Read all the information, the datasheet, mounting and operating instructions and
study the wiring and connection diagram before working with the product. For
personal and equipment safety, and for optimum product performance, make sure you
entirely understand the contents before installing, using, or maintaining this product.
For safety and licensing (CE) reasons, unauthor ised conversion and/ or modifications
of the product are inadmissible.
e product should not be exposed to abnormal conditions, such as: extreme
temperatures, direct sunlight or vibrations. Long-term exposure to chemical
vapours in high concentration can affect the product performance. Make sure the
work environment is as dry as possible; avoid condensation.
All installations shall comply with local health and safety regulations and local
electrical standards and approved codes. is product can only be installed by an
engineer or a technician who has expert knowledge of the product and safety
precautions.
Avoid contacts with energised electrical parts; always treat the product as if it is
live. Always disconnect the power supply before connecting, servicing or repairing
the product.
Always verify that you apply appropriate power supply to the product and use
appropriate wire size and charac teristics. Make sure that all the screws and nuts
are well tightened and fuses (if any) are fitted well.
Recycling of equipment and packaging should be taken into consideration and these
should be disposed of in accordance with local and national legislation/regulations.
In case there are any questions that are not answered, please contact your
technical support or consult a professional.
MIW-RMFPX-2R-EN-000 - 23 / 04 / 20183 - 11
back to the table of contents
www.sentera.eu
Page 4
RMFPX-2R
PRODUCT DESCRIPTION
ARTICLE CODES
INTENDED AREA OF USE
MULTIFUNCTIONAL
ROOM CONTROLLER
e RMFPX-2R are multifunctional room controllers featuring
adjustable temperature, relative humidity and CO2 setpoints. ey
have a wide range of low voltage power supply. e control algorithm
controls one single analog / modulating output based on the measured
T, rH and CO2 values. All parameters are accessible via Modbus RTU.
CodeSupply Connection
RMFPG-2R18—34 VDC / 15—24 VAC ±10 %3-wire
RMFPF-2R18—34 VDC4-wire
■
Control of indoor temperature, relative humidity and CO2 level in HVAC applications
■
Suitable for residential and commercial buildings
■
For indoor use only
TECHNICAL DATA
■
Fan speed control based on T, rH and CO
■
Analog / modulating output type:
►
0—10 VDCmode: min. load 50 kΩ (RL ≥ 50 kΩ)
►
0—20 mA: max. load 500 Ω (RL ≤ 500 Ω)
►
PWM (open-collector type): PWM Frequency: 1 kHz, min. load 50 kΩ (RL ≥ 50 kΩ);
PWM voltage level 3,3 or 12 VDC
■
Selectable temperature range: 0—50 °C
■
Selectable relative humidity range: 5—85 %
■
Selectable CO2 range: 0—2.000 ppm
■
Removable sensor CO2 element for easy calibration and verification
■
Compatible with SSCDM - Sentera Sensor Calibration Device
■
3 LEDs for status indication
■
Accuracy: ±0,4 °C (0—50 °C); ±3 % rH (5—85 % rH); ±30 ppm CO2 (0—2.000 ppm
CO2), depending on the selected parameter
■
Enclosure:
►
rear plate: plastic ABS, black (RAL 9004)
►
front cover: ASA, ivory (RAL 9010)
■
Protection standard: IP30 (according to EN 60529)
■
Operating ambient conditions:
►
temperature: 0—50 °C
►
rel. humidity: 5—85 % rH, (non-condensing)
■
Storage temperature: -10—60 °C
2
STANDARDS
MIW-RMFPX-2R-EN-000 - 23 / 04 / 20184 - 11
►
Low Voltage Directive 2014/35/EC;
►
- EN 60529:1991 Degrees of protection provided by enclosures (IP Code)
Amendment AC:1993 to EN 60529
►
- EN 60730-1:2011 Automatic electrical controls for household and similar use Part 1: General requirements
www.sentera.eu
back to the table of contents
Page 5
MULTIFUNCTIONAL
RMFPX-2R
ROOM CONTROLLER
OPERATIONAL DIAGRAMS
■
EMC Directive 2014/30/EC;
►
EN 60730-1:2011 Automatic electrical controls for household and similar use Part 1: General requirements
►
EN 61000-6-1:2007 Electromagnetic compatibility (EMC) - Part 6-1: Generic
standards - Immunity for residen tial, commercial and light industrial environments
EN 61000-6-3:2007 Electromagnetic compatibility (EMC) - Part 6-3: Generic
standards - Emission standard for residential, commercial and light-industrial
environments Amendments A1:2011 and AC:2012 to EN 61000-6-3
►
EN 61326-1:2013 Electrical equipment for measurement, control and laboratory
use - EMC requirements - Part 1: General requirements
►
EN 61326-2-3:2013 Electrical equipment for measurement, control and
laboratory use - EMC requirements - Part 2-3: Particular requirements - Test
configuration, operational conditions and performance criteria
■
WEE E 2012/ 19/ E C
■
RoHs Directive 2011/65/EC
CO
AO1 [%]
rH [%]T [°C]
[ppm]
2
100
AO1, max
range
AO1, min
range
Note: The output changes automacally depending on the highest T, rH or CO2 values, i.e. the highest of three output values controls the output. See the green line
in the operaonal diagram above.
60
40
Max
Min
0
0
5
0
rH Min range
CO
Min range
2
T Min
range
T Max
range
rH Max range
CO
Max range
2
50
85
2.000
WIRING AND CONNECTIONS
Article typeRMFPF-2RRMFPG-2R
VIN18—34 VDC18—34 VDC15—24 VAC ±10%
GNDGroundCommon ground*AC ~*
AModbus RTU (RS485), signal A
/BModbus RTU (RS485), signal /B
AO1Analog / modulating output - T, rH or CO2 (0—10 VDC / 0—20 mA / PWM)
GNDGround AOCommon ground*
ConnectionsSpring contact terminal blocks, cable cross sec tion: 1,5 mm
2
* Cauon: Never connect the common ground of G type arcles to other devices powered by a DC voltage. If an AC power supply is used with a unit on a Modbus
network, the GND terminal should NOT BE CONNECTED to other units on the network or via the CNVT-USB-RS485 converter. This may cause permanent damage to
the communicaon semiconductors and / or the computer!
MIW-RMFPX-2R-EN-000 - 23 / 04 / 20185 - 11
www.sentera.eu
back to the table of contents
Page 6
59,8
74,5
20
70,5
MULTIFUNCTIONAL
RMFPX-2R
ROOM CONTROLLER
MOUNTING & OPERATING INSTRUCTIONS IN STEPS
Before you start mounting the RMFPX-2R, read carefully “Safety and Precautions”.
Choose a smooth surface for installation (a wall, panel and etc.).
Follow these steps:
1. Using a flat screwdriver, remove the front white cover by releasing the snap-fits
on its both sides (see Fig. 1 Snap-fits release).
2. Insert the cables through the opening on the rear plate (See Fig. 2 Mounting
dimensions.)
3. Using suitable fastening materials (not supplied), position the room sensor at
least 1,5 m from the floor. When planning the installation, allow enough clearance
for maintenance and service. Mount the sensor in a well-ventilated area. Mind
the correct mounting position and unit dimensions. See Fig. 2 and Fig. 3.
Fig. 1 Snap-fits releaseFig. 2 Mounting dimension
2x Ø 6
9,8
104,5
25,6
104,5
Fig. 3 Mounting position
CorrectIncorrect
Position at min. 1,5 m
from the floor
MIW-RMFPX-2R-EN-000 - 23 / 04 / 20186 - 11
www.sentera.eu
back to the table of contents
Page 7
RX
RMFPX-2R
MULTIFUNCTIONAL
ROOM CONTROLLER
4. Do the wiring according to the wiring diagram (see Fig.4).
Fig. 4 Wiring and connections
Power supply
RMFPF-2R: 18—34 VDC
RMFPG-2R: 18—34 V DC /
15—24 VAC ± 10%
5. Put back the cover snap it in.
6. Switch on the mains supply.
5.
Optional settings
If your unit is the first or the last unit on the Modbus RTU network (see Example 1
and Example2), enable the NBT resistor via 3SModbus or Sensistant. If your device
is not an end device, leave the NBT disabled (default Modbus setting).
Example 1Example 2
Slave 1
RX
NBT
NBT
Slave 2
Master
ТX
NBT
Slave n
Master
NBT
Modbu s RTU
Analog / modulating
output
Slave 1
Slave 2
ТX
NBT
Slave n
ATTENTION
If an AC power supply is used with any of the units on a Modbus network, the
GND terminal should NOT BE CONNECTED to other units on the network or
via the CNVT-USB-RS485 converter. is may cause permanent damage to the
communication semiconductors and/or the computer!
ATTENTION
Do not exceed the maximum power supply rating! Measure before installation!
Unregulated 24 VAC supply units provide higher nominal output voltage and
activate the integrated fuse protection.
ATTENTION
We advise you not to use G and F-type articles together on the same network. If
G and F-type articles are used together on the same network, make sure you use
separate power supplies for both types. Always connect different article types to
separate AC transformers or use the same article version.
CAUTION
MIW-RMFPX-2R-EN-000 - 23 / 04 / 20187 - 11
Do not expose to direct sunlight!
www.sentera.eu
back to the table of contents
Page 8
MULTIFUNCTIONAL
RMFPX-2R
ROOM CONTROLLER
OPERATING INSTRUCTIONS
Calibration procedure:
No relative humidity and temperature sensor calibration is necessary.
By default, the CO2 sensor element is self-calibrating.
Optionally, the CO2 sensor element can be calibrated and verified manually via
SSCDM. For this purpose, the CO2 sensor element is removable.
More information is available in the SSCDM datasheet and mounting and operating
instructions.
Bootloader
anks to the bootloader functionality, the sensor firmware can be updated via
Modbus RTU communication. To enter ‘Boot mode”, put a jumper onto pins 3 and
4 of the P1 header and restart the power supply (see Fig. 5). Once ‘Boot mode’ is
activated, the firmware can be updated via SM Boot application (part of 3SModbus
software suite) or Sensistant.
Fig. 5 P1 header
123 45
123 45
Put a jumper onto pins 1 and 2 and wait
for at least 5 seconds to reset the Modbus
communication parameters
Put a jumper onto pins 3 and 4 and restart
the supply to enter bootloader mode
NOTE
LED indications
1. When the green LED is on, the measured value (temperature, relative humidity or
CO2) is between the minimum and maximum alert range values (Fig. 6 - 1).
2. When the yellow LED is on, the measured value (temperature, relative humidity
or CO2) is in the alert range (Fig. 6 - 2).
3. When the red LED is on, the measured value (temperature, relative humidity or
CO2) is below the minimum measurement range value or above the maximum
value. Blinking red LED indicates loss of communication with a sensor (Fig. 6 - 3).
Fig. 6 LED indications
3
2
1
By default, the LED indication refers to temperature measurements. is can be
changed to relative humidity or CO2 values via Modbus Holding Register 26 (see
Tabl e Holding registers below).
Ambient light sensor
e measured light intensity in luxes is available in Input Register 5. Additionally,
an active and standby level can be defined in Holding registers 34 and 35. Input
MIW-RMFPX-2R-EN-000 - 23 / 04 / 20188 - 11
back to the table of contents
www.sentera.eu
Page 9
MULTIFUNCTIONAL
RMFPX-2R
ROOM CONTROLLER
Register 6 indicates if the measured value is below standby level, above active level
or in between both levels:
■
If the measured light level is below the Standby level, Input Register 6 indicates
“Standby”.
■
If the measured ambient light level is above the Active level, Input Register 6
indicates “Active”.
■
If the measured ambient light level is between the active and stand-by level, Input
Register 6 indicates “Low intensity”. When this feature is used, it is advisable to
adjust the active and standby levels in Holding Registers 34 and 35 according to
the actual ambient light conditions around the sensor.
VERIFICATION OF INSTALLATION INSTRUCTIONS
After switching on the power supply one of the LEDs lights up according to the
status of the measured variable. If this is not the case, check the connections.
MODBUS REGISTER MAPS
INPUT REGISTERS
Data typeDescriptionDataValues
1Temperaturesigned int.Actual temperature level-300—700 500 = 50,0 °C
11Output v alue 1unsigned int.Ana log output va lue - T, rH or CO
12—13Reser ved, retur n “0”.
14Temper ature aler t agunsigned int.
15Relative hum idity aler t agunsigned int.
16CO2 aler t agunsigned int.
17Temperat ure range lim it ag unsigned int.
18
19CO2 range lim it agunsigne d int.
20
21CO2 Sensor faultunsigned int.
22A mbient light sensor faultunsigned int.
2
Relative humidity r ange
limit ag
Humidit y / temper ature
sensor fault
unsigned int.Actua l CO2 level0—2.000 2.000 = 2.000 ppm
unsigned int.
unsigned int.
Active o r Standby ind ication ac cording t he Active /
Standby light le vel d ened via holding regi sters 34
and 35. If the me asured li ght level is bet ween the
two leve ls, the indic ation is “0” (L ow intensit y)
2
Flag ind icates tha t measure d temperat ure is out side
set ale rt values . Set to ‘1’ when the mea sured valu e
is outs ide the temp erature alert values dened by
holding r egiste rs 20 and 21
Flag ind icates tha t measure d relative hu midity
is outs ide set aler t values. S et to ‘1’ when the
measur ed value is ou tside the r elative hum idity aler t
values d ened by hol ding regis ters 22 and 23
Flag ind icates tha t measure d CO2 level is ou tside set
aler t values. Se t to ‘1’ when the measur ed value is
outside the CO2 ran ge limi t valu es de ned by hold ing
regis ters 24 and 25
Flag ind icates tha t measure d temperat ure is out side
set ran ge limit value s. Set to ‘1’ when the me asured
value is ou tside the t emperat ure range lim it values
dene d by holding re gister s 14 and 15
Flag ind icates tha t measure d relative hu midity is
outsi de set range l imit values. Set to ‘1’ when the
measur ed value is ou tside the r elative humi dity limit
range va lues dene d by holding re gister s 16 and 17
Flag ind icates tha t measure d CO2 level is outside
set ran ge limit value s. Set to ‘1’ when the me asured
value is outside the CO2 values dened by hold ing
regis ters 18 and 19
Flag ind icates if th e communic ation with t he
tempe rature and h umidity se nsor is los t
Flag tha t shows if the co mmunicat ion with the CO2
senso r is lost
Flag tha t shows if the co mmunicat ion with the
ambient l ight senso r is lost
0—2
0—1.000
0—1
0—1
0—1
0—1
0—1
0—1
0—1
0—1
0—1
0 =
1 =
2 =
0 =
1.000 =
0 =
1 =
0 =
1 =
0 =
1 =
0 =
1 =
0 =
1 =
0 =
1 =
0 =
1 =
0 =
1 =
0 =
1 =
Low light intensity
Measur ed tempe rature is OK
Measur ed tempe rature is to o high/ low
Measur ed rH is OK
Measur ed rH is too h igh/ low
Measured CO2 is OK
Measured CO2 is too hig h/ low
Temperat ure range is O K
Temperat ure range is t oo high/ low
rH rang e is too high/ lo w
CO2 range is t oo high/ low
Active
Standby
0 %
100 %
rH rang e is OK
CO2 range is O K
Yes
Yes
Yes
No
No
No
MIW-RMFPX-2R-EN-000 - 23 / 04 / 20189 - 11
www.sentera.eu
back to the table of contents
Page 10
MULTIFUNCTIONAL
RMFPX-2R
HOLDING REGISTERS
1Device s lave addres sunsigned int. Modbus device address1—2471
2Modbus baud rateunsigned int. Modbus communication baud rate0—62
3Modbus p arity mo deunsi gned int. Parit y check mo de0—21
4Device typeunsigned int. Device type (Re ad onl y)RMFPX-2R = 1106
5HW versi onun signed int. Hardwa re versio n of the devic e (Rea d on ly)XXXX0 x0100 = HW versi on 1.00
6FW ver sionunsigned int. Fi rmware ver sion of the de vice (Re ad o nly)XXXX0 x0100 = FW ve rsion 1.00
7Reser ved, retur ns “0”
8Output 1 overwriteun signed int. Enable s the direc t contro l over the outp ut0—10
9—1 0Re served, r eturn “0”.
11Output 1 typeunsigned int. Se lect anal og / digital o utput typ e 1—31
12—13Rese rved, ret urn “0”.
Minimum temperature
14
range
Maximum temperature
15
range
Minimum relative
16
humidity range
Maximum relative
17
humidity range
18Minimum CO2rangeunsigned int.
19Maximum CO2 rangeunsigned int.
Minimum temperature
20
alert
Maximum temperature
21
alert
Minimum relative
22
humidity alert
Maximum r elative
23
humidity alert
24Minimum CO2 alertunsigned int. Minimum CO2 alarm value
25Maximum CO2 alertunsigned int. Maximum CO2 alarm value
26LED indic ation unsigned int. L ED indicat ion relate d to one of the p arameter s1—3 1
Internal voltage source
27
selection Output 1
28—2 9Reserve d, return “0 ”.
Modbus n etwork r esistor
30
termination (NBT)
31Outp ut 1 overwri te value unsigned int.
32—33Res erved, re turn “0”.
34Active level unsigned int.
35Standby levelunsigned int.
36Modbus re gister s resetunsigned int.
CO2 module s elf
37
calibr ation (ABC lo gic)
algorithm
38Minimum output valueunsigned int. Sets minimu m value of outp ut signal in pe rcentag e0—40020 = 20 %
39
Maximum output valueunsigned int. Sets m aximum value o f output sign al in perce ntage60—10010060 = 60 %
40Reser ved, retu rns “0”.
If you want to n d out more ab out Modbus ove r serial lin e, please vi sit: http://www.modbus.org/docs/Modbus_over_serial_line_V1_02.pdf
Data typeDescriptionDataDefault Values
unsigned int.
unsigned int.
unsigned int.
unsigned int.
unsigned int. Minimum temperature alarm value
unsigned int. Maximum temperature alarm value
unsigned int. Minimum relative humidity alarm value
unsigned int. Maximum relative humidity alarm value
unsigned int. Select ion of inter nal voltage s ource for P WM output 0 —10
unsigned int.
unsigned int.
ROOM CONTROLLER
Minimum va lue of the temp erature r ange; cannot b e
set high er than max. te mperatur e range minu s 5ºC
Maximum v alue of tempe rature ra nge; cannot be s et
lower tha n min. temper ature rang e plus 5ºC
Minimum va lue of the rH ra nge; cannot be s et higher
than max. r H range minu s 5 %
Maximum v alue of rH ran ge; cannot be se t lower than
min. rH ran ge plus 5%
Minimum va lue of the CO2 range; ca nnot be set hig her
than max. CO2 range min us 100 ppm
Maximum value of CO2 range; ca nnot be set low er
than min. CO2 range pl us 100 ppm
Set devi ce as ending t he line or not by c onnecti ng
NBT
Overw rite value f or output 1. Ac tive only if H olding
regis ter 8 is set t o 1
The ambi ent light leve l above which ‘Act ive’ is
indica ted in input r egister 6
The ambi ent light leve l below whic h ‘Standby’ i s
indica ted in input r egister 6
Reset s Modbus Ho lding regi sters to de fault value s.
When nis hed this reg ister is aut omaticall y reset to ‘0’
Enable s or disable s the CO2 module self-calibration
algori thm. If enable d, the senso r will typi cally reac h
its ope rational a ccurac y after 24 hou rs of contin uous
opera tion. The se nsor will mai ntain its ac curacy g iven
that it is e xposed to a r eferen ce level of 40 0 ppm CO2
at leas t once in a 7 day per iod
0 =
1 =
2 =
3 =
4 =
5 =
6 =
0 =
1 =
2 =
0 =
1 =
1 =
2 =
3 =
0 — (Max. rang e — 50) 010 0 = 10,0 °C
(Min. range + 50) – 500500500 = 50,0 °C
50 — (Max. ran ge — 50) 50200 = 20,0 % rH
(Min. range + 50) – 850850850= 85,0 % rH
0 – (Max. rang e — 100) 4001.000 = 1.000 ppm
(Min. range + 100) – 2.0002.0002.000 = 2.000 ppm
Min. temp erature r ange —
Max. temperature alarm
Min. temp erature al arm —
Max. temperature range
Min. rela tive humidit y range —
Max. relative humidity alarm
Min. rela tive humidit y alarm —
Max. rel ative humidi ty range
Min. CO2 range — Ma x. CO2
alarm
Min. CO2 alarm — Ma x. CO2
range
0—10
0—1.0000
0—32.0001001.000 = 1.000 lx
0—32.0001010 = 10 lx
0—10
0—11
0100 = 10,0 ºC
500500 = 50,0 ºC
50200 = 20,0 % rH
850850 = 85,0 % rH
400400 =400 ppm
2.0002.000 =2.000 ppm
1 =
2 =
3 =
0 =
1 =
0 =
NBT disconnected
1 =
0 =
1.000 =
0 =
Idle Rese t Modbus
1 =
0 =
1 =
57. 60 0
115.2 00
230.40 0
Disabled
Enabled
1—10 VD C
0—20 mA
temperature
3,3 VDC
12 VDC
NBT connected
registers
Disabled
Enabled
4.800
9.600
19.20 0
38.40 0
8N1
8E1
8O1
PWM
CO
0 %
100 %
rH
2
MIW-RMFPX-2R-EN-000 - 23 / 04 / 201810 - 11
www.sentera.eu
back to the table of contents
Page 11
MULTIFUNCTIONAL
RMFPX-2R
ROOM CONTROLLER
TRANSPORT AND STORAGE
Avoid shocks and extreme conditions; stock in original packing.
WARRANTY AND RESTRICTIONS
Two years from the delivery date against defects in manufactur ing. Any modifications
or alterations to the product after the date of publication relieve the manufacturer
of any responsibilities. e manufacturer bears no responsibility for any misprints or
mistakes in this data.
MAINTENANCE
In normal conditions this product is maintenance-free. If soiled, clean with a dr y or
damp cloth. In case of heavy pollution, clean with a non-aggressive product. In these
circumstances the unit should be disconnected from the supply. Pay attention that
no fluids enter the unit. Only reconnect it to the supply when it is completelydry.
MIW-RMFPX-2R-EN-000 - 23 / 04 / 201811 - 11
back to the table of contents