Sentera Controls DSTHG-2, DSTH 2 Series, DSTHF-2 Mounting And Operating Instructions

COMBINED TEMPERATURE AND RELATIVE HUMIDITY DUCT
DSTHX-2
Mounting and operating instructions
TRANSMITTER
COMBINED T AND rH DUCT
DSTHX-2
TRANSMITTER
Table of contents
PRODUCT DESCRIPTION 4
ARTICLE CODES 4
STANDARDS 4
OPERATIONAL DIAGRAMS 5
WIRING AND CONNECTIONS 5
OPERATING INSTRUCTIONS 8
VERIFICATION OF INSTALLATION INSTRUCTIONS 10
WARRANTY AND RESTRICTIONS 10
MAINTENANCE 10
MIW-DSTHX-2-EN-000 - 23 / 07 / 2019 2 - 10
www.sentera.eu
COMBINED T AND rH DUCT
DSTHX-2
TRANSMITTER

SAFETY AND PRECAUTIONS

Read all the information, the datasheet, mounting and operating instructions and study the wiring and connection diagram before working with the product. For personal and equipment safety, and for optimum product performance, make sure you entirely understand the contents before installing, using, or maintaining this product.
For saf ety and li censing (CE ) reasons , unauthor ised conver sion and/ or modifi cations of the product are inadmissible.
e product should not be exposed to abnormal conditions, such as: extreme temperatures, direct sunlight or vibrations. Long-term exposure to chemical vapours in high concentration can affect the product performance. Make sure the work environment is as dry as possible; avoid condensation.
All installations shall comply with local health and safety regulations and local electrical standards and approved codes. is product can only be installed by an engineer or a technician who has expert knowledge of the product and safety precautions.
Avoid contacts with energised electrical parts; always treat the product as if it is live. Always disconnect the power supply before connecting, servicing or repairing the product.
Always verify that you apply appropriate power supply to the product and use appropriate wire size and characteristics. Make sure that all the screws and nuts are well tightened and fuses (if any) are fitted well.
Recycling of equipment and packaging should be taken into consideration and these should be disposed of in accordance with local and national legislation/regulations.
In case there are any questions that are not answered, please contact your technical support or consult a professional.
MIW-DSTHX-2-EN-000 - 23 / 07 / 2019 3 - 10
www.sentera.eu
back to the table of contents
COMBINED T AND rH DUCT
DSTHX-2
TRANSMITTER

PRODUCT DESCRIPTION

ARTICLE CODES

e DSTHX-2 series are dual duct transmitters which measure temperature and relative humidity. ey feature a wide range of low voltage power supply and two analogue / modulating outputs. All parameters are accessible via Modbus RTU.

INTENDED AREA OF USE

TECHNICAL DATA

Article code Supply
DSTHG-2
DSTHF-2
Monitoring duct temperature and relative humidity in HVAC applications
Selectable temperature range: -30—70 °C
Selectable relative humidity range: 0—100 %
Accurac y: ±0,4 °C (0—50 ° C); ±3 % rH (5—85 % rH), depending on the selected parameter
Modbus RTU communication
Bootloader for updating the firmware via Modbus RTU communication
Minimum airflow velocity required: 1 m/s
Enclosure and probe material:
ASA, grey (RAL9002)
Protection standard: Enclosure: IP54, probe: IP20
Operating ambient conditions:
temperature: 0—50 °C
rel. humidity: 5—85 % rH, (non-condensing)
Storage temperature: -10—60 °C
18—34 VDC 1,6 8 W 1,2 6 W 70 mA
15—24 VAC ±10% 1,8 W 1, 35 W 75 mA
18—34 VDC 1,6 8 W 1,2 6 W 70 mA
Maximum power
consumption
Nominal power
consumption
Imax

STANDARDS

EMC Directive 2014/30/EC:
EN 61326-1:2013 Electrical equipment for measurement, control and laboratory use - EMC requirements - Part 1: General requirements
EN 61326-2-3:2013 Electrical equipment for measurement, control and laboratory use - EMC requirements - Part 2-3: Particular requirements - Test configuration, operational conditions and performance criteria for transducers with integrated or remote signal conditioning
WEE E Di rective 2012/19/EC
RoHs Directive 2011/65/EC
MIW-DSTHX-2-EN-000 - 23 / 07 / 2019 4 - 10
back to the table of contents
www.sentera.eu
COMBINED T AND rH DUCT
DSTHX-2
TRANSMITTER

OPERATIONAL DIAGRAMS

Analogue
output 1 [%]
100
-30
Min
range
Max
range
70 T [°C]
Analogue
output 2 [%]
100
0 Min
range
Max
range
100 rH [%]

WIRING AND CONNECTIONS

Article type DSTHF-2 DSTHG-2
VIN 18—34 VDC 18—34 VDC 15—24 VAC ±10%
GND Ground Common ground AC ~
A Modbus RTU (RS485), signal A Modbus RTU (RS485), signal A
/B Modbus RTU (RS485), signal /B Modbus RTU (RS485), signal /B
Analogue / modulating output 1 for
AO1
GND Ground AO1 Common ground
AO2
GND Ground AO2 Common ground
Connections Spring contact terminal blocks, cable cross section: 1,5 mm
temperature measurement (0—10 VDC /
0—20 mA / PWM)
Analogue / modulating output 2 for relative
humidity measurement (0—10 VDC /
0—20 mA / PWM)
Analogue / modulating output 1 for temperature
measurement (0—10 VDC / 0—20 mA / PWM)
Analogue / modulating output 2 for relative humidity
measurement (0—10 VDC / 0—20 mA / PWM)
2
CAUTION
MIW-DSTHX-2-EN-000 - 23 / 07 / 2019 5 - 10
e -F version of the product is not suited for 3-wire connection. It has separate grounds for power supply and analogue output. Connecting both grounds together might result in incorrect measurements. Minimum 4 wires are required to connect -F type sensors. e -G version is intended for 3-wire connection and features a ‘common ground’. is means that the ground of the analogue output is internally connected with the ground of the power supply. For this reason, -G and -F types cannot be used together on the same network. Never connect the common ground of -G type articles to other devices powered by a DC voltage. Doing so might cause permanent damage to the connected devices.
www.sentera.eu
back to the table of contents
Ø 12
18,5
42,3
50
4
70
66
COMBINED T AND rH DUCT
DSTHX-2
TRANSMITTER
MOUNTING & OPERATING INSTRUCTIONS IN STEPS
Before you start mounting the DSTHX-2 duct transmitter, read carefully “Safety and Precautions”.
Follow these steps:
1. When preparing to mount the DSTHX-2, bear in mind that the unit itself must be
installed onto the outer surface of the duct both via fixing the flexible flange or direc tly the unit enclosure, while the probe must be inserted inside the duct, see
Fig. 1 and Fig. 2 below.
Fig. 1 Mounting dimensions
With flange Without flange
2x Ø 5
60
285
86,8
100
105
Fig. 2 Mounting position
80
4x Ø 4,
34,5
Correct Incorrect
AIR F LOW
MIW-DSTHX-2-EN-000 - 23 / 07 / 2019 6 - 10
www.sentera.eu
AI R F LOW
back to the table of contents
DSTHX-2
Fig. 3 Mounting requirements
COMBINED T AND rH DUCT TRANSMITTER
2. Having selected the appropriate mounting location, proceed with the following steps:
2.1 Drill a Ø 13 mm hole into the duct and insert the probe. Apply an air-tight
sealing between probe and duct.
2.2 Fix the flange onto the duct outer surface using the self-drilling screws
delivered with the unit. If you do not intend to use the flange, insert the tube and fix the enclosure onto the duct. Mind the airflow direction (see Fig. 2 and Fig. 3).
7,5*D
(1)
3,5*D
ATTENTION
ATTENTION
ATTENTION
(1)
D = Duct diameter
Installation requirements: e DSTHX-2 must not be installed in turbulent air zones. Ensure sufficiently long settling zones upstream and downstream of the tapping point. A settling zone consists of a straight section of pipe or duct with no obstructions. Avoid installation near filters, cooling coils, fans, etc. e sensor will achieve the optimal result when the measurement is taken at least 7,5 duct diameters downstream and at least 3 duct diameters upstream from any turns or flow obstructions.
Installation of the unit near high EMI-emitting devices may lead to faulty measurements. Use shielded wiring in areas with high EMI.
Keep at least 15 cm distance between the sensor lines and the 230 VAC power lines.
2.3 Install the tube at the desired depth and, in case you use the flange, fix it via
the plastic white screw in the flexible flange.
2.4 Unscrew the cover of the unit to remove it and insert the connecting cables
through the cable gland of theunit.
2.5 Do the wiring according to the information in section “Wiring and
connections” adhering to Fig. 4 below.
MIW-DSTHX-2-EN-000 - 23 / 07 / 2019 7 - 10
back to the table of contents
www.sentera.eu
COMBINED T AND rH DUCT
DSTHX-2
Example 1 Example 2
TRANSMITTER
Fig. 4 Wiring and connections
3. Close the enclosure and fix the cover.
4. Switch on the power supply.
5. Customise the factory settings to the desired ones via the 3SModbus software
or Sensistant (if necessary). For the default factory setting see Tab le Modbus register maps.
Optional settings
To assure correct communication, the NBT needs to be activated in only two devices on the Modbus RTU network. If necessary, enable the NBT resistor via 3SModbus or Sensistant (Holding register 9).
Supply voltage
DSTHF-2: 18—34 VDC
DS THG -2: 18—34 V DC / 15—24 VAC ±10 %
Modbus
RTU
A
/B
Anal ogue / modulat ing output 2 - r H
(0—10 VDC/0—20 m A / PWM)
Analogue / modulating 1 - T
(0—10 VDC/0—20 m A / PWM)
Slave 1
NBT
NOTE
CAUTION
NBT
Slave 2
Master
On a Modbus RTU network, two bus terminators (NBTs) need to be activated.
Do not expose to direct sunlight!

OPERATING INSTRUCTIONS

Calibration procedure:
Both the relative humidity and temperature sensor elements are factory calibrated. Recalibration is not necessary.
RX
ТX
NBT
Slave n
Master
NBT
Slave 1
Slave 2
RX
ТX
NBT
Slave n
Bootloader
anks to the bootloader functionality, the sensor firmware can be updated via Modbus RTU communication. To enter “Boot mode”, put a jumper onto pins 3 and 4 of the P1 header and restart the power supply (see Fig. 5). Once ‘Boot mode’ is activated, the firmware can be updated via SM Boot application (part of 3SModbus software suite) or Sensistant.
MIW-DSTHX-2-EN-000 - 23 / 07 / 2019 8 - 10
www.sentera.eu
back to the table of contents
COMBINED T AND rH DUCT
DSTHX-2
TRANSMITTER
Fig. 5 P1 header
123 45
123 45
Put a jumper onto pins 1 and 2 and wait
for at least 5 seconds to reset the Modbus
communication parameters
Put a jumper onto pins 3 and 4 and restart
the supply to enter bootloader mode

MODBUS REGISTER MAPS

INPUT REGISTERS
Input Registers Data type Description Data Values
MODBUS REGISTER MAP
1 Temperature reading si gned int Actual temperature level -300—700 500 = 50,0°C
2 Output v alue 1 (T) un signed int Output v alue 1 (T) 0—1.000
3 Temperatu re alert a g unsigned int
4 Temperatu re range limit  ag unsigned int
5 Humidity, temperature sensor fault unsigned int
6—9 Reser ved, retur n 0
10 Relative humidity level uns igned int Actual r elative humi dity level 0—1.000 1.000 = 100,0 % rH
11 Output v alue 2 (rH) unsigned int Out put value 2 (rH) 0—1.000
12 Relative humi dity aler t ag unsigned int
13 Relative humi dity range l imit ag unsigned int
14 Humidity, temperature sensor fault unsigned int
15 Dew point leve l signed in t Calculated dew point -700—700 200 = 20,0°C
16—50 Reser ved, retur n 0
Flag indi cates that m easured Tempe rature is out side set alert v alues. Set to
'1' when the measured value is outside the Temperature alert values dened
by holding r egister s 13 and 14
Flag indi cates that m easured te mperatur e is outside s et range limit values. S et to '1' when the meas ured tempe rature is ou tside limit r ange
values de ned by holdi ng registe rs 11 and 12
Flag that s hows if the com munication w ith temper ature & humidi ty sensor is lost
Flag indi cates that m easured Rel ative humidit y is outsid e set alert values. S et to '1' when the meas ured value is o utside the Re lative
humidit y alert val ues dened by h olding regi sters 21 and 22
Flag indi cates that m easured Rel ative humidit y is outsid e set range lim it values. S et to '1' when the meas ured Relati ve humidity i s outside limi t
range val ues dened by h olding regi sters 19 and 20
Flag that s hows if the com municatio n with temper ature & humidi ty senso r is lost
0—1
0—1
0—1
0—1
0—1
0—1
0 = Temperature measurement OK
1 = Temperatu re measure ment too low/
0 = Temperatu re range OK
1 = Temperatu re range too l ow/high
0 = Relative h umidity mea surement O K
1 = Relative h umidity mea surement t oo
0 = Relative h umidity ran ge OK
1 = Relative h umidity ran ge too low/high
0 = 0 %
1.000 = 100 %
0 = No 1 = Yes
0 = 0 %
1.000 = 100 %
low/hi gh
0 = No 1 = Yes
high
HOLDING REGISTERS
Holding Registers Data type Descrip tion Data Values
1 D evice slave ad dress unsigned int Modbus device address
2 M odbus baud rate unsigned int Modbus communication baud rate
3 Mo dbus parity unsigned int Parit y check mod e
4 D evice type unsigned int Device type. Read only
5 H W version unsigned int Hardwar e version of t he device. Rea d only XXXX 0x0100 = HW vers ion 1.0
6 F W versio n unsigned int Firmware v ersion of th e device. Read o nly XXXX 0x0200 = F W version 2.2
7 Re served, re turns 0
8 M odbus safe ty timeou t unsigned int
Modbus n etwork re sistor
9
termination (NBT)
10 Modbus r egister s reset unsigned int
11 Minimum temperature rang e unsigned int
12 Maximum temperature range unsigned int
13 Minimum temperature alert unsigned int Minimum temperature alarm value
14 Maximum temperature alert unsigned int Maximum temperature alarm value
15 —18 Reser ved, retur n 0
unsigned int
Afte r time with no Mo dbus communi cation,
output s are set to 0.
Set devic e as end devic e of the line / or not by connecting NBT
Reset s Modbus Hold ing regist ers to defau lt values. W hen finish ed this regi ster is automatically reset to '0'
Minimum value of temperature range, cannot be set hig her than maximu m temperat ure range min us 5°C
Maximum value of temperature range, cannot be set le ss than minimum t emperatur e range plus 5°C
1—247 default: 1
0—6 default: 2
0— 2 default: 1
DSTHG -2 = 1.632 DSTHF-2 = 1.633
0—60 default: 0
0—1 default: 0
0—1 default: 0
-300 - (Max-50) default: 0
(Min+50)—700 default: 5 00
Min. tempe rature ra nge —Max. temperature alarm default: 0
Min. tempe rature ala rm —Max. temperature range default: 5 00
0 = 4.800 1 = 9.600 2 = 19.200 3 = 38.400 4 = 57.600 5 = 115.200 6 = 230.400
0 = 8N1
1 = 8E1
2 = 8O1
60 = 60 minut es
0 = NBT disc onnecte d
1 = NBT conn ected
1 = Reset Mo dbus Regist ers
0 = Idle
100 = 10,0 °C
500 = 50,0°C
500 = 50,0°C
500 = 50,0°C
MIW-DSTHX-2-EN-000 - 23 / 07 / 2019 9 - 10
www.sentera.eu
back to the table of contents
COMBINED T AND rH DUCT
DSTHX-2
HOLDING REGISTERS
Holding Registers Data type Descrip tion Data Values
Minimum relative humidity
19
range
Maximum relative humidity
20
range
Minimum relative humidity
21
alert
Maximum relative humidity
22
alert
23—40 Reser ved, return 0
41 Out put 1 type (T ) unsigned int Selec t analogue / mo dulating out put 1 type
42 Output 1 ove rwrite ( T) unsigned int
43 Output 1 over write valu e (T) un signed int
Internal voltage source
44
selec tion Outpu t 1 (T)
45—50 Res erved, re turn 0
51 Output 2 t ype (rH) unsigned int Selec t analogue / mo dulating out put 2 type.
52 Output 2 over write (rH) unsigne d int
Output 2 ove rwrite va lue
53
(rH )
Internal voltage source
54
selec tion Outpu t 2 (rH)
55—80 Reser ved, retu rn 0
If you want to nd o ut more about M odbus over se rial line, ple ase visit: http://www.modbus.org/docs/Modbus_over_serial_line _V1_02.pdf
TRANSMITTER
unsigned int
unsigned int
unsigned int Minimum relative humidity alarm value
unsigned int Maximum relative humidity alarm value
unsigned int
unsigned int
unsigned int
Minimum val ue of relativ e humidity ra nge, cannot b e set higher th an maximum rel ative humidity range minus 5%
Maximum va lue of relati ve humidity r ange, cannot b e set less tha n minimum rela tive humidity range plus 5%
Enable s the direct c ontrol over t he tempera ture output.
Overw rite value fo r output 1. Acti ve only if Holding r egister 42 is s et to 1.
Selec tion of inter nal voltage s ource for P WM output 1.
Enable s the direct c ontrol over t he relative humidity output.
Overw rite value fo r output 2. Act ive only if Holding r egister 52 i s set to 1.
Selec tion of inter nal voltage s ource for P WM output 2.
0—( Max-5 0) default: 0
(Min+50)—1.000 defau lt: 1.000
Min. rela tive humidit y range—Max. relative humidity alarm default: 0
Min. rela tive humidit y alarm —Max. relative humidity range defau lt: 1.000
1—3 default: 1
0—1 default: 0
0—1.000 default: 0
0—1 default: 0
1—3 default: 1
0—1 default: 0
0—1.000 default: 0
0—1 default: 0
200 = 20,0 % rH
850 = 85 % rH
200 = 20,0 % rH
850 = 85 % rH
1 = 0—10 VDC
2 = 0—20 mA
3 = PWM
0 = Disabl ed
1 = Enable d
0 = 0 %
1.000 = 100 %
0 = 3,3 VDC
1 = 12 VDC
1 = 0—10 VDC
2 = 0—20 mA
3 = PWM
0 = Disabl ed
1 = Enable d
0 = 0 %
1.000 = 100 %
0 = 3,3 VDC
1 = 12 VDC

VERIFICATION OF INSTALLATION INSTRUCTIONS

If your unit does not function as expected, please check the connections.

TRANSPORT AND STORAGE

Avoid shocks and extreme conditions; store in original packing.

WARRANTY AND RESTRICTIONS

Two years from the delivery date against defects in manufactur ing. Any modifications or alterations to the product after the date of publication relieve the manufacturer of any responsibilities. e manufacturer bears no responsibility for any misprints or mistakes in this data.

MAINTENANCE

In normal conditions this product is maintenance-free. If soiled, clean with a dry or damp cloth. In case of heavy pollution, clean with a non-aggressive product. In these circumstances the unit should be disconnected from the supply. Pay attention that no fluids enter the unit. Only reconnect it to the supply when it is completelydry.
MIW-DSTHX-2-EN-000 - 23 / 07 / 2019 10 - 10
www.sentera.eu
back to the table of contents