=Normal; A=Alarm
ToggleHigh PriorityDisplay
Primary
Pressure
Secondary
Pressure
Text (Maxi-
mum eight
BackgroundRemarks
characters)
DisabledNNNormalGreenDisplays primary pressure
or secondary pressure based
on the selection in the setup
display screen.
DisabledNAAlarmRedShows Alarm for second-
ary room if secondary room
is selected for the display.
If the pressure to display is
selected as Primary, display
switches to the secondary
room to show the alarm.
DisabledANAlarmRedShows Alarm for primary
room if primary room is
selected for display. If the
pressure to display is selected as secondary, display
switches to the primary
room to show the alarm.
25
ToggleHigh PriorityDisplay
Primary
Pressure
Secondary
Pressure
Text (Maxi-
mum eight
BackgroundRemarks
characters)
DisabledANAlarmRedShows Alarm for second-
ary room if secondary room
is selected for display. If
the pressure to display is
selected as Primary, display
switches to the secondary
room to show the alarm.
DisabledAAAlarmRedDisplay toggles between pri-
mary and secondary room.
DisabledAAAlarmRedDisplay toggles between pri-
mary and secondary room.
EnabledNNNormalGreenToggle between primary and
secondary room.
EnabledNAAlarmRedShows secondary alarm.
Display stops toggling.
EnabledNAAlarmRedShows secondary alarm.
Display stops toggling.
EnabledANAlarmRedShows primary alarm. Dis-
play stops toggling.
EnabledANAlarmRedShows primary alarm. Dis-
play stops toggling.
EnabledAAAlarmRedDisplay toggles between pri-
mary and secondary room.
EnabledAAAlarmRedDisplay toggles between pri-
mary and secondary room.
26
Calibration and
Self-Test
This page is used for calibration of the internal pressure transducer sensor
and testing operation of hardware circuitry. Calibration is only required for
highly accurate measurement needs such as those needed to comply with
federally mandated regulations. Calibration should only be performed by
qualied personnel.
1. Select Primary or Secondary room. When selected, the gray box to the
right will indicate if the calibration will be applied to the on-board sensor or
the external sensor (Analog Ch1 or Analog Ch2). The indicated pressure is
shown.
2. Calibration of the on-board sensor requires that the faceplate be removed
and the captive screw holding the display cover must be loosened (at the
bottom-center of the display bracket).
3. Lift the cover to expose the clear and red tubing connecting the on-board
sensor to the pressure ttings in the rear of the unit.
4. Remove the tubing from the high and low ports (red and clear tubing).
This disconnects the sensor from the room pressure.
5. After calibration, replace the red and clear tubing.
27
Zero Adjust
Span Adjust
Restore Factory User
Zero and User Span
Test
Pressing Zero Adjust button will bring up a “Is zero pressure
applied?” message. If yes, press OK. If the zero measure-
ment is within 10% of the factory zero measurement stored
in the unit, the zero value will be reset. Note: Zero Adjust
should only be performed after the unit has been operating
for 30 minutes in the installed location.
This requires the use of a Pressure Calibrator, such as a Setra
Model 869 or equivalent. Connect tubing from the Calibrator to the low and high ports identied near the PCBA
markings. Apply Full Range pressure, for example ± 0.1”
WC range, use 0.1” WC. When pressure reaches Full Range
pressure, press OK button. The output at Full Range must be
within 10% of the factory calibration to allow re-adjustment.
If the unit has been miscalibrated in the eld, the factory
zero and span settings can be restored.
The Buzzer, Relay and Internal Memory checksum can be
tested and veried.
System Information
The System Information screen reports Model Number, Serial Number,
Firmware Revision, Network Status, Last (Factory) Calibration Date and
Technical Support Contact.
Technical SupportAny string 30 characters or shorter
can be entered in this eld by pressing anywhere in the white text entry
box to enable the pop-up keyboard.
Enter an email address, name, or
phone number as needed.
Restore Factory Default
Restores the default settings for all con-
guration and setup screens. All congured
settings, including alarm thresholds and
audible alarming, that were modied after
installation will be lost if this function is
used. Primary and Secondary Room Labels
will show “???.” Normal operation of pressure measurement will not be affected.
28
USB
Conguration
Cloning
The SRCM has a USB port built in for the purpose of duplicating congurations
when multiple units are being setup with similar congurations. To use this function, a USB 2.0 thumb drive with 256 megabytes or larger must be used. The thumb
drive must have at least 100K or free memory available. The USB port should only
be accessed by qualied personnel.
Setra recommends the Kingston DataTraveler 112, 4GB (minimum) ash drive
along with the aid of a short mini-USB adapter cable from Tensility International
Corporation, P/N 10-00003. No PC is required.
ManufacturerModelSize (GB)Comment
KingstonDataTraveler1No issue
256 MBNo issue
DataTraveler4To make Kingston work,
DataTraveler8
DataTraveler
112
SandiskCruzer2To make Sandisk work,
4Passes out of the box with-
4
16
format as:
• Fat 32
• Must have volume label
• Do not use quick format
out formatting
format as:
• Fat 32
• Must have volume label
• Do not use quick format
To access the USB port, rst remove the faceplate cover and set it aside. The USB
port is located on the right side of the touch-screen display driver board, and is ac-
cessed by removing the security screw and ipping up the display housing. A miniA MICRO USB Host Mode OTG cable (from T& S Electronics, P/N: OTG-SBK6
or from SonoXY, P/N: USB_MIC-OTG) is required to connect a standard USB 2.0
compliant thumb-drive to the SRCM USB port.
To make use of the cloning feature, rst setup one SRCM with a conguration that
represents most other SRCM units that will be used during installation. Congure
the “master” unit with all parameters needed, including alarm thresholds, condition
banners, blinking operations, I/O conguration and so on. Make sure the Save &
Exit function is used to properly save your conguration. This “master” setup will
then be downloaded to the thumb drive and for use uploading to other units.
As soon as the thumb drive is connected to the SRCM it will be recognized and
bring up a Drive Connected menu.
29
USB Conguration
Cloning
USB Port
• Select Conguration Write to transfer the master SRCM conguration from the
unit to the thumb drive.
• Select START to initiate the copy operation.
Remove the thumb drive and cable and move to the rst “slave” unit to be cong-
ured. With power applied to that unit, connect the thumb drive and cable. Select
Conguration Read and START to write the master conguration to the new slave
unit.
A Write Process Successful message will appear if the conguration has been
written to memory. Review the various Menu screens of the slave unit and sub-
sequent units to conrm the proper conguration is stored. In most cases the only
change that will be required to clone SRCM units is Primary and Secondary Room
labels that match the location of installation.
30
Updating Firmware
Note: Before updating rmware, perform USB Conguration Cloning. Refer
to USB Conguration Cloning on previous page.
The USB port can be used for upgrading the SRCM rmware in the eld.
To upgrade the rmware you must rst download the rmware for the latest versions of the hex le for the host controller, the USB hex le and the
BACnet hex le, these are EMS1009.hex, usb.hex and BACnet.hex. Place the
new les on the thumb drive. Plug in the USB adapter cable, shown on previous page, and the ash drive.
The SRCM will automatically detect the USB drive bringing up a window.
1. Press the Change button.
2. Scroll to the Upgrade Host Firmware screen shown here.
3. After the host rmware has been updated, change to the Upgrade
Communication Firmware screen and press START.
31
Network Setup
The BACnet setup screen is enabled by pushing position 1 switch (labeled
MAC) to the on (right) position. After conguration the switch must be
moved to the off (left) position.
Five position dip
switch location
The Network Setup screen gives the option for the user to congure the
Network and other parameters which have to be read from the network.
BACnet conguration requires the user to congure the following parameters.
1. Baud Rate - User can select any one of the 4 standard Baud rates for
RS485 communication from 9600, 19200, 38400 and 76800 by using the
change button. Auto baud features is not supported.
2. MAC Address - User can enter Medium Access Control address specic
to this device by touching on this eld. The MAC address must be unique
across the network. Valid MS/TP MAC addresses are 0-127 for master devices and 0-254 for slave devices.
3. Device Instance - The Device instance number must be unique within a
BACnet internetwork to identify each device. Instance numbers are dened
as 22 bit long, in decimal instance number ranges from 0 to 4,194,303.
FFFFNDD is the network addressing scheme, here FFFF represents the Facility code. N is the number of the network in the building and DD ranges
from 0 to 99 to represent the individual device on the network.
32
4. APDU Timeout - Indicates the amount of time in milliseconds between retransmissions of the APDU requiring acknowledgement for which no acknowledge-
ment has been received. The default value for this property will be 3,000 ms and
max can be 65535.
Save and Exit to save settings or cancel to cancel setting changes.
Once this is complete disable the BACnet setup by moving the dip switch position
1 to off (left ) position.
Five position dip switch
location
Press Save and Exit.
5. After the unit returns to the main menu screen, disconnect the power to the unit
and reconnect in order to boot up with the proper MAC address and Device In-
stance. The power can also be cycled by removing Jumper JP1 and then reconnecting.
Removing the jumper
causes power loss.
Re-insert the jumper to
restore power.
The unit can also be congured through the BACnet interface as well as through
the Touch Screen User Interface.
33
Event Log
The SRCM can be enabled with an audit trail of changes made to the congurations/
modes of the system by Supervisor and Operator. When the Supervisor / Operator
changes any conguration through the menu, the action is captured and stored in a
string covering the User prole Screen name where the parameter is changed. There
will be 5 such instances stored in non-volatile memory of the unit. Any power failure
in the unit will lose the data and it will be the responsibility of BMS system to log
these strings after polling from the SRCM unit through BACnet. The SRCM unit
will store these strings as different instances of Character String Object.
The value to which the parameter is changed will not be logged for parameters like
User Dened Condition Banner text, Room Label, Message Text, etc., which needs
more memory. Other parameters whose variables are enumerated, real and integer
will be logged until the value is changed.
The string length of each instance of conguration change will be 50 Bytes in the
data memory area of the controller.
34
French Language
Support on Default
Screen & Data Entry
Screen
The home screen can be setup to show French Language words
using the Setup Display Menu
The following screens show the difference between English and
French Home screens.
Default screen for
English version.
Default screen for
French version.
35
On the default screen the following changes will be made for the French version.
PRESSUREPRESSION
OPERATIONOPĖRATION
NEGATIVENĖGATIVE
NEUTRALNEUTRE
STANDBYATTENTE
DOORPORTE
WARNINGALERTE
ALARMALARME
TEMPERATURETĖMPERATURE
SILENCE, NORMAL, HUMIDITY, RESET do not change
When the language is selected as French in the setup display screen, French characters entry in the data
screen will be enabled. Whenever user presses N (same for all French characters like A, E, I, O, U, C) a
child screen will pop up which will contain all corresponding French characters. In this case child screen
will contain French characters corresponding to N. When user presses any of these characters, that character will be taken as input and the child screen will disappear. If user does not want to enter any character, child screen will disappear when user presses N in the main screen.
Data Entry Screen for French Version
36
French Version—Letter A
French Version—Letter E
37
French Version—Letter U
French Version—Letter Y
38
French Version—Letter I
French Version—Letter O
39
French Version—Letter C
French Version—Letter N
40
Troubleshooting
Error/Trouble ConditionPossible CauseSolution
Display shows: "Factory Calibration
has been lost. Return to Factory for
Calibration".
Display shows: "Setup information
has been lost. Loading Default Values
Please Wait...".
User cannot enter into menus because
of password protection.
SRCM does not come onlineTwo or more controllers have the
Non-recoverable EEPROM checksum error of factory calibration data,
ER01.
Recoverable EEPROM checksum error of unit setup conguration, ER02.
User has lost password.Use default password "351".
same MAC address.
The MS/TP network has too many
devices.
Too many devices were installed
without any repeaters.
The MS/TP cable runs are broken.Locate the break and correct the wir-
MS/TP connections at the module
were reversed.
The SRCM does not have power.Apply power to the SRCM.
Return unit to factory for calibration.
Unit will auto recover by rebooting
and then displaying message: "Setup
information has been lost, default
conguration loaded. User should
recongure." User should press OK/
Cancel (User Acknowledgement) so
that device enters into default screen.
Modify each duplicate address to a
unique number.
Do not exceed the maximum number
of devices and maximum length al-
lowed by the EIA-485 specications.
Repeaters need to be installed as
specied in this document.
ing.
Respect polarity of the wires on a
MS/TP network.
41
RETURNING PRODUCTS FOR REPAIR
When returning a product to Setra Systems, the material should be carefully packaged and shipped prepaid to:
Setra Systems, Inc.
159 Swanson Road
Boxborough, MA 01719-1304
Attn: Repair Department
To assure prompt handling, please refer to return instructions on our Web site at http://www.setra.com/tra/repairs/cal_rep.htm.
WARRANTY AND LIMITATION OF LIABILITY
SETRA warrants its products to be free from defects in materials and workmanship, subject to the following
terms and conditions: Without charge, SETRA will repair or replace products found to be defective in materials or workmanship within the warranty period; provided that:
a) the product has not been subjected to abuse, neglect, accident, incorrect wiring not our own, improper installation or servicing, or use in violation of instructions furnished by SETRA;
b) the product has not been repaired or altered by anyone except SETRA or its authorized service agencies;
c) the serial number or date code has not been removed, defaced, or otherwise changed; and
d) examination discloses, in the judgment of SETRA, the defect in materials or workmanship developed under
normal installation, use and service;
e) SETRA is notied in advance of and the product is returned to SETRA transportation prepaid.
Unless otherwise specied in a manual or warranty card, or agreed to in writing and signed by a SETRA ofcer, SETRA pressure, humidity, and acceleration products shall be warranted for one year from date of sale.
The foregoing warranty is in lieu of all warranties, express, implied or statutory, including but not limited to,
any implied warranty of merchantability for a particular purpose.
SETRA’s liability for breach of warranty is limited to repair or replacement, or if the goods cannot be repaired
or replaced, to a refund of the purchase price. In no instance shall SETRA be liable for incidental or consequential damages arising from a breach of warranty, or from the use or installation of its products. No representative or person is authorized to give any warranty other than as set out above or to assume for SETRA any
other liability in connection with the sale of its products.
For all CE technical questions, contact Setra Systems, USA. EU customers may contact our EU representative
Hengstler GmbH, Uhlandstr 49, 78554 Aldingen, Germany (Tel: +49-7424-890; Fax: +49-7424-89500).
SS-SRCM-OPER Rev E 4/15
42
159 Swanson Road, Boxborough, MA 01719-1304
Tel: 800-257-3872/978-263-1400
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.