Sentrol ZX300, SENTROL ZX310 Installation & Programming

SENTROL ZX300/ZX310
Expandable Security System Control
Installation/
Programming
1
2
Table of Contents
Control Board T erminal Descriptions.........................................................................6
Zone Wiring.................................................................................................................... 7
Class ‘B’ End-Of-Line Resistor Supervised Zones ......................................................7
Non-Supervised Closed Circuit Loop (No EOL Resistor Supervision)........................7
ZXEX08 Zone Expander Module............................................................................. ... 7
Wireless Devices ..........................................................................................................8
Control Station Addressing and Supervision............................................................9
SSD, LCD, and VFD Control Stations......................................................................... 9
ICON Control Stations..................................................................................................9
LED Control Stations..............................................................................................9
Unsupervised and Supervised Control Stations..................................................... 9
T ABLE OF CONTENTS
Control Station Troubleshooting..............................................................................10
12 VDC Outputs .........................................................................................................11
Operating the System ................................................................................................13
Powering Up The Control ...........................................................................................13
Testing ...............................................................................................................13
Installer Arming and Disarming ..................................................................................13
Trouble Conditions .....................................................................................................1 3
Clearing Trouble Messages .......................................................................................13
Installer on Premises..................................................................................................13
Programming the Control.................................................................................................14
Introduction ...............................................................................................................14
Local Programming ....................................................................................................1 4
Programming Zone Names....................................................................................... 14
Installer Level Programming .....................................................................................15
Menu Options .............................................................................................................15
Program Function Map....................................................................................15
Entering a New Value at a Location................................................................15
Programming the Account Code and Telephone Number Digits....................16
Additional Programming Notes .......................................................................16
Program User Codes.......................................................................................16
Restore Factory Defaults ................................................................................16
Hours Until Next Comm Test...........................................................................1 7
Program RF Data............................................................................................17
Programming RF Zone Devices Into the RF Gateway ...................................17
Programming RF User Devices Into the RF Gateway....................................18
Programming RF Devices Into the Control Panel...........................................18
3
T ABLE OF CONTENTS
Specifications And Features .....................................................................................19
List of Compatible Accessories................................................................................22
SIA and Contact ID Formats......................................................................................23
Agency Requirements ...............................................................................................25
National Fire Protection Association (NFPA) Rules................................................27
FCC Compliance.........................................................................................................30
4
ZX300/ZX310 Wiring Diagram
WIRING DIAGRAM
7167-1459:114
FIGURE 1 Suggested UL Household Burglar Alarm and/or Fire (ƒƒ) Alarm Hookup
5
TERMINAL DESCRIPTIONS
Control Board Terminal Descriptions
TERMINAL FUNCTION DESCRIPTION
AC
BELL
NEG
KP+12V
GREEN
DAT A
WHITE
DAT A
NEG Zone 1 Zone 2 Zone 3 Zone 4 NEG Zone 5 Zone 6 NEG Zone 7 Zone 8
AC Input
Supervised Bell Output
(power-limited)
Common Negative
Keypad Power (power-limited)
Local Data Bus In
Local Data Bus Out
Zone Inputs
Connect a 16.5 VAC 15 VA UL Class II transformer minimum using 18 gauge minimum 2 conductor wire. Do not exceed 50 feet.
(+)12 VDC. Combined alarm current should not exceed 1.0 amps. Overcurrent protected at 1.35 amps (PTC2). A 1500 Ohm EOL resistor (CR854) a bell output fault will occur.
BLACK WIRE - (-)12 VDC. Negative connection for Control Stations, ODM, RF receiver, zone expander, motion detectors, bell output, and other devices.
RED WIRE - (+)12 VDC 500 mA continuous power connection for Control Stations, ODM, zone expander, and RF Gateway. Overcurrent protected at
1.35 amps (PTC1). CAUTION: Use the KP+12V and the +12V AUX
terminals when calculating total current drain.
GREEN WIRE - Connection for Control Stations, zone expander, ODM and RF
receiver. Use 22 gauge wire up to 1000 ft. Use 18 gauge wire up to 2000 ft. WHITE WIRE - Connection for Control Stations, zone expander, ODM and RF
receiver. Use 22 gauge wire up to 1000 ft. Use 18 gauge wire up to 2000 ft.
Each loop requires a 1500 Ohm end-of-line resistor (P/N CR854). A common negative is shared among all zones. The need for end-of-line resistors may be eliminated on all Burglar defined zones through programming.
must be connected between the Bell and Neg terminals; otherwise
2WS
+12V AUX
Two-Wire
Smoke Terminal
Auxiliary Power
(power-limited)
Current limited 100 mA terminal. Connection for two-wire/four-wire smoke detectors, glass break detectors, and devices requiring resettable power. The maximum series loop resistance for a two-wire smoke loop is 20 ohms. The maximum Alarm Impedance is 500 ohms.
(+)12 VDC 500 mA continuous power. Overcurrent protected at 1.35 amps (PTC1). Used for powering motion detectors, CO detectors, and other accessories. CAUTION: Use the KP+12V and the +12V AUX terminals when calculating total current drain.
6
Zone Wiring
ZONE WIRING
Class ‘B’ End-of-Line Resistor Supervised Zones
A Class ‘B’ zone must be supervised with a 1500 Ohm 1/2 Watt end-of-line resistor (P/N CR854). This resistor should be installed in series at the furthest point from the control. This configuration must be used whenever both Form A and Form B devices are connected and provides a high degree of pro­tection against compromise or tampering. The con­trol monitors the voltage level across the zone and uses the zone voltage levels in Table 1 to determine whether the zone is normal, open, or shorted. The operation of a zone is programmable (see Program­ming Record Book). Maximum total loop wire and
contact resistance (not including EOLs) must not exceed 100 Ohms for the loop to function prop­erly . The 1500 Ohm EOL resistor is optional for Form A connections but is required for Form B.
Normally
Open
Non-Supervised Closed Circuit Loop (No EOL Resistor Supervision)
The EOL resistor is not required on Burglar zones. A conventional closed circuit loop may be connected directly to a zone and the zone will have either a short or an open condition. See Programming Record Book for programming an unsupervised zone. Fire zones may not be installed as unsuper­vised. Only Burglar defined zones may be wired non­supervised.
NOTE
For UL Listed systems, EOL Supervision is required.
ZXEX08 Zone Expander Module
This module provides an additional 8 zones (zones 9-16) for the ZX300/ZX310 control. These zones are wired the same as the 8 on-board zones and the JP1 jumper must be in place.
1500Ω 1/2W
Primary Zone
Normally
Closed
Figure 2 Zone Wiring
CONDITION NOMINAL LOOP RESISTANCE VOL TAGE READING
Mount the module in a ZX310 enclosure as shown in the ZXEX08 insert using the screws and stand­offs provided. For mounting with the ZX300 or in a remote location, use a suitable enclosure, like the EB1511.
Connect the module to the ZX300/ZX310 local data bus using either the "quick connection" or the data bus terminals on the module. The "Active" LED flashes to indicate the module is communicating with the control.
NOTEONLY BURGLAR DEFINED ZONES MAY
Zone Open Infinite Ohms 9.75 - 13.85 V
Zone Normal 1500 Ohms 2.82 - 9.74 V
Zone Shorted 0 Ohms 0.00 - 2.81 V
Table 1 Zone Troubleshooting Chart
7
WIRELESS DEVICES
Wireless Devices
The ZX300/ZX310 provides an option for including Wireless (or RF) Devices. The RF Devices may con­sist of RF Zone Devices (Universals, Door Con­tacts, Glassbreaks, PIRs and Smoke Detectors) and RF User Devices (Handhelds). These RF Devices require that an RF Gateway be attached to the sys­tem. The ZX300/ZX310 is compatible with either a model 4710 or 4720 RF Gateway which are UL listed for household fire and burglary and commercial fire. If a 4720 RF Gateway is used, it must be set to ad­dress ‘1’. Refer to the RF Gateway instructions for address selection.
4710 RF Gateway - provides up to 8 RF Zone Devices and up to 8 RF User Devices. It can only provide for zones 9-16.
4720 RF Gateway - provides up to 16 RF Zone Devices and up to 8 RF User Devices. It can provide for zones 1-16.
Mount the RF Gateway as described in the RF Gate­way instructions. Wire the local data bus to the ter­minals: +12V - RED; DATA A - GREEN; DATA B ­WHITE; NEG - BLACK. Set Address switch. Rein­stall the cover.
See Installer Level Programming - Programming RF Data Into the RF Gateway . An RF User Device must be mapped to a valid user passcode by program­ming.
The RF Gateway and RF Zone Devices should be temporarily mounted in their desired locations until they have been tested with the Control Panel. These devices may need to be re-oriented or moved to achieve optimal reception. After testing has been completed, they should be permanently mounted.
ceived Signal Strength of the last transmission sent by the RF Zone Device. See results below:
Strong Signal (5 Control Station beeps): a strong or high level RF signal was measured by the receiver for that location of the transmitter. This is a good location for the transmitter and receiver.
Acceptable (3 Control Station beeps): a normal or acceptable level of RF signal was measured by the receiver for that location of the transmitter. This is a good location for the transmitter and receiver.
Low Signal (1 Control Station beep): a low or acceptable level of RF signal was measured by the receiver for that location of the transmitter. Make multiple test transmissions, making sure that obstruc­tions between the transmitter and receiver are nor­mal but minimized (hands away from units, metal ladders away from receiver, etc.) during these tests. The transmitter and/or receiver will need to be relo­cated to obtain ACCEPTABLE level readings.
No Signal (1 long Control Station beep): no RF sig­nal or an extremely low RF signal was measured by the receiver for that location of the transmitter. Bring the transmitter to the RF Gateway and activate the transmitter. The red LED on the RF Gateway should blink. If it does not, then the transmitter is not work­ing. If the red LED does blink, but the signal strength is still NO SIGNAL, then a programming error ex­ists. Check the programming of the zone in the RF Gateway. If the signal strength is STRONG or AC­CEPT ABLE, then the transmitter and/or receiver will need to be relocated to obtain ACCEPTABLE level readings. Be sure to power down the control to clear out all signal strength levels before testing the trans­mitter at its new location.
After testing has been completed, the RF Gateway and RF Zone Devices should be permanently mounted.
not
To test the Received Signal Strength of each RF Zone Device, use Test 6 - RF Signal Strength Test. From the Control Station press the “8” key , followed by the Installer Code (9632) and then press the “6” key . Next press the RF Zone Device Number (1-16). The Control Station will display and sound the Re-
NOTE
Series 4000 RF Gateways and transmitters which are not UL labeled are not allowed in UL Certificated installations.
8
CONTROL STATION ADDRESSING AND SUPERVISION
Control Station Addressing and Supervision
All LCD Control Stations are shipped from the fac­tory as Control Station #1 (#3 for Icon Control Sta­tions) and supervised. They may be set to other ad­dresses and to unsupervised as described below.
SSD, LCD, and VFD Control Stations
These Control Stations have a four position DIP switch on the circuit board to set the address and supervision. To change the Control Station to unsu­pervised, move DIP switch 4 to the ON position. To change the address, the DIP switch setting must be positioned according to Figure 3.
LED Control Stations
These Control Stations have two jumpers on the cir­cuit board to set the address and supervision. To change the address of Control Station #1 to Control Station #2, remove JP2 (see Figure 4). To change a Control Station to unsupervised, remove JP1 (see Figure 4).
Supervised and Unsupervised Control Stations
Figure 3 Control Station DIP Switch Settings
ICON Control Stations
These Control Stations have two jumpers on the cir­cuit board to set the address and supervision. To change the address of Control Station #3 to Control Station #4, remove JP2 (see Figure 4). To change a Control Station to unsupervised, remove JP1 (see Figure 4).
Remove JP1 to unsupervise
JP1
Remove JP2 for keypad 2 (LED) or keypad 4 (ICON)
JP2
A supervised Control Station is reported as missing when the system fails to get any response from it.
If more than one supervised Control Station is set to a particular address, then none of those Control Sta­tions will function properly. Only one supervised Control Station may be used at an address.
An unsupervised Control Station can be removed from the system without the system detecting that it is missing. The advantage of an unsupervised Con­trol Station is that a system can have as many Con­trol Stations as the power supply can support. Mul­tiple unsupervised Control Stations may be used at any address. When unsupervised SSD, LCD, and VFD Control Stations are used, they must be set to address 3 or 4. By adding additional power supplies, like the HCP12SULC, Control Stations may be added up to a total of 18 bus devices on the system.
For UL listed systems, unsupervised Control Sta­tions are not allowed.
If an unsupervised Control Station is set to the same address as a supervised Control Station, then the unsupervised Control Station will not function. Do
not mix a supervised Control Station with unsu­pervised Control Stations at the same address.
Figure 4 LED & ICON Control Station Jumpers
9
CONTROL ST A TION TROUBLESHOOTING
Control Station Troubleshooting
If a Control Station is incorrectly wired, it will not accept key­stroke entries. The following symptoms may appear:
SYMPTOM CONDITION
No Control Station display or LEDs Black or Red Wire removed or cut No response from key presses Green Wire removed or cut
Two supervised Control Stations at the same address
LEDs flash and may display White Wire removed or cut “No Communication From Control” code Green/White Wires reversed
Green & White Wires shorted together
The nominal voltage at the control (with a single Control Station connected) should measure as follows:
TERMINAL VOLTAGE
from Common Negative to GRN DATA ~ 9.3 VDC from Common Negative to WHT DATA ~ 10.7 VDC from Common Negative to KP+12V ~13.8 VDC
10
Loading...
+ 22 hidden pages