Sensus FM-1D/K Operating Instructions Manual

Page 1
Operating Instructions Frequency Converter FM-1D/K
Digital-analogue-converter and flow rate indicator for water meters
Contents
1. Description
2. Mounting
4. Calibration by hand
5. Protection
6. Test mode
7. Operation
8. Lightning protection
9. Trouble shooting
10. Replacing fuses
1. Description
FM-1D/K is a µP-controlled frequency converter with display.
It converts pulses into proportional cur­rent for flowrate display.
Input from the pulsers are converted to:
• Standardized current
• Pulse totalization
• LED display
2. Mounting
Snap action on 35mm top hat rail acc. to EN 50022
remove from top hat rail
Wall mounting with two screws
M5M4
5060
85
+ Sensor -
U+
N PE 24 VAC/DC
12345678
+
-
+
-
FM-1D/K
select
Page 2
3. Connection
Note:
• max cable cross section is 2.5 mm
2
• check power supply voltage before using
• with 24 VDC operation, the polarity is irrelevant
• Technical Data please see leaflet L S 5100 GB
Safety information
When making the electrical connections, it is essential to disconnect the FM-1 D/K from the power supply.
The connection of the FM-1D/K is only allowed by a specialist in accordance to the common safety standards.
Connection of 3-wire-sensors
4. Calibration by hand
+ Sensor -
U+
L N PE 24 VAC/DC
12345678
+-
FM-1D/K
select
+
-
Status LEDs
select keychange keys
LED display
Calibration
After connecting the FM-1 D/K needs to be calibrated:
1. Select With the SELECT- button the programming parameters can be chosen. The status LED indicates the actual selection.
2. Change By pressing either the (+) or (-) button the status LED and the first placed digit will flash. With the (+) and (-) button the settings can be changed. To activate the second placed digit the SELECT-but ton must be pressed.
3. Save To save the chosen settings the SELECT-but ton must be pressed after changing the last right hand digit. The settings will not be lost after a power failure.
Setting example
Water meter WPD DN 80 Pulser Opto OD 01 (1 imp = 1 Ltr.) Current output 0 ... 20 mA Max. flowrate 0 ... 100 m
3
/h
Pulse output 1 Imp. = 1 m
3
1. Flowrate range
After switching on, the display indicates ”0000.”. Pressing either the (+) or (-)-button the FM-1 D/K changes to the programming mode. The left digit of the display will flash. Set the digit ”0” with the (+) or (-)-but­ton. Pressing the SELECT-button changes to the sec­ond digit. As described set the 2.,3.,4. digit and the deci­mal point.The display should indicate ”0100.”. The pos­sible flowrate range is 0.001 ... 9999. m
3
/h
2. Counter reading
The FM-1 D/K counter reading can be set to match the counter reading of the water meter. When the upper sta­tus LED blinks the first 4 digits can be set and when
Page 3
the lower status LED blinks the last 4 digits can be set. The setting is identical as described in point 1. The posi­tion of the decimal point depends on the output pulse value ( see point 4)
3. Pulser
The setting of the pulse value of the sensor in litre per pulse. In this example with 1 litre per pulse the display is to be set to ”0001.”. The possible input pulse range is
0.001 ... 9999. litres/pulse. After the pulse value pro­gramm the signal mode suitable for the connected pulser. InPu= Opto OD 01-04 without evaluation of the direction signal InPb= Opto OD 01-04 with evaluation of the direction sig­nal
InPr= Opto OD 01-04 without direction signal
4. Pulse output
For example to set 1 pulse per m3, the display must indi­cate ”0001.”. The setting is identical as described in point 1. The possible output pulse value is 0.001 ...
9999.m
3
. Note ! The output pulse value has to be > to the input pulse value. At max. flowrate the output pulse rate must not exceed 1 Hz.
5. Current output
The actual current output range will be indicated at the display. With the (+) or (-)-button it can be toggled between 0...20mA and 4...20mA. Pressing the SELECT button saves the setting.
6. Damping
The damping determines the response time of the cur­rent output and the flowrate indication. If there are no special requirements for the response time please set damping value ”0004”. Setting 1 - no damping Setting 14 - max. damping
*) from serial no. 105.000
5. Protection
The FM-1D/K can be protected against unintentional changes to the setting. In the protect-mode all settings and measuring values can be displayed. Changing the values is not possible.
Simultaneously by pressing (+) and (-)-buttons and the SELECT-button, the present mode will be displayed.
display ”LOC 6”
- device in programming mode,
display ”LOC 8”
- device protected.
With the (+) or (-)-buttons modes can be toggled between ”LOC 6” and ”LOC 8”. Pressing the SELECT button saves the setting.
6. Test mode
In the test-mode the digital and ana-
logue output of the FM-1D/K can be checked on the integral counter and flowrate indicator, without having a pulser connected to the pulse input.
First the firmware revision will be indicated.
By pressing the (+) or (-)-buttons the test mode starts:
The current output toggles, as indicated on the display, in a 30 second interval between 0(4) und 20 mA. The flowrate indicator should alternate between ”0” and full scale.
At the pulse output terminals a pulse will be generated every 60 seconds. These pulses will be indicated on the pulse counter.
Pressing the SELECT-button leaves the test mode and changes into the standard mode.
Test
I in mA
t in sec.
Pulse
Pulse
30 60 90
20
4
120
Page 4
7. Standard mode
Rapid flashing of all status LED’s indicates incoming pulses.
The permanently illuminated status LED indicates the measuring units on the display.
The display can switch between:
• Flowrate indication At reverse flow direction the display shows “-000” *)
• Counter reading (first 4 digits)
• Counter reading (last 4 digits)
• Pulse value of the pulser input(Sensor)
• Pulse value of the pulse output
• Current output range
• Damping
• Firmware revision (Test)
*) from serial no. 105 000
To protect the FM-1D/K from voltage surges caused by lightning, installation of an adequate lightning protection device is recommended.
Depending on the situation on site, we recommend the
8. Lightning protection
Lightning protector 48 VDC/AC
230 VAC
Overvoltage protection
Lightning protector 15 VDC
Water meter e.g. WP-Dynamic
with pulser OD
Frequency converter FM-1D/K
Lightning protec­tor 48 VDC/AC
Max. 20km
Error Symptom Cause
Remedy
9. Trouble Shooting
Status lamps and LED dis­play not work­ing
No current out­put but internal display indi­cates flowrate
No power supply
Error in the current out­put circuit
Check current output using the test mode
Check connected indica­tor.
Check external totalizer and its power supply
No pulse output but the internal display counts the volume
Error in the pulse output circuit
Check pulse output using the test mode
Check external totalizer and its power supply
Check supply voltage For 230V: Check voltage
selector (Pos. 230 V) and fuse F 91 (200 mA m)
For 24 V: Check fuse F 92 (200 mA m)
Error Symptom Cause
Remedy
Trouble Shooting
Flowrate display “0“ and no output pulses but the water meter is work­ing and the pulser is con­nected.
Error in the pulse input circuit.
If status LED’s are flash­ing acc. to the incoming pulses:
Check the settings of FM-1D/K.
If the status LED’s are not flashing acc. to the sensor pulses:
Check input. Remove pulser, shortcircuit the sensor terminals
(+) and (-) with a wire.
- If status LED’s flash: Replace pulser.
- If status LED’s don’t flash: Check fuses F 111 and F 112
(32 mA m).
Page 5
Sensus Metering Systems GmbH Hannover
Meineckestrasse 10, 30880 Laatzen, Germany
D+49 (0) 5102 74 0 F +49 (0) 5102 74 3341
[email protected] www.sensus.com
Error Symptom Cause
Remedy
Trouble Shooting
FM-1D/K refus­es programma­tion
The device is locked against pro­gramming
Unlock device. (please see chapter 5, Protection).
Reading Flowrate is
too high
Check input pulse value. Increase max. value of flowrate.
Reading Input fre-
quency high­er than 1 kHz e.g. caused by bouncing Reed pulser
- Check settings
- Exchange pulser (Opto or inductive)
- Use additional contact protection relay
Indication “InPe”
Pulse error - Change pulse signal,
“InPb” or “InPu” for Opto OD, “InPr” for Reed RD.
10. Replacing fuses
• Disconnect the power from the FM-1 D/K
• Remove the 4 screws from the front plate
• Remove front plate with boards from the housing
• Remove the board with the blown fuse from the front plate
• Open the holding device; check and change the defective fuse
• Assemble the FM-1 D/K in reverse order
Size of fuses used
F 38 fuse 32 mA medium F 39 fuse 32 mA medium F 91 fuse 200 mA medium F 92 fuse 200 mA medium F 111fuse 32 mA medium F 112fuse 32 mA medium
Layout and Fuses
Material number MS5100IN Version: week 12/2008
Loading...