Heating / Cooling meter PolluStat E
Installation and operating instructions
PolluStat E
Installation and operating instructions
M H 4110 INT PolluStat E, page 1
The ultrasonic meter PolluStat E is suitable for the
measurement of energy consumption in heating or
cooling plants filled with the energy carrier liquid
water.
These installation and operating instructions
specify the installation and the operation of
PolluStat E and its variants. It is an essential part
of the delivered items and has to be handed over
to the final user.
Delivered items
PolluStat E (if applicable with already
connected temperature sensors)
2 screws, 2 dowels
2 gaskets
sealing material
these installation and operating
instructions
Content
1. Important directions ......................................... 2
2. Technical data ................................................. 3
shells for sizes DN 50 to 100 .......................... 13
Declaration of MID conformity ............................ 14
M H 4110 INT PolluStat E, page 2
®
-FTT10A plug-in module .... 12
Heating / Cooling meter PolluStat E
Installation and operating instructions
1. Important directions
The installation of PolluStat E requires
adequate professional knowledge and
should be carried out by specially trained
persons only.
The technical data specified in chapter 2
must not be exceeded during operation.
The connection cable between flow
sensor and calculator must not be cut,
shortened or extended.
During the installation of PolluStat E, the
well or ball valve, particular care is to be
taken that they are perfectly mounted,
because otherwise there might be the
danger of being scalded by leaking
heating liquid. Therefore, first of all, the
stop cocks are to be closed before
removal.
Depending on manufacturing conditions
the brass connection threads might be
sharp-edged. Therefore we recommend
wearing protection gloves.
Heating or cooling meters are measuring
instruments and have to be handled with
care. In order to protect them against
damages and soiling they should only be
taken from the package immediately
before installation.
The instrument must not be carried by the
cable.
For cleaning purposes use nothing else
but a cloth moistened with water.
Within the instrument there is a battery,
which must not be opened by force, come
into contact with water, be short-circuited
or exposed to temperatures exceeding
80 °C.
Empty batteries, no longer needed
electronic instruments or components are
hazardous waste and to be disposed of at
suitable collecting points.
If several meters are used in the same
billing unit, equal instrument types should
be chosen in the interest of the fairest
possible consumption billing.
Heating / Cooling meter PolluStat E
Installation and operating instructions
Mains-operated instruments:
The supply to mains-operated instruments must
be fused at 6 A. Only specially trained and
authorized personnel are permitted to carry
out the connection. Moreover attention is to be
paid to the national technical rules, e.g. VDE 0100
in particular.
Voltage: 220 ... 240 V AC
resp. 24 V AC
Frequency: 50/60 Hz
Max. power consumption: 0.5 VA
Cable length: ca. 1.1 m
2. Technical data
Temperature measuring
range
Temperature difference
range
Switch-off threshold 0.15 K
Measuring accuracy
Updating times and
integration cycles resp.:
Temperatures
Flow rate, power
Energy, volume
Optical data interface
Suitable temperature
sensors
Connection cable between
calculator and flow sensor
Power supply
(using period of the meter
may be defined by national
laws)
Electromagnetic
environment condition
Mechanical environment
condition
Protection class IP 54
Ambient temperature 5 … 55 °C
Storing temperature -20 … +65 °C
Relative air humidity < 93 %
Size (H x W x D)
in terms of wall mounting
Temperature range 5 … 130 °C
Protection class IP 65
Straight inlet and outlet
pipes
Calculator
= 2 … 180 °C
∆ = 3 … 150 K
Better than (%):
+ (0.5 + ∆
2 sec
4 sec
4 sec (16 sec *)
* in case of battery supply
Physical acc. to EN 61107
Data record acc to EN 13757-3
Pt 500 or Pt 100 (see
inscription at enclosure)
Connection in two- or four-wire
technology
1.5 m (optional: 5 m)
Battery for 6 years
(optional: 11 years)
or mains supply 230 V AC
resp. 24 V AC
Class E 1
Class M 2
ca. 159 x 125 x 52 mm
Flow sensor
Not required acc. to approval
directives
In case of stronger flow
disturbances a straight inlet
pipe of 5 x DN is recommended for the sizes
DN 50 bis 100
Depending on the version PolluStat E can be
used as a heating meter, as a cooling meter or as
a combined heating / cooling meter. Therefore the
text hereinafter includes following terms:
return pipe of heating plants: colder line
supply pipe of heating plants: warmer line
return pipe of cooling plants: warmer line
supply pipe of cooling plants: colder line
In case of meters with programmable installation place (see related inscription at
integrator) of the flow sensor the required position
(colder line or warmer line) has to be defined.
In order to do this, activate the display by
depressing the red key and releasing it again.
Then each one of the below mentioned options
can be selected one after the other by a short
keystroke. Having set the required position,
remove the bridge between terminal 3 and 4 in the
terminal block.
colder line warmer line
Attention!
Because of legal calibration regulations the
installation place can only be programmed
once. Therefore be very sure that you have set
the desired position before removing the
bridge.
M H 4110 INT PolluStat E, page 3
4.1 Flow sensor
Applicable standards: EN 1434-6
Standard installation of the flow sensor is in the
heating return pipe i.e. the colder line. If the flow
sensor is to be installed in the heating supply pipe
i.e. the warmer line, the integrator PolluStat EX is
to be used (X means that the integrator has been
adjusted for flow sensors in the warmer line).
An arrow on the body shows the flow
direction. The maximum operating pressure and
the maximum operating temperature must not be
exceeded.
It is absolutely advisable to install a dirt trap
before the flow sensor or at another suitable point
of the heating or chilling circuit as well as shut-off
valves before and after the flow sensor (in order to
avoid having to empty the pipeline if the meter is
to be exchanged). During initial installation a spool
piece is installed instead of the flow sensor and
the pipe system is thoroughly flushed. Then close
the shut-off valves, remove the spool piece, clean
the sealing surfaces and install the flow sensor
using new gaskets. Take care not to reduce the
pipe diameter by bad positioning of the gaskets,
particularly if flanged versions are installed.
In areas with thermal layering (e.g. after the
junction of two pipes with different temperatures)
a straight pipe of 10 x DN in front of the flow
sensor is recommended.
Special direction for horizontal installation of
meters of DN 50 to DN 100:
Both ultrasonic transducers in the flow sensor
have to be in horizontal position. For this reason
the PolluStat E has to be installed with the
integrator turned upwards.
In case of removed and separately mounted
integrator this is valid accordingly.
Heating / Cooling meter PolluStat E
Installation and operating instructions
Examples of installation in heating systems:
Fig. 1: Measurement after admixing
Fig. 2: Measurement in injection system
Fig. 3: Measurement with overflow valve
M H 4110 INT PolluStat E, page 4
Heating / Cooling meter PolluStat E
Installation and operating instructions
4.2 Installation of temperature sensors
PolluStat E is operated with separately approved
and paired temperature sensors type Pt 100 or
Pt 500. The applicable type is specified on the
integrator frontside. The two temperature sensors
can optionally be mounted in thermowells or
directly into the heating or cooling liquid. We
recommend using pairs of thermowells or ball
valves in order to facilitate future exchange.
For a general installation standard please refer to
EN 1434-2.
For temperature sensor type 45 mm x 5.2 mm
(length x diameter) and DS 27.5 acc. to EN 14342 we recommend the installation in our ball valves
with temperature sensor retainer M 10 x 1 or
complete installation kits including fitting pieces
and thread connections (please refer to data
sheet LH 4110 INT).
For Sensus temperature sensors of the overall
lengths 100 mm and 150 mm, the sensitive zone
is ca. 10 to 15 mm measured from the
temperature sensor’s tip and has to be positioned
as near as possible to the middle of the pipe diameter. Refer to the following guide for
installing such temperature sensors:
Nominal sizes < DN 80*:
Mount the temperature sensors in an angle of 45°
towards the flow direction (see fig. 4).
Nominal sizes > DN 65*:
Mount the temperature sensors at right angle to
the flow direction (see fig. 5).
* For DN 65 and DN 80 both positions are permitted.
For DN < 50 an installation in a bent tube is also
possible.
Fig. 4: Exemplary diagram
for nominal size DN 50
Fig. 5: Exemplary diagram
for nominal size DN 100
4.3 Mounting of the integrator
PolluStat E is delivered with the integrator
mounted on the flow sensor. Depending on the
flow sensor’s installation (horizontal or vertical)
the integrator can be turned through steps of 90
degrees. Lift the spring catch with a screw driver
and take the integrator from the carrier plate.
Then turn the integrator to the required position,
adjust it to the bottom edge of the carrier plate, lift
the spring catch, attach the integrator onto the
carrier plate and release the spring catch.
If liquid temperatures exceed 90°C the
integrator has to be mounted separately, in
order to avoid damages of electronic parts.
Unscrew the carrier plate from the flow sensor,
and fix it at the required place using the two
screws and the two enclosed dowels. Then attach
the integrator as specified above.
4.4 Connection of temperature sensors
The applicable temperature sensor type is
specified on the frontside of the integrator casing.
The required minimum distance from sources of
electromagnetic interference (generators,
frequency converters, ...), as well as from cables
carrying > 230 V, is 0.3 m. Two-wire or four-wire
connection is possible (to extend the length of the
temperature sensor cables by max. 23 m,
recommended cable type I-Y(St)Y 2x2x0.8,
minimum core size 0.5 mm²). Allocation as
follows:
M H 4110 INT PolluStat E, page 5
Installation and operating instructions
Supply pipe temperature sensor (warmer line):
Connection type Terminals
Two-wire connection 5, 6
Four-wire connection 5, 6 and 1, 2
Screening, if any
Return pipe temperature sensor (colder line)
Connection type Terminals
Two-wire connection 7, 8
Four-wire connection 7, 8 and 3, 4
Screeening, if any
Start by removing the respective preshaped
rubber part from the integrator casing (see fig. 6).
Then pull the cable through the hole in the
preshaped rubber part and provide for strain relief
by using one of the delivered cable binders (see
fig. 6). Now connect the cores to the
corresponding terminals and replace the
preshaped rubber part (see fig. 7).
Fig. 6: Example of t wo- wire connect io n
M H 4110 INT PolluStat E, page 6
Terminal connectors in integrator
5 1 2 6 7 3 4 8
1
Temperatur e
warmer line
sensor in
2
cable binder for
strain relief
3 4
Temperature
sensor in
colder line
with a screened cable
Heating / Cooling meter PolluStat E
Fig. 7: Cores connected, preshaped rubber part
replaced
Temperature sensor types, which are delivered
from the factory with already attached preshaped
rubber parts (see fig. 8) can be placed directly into
the integrator casing – it is not required to use a
cable binder for them.
Fig. 8: Cable incl. already attached preshaped
rubber part
In case of four-wire connection the cable handling
is corresponding.
Fig. 9: Example of four-wire connection
cable binder for
strain relief
Heating / Cooling meter PolluStat E
Installation and operating instructions
5. Display options
The different display options of PolluStat E are
divided into six menus. Depending on the type of
the meter and the display masking respectively,
some display items, which are marked with an
asterisk (*), can be masked. If required, the
masking can be changed via the optical data
interface of the meter with the service software
MiniCom. In the basic state the display switches
on for one second in intervals of 4 seconds and
shows the accumulated energy. By a stroke on
the red key the first display item in the user menu
(accumulated energy) is activated. The selection
menu for the other five menus can be obtained by
a pressure of 8 seconds onto the red key:
User menu
Target day menu
5.1 User menu
Error message
(only in case of error)
Accumulated energy
consumption
Target date energy
consumption with related
date *
Accumulated volume
Segment test
Flow sensor installation
place
(cold pipe = colder line)
Archive menu
Service menu
Control menu for tariff
purposes
Parameter menu
The menus can be selected in sequence by short
strokes on the red key. As soon as the desired
menu is displayed, hold the red key for 2 seconds
in order to obtain this menu. Each one of the
single display items in the menus will be called up
one after the other by a short keystroke. If there is
no key operation within ca. 4 minutes, the display
returns automatically to the basic state. In all
menus received flow signals are shown by a
blinking symbol (left bottom display corner).
In case of meters with display illumination the light
switches on automatically with the first keystroke
and switches off automatically ca. 4 minutes after
the last keystroke.
The shown value figures are to be considered
exemplarily.
Consumption tariff 1 *
(if activated)
Consumption cooling
energy *
(only for combined
heating / cooling meters)
Consumption of first
external meter *
(optional)
Consumption of second
external meter *
(optional)
Current flow rate *
Current heating resp.
cooling power *
Temperature in warmer
line *
Temperature in colder
line *
M H 4110 INT PolluStat E, page 7
Heating / Cooling meter PolluStat E
r
)
(
Installation and operating instructions
Temperature difference *
Customer specific
number *
Primary M-Bus address
(factory setting: 0) *
Secondary M-Bus
address
(factory setting:
meter serial numbe
5.2 Target day menu
All display items are marked with an arrow
symbol. Display of all stored values on an
adjustable annual target day.
*
5.3 Archive m en u
All display items are marked with a calendar sheet
symbol. As from the current date, the values on
the turn of the past 16 months are displayed (sixfigure date in the form of dd.mm.yy. below the
main display).
In addition the values for the current month can be
called up. For this purpose “today” has to be
selected for the month.
Select required month by
short keystroke, then
depress key for 2
seconds *
Energy consumption *
Volume *
Energy consumption *
Volume *
Consumption tariff 1
(if activated) *
Consumption cooling
energy *
(only for combined
heating /cooling meters)
Consumption of first
external meter *
(optional)
Consumption of second
external meter *
(optional)
Return to selection menu
(depress for 2 seconds)
Consumption cooling
Maximum heating resp.
Maximum heating resp.
Consumption tariff 1
(if activated) *
energy *
(only for combined heating
/cooling meters)
Consumption of first
external meter *
(optional)
Consumption of second
external meter *
(optional)
Maximum flow rate in
selected month with date
(averaged) *
Maximum flow rate in
selected month with time
(averaged) *
cooling power in selected
month with date
averaged) *
cooling power in selected
month with time
(averaged) *
M H 4110 INT PolluStat E, page 8
Heating / Cooling meter PolluStat E
Installation and operating instructions
Hours of error condition *
Hours of mains supply
failure *
(only for mains supplied
meters)
Return to month selection
(depress for 2 seconds)
5.4 Service menu
Each display item is marked with a man symbol.
The service menu shows maximum values and
meter settings.
Absolute maximum
Absolute maximum
Absolute maximum flow
rate with date
(averaged) *
Absolute maximum flow
rate with time
(averaged) *
heating resp. cooling
power with date
(averaged) *
heating resp. cooling
power with time
(averaged) *
Absolute maximum
temperature in warmer
line with date *
Absolute maximum
temperature in colder line
with date *
Current date *
Accumulated hours of
Battery voltage *
(calculated)
Accumulated hours of
error condition *
mains supply failure *
(only for mains supplied
meters)
Primary M-Bus address
(factory setting: 0) *
Secondary M-Bus
address (factory setting:
meter serial number) *
Data communication
mode (content of data
record) *
Version of firmware
Check sum
High-resolution energy *
High-resolution volume *
Return to selection menu
(depress for 2 seconds)
Current time *
Next target date *
Operating days *
M H 4110 INT PolluStat E, page 9
Heating / Cooling meter PolluStat E
)
Installation and operating instructions
5.5 Control menu for tariff purposes
Each display item is marked with the letters
„CTRL“. The settings for the tariff functions can be
controlled here.
Switch-over temperature
Switch-over temperature
Set averaging interval for
flow rate and heating
resp. cooling power *
Heating resp. cooling
power in current
averaging interval *
Flow rate in current
averaging interval *
Setting for tarif 1
(if activated) *
for cooling energy *
(only for combined
heating / cooling meters)
difference for cooling
energy *
(only for combined
heating / cooling meters)
Return to selection menu
(depress for 2 seconds)
Pulse value of first
Pulse value of second
Password enquiry
Set primary M-Bus
address *
Set secondary M-Bus
address *
Set customer specific
number *
Set averaging interval for
heating resp. cooling
power and flow rate *
Set data communication
mode
(One, All, One Plus) *
external meter
(0.25 to 10.000 litres per
pulse) *
external meter
(0.25 to 10.000 litres per
pulse) *
Set date *
5.6 Parameter menu
Each display item is marked with the tool symbol.
This menu is protected by password. The
password corresponds to the last three digits of
the eight-digit serial number on the meter casing.
At first „000“ appears. Then depress the key for
ca. 2 seconds, and the left zero starts blinking. By
continuously depressing the key, the value of the
blinking digit can be changed. As soon as the
desired value is obtained, release the key. A short
keystroke confirms the set value and switches on
to the next digit. Repeat the same procedure here.
As soon as the last digit is set, the menu will be
released.
Now the desired items can be selected by short
keystrokes, the values can be set in the same way
as entering the password.
Set time *
Set target day *
Reset absolute maxima *
Reset hours with failure
Reset hours of error
condition *
of mains supply *
(only for mains supplied
meters
Return to selection menu
(depress for 2 seconds)
M H 4110 INT PolluStat E, page 10
Heating / Cooling meter PolluStat E
Installation and operating instructions
6. Functional test, sealing
Having opened the shut-off valves, test the
installed units for leaks. For checking purposes
the current values of flow rate, heating resp.
cooling power as well as temperatures of warmer
and colder line can be called to the display
according to chapter 5.1. In order to protect the
meter against tampering, the delivered selflock
seals have to be attached to the following points:
unions of the flow sensor
insertion points of the temperature sensors
lid of the integrator (pull the sealing wire
through the lug at the bottom edge)
7. Possible error situations
PolluStat E is equipped with an automatic selfchecking function. As soon as an error is
detected, the display shows a four-digit error code
„Err XYZW“, which can be decoded as follows:
X: Checking the temperature sensors
Y: Checking the integrator
Z: Error statistics
W: Checking the ultrasonic measuring circuit
The following error message can appear, if – due
to insufficient venting of the pipe – there is air in
the flow sensor disturbing the ultrasonic signals.
Err 00 x 2
Here „x“ stands for a figure from 1 to 9 or for a
capital from A to F.
This error message can also appear on the
display of new heat meters, when – due to logistic
reasons – the flow sensor has not been filled with
water. This is no reason for a complaint because
such an error message will vanish after correct
installation of the meter.
If nominal flow rate is exceeded by more than
130 %, following error message is displayed:
Err xxx4
After reducing the flow, this message will
disappear.
Codes (extract) Decoding
Temperature sensors changed by
Err 1010
Err 2010 or 3010
Err 4010 or 5010
Err 6010 or 7010
Err 8010 or 9010
Err A010 or B010
Err C010 or D010
Err 0002 Air in flow sensor
mistake resp. temperature in
colder pipe exceeds temperature
in warmer pipe
One or both temperature sensors
is/are short-circuited
Cable failure of temperature in
colder line sensor resp. sensor is
not connected
Temperature sensor in warmer
line is short-circuited and cable
failure of temperature sensor in
colder line
Cable failure of temperature
sensor in warmer line resp.
sensor is not connected
Temperature sensor in colder line
is short-circuited and cable failure
of temperature sensor in warmer
line
Cable failure of temperature
sensors in warmer and colder line
resp. sensors are not connected
Error situation „Err 1010“ is usually caused by
temporary system conditions when temperature in
the warmer line drops by 3 K or more below the
temperature in the colder line.
In case of all other errors situations please inform
our service department.
8. Standard interfaces and optional
modules
PolluStat E is equipped with following interfaces
and can have the following optional equipments:
8.1 Optical interface
All meters are equipped with a standard optical
data interface. Via optical data coupler (e.g. order
number 04410230 for RS 232 connection or order
number 184023 for USB connection) settings can
be changed with the service software MiniCom, or
the meter can be read out via the readout system
DOKOM Mobile. The data interface is activated
for one hour by a short keystroke. Every data
communication causes this period of time starts
again, so that e.g. a logger readout at 15-minute
or hourly intervals is possible over a long period of
time.
8.2 Mini-Bus interface
The Mini-Bus interface is standard equipment and
is available at terminals 51 (signal) and 52 (earth).
It is suitable to connect the meter with an
inductive readout point (MiniPad) or other reading
and transmitting instruments (e.g. radio
transponders). The total length of the two-wire
cable between the meter and the readout point
must not exceed 50 m. The communication
M H 4110 INT PolluStat E, page 11
Installation and operating instructions
protocol corresponds to the M-Bus protocol, and
the meter can be read out via a MiniReader or
using DOKOM Mobile.
8.3 M-Bus plug-in module acc. to EN 13757-3
Order number: 68504020
This plug-in module allows a readout of the meter
via its primary or secondary address with an MBus level converter (300 and 2400 Baud,
automatic recognition). Both addresses can be set
in the parameter menu (see chapter 5.6) or with
the service software MiniCom. (General
information: The factory presetting of the
secondary address and the customer number
corresponds to the serial number shown on the
meter casing.) The primary address can be set to
between 0 and 250, and is preset in the factory to
0. Polarity of the two connection terminals (24 and
25) can be neglected.
8.4 Remote pulse plug-in module
Order number: 68503920
Remote pulse plug-in module for output of heat
quantity and volume pulses (for mains-operated
instruments only)
Order number: 68503922
Remote pulse plug-in module for output of heat
quantity pulses (for battery-operated instruments)
Pulse duration: ca. 125 ms
Max. voltage: 28 V DC or AC
Max. power: 0.1 A
Bounce- and potential-free
Nominal size
q
(m³/h)
p
0.6 bis 6 0.001 1
10 bis 60 0.01 10
8.5 M-Bus plug-in module with two contact
inputs
Order number: 68504686
In addition to the plug-in unit specified in chapter
8.3 there is the possibility to connect two external
consumption meters (cold water, electricity, gas,
others) with passive remote reading contact (reed
switch or open collector).
Specification of the contact inputs:
Required closing time: : > 62.5 ms
Input frequency: < 3 Hz
Terminal voltage: 3 V
The required parameters for
meter type
physical unit and pulse value
serial number
initial meter reading
M H 4110 INT PolluStat E, page 12
Pulse value for
energy (MWh / GJ)
Pulse value for
volume (litres)
Heating / Cooling meter PolluStat E
can be set on site via the service software
MiniCom.
8.6 USB plug-in unit (for M-Bus slot)
Order number: 68504688
With this plugin unit the integrator can be
connected to a PC / notebook or handheld
computer with USB input. In case there is an MBus plugin unit installed, this unit has to be
removed first. For the connection you need a
driver, which will be delivered on CD together with
the card. A description how to install the driver is
also available.
8.7 USB plug-in with 2 inputs for external
consumption meters
Order number: 68504902
Join this unit can plug an additional 2 meters with
pulse output and can be connected (see point 8.5)
Both contact inputs preset in the factory to:
- input 1: cold water meter, pulse valency
10 litres, initial meter reading 0.00 m³
- input 2: warm water meter, pulse valency
10 litres, initial meter reading: 0.00 m³
The activation of the inputs has to be done via the
service software MiniCom 3, menu item: „set
pulse input parameters“. The meter IDs of the
pulse meters have to be set there as well as the
primary M-Bus addresses if necessary; check
“counter 1 (2) visible on the M-Bus”.Starting
meter reading and pulse value can also be
adapted. Afterwards the pulse meters are
available as independent M-Bus meters on MBus. The consumption of the pulse meters is not
transferred in the M-Bus protocol of the heat
meters.
8.8 LONWORKS
Order number: 68504857
This plug-in module is used to implement the
meter via LONTALK
automation system. For detailed informations
please refer to data sheet LH 6130 INT.
8.9. Inserting the plug into the heat meter
In each processing unit is a slot for the M-Bus
Module (right rear) and the remote pulse-module
(left front). The computational work for the
modules may only be permitted in the designated
slots mounted.
®
-FTT10A plug-in module
®
protocol into a building
Heating / Cooling meter PolluStat E
Installation and operating instructions
M-Bus plug-in
(rear slot)
Remote pulse
plug-in FZS/B
Fig. 11: Mounting modules
The plug-in units mounted in the left and right
guidance from a white plastic plug.
The pins must not be bent and slide easily into the
appropriate contact sockets. The power cable
through the hole in the rubber mold, and with one
of the supplied cable tie strain relief. The veins at
the corresponding connecting terminals and the
rubber molding back.
8.10 Optional integrated data logger
If this option is incorporated, the casing lid is
additionally labeled with the word „Data Logger“.
The integrated data logger stores consumption
values and instantaneous values (heating resp.
cooling power, flow rate, temperatures) during a
selectable time interval ( 3 to 1440 minutes). The
logger data can be read out via the optical
interface, M-Bus or Mini-Bus with the service
software MiniCom. The time interval (preset in
factory to 60 minutes) can also be changed with
MiniCom.
For PC connection use either an optical data
coupler (see chapter 8.1) or a USB plug-in module
(order number: 68504688).
8.11 Combined heating / cooling meter
Descriptive name: PolluStat E H or PolluStat EX H
This PolluStat E version switches over at an
automatic switch-over point between metering
heating and cooling energy. The switch-over point
to cooling energy is preset in the factory to:
supply flow temperature < 25 °C and
negative temperature difference > - 0.15 K
Conditions to switch back to heat metering:
supply flow temperature > 25 °C and
positive temperature difference > 0.15 K
If required this switch-over point can be changed
on site with the service software MiniCom.
9. Attachment
9.1 Disassembly and assembly of plastic half
shells for sizes DN 50 to 100
Depending on the installation conditions it may be
necessary to remove the two plastic half shells
from the flow sensor in order to mount the flange
screws.
Disassembly
Removal of user seal (see fig. 12)
Unfastening the 4 cross slot screws (see fig.
12)
Removal of upper half shell
Removal of lower half shell – at this please
remove the cable with the preshaped rubber
part carefully (see fig. 13)
Fig. 12
Afterwards the flange screws can be put through
the corresponding holes of the flanges.
Assembly
Attaching of the upper half shell – at this the
position pin at the inner side of the half shell
must gear into the hole of the mounting
bracket (see fig. 13)
Inserting the preshaped rupper part in the
lower half shell
Connection of lower and upper half shell with
4 cross slot screws
Sealing of the half shells with user seal (see
fig. 12)
Mounting bracket with hole
Fig. 13: Meter with lower half shell
cross slot screws
user seal
Preshaped rubber part
M H 4110 INT PolluStat E, page 13
Declaration of MID conformity
Heating / Cooling meter PolluStat E
Installation and operating instructions
M H 4110 INT PolluStat E, page 14
Heating / Cooling meter PolluStat E
Installation and operating instructions
Space for extra notes:
M H 4110 INT PolluStat E, page 15
Qualitätsmanagementsystem Quality Austria-zertifiziert
Nach ISO 9001, Reg.-Nr. 3496/0
Heating / Cooling meter PolluStat E
Installation and operating instructions
Material number: 28504907
Edition: 004-11.2016
Subject to change without notice
Sensus GmbH Ludwigshafen
Industriestraße 16
D-67063 Ludwigshafen
Telefon: + 49 (0) 621 6904-1113
Fax: + 49 (0) 621 6904-1409
E-Mail: info.de@xyleminc.com
M H 4110 INT PolluStat E, page 16
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.