Sentrol ZX400, ZX410 Installation Manual

SENTROL ZX400/ZX410
Security System Control
Installation
1
2
Table of Contents
New Features............................................................................................................. 5
ZX400/ZX410 Wiring Diagrams................................................................................ 6
ZX400/ZX410 Terminal Descriptions........................................................................ 8
Conventional Methods of Wiring ........................................................................... 11
Class ‘B’ End-Of-Line Resistor Supervised Zones ..................................................... 11
Non-Supervised Closed Circuit Loop (No EOL Resistor Supervision) ...................... 11
Control Station Addressing and Supervision ......................................................... 12
SSD, LCD, and VFD Control Stations ...................................................................... 12
LED Control Stations .............................................................................................. 12
TABLE OF CONTENTS
Control Station Troubleshooting ............................................................................ 13
Clearing Trouble Messages ..................................................................................... 13
12 VDC Outputs ...................................................................................................... 14
Additional Outputs.................................................................................................. 14
Expansion Zones ..................................................................................................... 16
ZXEXP Zone Expander Module............................................................................... 17
Installation ............................................................................................................. 17
Wireless Devices ...................................................................................................... 18
Fire Zone Modules .................................................................................................. 19
ZEM Zone Expansion Module ................................................................................ 19
ZRM Zone Relay Module ........................................................................................ 21
ZXCFK Fire Module Kit ........................................................................................... 21
Power Issues ............................................................................................................ 22
Optional Battery Configurations ............................................................................. 22
ZX400/ZX410 Power Worksheet ............................................................................ 22
Auxiliary Power Supply Installation ......................................................................... 23
ZXPTR Printer Interface Module............................................................................. 24
3
TABLE OF CONTENTS
Specifications And Features .................................................................................... 25
Control Board ........................................................................................................ 25
Power Supply ......................................................................................................... 25
Recommended Battery ........................................................................................... 25
Recommended Transformer ................................................................................... 25
Enclosure................................................................................................................ 25
Digital Communicator............................................................................................ 25
Control Stations ..................................................................................................... 26
ZXLCD Control Station........................................................................................... 26
ZXVFD Control Station ........................................................................................... 26
ZXLED12 Control Station ....................................................................................... 26
ZXSSD Control Station ........................................................................................... 26
Optional Accessories .............................................................................................. 26
Output Provisions ................................................................................................... 27
List Of Compatible Accessories ............................................................................... 28
ESL Two-Wire Smoke Detectors .............................................................................. 28
ESL Four-Wire Smoke Detectors.............................................................................. 28
System Sensors Two-Wire Smoke Detectors............................................................ 28
System Sensors Four-Wire Smoke Detectors ........................................................... 28
Wheelock ............................................................................................................... 28
Compatible Central Station Receivers ..................................................................... 28
Agency Requirements ............................................................................................. 29
UL and ULC Listings ............................................................................................... 30
National Fire Protection Association (NFPA) Rules ................................................ 31
Smoke Detector Locations ...................................................................................... 31
Testing ................................................................................................................... 31
System Troubleshooting ......................................................................................... 32
FCC Compliance ...................................................................................................... 34
4
New Features
12 Zones with Sentrol’s unique “2 in 1” Zoning™
Plus one 2-wire fire zone
Expandable to 28 zones, plus two 2-wire fire zones
Integrated Sentrol Series 4000 Wireless
Two truly independent partitions
Up to 50 user codes with 15 levels of authority
75 event log
Four interchangeable Control Stations to choose from
Customized scheduling with special supervisory report
Ideal for residential, commercial, and industrial applications
Control Station programming in less than 2 minutes with factory defaults
NEW FEATURES
The Sentrol ZX400/ZX410 Security Control features ease of installation and programming. The ZX400/ ZX410 is easily programmed with any one of four Control Stations (LCD, LED, SSD, or VFD). The con­trol may also be programmed remotely with the aid of a personal computer (PC) and a modem using Sentrol’s remote programming software (RPM2PRO) and a panel support module (PRO400). The Control Stations are easy-to-operate and contain features such as cross-zoning, delay-before-dialing and an audibles “mute” function to help reduce false alarms.
The ZX400/ZX410 Security Control is pre-pro­grammed from the factory with twelve burglar zones (one delay, two interior, and nine instant) and one 2-wire smoke detector zone to allow for out-of-box power-up and operation. The twelve burglar zones have been configured in a ‘paralleled’ condition us­ing Sentrol’s unique “2 in 1” Zoning™. A zone ex­pander may be added to provide an additional 2­wire smoke detector zone and, with the use of “2 in 1” Zoning™, up to 16 additional zones.
Sentrol Series 4000 RF Gateway receivers and sen­sors allow you to overcome installation obstacles and increase profit potential. The wireless sensors have been engineered for long term stability and reliabil-
ity. Using the Series 4000 Wireless System, you can expand the ZX400/ZX410 to include up to 16 wire­less zones.
The Control’s on-board RAM maintains its data even with the power disconnected. A “Watchdog” timer monitors the microprocessor to ensure the opera­tional integrity of the system. The ZX400/ZX410 Control Board is equipped with one low current pro­grammable output (PGO1) and one high current bell output (BELL) which may be used for Fire, Burglar, Auxiliary and/or Holdup alarms. In addition, two ZXODMs (Output Driver Modules) can be added to provide 20 more programmable low current out­puts which may be used to trigger other devices.
The ZX400 Security Control may be purchased in the ZX410 pre-configured package assembly. This assembly incorporates the ZX400 Control Board mounted inside a larger 14" x 14" x 3.5" enclosure, EX1414. The ZX410 must be purchased for Com­mercial and Industrial UL Listed applications. For UL Listed Commercial Fire applications, the ZX440F is available. It consists of the ZX400 Control Board in a red EX1414 enclosure, with a ZXCFM (Commer­cial Fire Module), a CR860 dual battery harness and other cabling.
5
ZX400/ZX410 WIRING DIAGRAMS
ZX400/ZX410 Wiring Diagrams
J-3
7
6
NEG8DAT A
2WS
LISTED RATE OF RISE OR
FIXED TEMPERATURE THERMOSTAT
RED
BLACK
BROWN
9
DAT B10KP+1211NEG
GREEN
WHITE
CONTROL STATIONS
ZONE EXPANDER
PRINTER INTERFACE
ODMs
TO ANY ZONE DEFINED
AS 24-HOUR FIRE
POWER SUPERVISION UNIT
ESL MODEL 204-12/24V OR EQUIV.
Class II Power­Limited
RED
BLACK
BROWN
Z1/7
12
13
Z2/814NEG
N.O.
N.C. ZONE 1
1500
1/2 WATT
--
1500 (CR854) (CONV ZONING)
GROUND
SCREW
Enclosure Door Ground Wire
UNIFIED
EARTH
GROUND
Internally Fused.
Do Not Connect
Red and Black Leads RED = POS. (+) BLACK = NEG. (-)
12V SEALED
LEAD ACID BATTERY
Yuasa B-1270
FLOAT BATTERY VOLTAGE:
13.6 - 13.8V Max. current: 500mA.
QUIESCENT CHARGE CURRENT: 20mA. Replacement: Every 3 - 5 years.
UL LISTED RESISTORS
MODEL CR853 - 825 E.O.L. MODEL CR854 - 1500 E.O.L.
ON
OFF
1 2
~
AC XFMR
TRANSFORMER
Basler BE 116235
16.5VAC/35VA
U.L. Class II 50/60Hz
WARNING
Do Not Short.
To A Switched
Receptacle.
+--
+
POWER
SENTROL 4-WIRE MODELS
(See ZX400/ZX410 Interconnect Label
4
3
AUX125BELL
SW NEG
SIGNALING DEVICE
ALARM
CONTACTS
SMOKE DETECTOR
P/N 64600310-NOTE 2)
Class II Power­Limited
1500 EOL
SUPERVISION
UL LISTED
Ademco AB12M
15
16
Z4/10
NEG
17
Z3/9
METHOD 1
ZONE 3
N.C.
1500
1/2 WATT
ZONE 9
POWER
+
+
MOTION
DETECTOR
1500 (CR854)
(EOL DEVICE)
SMOKE DETECTOR
SENTROL 2-WIRE MODELS
(See ZX400/ZX410 Interconnect Label
P/N 64600310-NOTE 2)
825
1/4 WATT
N.C.
18
Z5/11
I.C. Load Number 1
PG01
19
Z6/1220NEG
METHOD 2
ZONE 5
N.C.
1500
1/2 WATT ZONE 11
N.C.
825
1/4 WATT
CONNECT
RJ31/33/45
CONNECTION OF UL COMMERCIAL
BURGLAR AUDIBLE
POLARIZATION AND NOISE SUPPRESSION DIODE
-
+
JUMPER
CORD
7
BELL
NEG
1500 (CR854)
(EOL DEVICE)
5
TEL
SUPV
J-10
J-4
13
Z2/8
ALL WIRING BETWEEN CONTROL & BELL MUST BE IN CONDUIT.
ADEMCO AB12M
GRADE A BELL COMMERCIAL
See Specification and Features section for a complete list of compatible accessories.
FIGURE 1 Suggested UL Household Burglar Alarm and/or Fire (ƒƒ) Alarm Hookup
6
ZX400/ZX410 WIRING DIAGRAMS
MPI-206
TEL
SUPV
INSTALL JUMPER
TELEPHONE
SUPERVISION
TG - COM NC NO
CONNECTION
TG+
MPI-206
TG - COM NC NO
TG+
+12V NEG
TO TERMINAL 10
TO TERMINAL 20
OPTIONAL - When relay is required
PROGRAMMABLE
OUTPUT 1
CONNECTION
PG01
TO TERMINAL 7
TO TERMINAL 4
CUT
JUMPER
J4
SENTROL RJ38 CORD
(shown)
OPTIONAL - When Telco Supervision is required
+12V NEG
ORANGE
BLUE
FIGURE 2 Programmable Output And Telco Supervision Wiring Diagram
7
ZX400/ZX410 TERMINAL DESCRIPTIONS
ZX400/ZX410 Terminal Descriptions
TERMINAL FUNCTION DESCRIPTION
1, 2 AC Input Connect the appropriate UL Class II transformer using 18 gauge minimum 2
conductor wire. Do not exceed 50 feet. Use a 16.5 VAC 35 VA transformer or an optional 16.5 VAC 20 VA transformer.
CAUTION: Do not short the terminals of the transformer together. This causes the internal fuse to blow. The transformer must be connected to a 120 VAC, 24-hour outlet not controlled by a switch other than an approved over-current protection device.
3 Switched Negative (-) Current limited 100 mA terminal. Negative connection for 4-wire smoke
4 Auxiliary Power (+)12 VDC 500 mA continuous power. Overcurrent protected at 1.35 amps
5 Supervised Bell Output (+)12 VDC. Combined alarm current should not exceed 1.5 amps. Overcurrent
(power-limited)
6 Two Wire Smoke (Zone 30) (+)12VDC of two-wire smoke detectors connected to this terminal. A 1500
(power-limited) Ohm EOL resistor (CR854) must be connected between terminals 6 and 7
7, 11 Common Negative BLACK WIRE - (-)12 VDC. Negative connection for Control Stations, zone
(power-limited)
8 Local Data Bus In (A) GREEN WIRE - Connection for Control Stations, zone expander, printer
9 Local Data Bus Out (B) WHITE WIRE - Connection for Control Stations, zone expander, printer
10 Control Station Power RED WIRE - (+)12 VDC 500 mA continuous power connection for control
(power-limited)
12 Zone 1/7 Loop (+) 13 Zone 2/8 Loop (+) 14 Common Negative 15 Zone 3/9 Loop (+) 16 Zone 4/10 Loop (+) 17 Common Negative 18 Zone 5/11 Loop (+) 19 Zone 6/12 Loop (+) 20 Common Negative
PGO1 Programmable Output 1 Use PGO1 as a +12V, 40 mA programmable output (see Figure 2).
TEL SUPV Telephone Supervision Use TEL SUPV as a telephone line trouble input (see Figure 2).
J4 Telco Jack RJ-31X connection.
detectors, glass break detectors, and devices requiring resettable power.
(PTC4). Used for powering motion detectors, 4-wire smoke detectors, glass break detectors, and other accessories.
CAUTION: Use terminals 4 and 10 when calculating total current drain.
protected at 1.85 amps (PTC2). A 1500 Ohm EOL resistor (CR854) must be con­nected between terminals 5 and 7; otherwise a bell output fault will occur.
regardless of whether a two-wire smoke detector is used or not. The maximum series resistance is 60 Ohms.
expander, printer interface, RF Gateway, ODMs, 2-wire smoke detectors, motion detectors, and other devices.
interface, RF Gateway and ODMs. Use 22 guage wire up to 1000 ft. Use 18 guage wire up to 2000 ft.
interface, RF Gateway and ODMs. Use 22 guage wire up to 1000 ft. Use 18 guage wire up to 2000 ft.
stations, zone expander, printer interface, RF Gateway and ODMs. Overcurrent protected at 1.35 amps (PTC4).
CAUTION: Use terminals 4 and 10 when calculating total current drain.
Each loop requires a 1500 Ohm end-of-line resistor (P/N CR854) for the primary zone, and an 825 Ohm end-of-line resistor (P/N CR853) for the secondary zone. A common negative is shared among all zones. The need for end-of-line resistors may be eliminated on all Burglar defined zones through programming. See Figure 1 for “2 in 1” Zoning™ wiring examples.
8
Secondary Zone
825 1/4W
1500 1/2W
Primary Zone
“2 in 1” Zoning™
“2 in 1” Zoning
NOTE
If a Normally Open Device (i.e., 4-wire smoke detector) is used with “2 in 1” Zoning™, a short will occur across both zone loops when that device goes into alarm. It is recommended that these types of devices be used with Conventional Zone wiring only.
The Sentrol ZX400/ZX410 Security Control intro­duces an all new method of wiring zones that saves both time and wire costs. “2 in 1” Zoning™ allows the installer to wire two separate zones in parallel into one set of terminals.
Each zone is uniquely identified by its end-of-line re­sistor. The Primary Zone (zones 1-6) in each termi­nal is identified by a 1500 Ohm EOL resistor. The Secondary Zone (zones 7 - 12) is identified by an 825 Ohm EOL resistor. The Primary and Secondary zones operate as two independent zones to provide separate reporting, programming, and displays. Each zone is fully programmable as described in the ZX400/ZX410 Programming Manual. The zones are for Form A, Form B, or Form C sensors. Maximum
total loop wire and contact resistance (not includ­ing EOL) must not exceed 100 Ohms for the loop to function properly.
There are two methods of wiring for “2 in 1” Zon­ing™. Method 1 wires one zone loop back to the control while a second zone loop is added in parallel off the first. This method may be employed in sys­tem retrofits, system expansions, or just simply to save wire cost and labor.
1500 1/2W
Primary Zone
Method 2 wires two separate zone loops back into one set of terminals. The panel recognizes each loop independently because two different EOL re­sistor values are used to differentiate between the Primary Zone (1500 Ohm 1/2 Watt) and the Sec­ondary Zone (825 Ohm 1/4 Watt). This method provides two zones with one set of terminals and is ideal for pre-wire or already installed wiring.
Figure 4 “2 in 1” Zoning™ Wiring - Method 2
NOTE
The resistors in Figure 3 & 4 are 1% values to maintain proper loop resis­tance values. If replacements are re­quired, please refer to the manufac­turer for correct replacements. The 1500 ohm resistor is color coded Brown•Green•Black•Brown•Brown. The 825 ohm resistor is color coded Gray•Red•Green•Black•Brown.
All zones sense five different voltage levels enabling one zone to act as two. Troubleshooting is simple using just a voltmeter at the control. The control monitors the voltage level across the zone and uses the voltage levels in Table 1 to determine whether the zone is normal, open, or shorted.
Secondary Zone
825 1/4W
Figure 3 “2 in 1” Zoning™ Wiring - Method 1
9
“2 in 1” Zoning™
CONDITION NOMINAL LOOP RESISTANCE VOLTAGE READING
Primary Zone and Secondary Zone Infinite Ohms 5.24 - 8.25 V Open Contacts; Loop Cut or Open
Secondary Zone Open Contact, 1500 Ohms 4.24 - 5.23 V Primary Zone Normal
Primary Zone Open Contact, 825 Ohms 3.24 - 4.23 V Secondary Zone Normal
Primary Zone and Secondary Zone 825 Ohms in parallel with 2.00 - 3.23 V Normal 1500 Ohms = 532 Ohms
Primary Zone and Secondary Zone 0 Ohms 0 - 1.99 V Shorted
TABLE 1 “2 in 1” Zoning™ Troubleshooting Chart
10
Conventional Methods of Wiring
CONVENTIONAL WIRING
Class ‘B’ End-Of-Line Resistor Supervised Zones
A Class ‘B’ zone must be supervised with a 1500 Ohm 1/2 Watt end-of-line resistor (P/N CR854). This resistor should be installed in series at the furthest point from the control. This configuration must be used whenever both Form A and Form B devices are connected and provides a high degree of protec­tion against compromise or tampering. The control monitors the voltage level across the Primary zone and uses the Primary zone voltage levels in Table 1 to determine whether the zone is normal, open, or shorted. The operation of a zone is programmable as described in the ZX400/ZX410 Programming
Manual. Maximum total loop wire and contact resistance (not including EOLs) must not exceed 100 Ohms for the loop to function properly. The 1500 Ohm EOL resistor is optional for Form A con­nections but is required for Form B.
Normally
Open
Non-Supervised Closed Circuit Loop (No EOL Resistor Supervision)
The EOL resistor is not required on Burglar zones. A conventional closed circuit loop may be connected directly to a primary zone and the zone will have either a short or an open condition. See the ZX400/ ZX410 Programming Manual for programming an un­supervised zone. Fire zones may not be installed as unsupervised. Only Burglar defined zones may be
wired non-supervised. “2 in 1” Zoning™ is not allowed.
1500 1/2W
Primary Zone
Normally
Closed
Figure 5 Conventional Zone Wiring Method
NOTE
For UL Listed systems, EOL Supervi-
is required.
sion
11
Loading...
+ 25 hidden pages