Read all the information, the datasheet, mounting and operating instructions and
study the wiring and connection diagram before working with the product. For
personal and equipment safety, and for optimum product performance, make sure you
entirely understand the contents before installing, using, or maintaining this product.
For saf ety and li censing (CE ) reasons , unauthor ised conver sion and/ or modi fication s
of the product are inadmissible.
e product should not be exposed to abnormal conditions, such as: extreme
temperatures, direct sunlight or vibrations. Long-term exposure to chemical
vapours in high concentration can affect the product performance. Make sure the
work environment is as dry as possible; avoid condensation.
All installations shall comply with local health and safety regulations and local
electrical standards and approved codes. is product can only be installed by
an engineer or a technician who has expert knowledge of the product and safety
precautions.
Avoid contacts with energised electrical parts. Always disconnect the power
supply before connecting, servicing or repairing the product.
Always verify that you apply appropriate power supply to the product and use
appropriate wire size and characteristics. Make sure that all the screws and nuts
are well tightened and fuses (if any) are fitted well.
Recycling of equipment and packaging should be taken into consideration and these
should be disposed of in accordance with local and national legislation/regulations.
In case there are any questions that are not answered, please contact your
technical support or consult a professional.
MIW-MTP-D010-AT-BT-EN-000 - 06 / 02 / 20193 - 7
back to the table of contents
www.sentera.eu
MTP-D010
PRODUCT DESCRIPTION
ARTICLE CODES
ACTIVE
POTENTIOMETER
MTP-D010 potentiometer series are intended for direct control of EC fans / motors
and actuators. ey require a supply voltage of 3—15 VDC and provide a stepless
output signal that can be set by a rotary knob within a range adjustable via two
trimmers for Vmin (10—70 % Vin) and Vmax (30—100% Vin). ey are suitable for
applications where a DC control signal is required. e -AT version features an off
position, while -BT provides control within the range Vmin—Vmax. eir enclosures
are splash-proof and suitable for both inset and surface mounting.
CodeOutput Off position
MTP-D010-AT0, Vmin—Vmax yes
MTP-D010-BTVmin—Vmaxno
INTENDED AREA OF USE
TECHNICAL DATA
■
Applications where a DC control signal is required
■
For indoor use only
■
Power supply: 3—15 VDC
■
Output:
►
MTP-D010-AT: 0, Vmin—Vmax
►
MTP-D010-BT: Vmin—Vmax
■
Load: RL ≥ 2 kΩ
■
Vmin: 10—70 % Vin
■
Vmax: 30—100% Vin
■
Enclosure:
►
External: ASA, white-ivory (RAL 9010), IP54 (according to EN 60529)
►
Internal: polyamide, white-ivory (RAL 9010), IP44 (according to IEC 60335)
■
Operating ambient conditions:
►
temperature: 0—40 °C
►
rel. humidity: < 100 % rH (non-condensing)
►
Storage temperature: -10—55 °C
STANDARDS
■
Low Voltage Directive 2014/35/EC
■
EMC Directive 2014/30/EC
■
WEE E Di rective 2012/19/EU
■
RoHs Directive 2011/65/EU
MIW-MTP-D010-AT-BT-EN-000 - 06 / 02 / 20194 - 7
back to the table of contents
www.sentera.eu
ACTIVE
MTP-D010
POTENTIOMETER
OPERATIONAL DIAGRAMS
MTP-D010-AT MTP-D010-BT
Output, VDC
100 % Vin
Vmax
70 % Vin
100 % Vin
70 % Vin
Output, VDC
Vmax
Vmin
30 % Vin
10 % Vin
Min.
O
Potenometer posion
On
Max
WIRING AND CONNECTIONS
Vin (+)Supply voltage (3—15 VDC)
Vin(-)Supply voltage, ground
Vout (-)Output, ground
Vout (+)Output voltage
ConnectionsCable cross section: max. 2,5 mm
MOUNTING INSTRUCTIONS IN STEPS
Before you start mounting your potentiometer, read carefully “Safety and Precautions”
and follow the steps:
For inset mounting
Vmin
10 % Vin
30 % Vin
Min
Potenometer posion
²
Max
1. Remove the knob by turning it to the right until it pops out.
2. Unscrew the loose nut to remove the cover of the external enclosure.
3. Do the wiring according to the wiring diagram (see Fig. 1 Wiring and connections).
4. Mount the internal enclosure into the wall according to the mounting dimensions
shown in Fig. 2 Mounting dimensions - inset mounting.
Fig. 1 Wiring and connections
Vmin adjustment
trimmer
Supply voltage
( 3—15 V DC )
MIW-MTP-D010-AT-BT-EN-000 - 06 / 02 / 20195 - 7
www.sentera.eu
Vmax adjus tment
trimmer
Output:
-A T: 0, Vmin—Vmax
-B T: Vmin—Vmax
back to the table of contents
2633
82
89
62
60
82
89
69
82
ACTIVE
MTP-D010
Fig. 2 Mounting dimensions - inset mounting
POTENTIOMETER
50
62
50x50
NOTE
Fig. 3 Mounting dimensions - surface mounting
Mount the unit so that the terminal block and connections are at the lower side.
5. Adjust the Vmin and Vmax trimmers.
6. Mount back the cover and secure it with the nut.
7. Put back the knob and turn it to off position (-AT version) or minimum position
(-BT version).
8. Turn on the power supply.
For surface mounting
1. Remove the knob by turning it to the right until it pops out.
2. Unscrew the nut to remove the cover of the external enclosure.
3. Mount the external enclosure onto the surface by means of screws and dowels
(notincluded in the set) adhering to the mounting dimensions shown in Fig. 3
Mounting dimensions - surface mounting.
62
62
4. Insert the cables through the grommets.
5. Do the wiring according to the wiring diagram (see Fig. 1 Wiring and connections).
6. Insert the internal enclosure into the external one and fix it using the screws and
washers included in the set.
NOTE
MIW-MTP-D010-AT-BT-EN-000 - 06 / 02 / 20196 - 7
Mount the unit so that the terminal block and connections are at the lower side.
7. Mount back the cover and secure it with the nut.
8. Put back the knob and turn it to off position (-AT version) or minimum position
(-BT version).
9. Turn on the power supply.
www.sentera.eu
back to the table of contents
MTP-D010
ACTIVE
POTENTIOMETER
NOTE
A 5 mm hole can be drilled at the bottom of the external enclosure to drain the
condensed water.
VERIFICATION OF INSTALLATION INSTRUCTIONS
ATTENTION
Use only tools and equipment with non-conducting handles when working on
electrical devices.
■
In case of faulty operation, please check if:
►
the right voltage is applied;
►
all connections are correct;
►
the regulated device is functioning.
TRANSPORT AND STORAGE
Avoid shocks and extreme conditions; stock in original packing.
WARRANTY AND RESTRICTIONS
MAINTENANCE
Two years from the delivery date against defects in manufacturing. Any modifications
or alterations to the product after the date of publication relieve the manufacturer
of any responsibilities. e manufacturer bears no responsibility for any misprints or
mistakes in this data.
In normal conditions this product is maintenance-free. If soiled, clean with a dry or
damp cloth. In case of heavy pollution, clean with a non-aggressive product. In these
circumstances the unit should be disconnected from the supply. Pay attention that no
fluids enter the unit. Only reconnect it to the supply when it is completelydry.
MIW-MTP-D010-AT-BT-EN-000 - 06 / 02 / 20197 - 7