Sentrol ZX300, SENTROL ZX310 Installation & Programming

Page 1
SENTROL ZX300/ZX310
Expandable Security System Control
Installation/
Programming
1
Page 2
2
Page 3
Table of Contents
Control Board T erminal Descriptions.........................................................................6
Zone Wiring.................................................................................................................... 7
Class ‘B’ End-Of-Line Resistor Supervised Zones ......................................................7
Non-Supervised Closed Circuit Loop (No EOL Resistor Supervision)........................7
ZXEX08 Zone Expander Module............................................................................. ... 7
Wireless Devices ..........................................................................................................8
Control Station Addressing and Supervision............................................................9
SSD, LCD, and VFD Control Stations......................................................................... 9
ICON Control Stations..................................................................................................9
LED Control Stations..............................................................................................9
Unsupervised and Supervised Control Stations..................................................... 9
T ABLE OF CONTENTS
Control Station Troubleshooting..............................................................................10
12 VDC Outputs .........................................................................................................11
Operating the System ................................................................................................13
Powering Up The Control ...........................................................................................13
Testing ...............................................................................................................13
Installer Arming and Disarming ..................................................................................13
Trouble Conditions .....................................................................................................1 3
Clearing Trouble Messages .......................................................................................13
Installer on Premises..................................................................................................13
Programming the Control.................................................................................................14
Introduction ...............................................................................................................14
Local Programming ....................................................................................................1 4
Programming Zone Names....................................................................................... 14
Installer Level Programming .....................................................................................15
Menu Options .............................................................................................................15
Program Function Map....................................................................................15
Entering a New Value at a Location................................................................15
Programming the Account Code and Telephone Number Digits....................16
Additional Programming Notes .......................................................................16
Program User Codes.......................................................................................16
Restore Factory Defaults ................................................................................16
Hours Until Next Comm Test...........................................................................1 7
Program RF Data............................................................................................17
Programming RF Zone Devices Into the RF Gateway ...................................17
Programming RF User Devices Into the RF Gateway....................................18
Programming RF Devices Into the Control Panel...........................................18
3
Page 4
T ABLE OF CONTENTS
Specifications And Features .....................................................................................19
List of Compatible Accessories................................................................................22
SIA and Contact ID Formats......................................................................................23
Agency Requirements ...............................................................................................25
National Fire Protection Association (NFPA) Rules................................................27
FCC Compliance.........................................................................................................30
4
Page 5
ZX300/ZX310 Wiring Diagram
WIRING DIAGRAM
7167-1459:114
FIGURE 1 Suggested UL Household Burglar Alarm and/or Fire (ƒƒ) Alarm Hookup
5
Page 6
TERMINAL DESCRIPTIONS
Control Board Terminal Descriptions
TERMINAL FUNCTION DESCRIPTION
AC
BELL
NEG
KP+12V
GREEN
DAT A
WHITE
DAT A
NEG Zone 1 Zone 2 Zone 3 Zone 4 NEG Zone 5 Zone 6 NEG Zone 7 Zone 8
AC Input
Supervised Bell Output
(power-limited)
Common Negative
Keypad Power (power-limited)
Local Data Bus In
Local Data Bus Out
Zone Inputs
Connect a 16.5 VAC 15 VA UL Class II transformer minimum using 18 gauge minimum 2 conductor wire. Do not exceed 50 feet.
(+)12 VDC. Combined alarm current should not exceed 1.0 amps. Overcurrent protected at 1.35 amps (PTC2). A 1500 Ohm EOL resistor (CR854) a bell output fault will occur.
BLACK WIRE - (-)12 VDC. Negative connection for Control Stations, ODM, RF receiver, zone expander, motion detectors, bell output, and other devices.
RED WIRE - (+)12 VDC 500 mA continuous power connection for Control Stations, ODM, zone expander, and RF Gateway. Overcurrent protected at
1.35 amps (PTC1). CAUTION: Use the KP+12V and the +12V AUX
terminals when calculating total current drain.
GREEN WIRE - Connection for Control Stations, zone expander, ODM and RF
receiver. Use 22 gauge wire up to 1000 ft. Use 18 gauge wire up to 2000 ft. WHITE WIRE - Connection for Control Stations, zone expander, ODM and RF
receiver. Use 22 gauge wire up to 1000 ft. Use 18 gauge wire up to 2000 ft.
Each loop requires a 1500 Ohm end-of-line resistor (P/N CR854). A common negative is shared among all zones. The need for end-of-line resistors may be eliminated on all Burglar defined zones through programming.
must be connected between the Bell and Neg terminals; otherwise
2WS
+12V AUX
Two-Wire
Smoke Terminal
Auxiliary Power
(power-limited)
Current limited 100 mA terminal. Connection for two-wire/four-wire smoke detectors, glass break detectors, and devices requiring resettable power. The maximum series loop resistance for a two-wire smoke loop is 20 ohms. The maximum Alarm Impedance is 500 ohms.
(+)12 VDC 500 mA continuous power. Overcurrent protected at 1.35 amps (PTC1). Used for powering motion detectors, CO detectors, and other accessories. CAUTION: Use the KP+12V and the +12V AUX terminals when calculating total current drain.
6
Page 7
Zone Wiring
ZONE WIRING
Class ‘B’ End-of-Line Resistor Supervised Zones
A Class ‘B’ zone must be supervised with a 1500 Ohm 1/2 Watt end-of-line resistor (P/N CR854). This resistor should be installed in series at the furthest point from the control. This configuration must be used whenever both Form A and Form B devices are connected and provides a high degree of pro­tection against compromise or tampering. The con­trol monitors the voltage level across the zone and uses the zone voltage levels in Table 1 to determine whether the zone is normal, open, or shorted. The operation of a zone is programmable (see Program­ming Record Book). Maximum total loop wire and
contact resistance (not including EOLs) must not exceed 100 Ohms for the loop to function prop­erly . The 1500 Ohm EOL resistor is optional for Form A connections but is required for Form B.
Normally
Open
Non-Supervised Closed Circuit Loop (No EOL Resistor Supervision)
The EOL resistor is not required on Burglar zones. A conventional closed circuit loop may be connected directly to a zone and the zone will have either a short or an open condition. See Programming Record Book for programming an unsupervised zone. Fire zones may not be installed as unsuper­vised. Only Burglar defined zones may be wired non­supervised.
NOTE
For UL Listed systems, EOL Supervision is required.
ZXEX08 Zone Expander Module
This module provides an additional 8 zones (zones 9-16) for the ZX300/ZX310 control. These zones are wired the same as the 8 on-board zones and the JP1 jumper must be in place.
1500Ω 1/2W
Primary Zone
Normally
Closed
Figure 2 Zone Wiring
CONDITION NOMINAL LOOP RESISTANCE VOL TAGE READING
Mount the module in a ZX310 enclosure as shown in the ZXEX08 insert using the screws and stand­offs provided. For mounting with the ZX300 or in a remote location, use a suitable enclosure, like the EB1511.
Connect the module to the ZX300/ZX310 local data bus using either the "quick connection" or the data bus terminals on the module. The "Active" LED flashes to indicate the module is communicating with the control.
NOTEONLY BURGLAR DEFINED ZONES MAY
Zone Open Infinite Ohms 9.75 - 13.85 V
Zone Normal 1500 Ohms 2.82 - 9.74 V
Zone Shorted 0 Ohms 0.00 - 2.81 V
Table 1 Zone Troubleshooting Chart
7
Page 8
WIRELESS DEVICES
Wireless Devices
The ZX300/ZX310 provides an option for including Wireless (or RF) Devices. The RF Devices may con­sist of RF Zone Devices (Universals, Door Con­tacts, Glassbreaks, PIRs and Smoke Detectors) and RF User Devices (Handhelds). These RF Devices require that an RF Gateway be attached to the sys­tem. The ZX300/ZX310 is compatible with either a model 4710 or 4720 RF Gateway which are UL listed for household fire and burglary and commercial fire. If a 4720 RF Gateway is used, it must be set to ad­dress ‘1’. Refer to the RF Gateway instructions for address selection.
4710 RF Gateway - provides up to 8 RF Zone Devices and up to 8 RF User Devices. It can only provide for zones 9-16.
4720 RF Gateway - provides up to 16 RF Zone Devices and up to 8 RF User Devices. It can provide for zones 1-16.
Mount the RF Gateway as described in the RF Gate­way instructions. Wire the local data bus to the ter­minals: +12V - RED; DATA A - GREEN; DATA B ­WHITE; NEG - BLACK. Set Address switch. Rein­stall the cover.
See Installer Level Programming - Programming RF Data Into the RF Gateway . An RF User Device must be mapped to a valid user passcode by program­ming.
The RF Gateway and RF Zone Devices should be temporarily mounted in their desired locations until they have been tested with the Control Panel. These devices may need to be re-oriented or moved to achieve optimal reception. After testing has been completed, they should be permanently mounted.
ceived Signal Strength of the last transmission sent by the RF Zone Device. See results below:
Strong Signal (5 Control Station beeps): a strong or high level RF signal was measured by the receiver for that location of the transmitter. This is a good location for the transmitter and receiver.
Acceptable (3 Control Station beeps): a normal or acceptable level of RF signal was measured by the receiver for that location of the transmitter. This is a good location for the transmitter and receiver.
Low Signal (1 Control Station beep): a low or acceptable level of RF signal was measured by the receiver for that location of the transmitter. Make multiple test transmissions, making sure that obstruc­tions between the transmitter and receiver are nor­mal but minimized (hands away from units, metal ladders away from receiver, etc.) during these tests. The transmitter and/or receiver will need to be relo­cated to obtain ACCEPTABLE level readings.
No Signal (1 long Control Station beep): no RF sig­nal or an extremely low RF signal was measured by the receiver for that location of the transmitter. Bring the transmitter to the RF Gateway and activate the transmitter. The red LED on the RF Gateway should blink. If it does not, then the transmitter is not work­ing. If the red LED does blink, but the signal strength is still NO SIGNAL, then a programming error ex­ists. Check the programming of the zone in the RF Gateway. If the signal strength is STRONG or AC­CEPT ABLE, then the transmitter and/or receiver will need to be relocated to obtain ACCEPTABLE level readings. Be sure to power down the control to clear out all signal strength levels before testing the trans­mitter at its new location.
After testing has been completed, the RF Gateway and RF Zone Devices should be permanently mounted.
not
To test the Received Signal Strength of each RF Zone Device, use Test 6 - RF Signal Strength Test. From the Control Station press the “8” key , followed by the Installer Code (9632) and then press the “6” key . Next press the RF Zone Device Number (1-16). The Control Station will display and sound the Re-
NOTE
Series 4000 RF Gateways and transmitters which are not UL labeled are not allowed in UL Certificated installations.
8
Page 9
CONTROL STATION ADDRESSING AND SUPERVISION
Control Station Addressing and Supervision
All LCD Control Stations are shipped from the fac­tory as Control Station #1 (#3 for Icon Control Sta­tions) and supervised. They may be set to other ad­dresses and to unsupervised as described below.
SSD, LCD, and VFD Control Stations
These Control Stations have a four position DIP switch on the circuit board to set the address and supervision. To change the Control Station to unsu­pervised, move DIP switch 4 to the ON position. To change the address, the DIP switch setting must be positioned according to Figure 3.
LED Control Stations
These Control Stations have two jumpers on the cir­cuit board to set the address and supervision. To change the address of Control Station #1 to Control Station #2, remove JP2 (see Figure 4). To change a Control Station to unsupervised, remove JP1 (see Figure 4).
Supervised and Unsupervised Control Stations
Figure 3 Control Station DIP Switch Settings
ICON Control Stations
These Control Stations have two jumpers on the cir­cuit board to set the address and supervision. To change the address of Control Station #3 to Control Station #4, remove JP2 (see Figure 4). To change a Control Station to unsupervised, remove JP1 (see Figure 4).
Remove JP1 to unsupervise
JP1
Remove JP2 for keypad 2 (LED) or keypad 4 (ICON)
JP2
A supervised Control Station is reported as missing when the system fails to get any response from it.
If more than one supervised Control Station is set to a particular address, then none of those Control Sta­tions will function properly. Only one supervised Control Station may be used at an address.
An unsupervised Control Station can be removed from the system without the system detecting that it is missing. The advantage of an unsupervised Con­trol Station is that a system can have as many Con­trol Stations as the power supply can support. Mul­tiple unsupervised Control Stations may be used at any address. When unsupervised SSD, LCD, and VFD Control Stations are used, they must be set to address 3 or 4. By adding additional power supplies, like the HCP12SULC, Control Stations may be added up to a total of 18 bus devices on the system.
For UL listed systems, unsupervised Control Sta­tions are not allowed.
If an unsupervised Control Station is set to the same address as a supervised Control Station, then the unsupervised Control Station will not function. Do
not mix a supervised Control Station with unsu­pervised Control Stations at the same address.
Figure 4 LED & ICON Control Station Jumpers
9
Page 10
CONTROL ST A TION TROUBLESHOOTING
Control Station Troubleshooting
If a Control Station is incorrectly wired, it will not accept key­stroke entries. The following symptoms may appear:
SYMPTOM CONDITION
No Control Station display or LEDs Black or Red Wire removed or cut No response from key presses Green Wire removed or cut
Two supervised Control Stations at the same address
LEDs flash and may display White Wire removed or cut “No Communication From Control” code Green/White Wires reversed
Green & White Wires shorted together
The nominal voltage at the control (with a single Control Station connected) should measure as follows:
TERMINAL VOLTAGE
from Common Negative to GRN DATA ~ 9.3 VDC from Common Negative to WHT DATA ~ 10.7 VDC from Common Negative to KP+12V ~13.8 VDC
10
Page 11
12 VDC Outputs
The control is supplied with one keypad power output, one auxiliary power output, one bell out­put, and one programmable (PGO1) low current output. (See Figure 1). The low current output on the control can supply 10 mA @ 3VDC.
Additional outputs can be added with the ZXODM Output Driver Module. The module receives its data from the local data bus and provides ten ad­ditional programmable outputs. The ODM outputs provide +12 VDC on activation and must be lim­ited to 40 mA of current draw.
The ODM comes defaulted from the factory as ODM1. Y ou may use multiple ODMs provided that power restrictions are followed. All ODMs must be addressed as ODM1 and they all will provide identical ouputs. Connect the ODM to the control as shown in Figure 5. Use the twelve (12) wire cable provided with the ODM for the outputs as shown.
12 VDC OUTPUTS
Output conditions can be programmed as one of many conditions. Refer to the Programming Record Book for programming information and re­strictions.
Figure 5 ZXODM Wiring Diagram
NOTE
The outputs on this module have lim­ited transient immunity and should not leave the enclosure. Mount mod­ule via the double-sided tape pro­vided on the back of the ODM to the inside of the control enclosure.
11
Page 12
12 VDC OUTPUTS
Outputs may be wired to indicator devices or relay module triggers (like the MPI-206) provided the 40 mA current draw condition is not exceeded. Figure 6 shows a wiring example for a relay to ODM 1 Out­put 2. Figure 7 shows a wiring example of ODM 1 Output 1 to trigger an LED.
MPI-206
+12V NEG
Red Wire
TG+
Black Wire
TG - COM NC NO
Pink Wire
Connects to J3 (part of 12-wire cable)
Neg
TAN WIRE
BLACK WIRE
* A 470-1000 resistor may be used
Output 1
Figure 7 Output Connected to an LED
NOTE
NOTE
The LED and current limiting resis­tor shown in Figure 7 are not sup­plied.
*
Figure 6 Output Connected to a Relay
NOTE
Do not exceed 250 mA of total cur­rent through the Red (+12V) and Black wires (Negative) of the twelve wire cable. Add 18 gauge wire from the appropriate control panel termi­nals for total current drains in excess of 250 mA.
12
Page 13
Operating the System
Powering Up The Control
OPERA TING THE SYSTEM
The control comes from the manufacturer with a fac­tory set (default) program. The factory default code for user passcode No. 1 is “1234”. This passcode is authorized to perform all user level functions. The default setting for the installer passcode is “9632”. The installer passcode performs the installer level functions. For purposes of discussion, the installer and the end user are both considered system us­ers, but have different levels of authorization (see the Programming Record Book).
When a Control Station is powered-up, it briefly dis­plays a test pattern followed by its data bus address. The Control Station will then begin displaying infor­mation from the control panel. During the first fif­teen seconds after power-up, the control panel will instruct the Control Station to display the panel’s software revision and flash the AWAY, STAY and NIGHT LEDs.
If the system is armed when it is powered up, viola­tions from all the Burglar zones are ignored for three minutes. This allows all armed PIRs to stabilize with out causing false alarms.
tem was armed by the installer passcode. For a detailed description of arming and disarming proce­dures, see the appropriate User Guide.
Trouble Conditions
The possible trouble conditions are:
AC Power Failure Fire Trouble Low Battery Silenced Fire Alarm Memory Error Zone Missing Communication Failure RF Point Not Reporting Missing Keypad Smoke Trouble RF Jamming RF Point Tamper Bell Fault RF Point Low Battery Telco Line Fault RF User Device Low Battery Zone Trouble
If RF Jamming is detected for at least 90 seconds, then all RF Burglar zones will be faulted.
Clearing Trouble Messages
Testing
The ZX300/ZX310 provides the following testing ca­pabilities: Walk Test, Battery Test, Bell Test, Com­municator T est, Keypad T est and RF Signal Strength Test. Refer to the appropriate User Guide for in­structions on performing these tests. Always en­sure that a Walk Test (and an RF Signal Strength Test when applicable) is performed on a new instal­lation.
Installer Arming and Disarming
The installer passcode may be used to arm the sys­tem. It may be used to disarm, but only if the sys­tem was armed by the installer passcode. It may be used to silence alarms and to silence trouble condi­tions. When it is used to silence a Burglar alarm, it will not disarm or cancel the alarm unless the sys-
Most trouble conditions are cleared automatically when the condition that initiated the trouble is re­stored or is eliminated. Three trouble conditions (Memory Error, Smoke Trouble and Missing Keypad) may be cleared manually by pressing and holding the Clear key for three seconds (until two beeps are heard). This action is also required to turn off the Duress output after it has been activated and to cause an "Installer Off Premises" event. A Bell Si­lenced trouble condition can only be cleared by per­forming a smoke reset operation.
Installer On Premises
The first time that an Installer level passcode is used to perform a function, an "Installer On Premises" event is logged to be reported. Before leaving the premises, press and hold the CLEAR key for three seconds and an "Installer Off Premises" event will be logged to be reported.
13
Page 14
PROGRAMMING THE CONTROL
Programming the Control
Introduction
The control may be programmed locally from any SSD, LCD, VFD, or ICON control station. Program­ming with an LED Control Station is not supported.
Local Programming
There are two levels of Control Station programming: User level and Installer level.
User Level
User level programming provides the ability to add, change, or delete user passcodes. A user passcode with authority level 1 is required to access the user level programming. See the appropriate User Guide for more information regarding user level program­ming.
Installer Level
Programming Zone Names
Zone names may be programmed on LCD and VFD Control Stations without going into Installer Level Programming. To program zone names:
1. Press the CLEAR and ENTER keys simulta­neously . The control station prompts you to en­ter the zone number you wish to program/ change.
2. Enter a number corresponding to the Zone ID and press Enter. Once a valid Zone ID is se­lected, the control displays the Zone ID and the current Zone Name with the cursor on the first character. Press the key associated with each character. Each keypress changes the display to the next character listed for that key . A maxi­mum of 10 characters, including spaces, may be used for each zone name.
The following table lists the characters available for the Zone name.
yeK sretcarahC
Installer level programming allows total customization of the control’s operating features. The installer passcode (User 9) is required to ac­cess installer level programming. Anyone attempt­ing installer level programming should be familiar with the contents of this publication prior to program­ming the control panel.
NOTE
If the installer code is lost or forgot­ten, it may be impossible to program the control locally.
1#@?>=<;:9876543210 2#CBA 3#FED 4#IHG 5#LKJ 6#ONM 7#SRQP 8#VUT 9#_^]¥[ZYXW 0#/.-,+*)('&%$#"!ecaps
cinaPtfeLnoitisopenotfelrosrucehtsevom
cinaPthgiRnoitisopenothgirrosrucehtsevom
3. If the ENTER or CLEAR key is pressed and no changes have been made, the control station returns to the Zone ID prompt. If the CLEAR key is pressed and changes have been made, all changes are cleared and the control station displays the original Zone Name. To save changes to the Zone Name, press the ENTER key. The control station returns to the Zone ID prompt. Press the CLEAR key to return to Ready mode.
14
Page 15
INST ALLER LEVEL PROGRAMMING
Installer Level Programming
Menu Options
Entering a New Value at a Location
This section will describe Installer Level Program­ming as performed locally from a Control Station. For upload/download capabilities, please contact Technical Support at 800.800.2027.
To enter Installer Level Programming, press the PROGRAM (9) key and enter the installer passcode (default = 9632). The Control Station will then prompt you to select a programming option from 1 to 9 where:
1 = RESERVED FOR FUTURE USE 2 = RESERVED FOR FUTURE USE 3 = PROGRAM FUNCTION MAP 4 = RESERVED FOR FUTURE USE 5 = PROGRAM USER CODES 6 = RESTORE FACTORY DEFAULTS 7 = SET HOURS UNTIL NEXT COMM TEST 8 = RESERVED FOR FUTURE USE 9 = PROGRAM RF DATA
Program Function Map
While the Control Station is displaying the value at a location, you can enter digits to change the value at that location. The new value is displayed as you enter the digits. Other keys work as follows:
ENTER - if pressed after new digits are
entered, the displayed value is stored at the current location.
- if pressed with no new digits entered, then it will go to the next location.
Right Panic Key - if pressed, it will go back one
location and ignore any digits entered.
CLEAR - if pressed after new digits are
entered, the new digits will be erased and the original value will be re-displayed at the lo­cation.
- if pressed with no new digits entered, then it will return to the LOCATION prompt.
Press the ’9‘ key and enter the installer passcode to enter programming mode. Press the ‘3’ key to enter Program Function Map mode. The Control Station will prompt you for a location to be programmed. See the Programming Record Book for location num­bers, definitions, and valid entries for the locations. From this mode, you may program the entire Func­tion Map except for User Codes. (See Installer Level Programming - Program User Codes).
From the LOCATION prompt, enter digits for the desired location number. The digits entered will be displayed. If more than three digits are entered, the first digit entered will be discarded. If you make a mistake, you may press the CLEAR key to clear out the location and start over. When the desired loca­tion number is displayed, press the ENTER key . The Control Station will then display the current value programmed at that location.
OFF CANCEL - if pressed, momentarily dis-
plays the present location number (SSD Control Sta­tion).
NOTE
When you press the ENTER key to store the new value, the system will store the value as entered. It is the responsibility of the programmer to enter a value within the specified range. If the value entered is out of the range, then undesirable operation may occur.
NOTEWHEN YOU PRESS THE ENTER KEY TO
STORE THE NEW VALUE, THE SYSTEM
WILL STORE THE VALUE AS ENTERED.
IT IS THE RESPONSIBILITY OF THE PROGRAMMER TO ENTER A VALUE WITHIN THE SPECIFIED RANGE. IF THE VALUE
15
ENTERED IS OUT OF THE RANGE, THEN
UNDESIRABLE OPERATION MAY OCCUR.
Page 16
INST ALLER LEVEL PROGRAMMING
Programming the Account Code and Telephone Number Digits
When the location being programmed is an account code or telephone number digit the value will be dis­played as an “H” followed by a single digit. The “H” indicates that this location is a Hexadecimal field. The valid entries for these locations are “0” through “F”, where A - F correspond to 10 - 15 respectively.
To program a digit, enter digits as normal. To enter an A - F, enter a ‘1’ followed by a ‘0’ through ‘5’.
As in programming normal fields, if too many digits are entered, the first digit entered will be discarded. The ENTER, OFF CANCEL, Right Panic, and CLEAR keys will work the same as described above.
Additional Programming Notes
To exit out of Edit Function Map mode and return the Control Station to the idle state, press the CLEAR key from the LOCATION prompt. (You may need to press the CLEAR key several times to get to the LOCATION prompt). When the installer passcode is used for the first time, an "Installer on Premises" event is logged to be reported. Before leaving, the CLEAR key must be pressed and held for 3 sec­onds to log an "Installer off Premises" event to be reported.
When programming the value at the last program­ming location, the Control Station will return to the LOCATION prompt if the ENTER key is pressed.
3. Enter the ID number then press the ENTER key.
4. Enter the new four-digit passcode. The Control Station will beep twice and return to the User ID prompt.
5. Enter a new ID number or press the CLEAR key to return to the Ready mode.
T o view an existing passcode, press the ENTER key after each digit is displayed. If the new passcode being entered is a duplicate of an existing one, the Control Station will sound an error tone and return to the first digit location so that you may try again.
If you wish to make a User passcode inoperable, enter “0,0,0,0” as the new four-digit passcode.
Restore Factory Defaults
This function provides a means to completely wipe out the panel’s memory and restore it to a factory default state. If successfully completed, the panel will:
default the entire Function Map (including User
Passcodes and Zone Names)
clear the Event Log
clear all alarm, trouble and armed conditions
not affect RF Data in the RF Gateway
Press the ’9‘ key and enter the installer passcode to enter programming mode. Press the ‘6’ key to enter Restore Factory Defaults mode. The Control Sta­tion will prompt you to re-enter the installer passcode for verification.
Program User Codes
The installer passcode has the authority to edit user passcodes locally . The control may be programmed with up to 8 user passcodes and the installer passcode (USER 9). See the Programming Record Book for instructions on setting the authority level for the 8 user passcodes. To program or change a user or installer passcode:
1. Press the ‘9’ key and enter the installer passcode to enter programming mode.
2. Press the ‘5’ key to Program User Codes. The Con­trol Station will prompt you to enter the User ID of the passcode that you wish to program/change.
If it is entered correctly, the Control Station will go into a locked out state for a few seconds and then may display the No Communication condition be­fore displaying the panel revision and returning to the Ready mode.
16
Page 17
INST ALLER LEVEL PROGRAMMING
Hours Until Next Comm Test
The scheduling of Automatic Communications T ests requires programming the number of “Days Between Comm T ests”. If “Days Between Comm T ests” is zero, then no automatic comm tests will occur. Other­wise, a comm test will occur on an interval deter­mined by the “Days Between Comm Tests”.
The time that an auto comm test occurs will be the same time on each comm test day. That time is automatically set via a random number whenever the system is powered-up. The time can also be ad­justed by setting the ”Hours Until Next Comm Test“.
Press the ’9‘ key and enter the installer passcode to enter programming mode. Press the ‘7’ key to set the Hours Until Next Comm Test. The Control Sta­tion will display zero (0).
Enter a number between 1 and 255. If a mistake is made, press the CLEAR key to start over. If a num­ber greater than 255 is entered, the first digit en­tered will be discarded. When the desired number of hours is displayed, press the ENTER key. The Control Station will return to idle. To exit out of this function without setting the number of hours, press the CLEAR key.
Programming RF Zone Devices Into the RF Gateway
Press the ‘9’ key and enter the installer passcode to enter programming mode. Press the ‘9’ key to Pro­gram RF Data. The Control Station prompts you to select an RF Device to program.
Enter 1 thru 16 to select an RF Zone and press EN­TER. The Control Station displays the eight digits that are currently programmed in the RF Gateway for that zone. The digits are displayed one at a time. For each digit, you may program a new value by pressing a digit key. The Control Station will auto­matically move to the next digit. To move to the next digit without changing the current digit, press the ENTER key.
The first digit to enter is the Supervision setting where:
0 = Unsupervised 1 = Reserved 2 = Reserved 3 = 4 Hours 4 = 24 Hours
The next seven digits to enter come directly off of a label on the RF Device.
Program RF Data
In order for an RF Zone Device or RF User Device to be received by the RF Gateway, the address of the RF Device must be programmed into the RF Gateway. The ZX300/ZX310 can support up to 16 RF Zones and 8 RF User Devices. The RF Zones are programmed into the RF Gateway as devices 1­16 corresponding to zones 1-16. The RF User De­vices are programmed into the RF Gateway as de­vices 17-24 in any order (there is no correlation be­tween these devices and the Control Panel’s configu­ration data). The 4710 RF Gateway is restricted to devices 9-16 for zones 9-16 and devices 17-24 for eight RF User Devices.
If you make a mistake while entering the eight dig­its, press the CLEAR key and the Control Station returns to the first digit.
After the last digit is entered, the data is sent to the RF Gateway and is confirmed and the Control Sta­tion returns to the RF Device selection prompt. If the data is successfully loaded into the RF Gate­way , the Control Station beeps twice. If the RF Gate­way does not respond, the Control Station sounds an error tone and briefly displays an error message. Check the data bus connections to the RF Gate­way. If the 8 digit number entered for the RF Zone is already stored in the RF Gateway for another zone, the Control Station sounds an error tone and briefly displays a message indicating the duplicate zone.
From the RF Device prompt, select another RF Zone Device or press the CLEAR key to exit.
17
Page 18
INST ALLER LEVEL PROGRAMMING
Programming RF User Devices Into the RF Gateway
Press the ‘9’ key and enter the installer passcode to enter programming mode. Press the ‘9’ key to Pro­gram RF Data. The Control Station prompts you to select an RF Device to program.
Enter 17 thru 24 to select an RF User Device and press ENTER. The Control Station displays the eight digits that are currently programmed in the RF Gate­way for that device. The digits are displayed one at a time. For each digit, you may program a new value by pressing a digit key. The Control Stations will automatically move to the next digit. To move to the next digit without changing the current digit, press the ENTER key.
Enter ‘1’ for the first digit. The second digit to enter defines the operation of
the key(s) on the RF User Device, where:
SEC KEY KEY KEY KEY
DIGIT A B C D
1 AWAY STAY NIGHT OFF/CANCEL 2 AWAY STAY ACCESS OFF/CANCEL 3 AWAY STAY PANIC/HOLDUP OFF/CANCEL 4 AWAY STAY AUX/MED OFF/CANCEL 5 AWAY STAY NOT USED OFF/CANCEL 6 AWAY PANIC/HOLDUP NOT USED OFF/CANCEL 7 STAY PANIC/HOLDUP NOT USED OFF/CANCEL 8 STAY PANIC/HOLDUP AUX/MED OFF/CANCEL 9 AWAY NOT USED NOT USED OFF/CANCEL
The next six digits to enter come directly off of a label on the RF User Device.
If you make a mistake while entering the eight dig­its, press the CLEAR key and the Control Station returns to the first digit.
Check the data bus connections to the RF Gate­way. If the 8 digit number entered for the RF User Device is already stored in the RF Gateway for an­other device, the Control Station sounds an error tone and briefly displays a message indicating the duplicate device.
From the RF Device prompt, select another RF User Device or press the CLEAR key to exit.
Programming RF Devices Into the Control Panel
After the RF Devices have been programmed into the RF Gateway, they must also be programmed in the Control Panel. The programming options for the Control Panel’s Function Map are described in the Programming Record Book. When RF Devices are used in an installation, be sure to consider the fol­lowing:
For an RF Zone Device, the zone data must be pro­grammed for the selected zone. The Zone T ype and Zone Attributes locations are programmed as usual. The Zone Supervision must be programmed to 7 (wireless zone).
For an RF User Device, a user passcode must be created (see Installer Level Programming - Program User Codes) that consists of the last four digits of the RF Device’s address. An appropriate authority level must also be programmed for that user.
NOTE
Once all the above steps are per­formed, the Control Station may sound a Trouble tone. The Con­trol Station will display ”Trouble­RF Point Not Reporting“ for each RF Zone. These conditions are cleared as a proper transmission is received from each wireless Zone Device.
After the last digit is entered, the data is sent to the RF Gateway and is confirmed and the Control Sta­tion returns to the RF Device selection prompt. If the data is successfully loaded into the RF Gate­way , the Control Station beeps twice. If the RF Gate­way does not respond, the Control Station sounds an error tone and briefly displays an error message.
If the Trouble condition does not clear, then there is an error in the programming of the Gateway or control or the RF Gateway is not responding to the RF signal from the sensor.
18
Page 19
SPECIFICA TIONS AND FEATURES
Specifications And Features
Recommended Batteries
ZX300/ZX310 Control Board
(supplied separately)
Eight (8) two-wire zones, each supervised with
a 1500 Ohm end-of-line resistor. Expandable to 16 two-wire zones with ZXEX08 zone expander.
Two-wire smoke detector zone on control (can
be used in place of zone 8).
Three (3) Control Station activated panic zones.
Nominal current drain for control board only 50
mA.
Watchdog microprocessor monitoring.
Superior six (6) stage lightning/transient protec-
tion.
One assignable high current alarm output. (Su-
pervised Bell Output).
One assignable low current output (10 mA @ 3
VDC).
Expandable to eleven (11) low current outputs
via an output driver module.
Continuous battery monitoring.
Low voltage detection monitoring @ 11.3 volts
threshold.
Automatic system shutdown if voltage falls be-
low 9.8V.
Operating temperature range inside the enclo-
sure: 32
Two or four-wire smoke zones available.
Keypad Programmable.
Loop response time: 320 msec (general pur-
pose hardwired zones), 1600 msec (two-wire smoke zone).
°F to 122°F (0°C to +50°C).
Power Supply
Fully regulated 13.8 volt 900 mA supply avail-
able with a 16.5 VAC 35 VA transformer.
Optional 16.5V 25 VA transformer provides 500
mA power.
Reverse polarity protection on battery inputs.
Float charging circuit: 13.8 volts DC.
Rechargeable 12 VDC 7 Ah sealed lead acid.
Use two (2) batteries to meet CSFM and House­hold Fire requirement of 24-hour standby at 450 mA.
Rechargeable 12 VDC 17.2 Ah sealed lead acid. Use
one (1) battery to meet CSFM requirement of 24 hours of standby at 450 mA.
Recommended Transformers
(supplied separately)
UL Listed Class II plug-in; 16.5 VAC 15 VA sec-
ondary; 120 V 60 Hz primary connected to 24­hour unswitched outlet.
Optional UL Listed Class II plug-in 16.5 VAC 25
VA secondary, 120 V 60 Hz primary connected to 24-hour unswitched outlet.
For UL Commercial Burglary, the transformer to be used is a 16.5 V AC 35 VA UL Class II Basler BE 116220.
Enclosure
Twenty (20) gauge metal cabinet with knockout
for optional cam lock. Dimensions: 9"W x 10"H x 2.875"D (228.6 mm x 254 mm x 73.02 mm).
Optional EX1414 20 gauge locking metal cabinet
with two keys. Dimensions 14"W x 14"H x 3.5"D (356 mm x 356 mm x 89 mm).
TC1100 T amper Resistant Enclosure: extra high
security cover (uses EX1414 option).
Optional pre-configured assembly: ZX310
(ZX300 Control Board mounted into the EX1414 enclosure).
Digital Communicator
DTMF Touchtone™ or Rotary (pulse) dialing.
Rotary speed: 10pps, (selectable U.S. style 60% break, 40% make or International style 67% break, 33% make).
Ringer equivalence: 0.0B.
Transmission formats include: Contact ID, SIA
Level 1, Pager.
19
Page 20
SPECIFICA TIONS AND FEA TURES
Reports to most major Central Station receiv-
ers.
Primary phone number can have up to 20 dig-
its.
Secondary phone number can have up to 20
digits.
Pager phone number can have up to 20 digits.
Reporting capabilities: two 6-digit account num-
bers, report by zone, opening and closing re­ports, force arm/bypass reports, restoral reports, trouble reports, cancel reporting, low battery , AC failure/restoral.
Dual and split reporting capability.
Pager capability with 16-digit programmable
message and 2-digit coded messages.
Disable call waiting.
Control Stations
Color-coded four-wire data bus connection.
19-Button keypad with audible feedback.
Three (3) Control Station panic button zones.
Surface mountable; mounts to any standard
single or double gang electrical box.
Built-in piezo sounder.
Easy-to-read arming level: AWAY, STAY, and
NIGHT backlit LEDs.
Backlit keys with door.
Unsupervised Control Stations allows up to 18
Control Stations.
ZXICON Control Station
Two seven-segment display digits.
Plain English icons.
Addressable as Control Station #3 or #4. Jumper
change makes Control Station unsupervised.
Nominal current drain: 50mA.
Size: 5.0"H x 4.5"W x 1.0"D (127 mm x 114.3
mm x 25.4 mm).
ZXLCD Control Station
Backlit display.
Two lines x 16 characters LCD display.
Addressable with DIP switches, supervised/un-
supervised.
Plain English display.
Nominal current drain: 20mA - 110mA.
Up to four (4) supervised Control Stations per
system.
Size: 5.33"H x 6.08"W x 1.024"D (135.4 mm x
154.4 mm x 26.0 mm).
ZXLED12 Control Station
Twelve (12) LEDs annunciate general purpose
zones 1 through 12.
Ready, trouble, and fire alarm LEDs.
Addressable as Control Station #1 or #2. Jumper
change makes Control Station unsupervised.
Nominal current drain: 23mA - 31mA.
Size: 5.0"H x 4.5"W x 1.0"D (127 mm x 114.3
mm x 25.4 mm).
ZXLED8 Control Station
Eight (8) LEDs annunciate zones 1 through 8.
Ready and trouble LEDs.
Addressable at Control Station #1 or #2. Jumper
change makes Control Station unsupervised.
Nominal current drain: 23mA - 31mA.
Size: 5.0"H x 4.5"W x 1.0"D (127 mm x 114.3
mm x 25.4 mm).
ZXSSD Control Station
Three 0.56" (14.2 mm) seven segment display
digits.
Ready and trouble LEDs.
Up to four (4) supervised Control Stations per
system.
Addressable with DIP switches, supervised/un-
supervised.
Nominal current drain: 23mA - 116mA.
Size: 5.0"H x 4.5"W x 1.0"D (127 mm x 114.3
mm x 25.4 mm).
20
Page 21
SPECIFICA TIONS AND FEATURES
ZXVFD Control Station
Two lines x 16 characters VFD display.
Addressable with DIP switches, supervised/
unsupervised.
Plain English display.
Nominal current drain: 20mA - 170mA.
Up to four (4) supervised Control Stations per
system.
Size: 5.33"H x 6.08"W x 1.024"D (135.4 mm x
154.4 mm x 26.0 mm).
Optional Accessories
ZXEX08 Zone expander module expands the
control to 8 additional zones. Nominal current drain :1 1mA
ZXODM: Output Driver Module: Provides ten (10)
fully programmable 40 mA + 12 VDC outputs. Nominal current drain: 10 - 13 mA with no outputs connected.
ZX310 - ZX300 Control Board mounted in EX1414
enclosure. (The ZX310 assembly is required for UL Commercial Burglary applications).
F2600 Transformer Enclosure: Ensures that the
AC plug-in transformer remains securely fixed to the AC wall outlet
T-1625 Transformer: UL Listed Class II plug-in 16.5
V AC 25 VA secondary .
T-1635 Optional Transformer: UL Listed Class II
plug-in 16.5 V AC 35 VA secondary .
HCP-12SUL Power Supply: Provides a 12 or 24
VDC power limited output with a current rating of
2.0 A continuous while the AC primary power source is present.
CR860 Dual Battery Harness: Allows for an
additional 12 VDC 7 Ah sealed lead acid battery connection to the control to meet additional standby requirements.
CR861 Battery Harness: Allows for 12 VDC 17.2
Ah sealed lead acid battery connection to the control to meet additional standby requirements.
EB1511 Auxiliary Enclosure: 15" x 11" x 4" enclo-
sure with cam lock allows wall mounting of acces­sories and batteries.
EX1414 Optional Larger Enclosure: 14" X 14" x
3.5".
AE912 Raucous Sounder: Current consumption:
28 mA @ 12 VDC.
MPI-266 Battery Cut-Off Module: Disconnects
battery from deep discharges.
MPI-267 Power Disconnect Module: Disconnects
battery from deep discharges.
MPI-268 Earth Ground Fault Detector: Current
consumption: less than 20 mA.
MPI-206 General Purpose Relay Module.
4710 RF Gateway (8 RF Zone Devices, 8 RF User
Devices). Nominal Current Drain: 80 mA.
4720 RF Gateway (16 RF Zone Devices, 8 RF User
Devices). Nominal Current Drain: 80 mA.
4110 Universal Transmitter and battery .
4545 Shatter Pro Glassbreak Detector with
Transmitter and batteries.
4655 Sharpshooter PIR with Transmitter and
battery .
4004 Four Button Wireless Key Transmitter and
Battery .
4310S, ST, SLT Wireless Smoke Detectors (UL
217) with T ransmitter and Battery.
4330S, ST, SLT , SLTM Wireless Smoke Detectors
(UL 268) with T ransmitter and Battery.
4113 Three Point Universal T ransmitter and
Battery .
4010 Single Button Panic Transmitter and Battery.
4011 Dual Button Panic/Medical T ransmitter and
Battery .
ZXLCDD1 LCD Keypad Demonstrator.
ZXICOND1 ICON Keypad Demonstrator.
TC1100 Tamper Enclosure.
Output Provisions
Low Current Trigger Outputs: One output on
main board (10 mA), expandable to 11 with ZXODM Output Driver Module (40 mA each).
Maximum combined continuous current drain at
KP+12V, 2WS, +12V AUX and PGO1 is 0.6 amps with 16.5 VAC 35 VA transformer.
Current Limits: The current at Bell Output is
limited to 1.35 amps (PTC2). The 12V Auxiliary current is limited by PTC2 to 2.5 amps. Reverse battery protection is limited to 2.5 amps (PTC3).
21
Page 22
COMP ATIBLE ACCESSORIES
List Of Compatible Accessories
ESL Two-Wire Smoke Detectors
429 AT, C, CT, CRT, CST: Standby Current: 70 µA max. (Max. of 10 detectors per zone) 521 B, BXT , CRXT: Standby Current: 70 µA max. (Max. 10 detectors per zone) 711U, 712U, 713-5U, 713-6U: Standby Current: 70 µA max. (Max. 10 detectors per zone) 721U, 721UT, 721UD, 722U, 722UD: Standby Current: 70 µA max. (Max. 10 detectors per zone) 731U, 732U: Standby Current: 70 µA max. (Max. 10 de­tectors per zone)
ESL Four-Wire Smoke Detectors
445 A T: Standby Current: 500µA @ 6 V ; 1.5 mA @ 15 V 445 C, CR, CRT, CS, CSH, CST, CSR, CSRT: Standby
Current: 40 µA @12 V ; 100 µA @ 24 V
449 CTE: Standby Current: 10 mA max. 449 C, CT , CRT , CST , CSRT , CSRH, CSST: Standby Cur-
rent: 70 µA max.
System Sensors Two-Wire Smoke Detectors
1 100 Ionization 2100T Photoelectric 1400 Ionization 2400 Photoelectric 1400TH Ionization 2400A T Photoelectric 2100 Photoelectric 2400TH Photoelectric
(Max. 6 detectors per zone)
System Sensors Four-Wire Smoke Detectors
1 112, 11 12 Ionization 2412B Photoelectric 1412B Ionization 2412THB Photoelectric 1451 Ionization 2412A T Photoelectric 21 12, 212 Photoelectric 2451 Photoelectric 21 12, 2124T Photoelectric 2451TH Photoelectric 21 12, 2124TSR Photoelectric
Wheelock
34T-12R Horn: Input voltage: 9-15.6 VDC; Rated Current:
0.125 A
EH-DL1-R Electronic Horn: Input voltage 12/24 VDC; Input Current; (@ 12 VDC) 0.015 A/(@24 VDC) 0.017 A EH-DL2-R Electronic Horn: Input voltage: 12 VDC; Input Current: 0.047 A EH-EL1-R Electronic Horn: Input voltage: 12/24 VDC; Input Current: (@12 VDC) 0.015 A/(@ 24 VDC) 0.017 A EH-EL2-R Electronic Horn: Input voltage: 12 VDC; Input Current: 0.047 A AES-DL2-R Multi-tone Electronic Signal: voltage: 12 VDC; Current (High): 0.050 A; Current (Low): 0.025 A AES-EL2-R Multi-tone Electronic Signal: voltage: 12 VDC; Current (High): 0.0100 A; Current (Low): 0.050 A
MIZ-12-R Mini horn: voltage: 12 VDC; Current: 0.010 A MIZ-12-W Mini-horn: voltage: 12 VDC;
Current 0.010 A CH-BF2-R Fire Chime: Input voltage: 12 VDC; Input Current: 0.020 A CH-CF2-W Fire Chime: Input voltage: 12 VDC; Input Current: 0.020 A CH-DF2-R Fire Chime: Input voltage: 12 VDC; Input Current: 0.020 A 46T-G4-12-R DC V ibrating Bells: Shell Size: 4 Inches; Input voltage: 12 VDC; Input Current: 0.125 A 46T-G6-12-R DC V ibrating Bells: Shell Size: 6 Inches; Input voltage: 12 VDC; Input Current: 0.125 A 46T-G10-12-R DC V ibrating Bells: Shell Size: 10 Inches; Input voltage: 12 VDC; Input Current: 0.080 A
Compatible Central Station Receivers
UL permits communication with the following UL Listed Cen­tral Station receivers:
Manufacturer Model Number Ademco 685 Fire Burglary Instruments CP-220 Osborne-Hoffman Quick Alert II Sur-Gard MLR2-DG Silent Knight 9000
22
Page 23
SIA AND CONT ACT ID FORMATS
SIA and Contact ID Formats
This section cross-references many of the reporting options and equivalent codes sent by Sentrol-manu­factured controls when transmitting in the SIA and Contact ID (CID) formats.
Simplified example of data sent in CID format:
SSSS 18 Q XYZ AA CCC
SSSS = 4-digit hexadecimal subscriber # 18 = CID que for automation systems
Simplified example of data sent in SIA format:
XXXXXX EE CCC
XXXXXX = 6-digit hexadecimal subscriber # EE = Event data code CCC = Zone, sensor, or user ID
Q = Event qualifier; 1 = new event or opening; 3
= new restore or closing; 6 = previously re-
ported event XYZ = Event code (3 decimal digits) AA = Area number (00 for all events) CCC= Zone, sensor, or user # (3 decimal digits)
EVENT TYPE CID CODE SIA CODE EVENT SOURCE
Zone Fire Alarm 1110 FA Zone (1 - 16) Zone Burglar Alarm 1130 BA Zone (1 - 16) Zone Holdup Alarm 1120 HA Zone (1 - 16) Zone Auxiliary Alarm 1100 MA Zone (1 - 16) Zone CO Detect Alarm 1162 GA Zone (1 - 16) Left Key Fire Alarm 1115 FA 500 + Keypad (1 - 4) Center Key or RF Device Holdup Alarm 1120 HA 500 + Keypad (1 - 4) Right Key or RF Device Auxiliary Alarm 1100 MA 500 + Keypad (1 - 4) Duress 1121 PA USER (1 - 8) Burglar Alarm Cancelled 3406 BC User (1 - 9) or Keyswitch (11 - 26) Recent Closing 3459 CR Quick (0), User (1 - 9), or Keyswitch (11 -26) User On Premises 1458 JP User (1 - 8) Exit Alarm 1374 EA Zone (1 - 16) Zone CCM Alarm 1150 UA Zone (1 - 16) Zone Swinger Trouble 1377 BD Zone (1 - 16) Zone Fire Trouble 1373 FT Zone (1 - 16) Zone Other Trouble 1370 UT Zone (1 - 16) Zone No Response on Bus 1333 E T Zone (1 - 16) RF Point Not Reporting 1381 US Zone (1 - 16) Smoke Detector Maintenance 1393 YX Zone (1 - 16) RF Sensor Tamper 1383 TA Zone (1 - 16) RF Point Low Battery 1384 XT Zone (1 - 16) Zone Fire Bypass 1571 FB Zone (1 - 16) Zone Burglar Bypass 1573 BB Zone (1 - 16) Zone 24-Hour Bypass 1572 UB Zone (1 - 16) Zone Other Bypass 1570 UB Zone (1 - 16) Zone Fire Alarm Restore 3110 F R Zone (1 - 16) Zone Burglar Alarm Restore 3130 BR Zone (1 - 16) Zone Holdup Alarm Restore 3120 HR Zone (1 - 16) Zone Auxiliary Alarm Restore 3100 MR Zone (1 - 16) Zone CO Detect Alarm Restore 3162 GR Zone (1 - 16) Zone CCM Alarm Restore 3150 UR Zone (1 - 16)
23
Page 24
SIA AND CONTACT ID FORMATS
EVENT TYPE CID CODE SIA CODE EVENT SOURCE
Zone Swinger Trouble Restore 3377 BE Zone (1 - 16) Zone Fire Trouble Restore 3373 FJ Zone (1 - 16) Zone Other Trouble Restore 3370 UJ Zone (1 - 16) Zone No Response Restore 3333 ER Zone (1 - 16) RF Point Reporting Again 3381 UR Zone (1 - 16) Smoke Detector Clean 3393 YZ Zone (1 - 16) RF Sensor Tamper Restore 3383 TR Zone (1 - 16) RF Point Low Battery Restore 3384 XR Zone (1 - 16) Zone Fire Bypass Restore 3571 FU Zone (1 - 16) Zone Burglar Bypass Restore 3573 BU Zone (1 - 16) Zone 24-Hour Bypass Restore 3572 UU Zone (1 - 16) Zone Other Bypass Restore 3570 UU Zone (1 - 16) User AWAY Arm 3401 CL User (1 - 9) User Other Arm 3456 CG User (1 - 9) Quick Arm 3408 CL No Data Keyswitch Arm 3409 CS Keyswitch (11 - 26) User Disarm 1401 OP User (1 - 9) Keyswitch Disarm 1409 OS Keyswitch (11 - 26) Walk Test Mode Begin 1607 TS User (1 - 9) Installer On Premises 1466 LB No Data Keypad Missing 1330 E T 500 + Keypad (1 - 4) AC Failure 1301 AT No Data Panel Low Battery 1302 YT No Data Bell Fault 1321 YA No Data RF Jamming 1344 XQ No Data RF User Device Low Battery 1384 XT User (1 - 8) Memory Error 1303 YF No Data Walk Test Mode End 3607 TE User (1 - 9) Installer Off Premises 3466 LX No Data Keypad Missing Restore 3330 ER 500 + Keypad (1 - 4) AC Restore 3301 AR No Data Panel Low Battery Restore 3302 YR No Data Bell Restore 3321 Y H No Data RF Channel Clear 3344 XH No Data Failed to Communicate Restore 3354 Y K No Data Auto-Comm Test (Not Normal) 1608 RY No Data Auto-Communicator Test 1602 R P No Data Remote Program End 3412 RS No Data Remote Program Aborted 1412 RU No Data Manual Communicator Test 1601 RX No Data
24
Page 25
Agency Requirements
AGENCY REQUIREMENTS
Underwriters Laboratories (UL) Notes In This Manual
Key “0” (Access) - The control has not been in­vestigated to UL 294 Access Control System re­quirements.
Unsupervised Burglary Zones - UL does not per­mit the use of unsupervised zones.
For UL Commercial Burglary, minimum trans­former should be 16.5 VAC 35 VA.
UL Notes About Program Functions
Entrance Delay Time (1 and 2) - Maximum of 45 seconds.
AW A Y Exit Delay T ime - Maximum of 60 seconds.
Burglar Alarm Cutof f T ime - 4 minutes minimum for household BA/FA and 15 minutes for com­mercial burglar alarm and police station con­nected burglar alarm system.
Fire Cutoff T ime - Minimum of 4 minutes for resi­dential fire.
Communicator Enable - Police station connected burglar alarm installations: The communicator must be enabled.
Days Between Comm. Tests - Commercial in­stallations: automatic test performed every 24 hours.
Time Between Dial Attempts - UL certified ac­counts: no more than 45 seconds between at­tempts.
Dial Type - Will not be programmed for foreign pulse.
Dial Attempts Before Shutdown - Five dial at­tempts minimum, ten dial attempts maximum.
Double Press Arming/Press & Hold Arming ­These functions will be disabled. Four digit passcodes will be used.
Enable Force Arming - This function will be dis­abled.
Enable Bypassing - This function will be disabled.
Burglar Alarm Output - Will be programmed to STEADY.
Fire Alarm Output - Will be programmed to TEM­PORAL.
Burglar Loop Audible Lockout - This function will be disabled.
Enable Bell Test Upon Arming - This function will be enabled for Grade A Local Central Sta­tion Connected installations.
Enable Keypad Sounder for BA Zones - The sys­tem will have an audible alarm output upon alarm.
UL Notes About Zone Planning
Burglar Loops - Will be defined as Alarm on Open/Alarm on Short.
Fire, Holdup, CO Detectors, and Auxiliary Emer­gency Zones - Will not be defined as bypassable.
Special Functions/Alarms - Burglar zones will have an audible output.
Medical Emergency - At least one Control Sta­tion will be used as part of the system.
UL Notes About RF Devices
For UL Burglary installations with wireless devices, an output programmed as “RF Annunciator” is re­quired and an audible device must be connected to it. After a trouble condition is silenced with an OFF + passcode, this output will pulse 3 times at 4 hour intervals if a wireless device has a low battery or a wireless point has been tampered.
25
Page 26
AGENCY REQUIREMENTS
UL and ULC Listings
APPLICATION LISTING
Household Burglary UL 1023 Household Fire UL 985 Household Burglary/Household Fire Combination UL 1023 / UL 985 Local Burglar Alarm Grades A, B and C Central Station UL 609 Police Station Connect Burglar Alarm Unit UL 365 Digital Alarm Communicator System UL 1635 Central Station Burglar Alarm Unit UL 1610 California State Fire Marshal 7167-1459:114 Residential Burglar System ULC 5310 Local Burglar Alarm ULC 5303 Central Station ULC 5301 Commercial Burglary ULC 5302 Burglar Alarm Units Central & Monitoring ULC 5304
Table 2 UL and ULC Listings
UL has established certain requirements which pertain to the installation, use, and programming of this equipment. The local Authority Having Jurisdiction (AHJ) and/or UL may have other requirements which apply to the installation of
responsibility of the installing dealer to check with the AHJ and/or UL before installing this system. The following table details guidelines that must be followed in order to comply with the UL listings as stated above.
this system that are not detailed in this manual. It is the
Max. Continuous
Application Listing
Current Drain
(mA) w/ 7 AH
Battery
Household Burglary UL1023 400 4 4 N/A UL listed signaling device
Household Fire CSFM 400 24 4 Required UL listed signaling device
Household Burglary/ UL 1023 400 4 4 Required UL listed signaling device Fire Combination UL 985 2 4
Central Station Burglary UL 1610 400 4 4 N/A TC 1100 Tamper Resistant (Grade C) UL 1635 cover with a ZX310
Central Station Burglary UL 1610 400 4 4 N/A TC 1100 Tamper Resistant (Grade B) UL 1635 cover with a ZX310 and a
Local Burglary UL 609 400 4 4 N/A TC 1100 Tamper Resistant (Grade A) cover with a ZX310 and a
Police Station Burglary UL 365 400 4 4 N/A TC 1100 Tamper Resistant Connection (Grade A) cover with a ZX310 and a
Maximum combined continuous current drain (standby) refers to terminals KP+12V, 2WS SWNEG, +12V AUX, and PGO1. Under alarm conditions, the combined output current drain should not exceed 950 mA with 16.5 VAC 35 VA transformer. For 24 hr standby, UL Household Fire & CSFM, two 7 Ah batteries are required.
Minimum
Battery
Standby
Time In
Hours
Control
Stations
Smoke Detector
ESL 429 & 700
series, System
Sensors 1400 &
2400 series
Auxiliary Equipment Required
UL Listed audible device (AB12M recommended)
UL Listed audible device (AB12M recommended)
UL Listed audible device (AB12M recommended)
Table 3 Agency Power and Configuration Requirement
26
Page 27
National Fire Protection Association
NFP A RULES
(NFPA) Rules
The National Fire and Burglar Alarm Association (NFP A) has established rules to follow pertaining to fire prevention and the installation of fire detection equipment.
Smoke Detector Locations
For residential applications, install smoke detectors in each bedroom and outside each separate sleep­ing area in the immediate vicinity of the bedrooms and on each additional story of the family living unit including basement and excluding crawl spaces and unfinished attics. In new construction, a smoke de­tector should also be installed in each sleeping area. For family living units with one or more split levels (i.e.: adjacent levels with less than one full story separation between levels), a smoke detector re­quired by the above is sufficient for an adjacent lower level, including basements. EXCEPTION: Where there is an intervening door between one level and the adjacent lower level, install a smoke detection on the lower level. For commercial applications, in­stall smoke detectors in each separate work area, including hallways and storage areas.
Testing
This system should be tested weekly. All switches, contacts, and accessories must be UL Listed de­vices. This equipment should be installed in accor­dance with the National Fire Protection Association Standard No. 72 (National Fire Protection Associa­tion, Batterymarch Park, Quincy MA 02269). Con­trol panel specifications are subject to change with­out notice.
Consult smoke detector specifications and local and national codes for coverage descriptions.
4 in.(0.1m) Minimum
CEILING
Acceptable Here
Never Here
Top of Detector Acceptable Here
NOTE: All measurements are to the closest edge of the detector
4 in.(0.1m) Minimum
12 in.(0.3m) Maximum
SIDE WALL
Install ceiling-mounted smoke detectors in the cen­ter of the room or hall, not less than 4 inches from any wall. When mounting the detector on a wall, place the top of the detector 4 to 12 inches from the ceiling.
Do not install smoke detectors where normal ambi­ent temperatures are above 100
½F. (37.8½C.)
Do not position smoke detectors in front of air con­ditioners, heating registers, ceiling fans, or other lo­cations where normal air circulation will keep smoke from entering the detector.
Heat from a fire rises to the ceiling, spreads out across the ceiling surface and begins to bank down from the ceiling. Corners where the ceiling and walls meet create air spaces in to which heat has diffi­culty penetrating. Usually, these dead air spaces measure about four (4) inches (0.1m) along the ceil­ing from the corner and four (4) inches (0.1m) down the wall. Do not place heat or smoke detectors in these dead air spaces.
Living
Basement
Indicates required smoke detector
Indicates smoke detector is optional if door is not provided between living and recreational rooms.
Indicates smoke detector required in new construction.
Dining Kitchen
TV
Room
Living
Bedroom
Bedroom BedroomHall
Recreation
Bedroom BedroomHall
DiningLiving
Basement
A smoke detector should be located on each story.
Bedroom
Bedroom
In family living units with more than one sleeping area, a smoke detector should be provided to protect each sleeping area in addition to the detectors required in bedrooms.
FIGURE 8 Smoke Detector Placement
27
Page 28
NFP A RULES
CO Detector Locations
Selecting a suitable location is critical to the opera­tion of CO detectors. You should install an detector in every bedroom and on each level of a dwelling. At a minimum, one detector should be placed outside the sleeping areas. See Figure 9.
Use the following guidelines to select a suitable lo­cation for the installation of CO detectors:
Mount detectors on a ceiling or wall at least 5
feet up from the floor.
Mount detectors at least 5 feet from outside
doors and windows.
Mount at least 5 feet from open flame appliances
such as furnaces, stoves, and fireplaces.
Mount at least 5 feet from any cooking appli-
ance.
For sloped, gabled, or peaked ceilings, locate
the detector 3 feet from the highest point.
Locate in a suitable environment as follows:
- Temperature between 40 degrees F and 100
degrees F.
- Humidity between 15 and 90% non-condens-
ing.
Locate away from air conditioners, heating reg-
isters, and any other ventilation source that may interfere with CO gas entering the detector.
Do not mount where furniture or draperies may
obstruct the airflow.
Mount detectors on a firm permanent surface.
NFP A RULES
FIGURE 9 CO Detector Placement
28
Page 29
Notes
______________________________________________________________________
______________________________________________________________________
______________________________________________________________________
______________________________________________________________________
______________________________________________________________________
______________________________________________________________________
NOTES
______________________________________________________________________
______________________________________________________________________
______________________________________________________________________
______________________________________________________________________
______________________________________________________________________
______________________________________________________________________
______________________________________________________________________
______________________________________________________________________
______________________________________________________________________
______________________________________________________________________
29
Page 30
FCC COMPLIANCE
FCC Compliance
Part 68 Notification
This equipment complies with Part 68 of the Fed­eral Communications Commissions (FCC) rules. All connections to the telephone network must be made through standard telephone company plugs and jacks, RJ-31X or equivalent, in such a manner as to allow for easy and immediate disconnection of the equipment. If the connecting cord is unplugged from the jack there shall be no interference to the tele­phone equipment still connected to the telephone network.
The FCC registration number and Ringer Equiva­lence Number (REN) can be found printed on the wiring connection label located inside the Control Box Enclosure. If requested, provide this informa­tion to your telephone company . The REN is useful to determine the quantity of devices that may be con­nected to your telephone line and still have all of those devices ring when your number is called. In most, but not all areas, the sum of the RENs of all devices should not exceed five (5.0).
In the unlikely event that the equipment should ever fail to operate properly, it should be disconnected from the telephone jack to determine if the problem is with the telephone network or with the equipment. If a problem is found with the equipment, leave dis­connected until it is repaired or replaced.
In the unlikely event that the equipment should ever cause harm to the telephone network, the telephone company may temporarily discontinue your service. If possible, they will notify you in advance. How­ever, if advance notice isn’t practical, the telephone company may temporarily discontinue service with­out prior notification. In the case of temporary dis­continuance, the telephone company shall promptly notify the telephone subscriber who will be given the opportunity to correct the situation. The cus­tomer also has the right to bring a complaint to the FCC if he feels the disconnection is not warranted.
Your telephone company may make changes in its facilities, equipment, operations, or procedures that could affect the proper operation of your equipment. If they do, you will be given advance notice so as to give you an opportunity to maintain uninterrupted service.
You should notify the telephone company if this equipment is removed from the premises and the telephone jack is no longer needed.
Part 15 Notification
This equipment has been tested and found to com­ply with the limits for a Class B digital device, pursu­ant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is oper­ated in a residential environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful in­terference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
• Reorient or locate the receiving antenna.
• Increase the separation between the equipment
and receiver.
• Connect the equipment into an outlet on a circuit
different from that to which the receiver is con­nected.
• Consult the dealer or an experience radio/TV tech-
nician for help.
CAUTION: Changes or modifications not expressly approved by the manufacturer could void the user’s authority to operate the equipment.
Canadian Notice
The Canadian Department of Communications la­bel identifies certified equipment. This certification means that the equipment meets certain telecom­munications network protective, operational and safety requirements. The Department does not guar­antee the equipment will operate to the user’s satis­faction. Before installing this equipment, users should ensure that it is permissible to be connected to the facilities of the local telecommunications com-
30
Page 31
FCC COMPLIANCE
pany. The equipment must also be installed using an acceptable method of connection. In some cases, the company’s inside wiring associated with a single line individual service may be extended by means of a certified connector assembly (telephone exten­sion cord). The customer should be aware that com­pliance with the above conditions may not prevent degradation of service in some situations. Repairs to certified equipment should be made by an autho­rized Canadian maintenance facility designated by the supplier. Any repairs or alterations made by the user to this equipment, or equipment malfunctions, may give the telecommunications company cause to request the user to disconnect the equipment. Users should ensure for their own protection that the electrical ground connections of the power util­ity, telephone lines and internal metallic water pipe system, if present, are connected together. This precaution may be particularly important in rural ar­eas.
CAUTION: Users should not attempt to make such connections themselves, but should contact the ap­propriate electric inspection authority, or electrician, as appropriate.
LOAD NUMBER (LN) assigned to each termi-
The nal device denotes the percentage of the total load to be connected to a telephone loop which is used by the device, to prevent overloading. The termina­tion on a loop may consist of any combination of devices subject only to the requirement that the to­tal of the Load Numbers of all the devices does not exceed 100. The LOAD NUMBER for the system is
2. This equipment is a Class B Digital apparatus which
complies with the radio interference regulations, CRC c. 1374.
Limitations
The ZX300/ZX310 is part of a system designed to warn against unauthorized entry or of other situa­tions. However, it is not a guarantee of protection against the occurrence of those events. Any alarm system is subject to compromise or failure to warn for various reasons. Unauthorized access can be gained through unprotected points or by disarming or bypassing protected points. Sensing devices are power driven and will not operate without power. Telephone lines over which alarm signals are trans­mitted may be out of service or rendered inoperable by an intruder. Smoke detectors have limitations and cannot detect all types of fires, or sense smoke which is out of the effective range of the detector.
All Rights Reserved
No part of this publication may be reproduced, stored in a retrieval system, or transmitted in any form, or by any means - electronic, mechanical, photocopy­ing, recording, or otherwise without the prior written permission of the manufacturer. The material in this publication is for information purposes and subject to change without notice. The manufacturer as­sumes no responsibility for any errors which may appear in this publication. Printed in USA.
ƒƒ SPECIAL NOTE referencing use of
the word “Fire” in this manual.
Use of this control for fire detection and/or annun­ciation may not be permitted by certain states, coun­ties, municipalities, or local jurisdiction. It is the re­sponsibility of the installing alarm company to check with their local AHJ (Authority Having Jurisdiction) or State Fire Marshal’s office prior to using this con­trol for fire detection.
UNDERWRITERS LABORATORIES INC.
This Product is Listed by
and Bears the Mark:
See Page 26 for listing information
31
Page 32
32
X-3908-0999
1030242B
Loading...