Sentrol ZX200, ZX210 Installation And Programming Manual

SENTROL ZX200/ZX210
Security System Control
Installation/
Programming
1
2
Table of Contents
Feature Overview ..................................................................................................... 5
A New Standard For Value ........................................................................................5
”More Than A Security System“ ................................................................................5
”Self-Watch“ Fire Zone Features................................................................................5
ZX200/ZX210 Wiring Diagram ................................................................................ 6
Control Board Terminal Descriptions ...................................................................... 7
“2 in 1” Zoning™ ..................................................................................................... 8
Conventional Methods of Wiring .......................................................................... 10
Class ‘B’ End-Of-Line Resistor Supervised Zones ......................................................10
Non-Supervised Closed Circuit Loop (No EOL Resistor Supervision) ........................ 10
TABLE OF CONTENTS
Wireless Devices ..................................................................................................... 11
Control Station Addressing and Supervision ........................................................ 12
SSD, LCD, and VFD Control Stations .......................................................................12
LED Control Stations ...............................................................................................12
Control Station Troubleshooting ........................................................................... 13
12 VDC Outputs ..................................................................................................... 14
Direct Connection to a PC for Remote Programming .......................................... 16
Operating the System ............................................................................................ 17
Powering Up With The Control Station ...................................................................17
Installer Arming and Disarming ............................................................................... 17
Installer On Premises ...............................................................................................17
Trouble Conditions .................................................................................................17
Clearing Trouble Messages ......................................................................................17
Testing ....................................................................................................................17
Programming the Control ..................................................................................... 18
Introduction ...........................................................................................................18
Local Programming .................................................................................................18
Remote Programming (RPM/2 Pro).........................................................................18
LED Control Station Programming ..........................................................................18
Programming Zone Names .....................................................................................19
3
TABLE OF CONTENTS
Installer Level Programming .................................................................................. 20
Menu Options.........................................................................................................20
Function Map ......................................................................................................... 24
Programming Notes ...............................................................................................40
Remote Connect ...........................................................................................20
Edit Function Map .........................................................................................20
Entering a New Value at a Location..................................................... 20
Programming the Account Code, Report Code, and Telephone Number Digits ..
Additional Programming Notes .......................................................... 21
Program User Codes......................................................................................21
Restore Factory Defaults ................................................................................21
Hours Until Next Comm Test.........................................................................22
Call RPM ....................................................................................................... 22
Program RF Data ...........................................................................................22
Programming RF Zone Devices Into the RF Gateway ............................22
Programming RF User Devices Into the RF Gateway .............................23
Programming RF Devices Into the Control Panel ..................................24
System Times ................................................................................................25
System Options .............................................................................................26
Keypad Options ............................................................................................ 27
Zone Definitions ............................................................................................ 28
User Authority Levels .....................................................................................29
Bell Output Activation ...................................................................................30
Programmable Outputs ................................................................................. 30
Programmable Output Activation.........................................................31
Communicator Options ................................................................................32
Event Reporting Phone Selection ................................................................... 33
Telephone Numbers ......................................................................................34
Dialed Digits Allowed ...........................................................................34
Account Numbers .........................................................................................34
Zone Report Code Digits ...............................................................................35
User Report Code Digits ................................................................................36
Auxiliary Key Alarm Report Code Digits .........................................................37
Other Trouble Report Code Digits .................................................................37
Other Event Report Code Digits ....................................................................39
21
Specifications And Features ................................................................................... 43
List of Compatible Accessories .............................................................................. 46
Digital Communicator Table For Contact ID Formats........................................... 47
Agency Requirements ............................................................................................ 49
National Fire Protection Association (NFPA) Rules ............................................... 51
FCC Compliance ..................................................................................................... 54
4
Feature Overview
FEATURE OVERVIEW
8 zones
2 or 4-wire fire zone capability
Integrated Sentrol Series 4000 wireless
Compatible with ESL 521 Smoke Detector for automatic “Clean Me” maintenance reporting
Four exciting new keypads
Pager reporting
A New Standard For Value
The ZX200/ZX210 Control System sets a new stan­dard for value and end-user benefits. Highlights in­clude 8 zone hardwire/wireless flexibility, unique Lifestyle Enhancement features, and an easy to use family of keypads. The ZX200/ZX210 control is pre­programmed at the factory with eight burglary zones so it’s ready to power up and operate out of the box. An optional output driver module provides 10 additional programmable outputs when desired.
ZX System Advantages
Built-in telephone line monitor
Supervised bell circuit
Temporal rhythm fire bell coding
Automatic Smoke Detector Reset feature
Fuse-Free
14" x 14" ‘Big Box’ enclosure avail­able (model ZX210)
system at night can be as easy as saying…or pressing
“Night, Night”.
“More Than A Security System”
The ZX200/ZX210 does more than provide reliable home security - it provides features that complement family lifestyles. User On Premise lets you know when someone’s arrived.
Pager Reporting notifies users of trouble, alarm con­ditions, or other reportable conditions on pagers with digital displays.
The new ZX Control System offers significant benefits for both the installer and end user. Commonality in programming, operation, and accessories mean ZX controls are easier to install and program and reduce inventory and installation costs.
Compatible wireless receivers and sensors overcome installation obstacles and increase sales and profit po­tential. Sensors have been engineered for long-range stability and reliability and the modular 8-zone receiver, with true diversity antenna, mounts anywhere for im­proved reception and performance.
Four all-new keypads provide unique features and dis­plays for easy end-user operation. Each keypad fea­tures three distinct arming levels (Away, Stay & Night) with backlit keys that show system status at a glance and an easy to find Off key with automatic “Mute” feature. Arming the system is easy with quick Two- Button Arming or Double Press Arming. Arming the
“Self-Watch” Fire Zone Features
The ZX200/ZX210 ensures optimum fire zone per­formance and safety with unique “Self Watch” fea­tures. The ZX200/ZX210 is compatible with ESL’s new 521 series smoke detectors for “Clean Me” Au- tomatic Self-Diagnostic Reporting. This feature en­ables the panel to sense when the smoke detector needs cleaning or maintenance over the same two wires used for power and alarm signaling. The con­trol will then signal the Central Station that a smoke detector maintenance trouble signal has occurred ­letting you know
For added security, the ZX200/ZX210 incorporates Automatic Smoke Detector Reset which automati­cally resets the smoke detectors following a manual disarm of the fire system. The ZX200/ZX210 also complies with new NFPA requirements for residen­tial fire installations by providing Temporal Rhythm
Fire Coding and a Supervised Bell Circuit.
5
before a problem occurs.
WIRING DIAGRAM
ZX200/ZX210 Wiring Diagram
+12V NEG
KEYPAD
EARTH
GROUND
UNIFIED
EARTH
GROUND
BATT
XFMR
TRANSFORMER
Recommended:
Basler BE 116220
16.5V / 20VA MIN.
U.L. CLASS II 50/60Hz
WARNING
Internally Fused.
Do Not Short.
Do Not Connect
To A Switched
Red and Black Leads RED = POS. (+) BLACK = NEG. (-)
Receptacle.
12V SEALED
LEAD ACID BATTERY
Yuasa B-1270
QUIESCENT CHARGE CURRENT: 20mA. Replace: Every 3 - 5 years.
OWNERS INSTRUCTION
THIS EQUIPMENT SHOULD BE INSTALLED IN ACCORDANCE WITH THE NATIONAL FIRE PROTECTION ASSOCIATION’S STANDARD 72 (NATIONAL FIRE PROTECTION ASSOCIATION, BATTERYMARCH PARK, QUINCY, MA
02269). PRINTED INFORMATION DESCRIBING PROPER INSTALLATION, OPERATION, TESTING, MAINTENANCE, EVACUATION PLANNING AND REPAIR SERVICE IS TO BE PROVIDED WITH THIS EQUIPMENT.
FLOAT BATTERY
VOLTAGE:
13.6 - 13.8V
Max. current: 500mA.
NOTICE -
Class II Power­Limited
AC
BELL
NEG
1500
1/2 WATT
UL LISTED RESISTORS
MODEL CR853 - 825 E.O.L. MODEL CR854 - 1500 E.O.L.
CONNECTION OF UL COMMERCIAL
POLARIZATION AND NOISE SUPPRESSION DIODE
JUMPER
Class II Power­Limited
KP
+12V
BLACK
CONTROL STATIONS
AND OTHER
PERIPHERALS
UL LISTED
SIGNALING DEVICE
Ademco AB12M
BURGLAR AUDIBLE
-
+
1500 (CR854)
(EOL DEVICE)
GREEN WHITE
DATA
RED
BELLNEG
J-4
WHITE
GREEN
ZONE
2/6
ALL WIRING BETWEEN CONTROL & BELL MUST BE IN CONDUIT.
ADEMCO AB12M
GRADE A BELL COMMERCIAL
TO +12V AUX TERMINAL
ZONE
1/5
NEG
N.O.
N.C. ZONE 1
1500
1/2 WATT
ZONE
METHOD 1
N.C.
1/2 WATT
ZONE 6
825
1/4 WATT
MOTION
DETECTOR
TO NEG TERMINAL
ZONE
2/6
3/7
METHOD 2
N.C.
N.C.
ZONE 2
1500
N.C.
TG+
PG01
NEG
ZONE 3
1500
1/2 WATT
ZONE 7
825
1/4 WATT
+
MPI-206
TG - COM NC NO
PROGRAMMABLE
OUTPUT 1
CONNECTION
Class II Power­Limited
ZONE
2WS
4/8
SWNEG
+--
POWER
CONNECT
RJ31/33/45
CORD
+12V
TELCO
AUX
JACK
LISTED RATE OF RISE OR
FIXED TEMPERATURE THERMOSTAT
--
+
+
POWER
LISTED RATE OF RISE OR
FIXED TEMPERATURE THERMOSTAT
RED
BLACK
BROWN
ALARM
CONTACTS
SENTROL 4-WIRE MODELS
Telephone connection of the fire alarm signal from this system to a fire alarm headquarters or central station is permitted only with the approval of the authority having jurisdiction.
1500 (CR854)
(EOL DEVICE)
SMOKE DETECTOR
SENTROL 2-WIRE MODELS
(See ZX200/ZX210 Interconnect Label
P/N 64600285-NOTE 2)
TO ANY ZONE DEFINED
AS 24-HOUR FIRE
BROWN
POWER SUPERVISION UNIT
ESL MODEL 204-12/24V OR EQUIV.
1500 (CR854)
SMOKE DETECTOR
(See ZX200/ZX210 Interconnect Label
P/N 64600285-NOTE 2)
(CONV ZONING)
FIGURE 1 Suggested UL Household Burglar Alarm and/or Fire (ƒƒ) Alarm Hookup
6
Control Board Terminal Descriptions
TERMINAL FUNCTION DESCRIPTION
AC
XFMR
BELL
AC Input
Supervised Bell Output
(power-limited)
Connect a 16.5 VAC 35 VA UL Class II transformer minimum using 18 gauge minimum 2 conductor wire.Do not exceed 50 feet.
(+)12 VDC. Combined alarm current should not exceed 1.5 amps. Overcurrent protected at 1.85 amps (PTC2). A 1500 Ohm EOL resistor (CR854) bell output fault will occur.
must be connected between the Bell and Neg terminals; otherwise a
TERMINAL DESCRIPTIONS
NEG
KP
+12V
GREEN
DATA
WHITE
DATA
ZONE 1/5
NEG ZONE 2/6 ZONE 3/7
NEG ZONE 4/8
2WS
SWNEG
+12V
AUX
Common Negative
Keypad Power
(power-limited)
Local Data Bus In
Local Data Bus Out
Zone 1/5 Loop (+) Common Negative Zone 2/6 Loop (+) Zone 3/7 Loop (+) Common Negative Zone 4/8 Loop (+)
Two-Wire/Four-Wire Smoke
Switched Negative
Auxiliary Power (power-limited)
BLACK WIRE - (-)12 VDC. Negative connection for Control Stations, ODM, RF receiver, motion detectors, bell output, and other devices.
RED WIRE - (+)12 VDC 500 mA continuous power connection for Control Stations, ODM, and RF Gateway. Overcurrent protected at 1.85 amps (PTC1). CAUTION: Use the KP+12V and the +12V AUX terminals when calculating total current drain.
GREEN WIRE - Connection for Control Stations, ODM and RF receiver. Use 22 gauge wire up to 1000 ft. Use 18 gauge wire up to 2000 ft.
WHITE WIRE - Connection for Control Stations, ODM and RF receiver. Use 22 gauge wire up to 1000 ft. Use 18 gauge wire up to 2000 ft.
Each loop requires a 1500 Ohm end-of-line resistor (P/N CR854) for the primary zone and an 825 Ohm end-of-line resistor (P/N CR853) for the secondary zone. A common negative is shared among all zones. The need for end-of-line resistors may be eliminated on all Burglar defined zones through programming. See Figure 2 and 3 for “2 in 1” Zoning™ wiring examples.
(-) Current limited 60 mA terminal. Negative connection for two-wire/four­wire smoke detectors, glass break detectors, and devices requiring resettable power. The maximum series loop resistance for a two-wire smoke loop is 20 ohms. The maximum Alarm Impedance is 500 ohms.
(+)12 VDC 500 mA continuous power. Overcurrent protected at 1.85 amps (PTC1). Used for powering motion detectors, two-wire/four-wire smoke detectors, glass break detectors, and other accessories. CAUTION: Use the
KP+12V and the +12V AUX terminals when calculating total current drain.
7
“2 in 1” Zoning™
“2 in 1” Zoning
NOTE
If a Normally Open Device (i.e., 4­wire smoke detector) is used with “2 in 1” Zoning™, a short will oc­cur across both zone loops when that device goes into alarm. It is recommended that these types of devices be used with Conventional Zone wiring only.
The ZX200/ZX210 Security Control uses the “2 in 1” Zoning™ method that allows the installer to wire two separate zones in parallel into one set of termi­nals that will save both time and wire costs.
Each zone is uniquely identified by its end-of-line resistor. The Primary Zone (zones 1-4) in each ter­minal is identified by a 1500 Ohm EOL resistor. The Secondary Zone (zones 5 - 8) is identified by an 825 Ohm EOL resistor. The Primary and Secondary zones operate as two independent zones to provide sepa­rate reporting, programming, and displays. Each zone is fully programmable (See Installer Level Pro­gramming). The zones are for Form A, Form B, or Form C sensors. Maximum total loop wire and con-
tact resistance (not including EOL) must not ex­ceed 100 Ohms for the loop to function properly.
There are two methods of wiring for “2 in 1” Zon­ing™. Method 1 wires one zone loop back to the control while a second zone loop is added in paral­lel off the first. This method may be employed in system retrofits, system expansions, or just simply to save wire cost and labor.
Method 2 wires two separate zone loops back into one set of terminals. The panel recognizes each loop independently because two different EOL resistor values are used to differentiate between the Primary Zone (1500 Ohm 1/2 Watt) and the Secondary Zone (825 Ohm 1/4 Watt). This method provides two zones with one set of terminals and is ideal for pre­wire or already installed wiring.
1500 1/2W
Primary Zone
Secondary Zone
825 1/4W
Figure 3 “2 in 1” Zoning™ Wiring - Method 2
NOTE
The resistors in Figures 2 & 3 are 1% values to maintain proper loop resistance values. If replacements are required, please refer to the manufacturer for correct replace­ments. The 1500 Ohm resistor is color coded Brown•Green• Black•Brown•Brown. The 825 Ohm resistor is color coded Gray•Red•Green•Black•Brown.
1500 1/2W
Primary Zone
Secondary Zone
825 1/4W
Figure 2 “2 in 1” Zoning™ Wiring - Method 1
All zones sense five different voltage levels enabling one zone to act as two. Troubleshooting is simple using just a voltmeter at the control. The control monitors the voltage level across the zone and uses the voltage levels in Table 1 to determine whether the zone is normal, open, or shorted.
8
“2 in 1” Zoning™
CONDITION NOMINAL LOOP RESISTANCE VOLTAGE READING
Primary Zone and Secondary Zone Infinite Ohms 5.24 - 8.25 V Open Contacts; Loop Cut or Open
Secondary Zone Open Contact, 1500 Ohms 4.24 - 5.23 V Primary Zone Normal
Primary Zone Open Contact, 825 Ohms 3.24 - 4.23 V Secondary Zone Normal
Primary Zone and Secondary Zone 825 Ohms in parallel with 2.00 - 3.23 V Normal 1500 Ohms = 532 Ohms
Primary Zone and Secondary Zone 0 Ohms 0 - 1.99 V Shorted
Table 1 “2 in 1” Zoning™ Troubleshooting Chart
9
CONVENTIONAL WIRING
Conventional Methods of Wiring
Class ‘B’ End-Of-Line Resistor Supervised Zones
A Class ‘B’ zone must be supervised with a 1500 Ohm 1/2 Watt end-of-line resistor (P/N CR854). This resistor should be installed in series at the furthest point from the control. This configuration must be used whenever both Form A and Form B devices are connected and provides a high degree of protec­tion against compromise or tampering. The control monitors the voltage level across the Primary zone and uses the Primary zone voltage levels in Table 1 to determine whether the zone is normal, open, or shorted. The operation of a zone is programmable (see Installer Level Programming). Maximum total
loop wire and contact resistance (not including EOLs) must not exceed 100 Ohms for the loop to function properly. The 1500 Ohm EOL resistor is optional for Form A connections but is required for Form B.
Normally
Open
Non-Supervised Closed Circuit Loop (No EOL Resistor Supervision)
The EOL resistor is not required on Burglar zones. A conventional closed circuit loop may be connected directly to a primary zone and the zone will have either a short or an open condition. See Installer Level Programming for programming an unsupervised zone. Fire zones may not be installed as unsuper­vised. Only Burglar defined zones may be wired
non-supervised. “2 in 1” Zoning™ is not allowed.
NOTEONLY BURGLAR DEFINED ZONES MAY BE WIRED NON-SUPERVISED. “2 IN 1” ZON-
ING™ IS NOT ALLOWED.
1500 1/2W
Primary Zone
Normally
Closed
Figure 4 Conventional Zone Wiring Method
NOTE
For UL Listed systems, EOL Supervi-
is required.
sion
10
Wireless Devices
WIRELESS DEVICES
The ZX200/ZX210 provides an option for including Wireless (or RF) Devices. The RF Devices may consist of RF Zone Devices (Universals, Door Contacts, Glassbreaks, PIRs and Smoke Detectors) and RF User Devices (Handhelds). These RF Devices require that an RF Gateway be attached to the system. The ZX200/ZX210 is compatible with either a model 4710 or 4720 RF Gateway. If a 4720 RF Gateway is used, it must be set to address ‘1’. Refer to the RF Gateway instructions for address selection.
Mount the RF Gateway as described in the RF Gate­way instructions. Wire the local data bus to the ter­minals: +12V - RED; DATA A - GREEN; DATA B ­WHITE; NEG - BLACK. Set Address switch. Reinstall the cover.
Each of the eight zones on the ZX200/ZX210 may be programmed to be wireless (see Installer Level Programming - Zone Definitions). If a zone is pro­grammed to be wireless, then its hardwire connec­tion is ignored and the zone’s status is retrieved from the RF Gateway.
Up to eight RF Zone Devices and six RF User Devices may be used (see Installer Level Programming - Pro­gramming RF Data Into the RF Gateway). An RF Zone must be mapped to a zone by programming. An RF User Device must be mapped to a valid user passcode by programming.
The RF Gateway and RF Zone Devices should be tem­porarily mounted in their desired locations until they have been tested with the Control Panel. These de­vices may need to be re-oriented or moved to achieve optimal reception. After testing has been completed, they should be permanently mounted.
Strong Signal (HOT or 5 Control Station beeps): a strong or high level RF signal was measured by the receiver for that location of the transmitter. This is a good location for the transmitter and receiver.
Acceptable (ACC or 3 Control Station beeps): a normal or acceptable level of RF signal was mea­sured by the receiver for that location of the trans­mitter. This is a good location for the transmitter and receiver.
Low Signal (LO or 1 Control Station beep): a low or
not acceptable level of RF signal was measured by the receiver for that location of the transmitter. Make multiple test transmissions, making sure that obstructions between the transmitter and receiver are normal but minimized (hands away from units, metal ladders away from receiver, etc.) during these tests. The transmitter and/or receiver will need to be relocated to obtain ACCEPTABLE level readings.
No Signal (NO or 1 long Control Station beep): no RF signal or an extremely low RF signal was mea­sured by the receiver for that location of the trans­mitter. Bring the transmitter to the RF Gateway and activate the transmitter. The red LED on the RF Gate­way should blink. If it does not, then the transmitter is not working. If the red LED does blink, but the signal strength is still NO SIGNAL, then a program­ming error exists. Check the programming of the zone in both the RF Gateway and the panel. If the signal strength is STRONG or ACCEPTABLE, then the transmitter and/or receiver will need to be relocated to obtain ACCEPTABLE level readings. Be sure to power down the control to clear out all signal strength levels before testing the transmitter at its new location.
After testing has been completed, the RF Gateway and RF Zone Devices should be permanently mounted.
To test the Received Signal Strength of each RF Zone Device, use Test 6 - RF Signal Strength Test. From the Control Station press the “8” key, followed by the Installer Code (9632) and then press the “6” key. Next press the RF Zone Device Number (1 to
8). The Control Station will display and sound the Received Signal Strength of the last transmission sent by the RF Zone Device.
NOTE
Series 4000 RF Gateways and transmit­ters which are not UL labeled are not allowed in UL Certificated installations.
11
CONTROL STATION ADDRESSING AND SUPERVISION
Control Station Addressing and Supervision
All Control Stations are shipped from the factory as Control Station #1 and supervised. They may be set to other addresses and to unsupervised as described below.
A supervised Control Station is reported as missing when the system fails to get any response from it. In order to maintain supervision, each supervised Control Station must have its own unique address.
An unsupervised Control Station can be removed from the system without the system detecting that it is missing. The advantage of an unsupervised Con­trol Station is that a system can have as many Con­trol Stations as the power supply can support. By adding additional power supplies, like the HCP­12SUL, Control Stations may be added up to a total of 18 bus devices on the system. For UL listed sys­tems, unsupervised Control Stations are
not allowed.
SSD, LCD, and VFD Control Stations
When unsupervised Control Stations are used, ALL unsupervised LED Con­trol Stations or 2, ALL unsupervised SSD, LCD, and VFD Control Stations must be ad­dressed as 3 or 4. You cannot mix a supervised keypad and an unsuper­vised keypad with the same address setting.
NOTE
must be addressed as 1
LED Control Stations
These Control Stations have two jumpers on the cir­cuit board to set the address and supervision. To change the address of the Control Station #1 to Control Station #2, remove JP2 (see Figure 6). To change a Control Station to unsupervised, remove JP1 (see Figure 6).
These Control Stations have a four position DIP switch on the circuit board to set the address and supervision. To change the Control Station to unsu­pervised, move DIP switch 4 to the ON position. To change the address, the DIP switch setting must be positioned according to Figure 5.
1
ON
OFF
1234
3
ON
OFF
1234
Figure 5 Control Station DIP Switch Settings
2
1234
4
1234
Remove JP1 to unsupervise
JP1
Remove JP2 for keypad 2
JP2
Figure 6 LED Control Station Jumpers
12
CONTROL STATION TROUBLESHOOTING
Control Station Troubleshooting
If a Control Station is incorrectly wired, it will not accept keystroke entries. The following symptoms may appear:
SYMPTOM CONDITION
No Control Station display Black or Red Wire removed or cut
No response from key presses Green Wire removed or cut
Displays “No Communication From Control” code White Wire removed or cut
Green/White Wires reversed Green & White Wires shorted together
The nominal voltage at the control should measure as follows:
TERMINAL VOLTAGE
from Common Negative to GRN DATA ~ 8.7 VDC
from Common Negative to WHT DATA ~ 3.5 VDC
from Common Negative to KP+12V ~13.8 VDC
13
12 VDC OUTPUTS
12 VDC Outputs
The control is supplied with one keypad power output, one auxiliary power output, one bell out­put, and one programmable (PGO1) low current output. (See Figure 1). The low current output on the control can supply 10 mA @ 3VDC.
Additional outputs can be added with the ZXODM Output Driver Module. The module receives its data from the local data bus and provides ten ad­ditional programmable outputs. The ODM outputs provide +12 VDC on activation and must be lim­ited to 40 mA of current draw.
The ODM must be addressed as ODM1. The ODM comes defaulted from the factory as ODM1. You may use multiple ODMs provided that power re­strictions are followed. Connect the ODM to the control as shown in Figure 7. Use the twelve (12) wire cable provided with the ODM for the out­puts as shown.
Output conditions can be programmed as one of many conditions. Refer to Installer Level Program­ming for programming information and restric­tions.
J3 CONNECTIONS
OUTPUT
WIRE COLOR
1Tan
2Pink
3Gray
4 Violet
5 Yellow
6 Orange
7Blue
8 Dk Brown
9 Green
10 White
NEG Black
12V* Red
DATA BUS CONNECTION
RED Connect to Control KP+12V GREEN Connect to Control GREEN WHITE Connect to Control WHITE
BLACK Connect to Control NEG
R19
C7
R21
C3
+
D9D7D6
R18
C5
R25
R29
HICKORY, NC
ASSEMBLED
IN USA
R22
R23
R28
60821484 REV A
COPYRIGHT 1996
D4
C11
D5
D10
R12
R15
R20
R16
D2C6D1
V3
V2
R27
Q2
ACTIVE
C10
D3
Q1
R14
R13
U2
C4
+
V1
J2
B NEG
A
12V
R24
R26
J1
U1
R2
1234
SENTROL
CONTROLS GROUP
Y1
C8
R17
PC BOARD
MADE IN (USA)
R3R4R5R6R7
OUTPUTS
5678
C2
C9
C1
R1
D8
+
U4
R9
R8
R11
R10
J3
NEG
910
12V
14
Data bus connection
Figure 7 ZXODM Wiring Diagram
NOTE
The outputs on this module have lim­ited transient immunity and should not leave the enclosure. Mount mod­ule via the double-sided tape provided on the back of the ODM to the inside of the control enclosure.
J3 Connector
12 VDC OUTPUTS
Outputs may be wired to indicator devices or relay module triggers (like the MPI-206) provided the 40 mA current draw condition is not exceeded. Figure 8 shows a wiring example for a relay to ODM 1 Output 2. Figure 9 shows a wiring example of ODM 1 Output 1 to trigger an LED.
MPI-206
+12V NEG
Red Wire
TG+
Black Wire
TG - COM NC NO
Pink Wire
Connects to J3 (part of 12-wire cable)
Neg
TAN WIRE
BLACK WIRE
* A 470-1000 resistor may be used
Output 1
Figure 9 Output Connected to an LED
NOTE NOTE
The LED and current limiting resistor shown in Figure 9 are not supplied.
*
Figure 8 Output Connected to a Relay
NOTE
Do not exceed 250 mA of total cur­rent through the Red (+12V) and Black wires (Negative) of the twelve wire cable. Add 18 gauge wire from the appropriate control panel termi­nals for total current drains in excess of 250 mA.
15
DIRECT CONNECTION TO A PC
Direct Connection to a PC for Remote Programming
This system requires that a line voltage be provided in order for the telephone interface to operate. This is normally provided via the telephone lines. When performing a direct connection between the system and a modem on a PC, the line voltage must be
ZX200/ZX210
ZONE
ZONE
2/6
3/7
NEG
ZONE
4/8
Red
1 Watt
Resistor
2WS
SWNEG
100
Green
provided from the control panel’s terminal strip. Connect a cable as shown below. This cable may be purchased (P/N ZXDCC01 - ZX200 PC Direct Con­nection Cable) from Sentrol.
+12V
TELCO
AUX
JACK
RJ11
Red
Green
RJ11
Telco In
MODEM
Figure 10 Direct Connection to a PC
16
Operating the System
OPERATING THE SYSTEM
Powering Up With The Control Station
The control comes from the manufacturer with a factory set (default) program. The factory default code for user passcode No. 1 is “1234”. This passcode is authorized to perform all user level func­tions. The default setting for the installer passcode is “9632”. The installer passcode performs the in­staller level functions. For purposes of discussion, the installer and the end user are both considered sys­tem users, but have different levels of authorization. (See Installer Level Programming - User Authority Levels).
When a Control Station is powered-up, it briefly dis­plays a test pattern followed by its data bus address. The Control Station will then begin displaying infor­mation from the control panel. During the first fif­teen seconds after power-up, the control panel will instruct the Control Station to display the panel’s software revision and flash the AWAY, STAY, NIGHT, READY, and TROUBLE LEDs.
Installer Arming and Disarming
The installer passcode may be used to arm the sys­tem. It may be used to disarm, but only if the sys­tem was armed by the installer passcode. It may be used to silence alarms and to silence trouble condi­tions. When it is used to silence a Burglar alarm, it will not disarm or cancel the alarm unless the sys­tem was armed by the installer passcode. For a de­tailed description of arming and disarming proce­dures, see the appropriate User Guide.
Installer On Premises
The first time that an Installer level passcode is used to perform a function, an “Installer On Premises” event is logged to be reported. Before leaving the premises, press and hold the CLEAR key for three seconds and an “Installer Off Premises” event will be logged to be reported.
Trouble Conditions
The possible trouble conditions are:
AC Power Failure Fire Trouble Low Battery Silenced Fire Alarm Memory Error Zone Missing Communication Failure RF Point Not Reporting Missing Keypad Smoke Trouble RF Jamming RF Point Tamper Bell Fault RF Point Low Battery Telco Line Fault RF User Device Low Battery
Zone Trouble
If RF Jamming is detected for at least 90 seconds, then all RF Burglar zones will be faulted.
Clearing Trouble Messages
Most trouble conditions are cleared automatically when the condition that initiated the trouble is re­stored or is eliminated. Three trouble conditions (Memory Error, Smoke Trouble and Missing Keypad) may be cleared manually by pressing and holding the Clear key for three seconds (until two beeps are heard). This action is also required to turn off the Duress output after it has been activated and to cause an “Installer Off Premises” event (see Operating the System - Installer On Premises).
Testing
The ZX200/ZX210 provides the following testing ca­pabilities: Walk Test, Battery Test, Bell Test, Commu­nicator Test, Keypad Test and RF Signal Strength Test. Refer to the appropriate User Guide for instructions on performing these tests. Always ensure that a Walk Test (and an RF Signal Strength Test when applicable) is performed on a new installation.
17
Loading...
+ 39 hidden pages