Server Technology C-8HFE-P323, C-16HF2-L30, C-16HFE-P32, C-16HFE-C20, C-8HFE-C203 User Manual

...
Page 1
Rack-Mount Fail-Safe Transfer Switch
C-8HFx
• C-16HFx
Installation and Operations Manual
© 2006-2007 Server Technology, Inc. All rights reserved.
Page 2
Instructions This symbol is intended to alert the user to the presence of important operating and maintenance (servicing) instructions in the literature accompanying the appliance.
Dangerous Voltage
This symbol is intended to alert the user to the presence of un-insulated dangerous voltage within the product’s enclosure that may be of sufficient magnitude to constitute a risk of electric shock to persons.
Protective Grounding Terminal This symbol indicates a terminal that must be connected to earth ground prior to making any other connections to the equipment.
Life-Support Policy
As a general policy, Server Technology does not recommend the use of any of its products in the following situations:
life-support applications where failure or malfunction of the Server Technology product can be reasonably expected to cause failure of the life-support device or to significantly affect its safety or effectiveness.
direct patient care.
Server Technology will not knowingly sell its products for use in such applications unless it receives in writing assurances satisfactory to Server Technology that:
the risks of injury or damage have been minimized,
the customer assumes all such risks, and
the liability of Server Technology is adequately protected under the circumstances.
The term life-support device includes but is not limited to neonatal oxygen analyzers, nerve stimulators (whether used for anesthesia, pain relief or other purposes), auto-transfusion devices, blood pumps, defibrillators, arrhythmia detectors and alarms, pacemakers, hemodialysis systems, peritoneal dialysis systems, neonatal ventilator incubators, ventilators (for adults or infants), anesthesia ventilators, infusion pumps, and any other devices designated as “critical” by the U.S. FDA.
Notices
301-0128-1 Rev. B (081007) Copyright © 2006-2007 Server Technology, Inc. All rights reserved. 1040 Sandhill Drive Reno, Nevada 89521 USA
All Rights Reserved
This publication is protected by copyright and all rights are reserved. No part of it may be reproduced or transmitted by any means or in any form, without prior consent in writing from Server Technology.
Patents Pending. The information in this document has been carefully checked and is believed to be accurate. However, changes are made
periodically. These changes are incorporated in newer publication editions. Server Technology may improve and/or change products described in this publication at any time. Due to continuing system improvements, Server Technology is not responsible for inaccurate information which may appear in this manual. For the latest product updates, consult the Server Technology web site at
www.servertech.com. In no event will Server Technology be liable for direct, indirect, special, exemplary, incidental or consequential
damages resulting from any defect or omission in this document, even if advised of the possibility of such damages. In the interest of continued product development, Server Technology reserves the right to make improvements in this document and
the products it describes at any time, without notices or obligation. Sentry and Rack-Mount Fail-Safe Transfer Switch are trademarks of Server Technology, Inc.
Other trademarks and trade names may be used in this document to refer to either the entities claiming the marks and names or their products. Server Technology, Inc. disclaims any proprietary interest in trademarks and trade names other than its own.
Please Recycle Shipping materials are recyclable. Please save them for later use, or dispose of them appropriately.
Page 3
Table of Contents
CHAPTER 1: INTRODUCTION 4
Quick Start Guide.............................................................................................................................4
Technical Support ............................................................................................................................4
Equipment Overview........................................................................................................................5
CHAPTER 2: INSTALLATION 6
Standard Accessories........................................................................................................................6
Additional Required Items ...............................................................................................................6
Safety Precautions............................................................................................................................6
Installing the Power Input Retention Bracket...................................................................................7
Mounting ..........................................................................................................................................7
Optimizing the Transfer Thresholds.................................................................................................7
Connecting to the Power Source ......................................................................................................7
Connecting Devices..........................................................................................................................7
CHAPTER 3: OPERATIONS 8
Modes of Operation..........................................................................................................................8
CHAPTER 4: APPENDICES 9
Appendix A: Technical Specifications.............................................................................................9
Appendix B: Warranty, Product Registration and Support ............................................................11
Page 4

Chapter 1: Introduction

Quick Start Guide

The following instructions will help you quickly install and configure your Rack-Mount Fail-Safe Transfer Switch for use on your network. For detailed information on each step, go to the page number listed to the right.
1. Mount the Rack-Mount Fail-Safe Transfer Switch ....................................................................
2. Optimize the transfer thresholds.................................................................................................
3. Connect to the power sources.....................................................................................................
4. Connect the devices to the Fail-Safe Transfer Switch................................................................

Technical Support

Experience Server Technology's FREE SMARTER Technical Support - Learn more...
Server Technology understands that there are often questions when installing and/or using a new product. Free Technical Support is provided from 6:00 AM to 7:00 PM, Monday-Friday, Pacific Time.
Server Technology, Inc. 1040 Sandhill Drive Tel: 775.284.2000 Web: www.servertech.com Reno, Nevada 89521 USA Fax: 775.284.2065 Email: support@servertech.com
7
7
7
7
4 Introduction Rack-Mount Fail-safe Transfer Switch
Installation and Operations Manual
Page 5

Equipment Overview

1. The Voltage Selector switch configures the Rack-Mount Fail-Safe Transfer Switch for the installed
operational voltage.
NOTE: This configures the brownout/over-voltage switching points.
2. The power inlets connect the Rack-Mount Fail-Safe Transfer Switch to the electrical power
sources.
3. LEDs display the input feeds power status.
1
2
3
Figure 1. Sentry Rack-Mount Fail-Safe Transfer Switch Views
Rack-Mount Fail-safe Transfer Switch Introduction 5
Installation and Operations Manual
Page 6

Chapter 2: Installation

Before installing your Rack-Mount Fail-Safe Transfer Switch, refer to the following lists to ensure that you have all the items shipped with the unit as well as all other items required for proper installation.

Standard Accessories

Mounting hardware: Two removable flanges with M4 screws.
Outlet retention clips (208-240V models).
Additional items for Cx-xxx-C20 models:
Separate power input cords.
Power input retention bracket hardware (may be installed):
Four removable T-brackets with four 40mm screws.

Additional Required Items

Flathead and Phillips screwdrivers
Screws, washers and nuts to attach the CDU to your rack

Safety Precautions

This section contains important safety and regulatory information that should be reviewed before installing and using the Sentry Rack-Mount Fail-Safe Transfer Switch. For input and output current ratings, see
Only for installation and use in a Service Access Location in accordance with the following installation and use instructions.
This equipment is designed to be installed on a dedicated circuit.
Dedicated circuit must have circuit breaker or fuse protection. CDUs have been designed without a master circuit breaker or fuse to avoid becoming a single point of failure. It is the customer’s responsibility to provide adequate protection for the dedicated power circuit. Protection of capacity equal to the current rating of the CDU must be provided and must meet all applicable codes and regulations. In North American, protection must have a 10,000A interrupt capacity.
The plug on the power supply cord shall be installed near the equipment and shall be easily accessible.
Always disconnect the power supply cords before opening to avoid electrical shock.
WARNING! High leakage current! Earth connection is essential before connecting supply!
WARNING! Cx-xxE-x units Double Pole/Neutral Fusing
Power Ratings in Appendix A: Technical Specifications.
Destiné à l'installation et l'utilisation dans le cadre de Service Access Location selon les instructions d'installation et d'utilisation.
Cet équipement est conçu à être installé sur un circuit spécialisé.
Le circuit spécialisé doit avoir un disjoncteur ou une protection de fusible. CDUs ont été conçus sans disjoncteur général ni fusible pour éviter que cela devient un seul endroit de panne. C’est la responsabilité du client de fournir une protection adéquate pour le circuit-alimentation spécialisé. Protection de capacité équivalant à la puissance de l'équipement, et respectant tous les codes et normes applicables. Les disjoncteurs ou fusibles destinés à l'installation en Amérique du Nord doivent avoir une capacité d'interruption de 10.000 A.
La prise sur le cordon d’alimentation sera installée près de l’équipement et sera facilement disponible.
Toujours déconnecter le cordon d’alimentation avant d’ouvrir pour éviter un choque électrique.
ATTENTION ! Haut fuite très possible ! Une connection de masse est essentielle avant de connecter l’alimentation !
ATTENTION! Les unités Cx-xxE-x Double Pôle/Fusible sur le Neutre
Nur für Installation und Gebrauch an Anschlusszugriffspunkten gemäß der folgenden Installations- und Gebrauchsanweisungen.
Diese Ausrüstung ist zur Installation in einem festen Stromkreis vorgesehen.
Der feste Stromkreis muss mit einem Schutzschalter oder einem Sicherungsschutz versehen sein. CDUs verfügt über keinen Hauptschutzschalter bzw. über keine Sicherung, damit kein einzelner Fehlerpunkt entstehen kann. Der Kunde ist dafür verantwortlich, den Stromkreis sachgemäß zu schützen. Der Kapazitätsschutz entspricht der aktuellen Stromstärke der Geräte und muss alle relevanten Codes und Bestimmungen erfüllen. Für Installation in Nordamerika müssen Ausschalter bzw. Sicherung über 10.000 A Unterbrechungskapazität verfügen.
Der Stecker des Netzkabels muss in der Nähe der Ausrüstung installiert werden und leicht zugänglich sein.
Ziehen Sie vor dem Öffnen immer das Netzkabel heraus, um die Gefahr eines elektrischen Schlags zu vermeiden.
ACHTUNG! Hoher Ableitstrom! Ein Erdungsanschluss ist vor dem Einschalten der Stromzufuhr erforderlich!
ACHTUNG!: Cx-xxE-x Zweipolige bzw. Neutralleiter-Sicherung
6 Installation Rack-Mount Fail-safe Transfer Switch
Installation and Operations Manual
Page 7

Installing the Power Input Retention Bracket

For units with a total maximum output <30A, it may be necessary to install the power input retention bracket prior to mounting the unit within the rack.

To install the power input retention bracket:

1. Remove the two screws attaching the IEC 60320 C19 inlet
to the enclosure.
2. Assemble and attach the retention bracket to the enclosure
as shown.

Mounting

1. Select the appropriate bracket mounting points for
proper mounting depth within the rack.
2. Attach the brackets to these mounting points with two
screws for each bracket.
3. Install the enclosure into your rack, using the slots in
each bracket. The slots allow about ¼ inch of horizontal adaptability to align with the mounting holes of your rack.
NOTE: A mounting bracket kit for 23” wide racks or cabinets is available. Contact your Server Technology Sales Representative for more information.
Figure 2.1 Retention Bracket assembly
Figure 2. Mounting

Optimizing the Transfer Thresholds

The Voltage Selector switch is used to optimize the transfer threshold by configuring the Transfer Switch for the nominal operational voltage of the installation. The Transfer Switch uses this setting to
calculate the brownout and over-voltage threshold (± 13% ).
To optimize the transfer threshold:
Select the voltage setting that most closely matches the nominal operating voltage of the power sources.

Connecting to the Power Source

To attach a power cord to the unit:
1. Plug the female end of the power cord firmly into its connector at the base.
2. Use a screwdriver to tighten the two screws on the retention bracket.
To connect to the power source:
Plug the male end of the power cord into the AC power source.

Connecting Devices

1. Keep the device’s on/off switch in the off position until after it is plugged into the outlet.
2. Connect devices to the CDU outlets.
NOTE: Server Technology recommends even distribution of attached devices across all available outlets to avoid exceeding the outlet, branch or phase limitations. See Power Ratings on page 9 for more information.
Always disconnect ALL power supply cords before opening to avoid electrical shock. Afin d’éviter les chocs électriques, débranchez TOUTES les cables électrique avant d’ouvrir. Immer ALLE Netzleitungen auskuppeln vor den Aufmachen um elektrischen Schlag zu vermeiden.
Rack-Mount Fail-safe Transfer Switch Installation 7
Installation and Operations Manual
Page 8

Chapter 3: Operations

Modes of Operation

The Sentry Rack-Mount Fail-Safe Transfer Switch is designed to operate in the following modes:
Normal
Infeed A provides power to branches A1 & A2 and Infeed B provides power to branches B1 & B2. Each infeed is monitored individually for voltage and current.
Input Failure
The equipment powered by the failed input is transferred to the remaining input. The input current LED display of the failed input will be blank and the remaining display will report the total current load for the unit.
Recovery from Input Failure
When voltage is restored to the failed input and remains within ±7% of nominal for 2 seconds, the
equipment normally supported by that input is transferred back returning the Sentry to a ‘Normal’ mode with the input current LED displays reporting the total current load for each respective infeed.
Brownout/Over-Voltage
When an input’s voltage varies from its nominal by ±13% or more, the equipment powered by that
input is transferred to the remaining input. The input current LED display of the input in the brownout/over-voltage state will be blank and the remaining display will report the total current load for the unit.
Nominal Voltage* Brownout Recovery Voltage Over-Voltage
100V 87.0V 93.0V 107.0V 113.0V 110V 95.7V 102.3V 117.7V 124.3V 115V 100.0V 106.9V 123.0V 129.9V 120V 104.4V 111.6V 128.4V 135.6V 208V 181.0V 193.4V 222.6V 235.0V 220V 191.4V 204.6V 235.4V 248.6V 230V 200.1V 213.9V 246.1V 259.9V 240V 208.8V 223.2V 256.8V 271.2V
*
Nominal operating voltage is configured by the Voltage Selector Switch.
Recovery from Brownout/Over-Voltage
When the input’s voltage returns to and remains within ±7% of nominal for 2 seconds, the
equipment normally supported by that input is transferred back returning the Sentry to a ‘Normal’ mode input current LED displays reporting the total current load for each respective infeed.
Critical Brownout
A critical brownout is when an input’s voltage drops below its nominal by -25%.
When an input is already in a brownout/over-voltage state AND the remaining input
experiences a critical brownout, ALL equipment will be transferred to the input only experiencing a brownout/over-voltage.
When an input has already failed AND the remaining input experiences a critical
brownout, ALL outlets will turn off.
Recovery from Critical Brownout
When the input’s voltage returns to and remains within ±7% of nominal for 2 seconds, the
equipment normally supported by that input is transferred back.
8 Operations Rack-Mount Fail-safe Transfer Switch
Installation and Operations Manual
Page 9

Chapter 4: Appendices

V
V
A
A
A
A
A
A
A
A

Appendix A: Technical Specifications

Domestic Models

Model Rated Voltage Input Cordset and Plug (10’) Outlets
C-8HF2-C203 208-240V, 50/60Hz IEC 60320 C201 8 IEC 60320/C19 C-8HF2-L303 208-240V, 50/60Hz 2 x NEMA L6-30P, 30A/208V Locking 8 IEC 60320/C19 C-16HF1-C20 100-120V, 50/60Hz IEC 60320 C201 16 NEMA 5-20R C-16HF1-L30 100-120V, 50/60Hz 2 x NEMA L5-30P, 30A/120V Locking 16 NEMA 5-20R C-16HF2-C20 208-240V, 50/60Hz IEC 60320 C201 16 IEC 60320/C13 C-16HF2-L30 208-240V, 50/60Hz 2 x NEMA L6-30P, 30A/208V Locking 16 IEC 60320/C13

International Models

Model Rated Voltage Input Cordset and Plug (10’) Outlets
C-8HFE-C203 230V, 50/60Hz IEC 60320 C201 8 IEC 60320/C19 C-8HFE-P323 230V, 50/60Hz 2 x IEC 60309, 32A 3-pin 6Hr Blue 8 IEC 60320/C19 C-16HFE-C20 230V, 50/60Hz IEC 60320 C201 16 IEC 60320/C13 C-16HFE-P32 230V, 50/60Hz 2 x IEC 60309, 32A 3-pin 6Hr Blue 16 IEC 60320/C13
1
Input cordset selected at time of purchase

Power Ratings

Input Current Ratings
L’indice du courant d’entrée L’indice du courant de sortie
Eingangsstromstärke Ausgangsstromstärke
Model
Modele Tension Courrant Tension Prise
Modell Spannung Strom Spannung Anschlussstelle Zweigstromkreis Insgesamt
C-16HF1-C20
C-16HF1-L30
C-8HF2-C203
C-8HF2-L303
C-16HF2-C20
C-16HF2-L30
C-8HFE-C203
C-8HFE-P323
C-16HFE-C20
C-16HFE-P32
1
All current ratings are in amperes. Tous les indices de courant sont en ampères. Alle Angaben der Stromstärke erfolgen in Ampere.
oltage Current
100-120V
50/60Hz
100-120V
50/60Hz
208-240V
50/60Hz
208-240V
50/60Hz
208-240V
50/60Hz
208-240V
50/60Hz
230V
50/60Hz
230V
50/60Hz
230V
50/60Hz
230V
50/60Hz
: 16 B: 16 A: 24 B: 24
: 16 B: 16
: 24 B: 24
: 16 B: 16
: 24 B: 24
: 16 B: 16
: 32 B: 32
: 16 B: 16 A: 32 B: 32
1
oltage Outlet Branch Circuit Phase Total
100-120V
50/60Hz
100-120V
50/60Hz
208-240V
60Hz
208-240V
60Hz
208-240V
60Hz
208-240V
60Hz
230V
50/60Hz
230V
50/60Hz
230V
50/60Hz
230V
50/60Hz
Output Current Ratings
Circuit de la Branche
16 16 16
16 16 24
16 16 16
16 16 24
12 16 16
12 16 24
16 16 16
16 20 32
10 16 16
10 20 32

Physical Specifications

Operating Storage Temperature 32° to 104° F (0° to 40° C) -40° to 185° F (-40° to 85° C)
Elevation(above MSL) 0 to 10,000 ft (0 to 3000m) 0 to 50,000 ft (0 to 15000m) Relative Humidity 10 to 90%, non-condensing 10 to 90%, non-condensing Dimensions (H x W x D) Weight
C-xHF 3.5 x 17.0 x 14.0 in. (90 x 437 x 356 mm) 20.7 lbs (9.4 kg)

Transfer Rate

Power transfer 18 milliseconds.
Total
Rack-Mount Fail-safe Transfer Switch Appendices 9
Installation and Operations Manual
Page 10

Regulatory Compliance

Product Safety
Units have been safety tested and certified to the following standards:
USA/Canada UL 60950:2003 and CAN/CSA 22.2 No. 60950-1-03
European Union EN60950-1:2001
This product is also designed for Norwegian IT power system with phase-to phase voltage 230V.
USA Notification
Note: This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at the user’s own expense.
Modifications not expressly approved by the manufacturer could void the user's authority to operated
the equipment under FCC rules.
Canadian Notification
This Class A digital apparatus complies meets all requirements of the Canadian Interference-Causing Equipment Regulations.
Cet appareil numérique de la classe A respecte toutes les exigencies du Règlement sur le matériel
brouilleur du Canada.
European Union Notification
Products with the CE Marking comply with both the EMC Directive (89/336/EEC) and the Low Voltage Directive (73/23/EEC) issued by the Commission of the European Community.
Compliance with these directives implies conformity to the following European Norms:
EN55022 Electromagnetic Interference
EN55024 Electromagnetic Immunity
EN60950-1 Product Safety
EN61000-3 Harmonics and Flicker
Products with the following mark comply with the RoHS Directive (2002/95/EC) issued by the Commission of the European Community.
Japanese Notification
この装置は、情報処理装置等電波障害自主規制協議会(VCCI)の基準に基づくクラ スA情報技術装置です。この装置を家庭環境で使用すると電波妨害を引き起こすことが あります。この場合には使用者が適切な対策を講ずるよう要求されることがあります。

Recycling

Server Technology Inc. encourages the recycling of its products. Disposal facilities, environmental conditions and regulations vary across local, state and country jurisdictions, so Server Technology encourages consultation with qualified professional and applicable regulations and authorities within your region to ensure proper disposal.
Waste Electrical and Electronic Equipment (WEEE)
In the European Union, this label indicates that this product should not be disposed of with household waste. It should be deposited at an appropriate facility to enable recovery and recycling.
For information on how to recycle this product responsibly in your country, please visit:
www.servertech.com/support/recycling.
10 Appendices Rack-Mount Fail-safe Transfer Switch
Installation and Operations Manual
Page 11

Appendix B: Warranty, Product Registration and Support

Warranty

For Server Technology Warranty information, please see our website.

Product Registration

Registration is your key to special offers and services reserved for Registered Users.
Excellent Technical Support Services
Special Update and Upgrade Programs
Warranty Protection
Extended Warranty Service
New Product Information
Register your products online today!

Technical Support

Experience Server Technology's FREE SMARTER Technical Support - Learn more...
Server Technology understands that there are often questions when installing and/or using a new product. Free Technical Support is provided from 6:00 AM to 7:00 PM, Monday-Friday, Pacific Time.
Server Technology, Inc. 1040 Sandhill Drive Tel: 775.284.2000 Web: www.servertech.com Reno, Nevada 89521 USA Fax: 775.284.2065 Email: support@servertech.com

Return Merchandise Authorization

If you have a unit that is not functioning properly and is in need of technical assistance or repair:
Please review Server Technology’s
Return Merchandise Authorization process on our website.
Rack-Mount Fail-safe Transfer Switch Appendices 11
Installation and Operations Manual
Page 12
Server Technology
HEADQUARTERS – NORTH AMERICA EMEA APAC
Server Technology, Inc. Server Technology Intl Server Technology, Inc.
1040 S and hill Driv e Sienna Court Singapore Reno, NV 89521 The Broadway +65 (0) 6829 7008 Tel United States Maidenhead +65 (0) 6234 4574 Fax +1.775.284.2000 Tel Berkshire salesint@servertech.com +1.775.284.2065 Fax SL6 1NJ sale s@ servertech.com United Kingdom www.servertech.com +44 (0) 1628 509503 Tel www.servertechblog.com +44 (0) 1628 509100 Fax salesint@servertech.com