Senztek Solastat 2-3 User Manual

USER GUIDE
SolaStat
-2-3
An Intelligent Technology Solution for Water Heating
SolaStat™-2-3 User Guide
Version 1.11 – November 2011 Table of Contents
Table of Contents
Introducing your SolaStat™ Controller ....................................................................... 1
The Display Panel ...................................................................................................... 2
Saving Power with SolaStat™ .................................................................................... 3
Using your SolaStat™ ................................................................................................ 4
Trouble Shooting Guide ........................................................................................... 10
Programming Table .................................................................................................. 11
For technical help contact your installer or maintenance technician.
Installer Details:
www.senztek.com
Senztek Holdings Ltd. 2009
SolaStat™-2-3 User Guide
Version 1.11 – November 2011 Page 1
INTRODUCING YOUR SOLASTAT CONTROLLER
About Your SolaStat™ Controller
Your SolaStat™ Controller has a microcomputer, which intelligently and automatically controls water flow and energy inputs into your hot water system.
Your SolaStat™ will balance water flow and energy inputs from solar, and electrical sources so you can minimise your energy costs.
It has two main aims:
To make sure your hot water is being heated cost-efficiently.
To make sure you don’t run out of hot water when you need it.
How Does It Work?
Your SolaStat™ Controller works by measuring and comparing the temperature at three different places in the system: the collector (ROOF), the top of your hot water cylinder (TANK) and the bottom of your hot water cylinder (INLET).
If the temperature at the ROOF is higher than the INLET temperature by a pre-set amount, then the pump turns on automatically to transfer heated water from your solar collector to your hot water cylinder, and replace it with cooler water from the bottom of the cylinder.
This makes the hot water cylinder heat up and the collector on your roof cool down. When the temperature difference reduces to the pre-set level again, the pump automatically stops.
It can also optimise the timing of heating your water, so heat is only applied to the water in your cylinder when necessary, not all the time.
The SolaStat™ is also designed to protect your hot water system from very high or freezing temperatures, as well as make sure that safe water conditions are maintained (BioSafe).
SolaStat™-2-3 User Guide
Version 1.11 – November 2011 Page 2
THE DISPLAY PANEL
The
ROOF,
TANK
and
INLET lights indicate which temperature is being displayed. If any of these lights flashes, the unit is in Smart Shutdown Mode and ‘SSd’ will be displayed.
NEXT Button
Press to obtain the next displayed temperature.
The DISPLAY PANEL
shows
the temperatures of the relevant sensors in 0C or 0F. This is factory pre-set and cannot be changed.
HWC Button
Press and let go for a one-off user heat up to a maximum temperature – it will then switch off and revert to automatic. Press again to cancel.
When in Programming Mode, use this to
decrease the display value on the screen.
TEST Button
Press to test the display of the screen. ‘888’ will be displayed and all the lights will be on at the same time for about two seconds. All the lights (except the PWR light) will then flash and the display will show the number of times the pump has been on (up to 999).
The
PUMP
light comes on when the
pump is on (in normal or FROST operation, or when the PUMP button is pressed). The PUMP light flashes when the maximum tank temperature has been reached.
HWC
The HWC light is on when the element is on.
The TOPOUT
light is on when the hot water tank has reached its maximum temperature.
The
FROST
(and PUMP
)
light is on when the pump is circulating water to stop the collector from freezing.
CAUTION: Do not turn the power off when the FROST light is on.
PUMP
Button
Press and hold this button to turn the pump on or off (after it has run for ten minutes, it automatically switches off for one minute, to let air escape and prevent overheating)
When in Programming
Mode, use this to increase the display value
on the screen.
SolaStat™-2-3 User Guide
Version 1.11 – November 2011 Page 3
SAVING POWER WITH SOLASTAT
TThhrreeee TToooollss ttoo AAcchhiieevvee PPoowweerr SSaavviinnggss
SolaStat™ has three tools to help you save power:
1. Controlling the amount of hot water that enters your tank.
You can alter the amount of water entering your tank using the PUMP function.
Your SolaStat™ is set to make the pump automatically turn on or turn off, depending on the temperature in the tank, at the inlet and at the collector.
2. Controlling the activity of the heating element.
To ensure that the water in your tank is not heated by electricity unnecessarily (for example, when the water from your collector is already hot enough), the heat applied to the element is computer controlled.
3. Running BioSafe as a background activity.
To protect your hot water from harbouring bacteria, hot water tanks need to be run at 60°C/140°F for at least one hour every 72 hours.
Rather than the traditional method of running your tank continuously at 60
°C/140°F, and using up valuable energy doing so, your SolaStat™
Controller ‘remembers’ when your tank was last heated to 60°C and makes sure than it heats up to that temperature once every 72 hours for at least one hour.
SolaStat™-2-3 User Guide
Version 1.11 – November 2011 Page 4
USING YOUR SOLASTAT
RReeaaddiinngg tthhee DDiissppllaayy
The Display Lights show where the current display temperature is being read from: ROOF, TANK, or INLET.
To find out the temperature on the other sensors, press the NEXT button. The display light will confirm which sensor is being read.
Note that the Sola-2-3atTM- ST is factory set to display temperature in degrees Centigrade/ Celsius. The Sola-2-3at
TM
- 2F is factory set to display temperature in degrees Fahrenheit. These settings cannot be changed. Refer to the label on the side of the enclosure and the box.
Continued on next page
This indicates that the ROOF sensor reading is currently on display, in this case 370C.
Press NEXT to toggle between the ROOF, TANK and INLET sensors.
This indicates that the TANK sensor reading is currently on display, in this case 310C.
Press NEXT to toggle between the ROOF, TANK and INLET sensors.
This indicates that the INLET sensor reading is currently on display, in this case 400C.
Press NEXT to toggle between the ROOF, TANK and INLET sensors.
SolaStat™-2-3 User Guide
Version 1.11 – November 2011 Page 5
USING YOUR SOLASTAT™, CONTINUED
PPuummpp AAccttiivvaattiioonn
Press and hold the PUMP button to manually operate the pump. It will circulate the water between the panel and the hot water tank.
After it has run for ten minutes (on automatic or manual), the pump automatically switches off for one minute, to let air escape and prevent overheating.
Continued on next page
Press the PUMP button to manually pump water from the collector into the tank.
While the pump is operating, this light will be on.
You will see a number displayed on the screen. In this case, (as the ROOF light is on), it indicates that the ROOF sensor is at 800C.
SolaStat™-2-3 User Guide
Version 1.11 – November 2011 Page 6
USING YOUR SOLASTAT™, CONTINUED
Manual/User Reheat
To manually start a reheat of the water in your tank, press the HWC button. Press the HWC button again to turn it off.
However, if Reheat is already on, pressing the HWC button will not turn it off.
Continued on next page
Press HWC for one-off heat up mode. This will heat the water to the Reheat Upper temperature (pre-set to 55°C/131°F.
HWC will flash when the user presses the HWC button to manually reheat the tank.
SolaStat™-2-3 User Guide
Version 1.11 – November 2011 Page 7
USING YOUR SOLASTAT™, CONTINUED
Testing Mode Pressing the TEST button will make sure the display panel and all lights in
the system are working.
All the lights will stay on, and ‘888’ will be shown for about two seconds.
Then all lights will flash and the display shows how many times the pump has been activated (up to 999) for three seconds.
Continued on next page
Then, all the lights (except the PWR light) will flash, and the display will tell you how many times the pump has been activated (in this case, 123 times).
Press the TEST button to check that all lights in the system are working.
For the next two seconds, all the lights come on and ‘888’ is shown on the screen.
SolaStat™-2-3 User Guide
Version 1.11 – November 2011 Page 8
USING YOUR SOLASTAT™, CONTINUED
Smart Shutdown Mode
‘Smart Shutdown’ is a mode that your controller will enter to minimise damage. It can be activated when the temperature at the ROOF sensor is less than -40°C/-40°F or more than 142°C/288°F.
This may occur because:
there is a fault in the sensor wiring, OR
the Solar Collector has reached a very high temperature.
If Smart Shutdown Mode is activated, you will see SSd on the display as shown on the screen below.
The ROOF sensor temperature may reduce to a safe level by itself and the uniit will return to normal operation. ‘SSd’ will no longer appear on the display.
This is a normal condition and it is not necessary to contact your installer or maintenance technician unless ‘SSd is on the display for more than 12 hours.
Continued on next page
SSd on the display shows the controller is in Smart Shutdown Mode – i.e. there is a fault condition.
When SSd is displayed, the ROOF, TANK or INLET will be on or flashing to indicate which sensor is faulty. In this case, a faulty ROOF sensor has been detected.
SolaStat™-2-3 User Guide
Version 1.11 – November 2011 Page 9
USING YOUR SOLASTAT™, CONTINUED
Lockout Mode
The Lockout Mode is activated when the water temperature in the collector is less than 20°C/68°F. In this case, the collector will not contribute any useful heat, even to cold water.
In this (Lockout) mode, the controller will not turn on the pump even if the correct temperature differential is reached.
However, if a frost condition is detected, this Lockout Mode is overridden and the pump operates to protect the system from freezing.
Frost Mode The FROST value is set by your installer. It is shown in the Programming
Table on Page 11.
This function is designed to protect your collector and hot water system from freezing and bursting.
When the FROST temperature is reached, the pump will come on just enough to raise the temperature of water by 2-3°C/4-6ºF.
Only a small amount of warm water is needed to protect the collector and plumbing.
When the unit is in Frost Mode, the FROST and PUMP lights will come on.
CAUTION: Do not turn the power off when the FROST light is on.
As soon as the collector reaches the FROST temperature, the FROST and PUMP lights will turn on.
SolaStat™-2-3 User Guide
Version 1.11 – November 2011 Page 10
TROUBLE SHOOTING GUIDE
Symptom Cause Solution
No operation, no display and no lights.
No power/fault.
Check mains outlet.
Check fuses.
POWER light ON but no display or corrupted display.
Power brown out (mains power not
running at full voltage).
Unit faulty.
Switch off power while mains
power is in brown out condition.
Switch off power for 10 minutes,
switch on power and see if unit is operating. If not, unit needs repair. Contact installer.
Display on, pump not running, but sunny outside. Pump light ON.
Pump damaged or disconnected.
Pump timer has turned pump off.
See if the pump has become
unplugged.
Wait one minute for the pump to
restart.
Pump is running continuously.
Pump is cavitating.
Special installation.
Setting is incorrect.
Airlock in pipe.
If pump sounds like stones are
passing through it, the pump may be cavitating. Contact your installer or maintenance technician.
Long pump running times may be
normal for a special installation.
Contact your installer or
maintenance technician.
Hot water drops significantly at night, yet little or no draw off be user.
System is reverse thermo-
siphoning.
System is in a high frost area.
Tank is losing heat.
The non-return valve is not fitted
correctly or is malfunctioning.
Discuss non-frost sensitive options
with your energy provider.
Install better insulation on the hot
water tank.
HWC light never comes on.
Collectors are heating tank to
greater than adjustable values.
Normal operation.
HWC light flashing.
HWC Reheat Upper adjustable
value has not been reached.
Tank Thermostat incorrectly set
Wait for the tank to heat up to
Reheat Upper temperature.
Contact your installer or
maintenance technician.
‘Lo’ on display.
Sensor below -20°C/-4°F.  Check outside temperature.
‘Hi’ on display.
Sensor above 139°C/284°F.  Check collector has water in it.
‘SSd’ on display.
System is in ‘Smart Shutdown’
Mode.
Contact your installer or
maintenance technician if the display shows’ SSd’ for more than 12 hours.
Note: When power is removed, the internal timer will keep running for at least 7 days.
SolaStat™-2-3 User Guide
Version 1.11 – November 2011 Page 11
PROGRAMMING TABLE
Your installer may enter special programming information for your controller in the table below. Settings can be changed by a qualified installer or maintenance technician.
Programming Table for Adjustable Values
Adjustable
Values
Function Light
indication
Pre-Set
Value
Range Installation
Values
Pump Off
The temperature difference
between the Roof and the Tank
that will turn the pump off.
PUMP Flash 6°C
11°F
1-20°C
2-36°F
____ °C
____ °F
Pump On
The temperature difference
between the Roof and the Tank
that will turn the pump on.
PUMP On 12°C
22°F
2-21°C
4-38°F
____ °C
____ °F
Holdoff
Timer
How long the timer will override the element coming on (as long
as the tank temperature is
above Reheat Lower).
HWC on 4 hours 1-23 hours
>23 hours = OFF
<1 hour = thr
____ hours
Reheat
Lower
The tank temperature at which
the heating element will
automatically start to reheat the
water in your cylinder.
HWC slow
flash
40°C
104°F
1-70°C
34-158°F
<1ºC = OFF
Set Holdoff Timer to
thr = OFF
____ °C
____ °F
Reheat
Upper
The temperature (in the tank) at
which the heating element will
automatically stop reheating the
water in your cylinder.
HWC fast
flash
55°C
131°F
2-90°C
36-194°F
Set Holdoff Timer to
off = OFF
____ °C
____ °F
BioSafe
BioSafe target temperature.
No lights
(except PWR)
60°C
140°F
50-70°C
122-158°F
<50°C = OFF
____ °C
____ °F
Topout
Maximum allowable tank
temperature before the pump is
de-activated to protect system
from overheating.
TOPOUT on 80°C
176°F
1-120°C
34-248°F
<1°C = OFF
____ °C
____ °F
Frost
Minimum allowable panel
temperature before the pump is
activated to protect system from
freezing damage.
FROST on
4°C
39°F
1-10°C
34-50°F
>10°C = OFF
____ °C
____ °F
Senztek NZ Ltd Senztek Australia Ltd Senztek UK Ltd
Loading...