Sentrol 4300 Series User Manual

sentrol
Wireless
U
L
LISTED
D
E
T
B
S
Y
I
L
U
A
N
D
D
A
E
N
R
A
W
C
R
F
I
T
O
E
R
S
S
E
I
L
R
A
O
B
T
O
A
R
4300 Series
4300 Series Wireless Smoke Detector
Wireless Smoke Detector
DESCRIPTION
The Sentrol 4300 Series smoke detector requires a Sentrol 4000 RF gateway receiver with Rev J or higher software and a compatible control panel sold sepa­rately. To install the detector, you will need the programming guide for the control panel.
Depending on the model, the detector provides the following features:
CleanMe
self-diagnostics monitors its own sensitiv-
ity and operational status. If the detector drifts out of the UL listed sensitivity range or fails internal diagnos­tics, it extinguishes its LED and sends a trouble signal to the control panel.
Detector/base lock discourages unauthorized removal of the detector by requiring a screwdriver to remove the detector from the base.
Optional base tamper sends a trouble signal to the control panel when the detector is removed from its mounting base.
Optional mercury-tilt tamper
sends a trouble signal
to the control panel when the detector is not upside down and/or horizontal. Used for installations on removeable ceiling panels
Optional integrated fixed 135°F temperature and rate of rise heat detector trips an alarm based on
temperature detected. Optional low temperature supervision sends a low
temperature signal when the ambient temperature around the detector reaches approximately 43°F (6°C). A separate transmitter signal (secondary address) is assigned to a Critical Condition Monitoring(CCM) zon
TRANSMITTED SIGNAL OUTPUTS
Depending on the model, the detector transmits the following signals to the control panel:
• Alarm
• Alarm restore
• Tamper
• Low battery
CleanMe
Maintenance alert
Supervisory
Low temperature supervison
U
CSFM
L
LISTED
Sounder vent
LED
Optional temperature sensor
T est/Silence button
SELECTING A LOCATION
Selecting a suitable location is critical to the operation
of smoke detectors. This equipment should be installed in accordance with the National Fire Protection Association’s (NFPA) Standard 72. See Figure 2.
A-8-1.2.1.C Are More Smoke Detectors Desirable? The required number of smoke detectors might not
provide reliable early warning protection for those areas separated by a door from the areas protected by the
e.
required smoke detectors. For this reason, it is recom­mended that the householder consider the use of additional smoke detectors for those areas for in­creased protection. The additional areas include the basement, bedrooms, dining room, furnace room, utility room, and hallways not protected by the required smoke alarms. The installation of smoke detectors in kitchens, attics (finished or unfinished), or garages is not normally recommended, as these locations occa­sionally experience conditions that can result in im­proper operation.
Bedroom
Living Room
Basement
= Required smoke detectors
Bedroom
Dining Room
= Additional smoke detectors required for new construction
TV Room
Bedroom
Figure 2 - Detector Placement
Dining Room
Living Room
Kitchen Bedroom
Bedroom
Important: Regulations pertaining to smoke detector installations vary from state to state. For more infor­mation, contact your local fire department or local authority having jurisdiction.
1
In addition to NFPA 72, use the following location guide­lines to optimize performance and reduce the chance of
false alarms from the detector:
Locate ceiling-mounted smoke detectors in the center
of a room or hallway at least 4 inches from any walls or partitions.
Locate wall-mounted smoke detectors so the top of the detector is 6 to 12 inches below the ceiling.
Locate in a suitable environment as follows:
- T emperature between 40°F (4.4°C) and 100°F (37.8°C)
- Humidity between 0 and 95% non-condensing
Locate away from air conditioners, heating registers and any other ventilation source that may interfere with smoke entering the detector.
Mount smoke detectors on a firm permanent surface. If the detector has a tilt tamper, it can be mounted on removable ceiling panels.
Knockout
Knockout
Figure 3 - Base Lock Knockouts
Locate away from large metallic objects.
INSTALLING THE DETECTOR
1. If you are using the detector/base lock, remove the
two knockouts on the mounting base. See Figure 3.
2. Slide the battery compartment cover away from the
detector to unsnap it and lift it off. See Figure 4.
3. Observing proper polarity, insert the two lithium
batteries provided into the detector battery compart­ment and replace the battery compartment cover.
4. Record the seven digit ID address from the label on
the backside of the detector. This address must be programmed into the RF gateway receiver. See the control panel programming guide.
For an L model detector, program the Fire Address plus 1 secondary address into the panel in a separate non-fire CCM non-supervised or 24hr non-supervised auxiliary zone.
5. Program the RF gateway receiver and the control
panel. See the control panel programming guide.
6. Remove the red plastic dust cover from the detector.
The detector is shipped with a dust cover for protec­tion on construction sites with dusty environments.
7. Disconnect the alarm notification appliances, service
release devices, and extinguishing systems and test the communication between the control panel and each smoke detector before permanently mounting the detectors as follows:
- Press the Test/Silence button on the detector for 2 seconds. The detector sends a test signal to the control panel.
- At the control panel, verify the test signal was received and the RF signal strength is ad­ equate. If no signal is received or the RF signal is low, relocate the detector and retest.
8. Using the two screws and anchors provided, mount
the base.
Tab
Slot
Battery compartment
Figure 4 - Detector-to-Base Alignment
9. Attach the detector to the mounting base as follows:
- Line up the raised tab on the lip of the detector with the slot on the lip of the mounting base. See Figure 4.
- Insert the detector into the base and turn clockwise approximately 15 degrees. It should snap firmly into place.
Important: The detector cannot be attached to the
mounting base if no batteries are installed.
10.Test the communication between the control panel and each smoke detector as follows:
- One at a time, press the Test/Silence button on the detector for 2 seconds. The detector sends a test signal to the control panel.
- At the control panel, verify the test signal was received.
11. Test each detector (see
Detector)
and reconnect all alarm notification
Smoke Testing the
appliances, service release devices, and extinguish­ ing systems.
Important: The control panel alarm and all auxiliary functions should be verified for a complete test of the system.
2
SMOKE TESTING THE DETECTOR
Smoke detectors should be tested in place annually using smoke or canned aerosol simulated smoke. Follow the instructions on the canned smoke or use the following steps to test the detector with smoke:
1. Hold a smoldering punk or cotton wick close to the smoke entry openings.
2. Gently direct the smoke into the detector for 20 seconds or until an alarm is indicated.
BE SURE TO PROPERLY EXTINGUISH THE SMOKE SOURCE AFTER TESTING! The detector LED should remain on while the built-in transmitter sends an alarm signal to the control panel. The detector will sound a temporal rhythm until the Test/Silence button is pressed. The detector automatically resets when smoke is no longer present.
TESTING THE DETECTOR SENSITIVITY
The 4300 Series provides a sensitivity level test mode that allows you to check the detector sensitivity using the Test/ Silence button and the LED indicator on the detector as follows:
1. Press the Test/Silence button on the detector for 2 seconds. The detector performs a test, and the LED flashes one to nine times.
2. Count the number of times the LED flashes and use the following table to determine the status of the detector sensitivity and what action to take, if any.
sehsalF noitarucsbO
1A/NelbaecivresnU
3-2A/NtonsirotceteD
4 tf/%1.3 nihtiwsirotceteD 5 tf/%6.2 6 tf/%1.2 7 tf/%6.1
9-8A/NootsirotceteD
)xorppA(
After the flashes, if the sensitivity is within limits and all other tests pass, the detector goes into alarm and resets after 5 seconds.
If the sensitivity is not within limits, or an unservice-
able hardware fault is detected, the LED extinguishes until the detector is serviced and the built-in transmitter
sends a CleanMe
or maintenance alert signal to the
control panel.
noitacidnI noitcA
.detceted
.egnar
.evitisnes
tluaferawdrah
.hguoneevitisnes
A/N
ytivitisneslamron
nurerdnatinuteseR
rorreehtfI.tsetytivitisnes
.tinuehtecalper,stsisrep tinuteseR.tinuehtnaelC
.tsetytivitisnesnurerdna
,stsisreprorreehtfI
.tinuehtecalper
ekomsehttahtyfireV
deppanssirebmahc
.tinunaelC.ylerucesnwod
Detector/base lock
Figure 5 - Detector/Base Lock
UNDERSTANDING THE TEST/SILENCE BUTTON
Depending on the model, the Test/Silence button on 4300 Series performs three functions as follows:
Testing = Press the Test/Silence button for 2 seconds. The detector performs a sounder test (4310 models only) and a sensitivity test and then sends a test signal to the control panel.
Silence alarm = Press to silence the sounder during an alarm. After a few minutes, the sounder and alarm resume if smoke is still present.
Silence trouble chirp = Press to silence a trouble chirp. The trouble chirp resumes after 24 hours if the trouble condition is not corrected.
UNDERSTANDING THE LED
The LED on the 4300 Series indicates the status of the detector as follows:
FLASHING = Flashes every 9 seconds to indicate normal operation.
ON = Detects smoke, sending an alarm. OFF = Trouble or maintenance is required. Check the
control panel to determine what action to take.
ATTACHING AND REMOVING THE DETECTOR
To remove the detector from the mounting base,
grasp the detector and turn it counterclockwise approxi­mately 15 degrees. The detector should snap off of the mounting base.
To remove the detector from the mounting base when the detector/base lock is used, insert a small
screwdriver into the locking tab slot on the side of the base and press in while simultaneously turning the detector counterclockwise 15 degrees. See Figure 5.
3
Loading...
+ 5 hidden pages