Because of the very high efficiency of the Seton boiler the flue gas exhaust temperatures
can be low enough to cause condensation in the chimney. This condensation may, over
time, damage a masonry chimney. If you have condensation in your chimney, a insulated
stainless steel chimney liner should be installed inside the flue
SAFETY INSTRUCTIONS
Safety Notice: If this is not properly installed, a house/building fire may result. For your
safety, contact local building or fire officials about permits, restrictions, and installation
requirements for your area.
NEVER BLOCK DRAFT IN OPEN POSITION
NEVER OPERATE WITH THE FEED DOOR OPEN!!
THE SETON BOILER MUST BE INSTALLED IN A ENCLOSED, INSULATED ROOM.
IT SHOULD BE REMOTE FROM THE LIVING SPACE.
PLUMB BOTH RELIEF VALVES TO A SAFE LOCATION
PIPE MUST RUN DOWN HILL ITS FULL LENGTH. PLUMB TO AN OUTSIDE AREA., DO NOT
ALLOW THE PIPE TO EXTEND OUTSIDE FAR ENOUGH TO FREEZE. O NOT REDUCE THE PIPE SIZE.
DO NOT PUT THREADS ON THE OPEN END OF THE DRAIN PIPE
DO NOT JOIN THE TWO DRAINS TOGETHER
WARNING!! ATOMIZED POLYPROPYLENE GLYCOL AT
HIGH TEMPERATURES CAN CAUSE AN EXPLOSION!!
Do not open the feed door until the wood has burned down some.
Avoid trying to see how the fire is burning shortly after you fill it.
All wood burning appliances will smoke if you open the feed door
when it is full of wood.
Do not over-fire the boiler.
Over-firing will occur if the feed door is left open
or the draft is blocked open during operation.
Such actions can result in very dangerous operating conditions.
IF AFTER THREE DAYS OF FIRING THE CHIMNEY OR THE BOILER IS DRIPPING
CONDENSATE, THE CHIMNEY IS INADEQUATE.
The Seton Boiler is the worlds most efficient wood boiler, it has very low exhaust
temperatures. If the exhaust temperature drops below 300° before it exits the top
of the chimney it will restrict the draft necessary for a clean burn, this will cause
the pressure vessel to form creosote and will cause the boiler and the chimney to
make water that will corrode the boiler and the chimney.
•The Seton boiler does require a strong draft, which is provided by a proper chimney. The draft
must be measured by either temperature or a manometer. The manometer must read at least .06 on a 8
inch chimney while the draft is open and the boiler up to temperature. In the case no manometer is
available you can measure the exhaust temperature, it should read between 350° to 450° while the
draft is open and the boiler is up to temperature. This measurement must be done in the exhaust
stream not on the surface of the pipe.
•The Seton boilers are designed to work with at least 15 Ft. of eight inch insulated stainless steel
class A chimney, without a chimney cap . But you can use a “China Cap”
•If the chimney is too tall or the draft is too strong you will need to install a draft restrictor not a
barometric damper.
•Do not run the boiler with out connecting both relief valves to drain pipes, drains must run down
their full length and must not be exposed to freezing in such a way that they will fill with ice and
block the flow.
•The second aquastat must be wired into the dump zone, so that any boiler temperature above 200°
will lower the boiler water temperature.
•The boiler must be plumbed so that fill water is always available to it and that if the T&P relieves
water because of a high water temperature the cold fill water will flow up through the boiler to cool
it.
•The Seton Boiler is not designed to be installed inside the living area, it must be in an enclosed
structure.
•The Seton boiler must in installed in a heated space, if installed in a small shed it should be well
insulated. The small shed should not be more than 2,000 Cu. Ft. unless it is heated.
•The draft must close tightly and must open at least 60°, do not limit the draft air with the draft
motor.
•Provide combustion air for any room the boiler is installed in.
•The Seton Boiler does not smoke or smolder in the off cycle.
•The white exhaust during the off cycle in the first few cycles after filling the boiler is steam
caused by the high temperatures off the refractory chamber drying the charge.
•A blue tint to the smoke during the off cycle is a sign of a combustion air leak in the draft or door
The boiler must be plumbed so that if the draft motor sticks open for any reason the cold feed water
will flow up through the boiler pressure vessel and protect it from overheating.
The temperature and pressure relief valve must be mounted on top of the boiler before the check valve.
TEMPERATURE AND PRESSURE RELIEF VALVE OPENS AT 210°
AQUASTAT FOR PUMP CONTROL 110° OPEN ON RISE
AQUASTAT FOR DRAFT CONTROL 180° OPEN ON RISE
AQUASTAT FOR DUMP ZONE 200° CLOSE ON RISE
1” SWING CHECK VALVE
AUTO AIR VENT
TEMPERATURE AND PRESSURE GAUGE
WOOD BOILER
PLUMB BOTH RELIEF VALVES TO A SAFE LOCATION
PIPE MUST RUN DOWN HILL ITS FULL LENGTH
PLUMB TO AN OUTSIDE AREA., DO NOT
ALLOW THE PIPE TO EXTEND OUTSIDE FAR ENOUGH TO FREEZE.
DO NOT REDUCE THE PIPE SIZE.
DO NOT PUT THREADS ON THE OPEN END OF THE DRAIN PIPE
DO NOT JOIN THE TWO DRAINS TOGETHER
WARNING!! ATOMIZED POLYPROPYLENE GLYCOL AT
HIGH TEMPERATURES CAN CAUSE AN EXPLOSION!!
When the boiler is plumbed this way it is protected from over temperature.
When the T&P valve releases because of over temp the cold water will come up through the
Without the T&P in front of the check valve the feed water will reverse feed through the
boiler supply pipe and allow the boiler to be damaged.
ITEM PROPOSE
TEMP & PRESS GAUGE TEMPERATURE SHOULD BE 180, PRESSURE WILL GO FROM 12# COLD TO 25# HOT
FIRST AQUASTAT OPERATES THE DRAFT, SET AT 160° to 180°
SECOND AQUASTAT OVER TEMPERATURE PROTECTION, SET AT 200°
THIRD AQUASTAT TURNS UMP ON, SET AT 120°
FLOAT VENT REMOVES AIR, CAP MUST BE LOOSE
30# POP OFF PRESSURE RELIEVE VALVE
T@P VALVE OVER TEMPERATURE PROTECTION
SS HEAT EXCHANGER EXCHANGES HEAT FROM BOILER WATER TO HEATING WATER
12# FILL VALVE KEEPS BOILER FILLED WITH WATER, IF YOU PUT ANTIFREEZE IN THE BOILER
YOU MUST INSTALL A BACKFLOW PREVENTER HERE
EXPANSION TANK ALLOWS HOT WATER TO EXPAND 12# WITH NO PRESSURE ON SYSTEM
CIRCULATING PUMP CIRCULATES WATER THROUGH BOILER AND HEAT EXCHANGER
DRAIN VALVE FOR DRAINING WATER FROM BOILER
POWER CORD 11O VOLTS 100 WATTS
DRAFT MOTOR OPENS AND CLOSES DRAFT TO CONTROL WATER TEMPERATURE
ANTIFREEZE
ANTIFREEZE IS CORROSIVE AND WILL SHORTEN THE LIFE OF YOUR BOILER IF
NOT MAINTAINED
YOU SHOULD USE PROPYLENE GLYCOL,
YOU SHOULD USE A 35% ANTIFREEZE TO 65% WATER FORMULA
ANTIFREEZE WILL CUT DOWN ON THE HEAT TRANSFER OF BOTH THE BOILER,
HEAT EXCHANGER AND THE OUTPUT OF THE TUBING.
A 50% FORMULA WILL CUT THE HEATING OUTPUT OF YOUR SYSTEM BY UP TO
30%
PLUMB BOTH RELIEF VALVES TO A SAFE LOCATION
PIPE MUST RUN DOWN HILL ITS FULL LENGTH, PLUMB TO AN OUTSIDE AREA., DO NOT
ALLOW THE PIPE TO EXTEND OUTSIDE FAR ENOUGH TO FREEZE. DO NOT REDUCE THE PIPE SIZE.
DO NOT PUT THREADS ON THE OPEN END OF THE DRAIN PIPE
DO NOT JOIN THE TWO DRAINS TOGETHER
WARNING!! ATOMIZED POLYPROPYLENE GLYCOL AT
HIGH TEMPERATURES CAN CAUSE AN EXPLOSION!!
Do not open the feed door until the wood has burned down some.
Avoid trying to see how the fire is burning right after you fill it.
All wood burning appliances will smoke if you open the feed door when it is full of wood.
Your SETON solid fuel boiler is designed to provide supplemental or central heating for your home.
This solid fuel boiler may be installed in conjunction with a boiler that is in proper operating condition
and meets all national and/or local building codes, safety standards, required controls, and has been installed in accordance with appropriate standards of the National Fire Protection Association and in accordance with the clearances specified on the boiler nameplate.
Installation of the SETON boiler should be accomplished by a qualified heating contractor (one who is
engaged in and is responsible for, or is thoroughly familiar with the installation and operation of gas, oil,
and solid fuel burning heating appliances, who is experienced in such work and familiar with all the requirements of the authority having jurisdiction.) The installation shall be in strict accordance with the
manufacturer’s installation instructions furnished with the solid fuel boiler.
The chimney connector of the boiler is to be installed to provide clearances to combustible materials not
less than specified in the individual classifications and marked on the furnace. The chimney suitable for
use with residential type or building heating appliances which burn solid fuel.
The boiler is designed to operate in either a parallel arrangement with the central boiler or as a boiler by
itself.
CAUTION
BOILER UNITS ARE HEAVY!
THE B-90 WEIGHS 2,400 LBS.
THE B-130 WEIGHS 3,000 LBS.
THE B-180 WEIGHS 3,800 LBS.
MAKE SURE YOU HAVE PROPER EQUIPMENT OR SUFFICIENT
MANPOWER TO PREVENT INJURY WHEN DELIVERING AND LOCATING UNITS.
Assuming a 96% to 99% combustion efficiency, which is available with the combustion temperatures we
achieve as long as the chimney is drawing enough air into the draft. Our exhaust temperature indicates a
84% to 90% thermal transfer efficiency. The boiler actually operates as a condensing state during parts of
the charge cycle. The first cycle after charging is usually condensing because the exchanger tries to remove too much heat and combustion temperatures are not achieved with cold wood. After that each cycle
rapidly climbs to 1600+ degrees F. fire box temperature. The exhaust stays below 400 degrees unless the
draft is too strong. I recommend .05 inches water column or more for a draft. After the initial firing, with
each charge the fire reaches a steady state that is very efficient and very clean if the wood is not undersized. Large amounts of very small wood or lumber scraps will release too much gas for the amount of
available draft and will make an incomplete burn and will make creosote in the back of the boiler on the
boiler tubes.
Before starting the installation of a new boiler and heating system it is beneficial to become informed
about the boiler so that the proper unit is selected to properly supply your heating needs. Learning
about boiler location, positioning and set-up before beginning installation will lead to a better, more
efficient installation.
1. The installation of this boiler must comply with your local building code rulings. Do observe the
clearances to combustibles.
2. Do not install this boiler in a mobile home or trailer. Install the boiler outside and pipe the hot water
into the home.
3. Always connect this boiler to a chimney and vent to the outside. NEVER vent to another room or inside
a building.
4. DO NOT CONNECT to an aluminum Type B gas vent. This is not safe. Use approved masonry or a
UL 103 HT Listed Residential Type and Building Heating Appliance Chimney. Use an 8” diameter chimney
that is high enough to provide required draft. DO NOT USE A CHIMNEY CAP. You can use a (China Cap)
5. Be sure that your chimney is safely constructed and in good repair. Have the chimney inspected by
the fire department or a qualified inspector.
6. Inspect flue pipes, pipe joints, and flue pipe seals regularly to ensure that smoke and flue gasses are
not drawn into and circulated by the air circulation system.
7. Cleanout of heat exchanger, flue pipe, chimney, and draft inducer (if used) is especially important at
the end of the heating season. Accumulated ash may cause corrosion during the summer months.
8. Creosote or soot may build up in the chimney connector and chimney and cause a house/building fire.
Inspect the chimney connector and chimney once monthly during the heating season and clean if necessary.
9. To prevent injury, do not allow anyone to use this boiler who is unfamiliar with the correct operation
of the boiler.
10. Do not operate boiler while under the influence of drugs or alcohol.
11. For further information on using your furnace safely, obtain a copy of the National Fire Protection
Association (NFPA) publication, “Using Coal and Wood Furnaces Safely” NFPA No,. HS-10-1978. The address of the NFPA is: Battery March Park, Quincy, MA 02269.
12. Ashes should not be allowed to accumulate higher than the draft holes. Dispose of ashes in a metal
container with a tight-fitting lid. Keep the closed container on a noncombustible floor or on the ground, well
away from all combustible materials. Keep the ashes in the closed container until all cinders have thoroughly
cooled. The ashes may be buried in the ground or picked up by a refuse collector.
13. Paint discoloration will occur if boiler is over-fired.
14. This boiler has a painted surface which is durable but it will not stand rough handling or abuse.
When installing your boiler, use care in handling. Clean with soap and water when boiler is not hot.
15. While boiler is in operation, all persons, especially young children should be alerted to the hazards
from high surface temperatures and should be kept away to avoid burns or clothing ignition. Small children
should be carefully supervised when they are in the same room with the boiler.
16. Keep boiler area clear and free from all combustible materials, gasoline, and other flammable vapors
and liquids.
17. To prevent burns, always wear protective clothing, leather hearth gloves and eye protection, while
tending the fire.
18. While in operation, keep the feed door, ash door, and cabinet door closed and secured at all times except while tending the fire.
CAUTION: Keep furnishings and other combustible materials away from the boiler.
NOTE: Installation should be made by a qualified heating equipment installer (one who is engaged in
and is responsible for, or is thoroughly familiar with the installation and operation of gas, oil, and solid fuel burning heating appliances, who is experienced in such work and familiar with all the building requirements and/or fire
codes of the authority having local jurisdiction.)
1. The installation is to be completed in accordance with National Fire Protection Association NFPA) installation
standards No. 89M, 90B, 211, 70 (National Electrical Code) and Uniform Mechanical Code 913, 6-4 in states
where applicable (where code offers making flue pipe connections into an existing chimney with other fuel
burning appliances).
2. Wood-burning appliances need air for combustion and circulation to the house. Provision must be made to provide make-up air so as not to starve the central heating system of combustion air. Have the local regulating
authority determine that make-up air supply is adequate. Reference NFPA standards No. 30 & 54, Code for
Installation of Gas and Oil Equipment.
3. Position the boiler according to clearances (see page 4)
4. Make flue pipe connections to the chimney with 24-gauge pipe and elbows (not included with boiler) maintaining proper clearances. Seal the flue pipe in the chimney with furnace cement.
Chimney connections must be securely supported and joints fastened with sheet metal screws
or rivets.
5. Make electrical supply connections in the electrical junction box and connect power supply wires to des-
ignated wires using wire nuts (see wiring diagram page 19 & 21) The power cord supplied may be used for installation if local codes and regulations permit. If not permitted, power supply wiring must be minimum of 18-ga.
AWG copper and rated for 90 deg. Centigrade installed in a metal cable or conduit. Power connections should be
made by a qualified installer to comply with NFPA Standard No. 70 and all local codes and regulations.
ANTIFREEZE,
Do no install antifreeze in the boiler for a few weeks, in case of boiler problems that would
blow the antifreeze out. Also it is best to drain the boiler at least three times with hot water in
it to remove any residual oil or impurities in it.
PRESSURE RELIEF VALVE (POP-OFF),
The relief valve must be exercised at least once a year, to prevent chemical buildup in the
valve that will prevent it from operating properly. Replace the relieve valve immediately if it
starts to leak or drip. Never block relieve valves. Relieve valves should have an air gap so
you can see if they are leaking. Drain lines must slope down so they do not collect water and
to prevent freezing.
The boiler must be placed on noncombustible floor solid concrete or masonry floor is preferable.
Observe the clearances to combustible materials.
The boiler must have its own flue. Do not Connect this unit to a chimney flue serving other appli-
ances.
Install exhaust pipe, elbows, and thimble as required, utilizing either a recently cleaned and inspected 8”
masonry chimney or an 8” I.D. class - A listed chimney.
THE ONLY APPROVED CHIMNEY CAP IS THE CHINA HAT TYPE OF CHIMNEY CAP.
Use 8” round stove pipe. Secure each pipe section and/or elbow joint with three (3) sheet metal screws
per joint to firmly hold the sections together.
Re-check clearances from the boiler, connector stove pipe, and corner clearances using the illustrations in
your local building codes or fire protection ordinances.
DO NOT install this boiler in a mobile home or trailer.
The clearances provided are minimum dimensions determined by the manufacturer’s testing facility. In-
stallation of this boiler must comply with the latest edition of NFPA 211 for reduced clearances and/or
your local building code rulings (use whichever minimum dimensions are LARGEST).
CHIMNEY DRAFT: The Seton Boiler is designed to burn wood without creating creosote; you can get a
dirty burn by not having enough draft. This is normally caused by a poor chimney or burning small pieces of
wood which releases more gas than the draft can produce oxygen for.
Do not expect the boiler to draw. Draft is a function of the chimney, not the boiler. Smoke spillage into the house or excessive
buildup of condensation or soot in the chimney are warnings that the chimney is NOT functioning properly. Correct the problem before using the boiler. Following are some possible causes for improper draft.
1. Do not push the connector stove pipe into the chimney too far; it will plug the chimney and stop the draft. DO NOT USE
A CHIMNEY CAP.
2. If the chimney is operating too cool, water will condense in the chimney and run back into the boiler. Soot formation will
be rapid and may block the chimney. Operate the boiler at a high enough fire level to keep the chimney warm, preventing this
condensation. Water temperature control should be set at 180°.
3. If the fire burns well but sometimes smokes or burns slowly, it may be caused by the chimney top being lower than an-
other part of the house or a nearby tree. The wind blowing over a house or tree, falls on top of the chimney like water over a
dam, beating down the smoke. The top of the chimney should be at least three (3) feet above the roof and be at least two (2) feet
higher than any point of the roof within ten (10) feet.
NOTE: A draft reading of 0.06 to 0.07 W.C. (Water Column) is required for proper burning of this boiler.
NOTE: Any chimney that has been used before should be inspected by a qualified person be-
fore this boiler is connected to it
CREOSOTE - Formation and Removal
When wood is burned slowly, it produces tar and other organic vapors which combine with expelled moisture to form creosote. The creosote vapors condense in the relatively cool chimney flue of a slow-burning fire. As a result, creosote residue
accumulates on the flue lining. If ignited, this creosote creates an extremely hot fire which may ignite surrounding materials
resulting in a building fire.
The chimney connector and chimney should be inspected at least once a month during the heating season to determine if a
creosote buildup has occurred.
If creosote has accumulated, it should be removed. Failure to remove creosote may result in ignition and may cause a house/
building fire. Creosote may be removed using a chimney brush or other commonly available materials from your local hardware retailer.
Chimney fires burn very hot. If the chimney connector should glow red, immediately call the fire department, then reduce
the fire by closing the inlet air control and pour a large quantity of coarse salt, baking soda, or cool ashes on top of the fire in
the firebox.
CAUTION: A chimney fire may cause ignition of wall studs or rafters which were
assumed to be a safe distance from the chimney.
If a chimney fire has occurred, have your chimney inspected by a qualified person before using again.
Draft is a function of the chimney flue, not the furnace. The natural draft generated through a chimney is
dependent on several factors including chimney height, temperature of flue gases, cross-sectional area of the
chimney, chimney wall insulation value, dilution air, and total volume of flue gases.
To operate properly, the Seton Boiler requires a draft of .06" to .07" wc (water column). Symptoms of an improperly designed or installed flue include visible smoke out the chimney, smoke escaping into the room,
creosote buildup in the flue, and/or poor heating performance.
The following procedure describes how to measure draft using a manometer-a device that measure draft:
1. Close all windows and doors in the building and turn on all appliances that remove air from the home (e.
g., heat pump, air conditioner, exhaust fan, clothes dryer, fireplaces, etc.).
2. Drill a hole in the connector pipe (just large enough for the tube of the manometer) at least 1 foot above
the furnace outlet collar.
3. After all chimney connections, plumbing and wiring is complete, build a fire and allow the furnace to settle into stable operation. If the boiler has been installed in conjunction with a Type A flue pipe, take the draft
reading after 1 hour. For all chimneys other than Type A flue pipe, take the draft reading after 2 hours.
4. Using the manometer, measure the draft in the flue.
a. If the draft measurement is below .06" wc (12.45 Pa), there is too little draft and a draft inducer or other
corrective measures are required to avoid air-starvation of the boiler. A draft inducer fan can be mounted in
the chimney.
This chimney has three 90 degree bends plus two 45 degree bends, a total of 360
degrees, plus a 2 inch reduction all in single wall pipe. This will not draw properly, it
will need a draft inducer.
THE BEST CHIMNEY IS THE INSULATED STAINLESS STEEL TYPE
SUCH AS “METALBESTOS HT”
OR OTHER CHIMNEY SYSTEM APPROVED FOR WOOD BURNING STOVES.
IN ALL CASES THE CHIMNEY MANUFACTURER’S INSTRUCTIONS MUST BE FOLLOWED.
Chimneys perform two functions.
1. As a means of exhausting smoke and flue gasses which are the result of fuel combustion.
2. The chimney provides “draft” which allows oxygen to be continuously introduced into the appliance, so that proper combustion is possible.
As of April 1, l987 all stoves should be installed using a factory built chimney that meets the “Type HT”
requirement of UL 103 (when using a factory built chimney).
Note: your boiler does not create draft. Draft is a function of the chimney. A minimum of 0.06 w.c,
(measured in water column) is required for proper drafting to prevent back-puffing, smoke spillage, and
to maximize performance. (Gauges to measure chimney draft are readily available at furnace shops and
are economical to purchase or rent.)
IMPORTANT INSTALLATION POINTS
1. Size the chimney flue to the furnace pipe. ( 8” outlet pipe = 8” chimney flue).
2. Use elbows only as necessary. Elbows reduce draft, no more than two should be used in any
chimney.
3. Make sure all horizontal runs of connector pipe have a minimum outward rise of 1/4” per horizontal foot. This allows any condensation or creosote buildup to run back into the firebox.
Masonry Chimneys will not always work
with the Seton boiler
Before using an existing masonry chimney, clean the
chimney, inspect the flue liner and make any repairs
needed to be sure it is safe to use. Make repairs before
attaching the boiler.
If the connector stove pipe must go through a combustible wall before entering the masonry chimney, consult a
qualified mason or chimney dealer. The installation
must conform to local building and fire codes and latest
edition of NFPA 211.
Do not connect this boiler into the same chimney flue as
the fireplace, gas appliance, or a flue connected with
any other furnace or boiler.
THE SETON BOILER WILL NOT ALWAYS WORK ON A MASONRY CHIMNEY.
The chimney used for the boiler must not be used to ventilate the cellar or basement. If there is a cleanout opening in
the base of the chimney, close it tightly.
Listed chimney
Carefully follow chimney manufacturer’s instructions. Use only a listed chimney. If your chimney starts at the ceiling,
you will need enough 8” round black stove pipe to reach the ceiling. The top of the chimney must be at least three (3)
feet above the roof and be at least two (2) feet higher than any point of the roof within ten (10) feet.
If you have any questions regarding venting your boiler, contact the manufacturer or contact the National Fire Protection
Association (NFPA) and request a copy of the latest editions of NFPA Standard 211 and NFPA Standard 908. Their address is:
Battery March Park, Quincy, MA 02269
Because of the very high efficiency of the Seton boiler the
flue gas exhaust temperatures can be low enough to
cause condensation in the chimney. This condensation
may, over time, damage a masonry chimney. If you have
condensation in your chimney, a stainless steel chimney
liner must be installed inside the flue
Chimney caps will drip creosote on the ground and roof.
The chimney used for the boiler must not be used to ventilate the cellar or basement. If there is a
cleanout opening in the base of the chimney, close it tightly.
Listed chimney
Carefully follow chimney manufacturer’s instructions. Use only a listed chimney. If your chimney
starts at the ceiling, you will need enough 8” round black stove pipe to reach the ceiling. The top of
the chimney must be at least three (3) feet above the roof and be at least two (2) feet higher than any
point of the roof within ten (10) feet.
If you have any questions regarding venting your boiler, contact the manufacturer or contact the National Fire Protection Association (NFPA) and request a copy of the latest editions of NFPA Standard 211 and NFPA Standard 908. Their address is: Battery March Park, Quincy, MA 02269
This is the best method to install a chimney on the Seton Boiler.