The Radio Ohmstik Live-Line Micro Ohmmeter measures the micro-ohm resistance of
conductors, connectors, splices and switching devices positioned directly on energized,
high voltage lines. The Radio Ohmstik calculates resistance by measuring the AC
amperage in the line and the voltage drop due to the resistance of the line segment
under test. Using the AC current in the line insures that realistic current distributions
through the connection are being measured. The instrument is pressed against the
splice or connector in such a manner that the connection under test is between the
two electrodes.
The Radio Ohmstik sends its status and measurements to both the Remote Display
and the Radio Ohmstik Software on the user's laptop. At the same time, the GPS
device sends location data to the Software. When a valid measurement is received,
the software writes the data to a comma separated (CSV) fi le. This allows the user to
map the location of the connector as well as its condition.
Safety Information:
The probes on the Radio Ohmstik measure voltage drop and
are intended to measure the micro voltage drop from the
same phase.
Connecting the probes in a phase to phase, phase to ground,
or any application where the voltage potential between
the probes is more than 2.5 volts will cause damage to the
instrument and create a system fault.
Do not touch or engage the air gap of adjacent phases or
ground connections with the probes.
FCC & Industry Canada statements
United States of America and Canada
Contains FCC ID: OUR-XBEEPRO
Contains Model XBee-PRO Radio, IC: 4214A-XBEEPRO
The/XBee-PRO® RF Module has been certifi ed by the FCC for use with other products without
any further certifi cation (as per FCC section 2.1091). Modifi cations not expressly approved by
Digi could void the user's authority to operate the equipment.
This equipment has been tested and found to comply with the limits for a Class B digital
device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide
reasonable protection against harmful interference in a residential installation. This
equipment generates, uses and can radiate radio frequency energy and, if not installed
and used in accordance with the instructions, may cause harmful interference to radio
communications. However, there is no guarantee that interference will not occur in a
particular installation.
If this equipment does cause harmful interference to radio or television reception, which can be
determined by turning the equipment off and on, the user is encouraged to try to correct the
interference by one or more of the following measures: Re-orient or relocate the receiving antenna,
Increase the separation between the equipment and receiver, Connect equipment and receiver
to outlets on different circuits, or Consult the dealer or an experienced radio/TV technician for
help.
Page 3
Specifi cations
Model Number & Type8-1828-184
TypeStandardWide Jaw
Sensor Opening2.5 in, 6.35 cm3.86 in, 9.8 cm
Weight2.3 lbs, 1.05 kg4.0 lbs, 1.81 kg
Measurements
Amps1-1400 A
Microohms5-2500 µ
Accuracy
Amps±1% 1 A
Microhms Absolute±2% 2
Microhms Repeatability ±1% 2
Accuracy is diminished if the current is less than 15 amps 0-35kV and when current is less than 50 A while on 36-500kV
Range of Operation
VoltageRated 500kV
Resolution
Amps 1.9-99 A0.1 A
Amps 100-1400 A1.0 A
Microhms 0-999 µ1 µ
FrequencyActual frequency indicated on the unit
50Hz Calibrated47 to 53Hz
60Hz Calibrated57 to 63Hz
Radio
FrequencyISM 2.4 GHz
Power63 mW, 10 mW in Europe & Japan
Range150', (46 meters) Line of Sight, 120' (36.5 meters) in Europe & Japan
Mechanical
Battery9 Volt Alkaline, 1 each per unit
Battery Life6-8 Hours at 68°F or 20°C, 3-4 Hours at 32°F or 0°C
Detachable ProbesFused Probe or Adjustable Probe
Ambient Temperature-4 to +140° F, -20 to +60° C
DisplayGraphics LCD
Software RequirementsRadio Ohmstik Software
System RequirementsWindows XP, Vista, Windows 7, Windows 8
Hardware RequirementsMinimum of two USB ports
EEC StandardsSuccessfully passed international test standards indicated by CE
Page 4
Radio Ohmstik Software
The Radio Ohmstik Software will display information on the Display Unit and will
also write the collected data to a comma separated value (CSV) fi le in software.
The following data is collected: Amps, Micro-Ohms, Date, Time, Comments,
Latitude, and Longitude (with the GPS USB plugged into the laptop).
System Requirements
The Radio Ohmstik software installs on all computers running Windows XP, Vista,
Windows 7 & 8. The GPS and Radio Ohmstik Software each require a USB port.
Software Installation
1. Place the Radio Ohmstik Software Install CD in your computer’s CD Drive
2. The Installation Wizard will automatically load and display on your PC.
**If you need to launch the install manually, go to the Start Menu, select RUN
and type :\SETUP.EXE, OR - Click on browse, open the drive that your CD is
located, and double click on fi le titled SETUP
3. You must agree to the licensing agreement to proceed with the download
4. A dialog box will appear to let you know when the download is complete
5. Shortcut paths will automatically load during the install
USB Port Permissions
Computers managed by electric utility organizations often limit the programs that
can be installed. The USB devices in this kit have install programs that run the
fi rst time they are installed. The user may have rights to install programs but may
not be aware that the USB ports are locked. If the USB devices are not discovered
automatically, their drivers will need to be installed manually. The USB Radio
Drivers are loaded on the program CD. The USB GPS Driver came on a CD with
the USB GPS device. Please contact your network administrator for permission and
instructions to complete the install If the drivers need to be installed manually.
Communicating the Measurement
The user is able to view the measuremet sets on both a Display Unit and on a laptop
running Radio Ohmstik software. These communications may be used singly, or at
the same time.
Communicating to the Display Unit: The Display Unit is designed to be attached
to a hot stick, or held by hand. The sensor transmits the live readings to the Display
Unit via radio. This functionality allows the user to easily see readings were taken.
Readings are not saved on the Display unit.
Communicating to the Laptop: With the Radio Ohmstik software loaded, and the
radio adapter plugged in, the Sensor will transmit the data and readings to the laptop. The measurement set will automatically be saved as a .csv fi le for future review.
Page 5
Operating Instructions
Setup Communication with Radio Ohmstik Software
1. Plug the 7-024 USB Radio and the 7-025 USB GPS devices into the laptop's USB
ports. It will take several seconds for the computer to discover the devices
2. Open the Radio Ohmstik Software
3. The program starts by asking the user to select a fi le name and location to
write the data.
and time the application is opened.
Note: The default File Name is a date and time code for the date
4. Select Save; the Radio Ohmstik Dashboard will load and is ready for
measurments
Page 6
Setup Communication with Display Unit
1. Place the Display Unit on the hot stick with the Velcro strap so the LCD display
is visible while taking measurements
2. Press the function button on the Display Unit. The display will run through its
boot screens, ending in No Signal
SensorLink
Copyright 2011
Setup Radio Ohmstik Sensor
1. Attach the Probe to the back of the Radio Ohmstik.
2. Press the function button on the Radio Ohmstik sensor. The Radio Ohmstik
transmits to both the Display and the Radio Ohmstik Software
3. They both indicate the Radio Ohmstik is ready to take measurements
F574 8XP 300
Firmware XXX
No Signal
DisplaySoftware Dashboard
Page 7
Taking a Measurement:
1. Place the Radio Ohmstik on a conductor as depicted in Figure 3.0. It is essential
you make contact between the conductor and the voltage sensor, which is the
V-shaped plate between the jaws, as well as the voltage probe.
2. Measurement begins as soon as the Ohmstik is in position and is stable
Figure 3.0
3. While the Radio Ohmstik is taking the measurement, the screens will display:
4. The display screens will show the current in the conductor as well as the Micro-
Ohm resistance of whatever is between the two voltage probe
5. Remove the Ohmstik from the conductor. It holds the reading and displays
it as follows:
6. Remove the Radio Ohmstik from the conductor or splice
7. The measurements are now written to the Radio Ohmstik software
8. The displays will continue to show readings until the Radio Ohmstik is placed on
a new current carrying conductor or until it powers down
Page 8
Reviewing Measurements in Software
1. The Radio Ohmstik software will display the completed measurement and GPS
location on the Dashboard
2. The data will automatically be written to a comma-separated values (CSV) fi le
when the Radio Ohmstik is removed from the conductor
3. A comment may be added before the reading is taken. Any comment written
will be a part of the record for the next reading
4. To review the data, open the saved CSV fi le in any spreadsheet or word
processing application
Note: Opening the CSV fi le while the dashboard is open, will stop the recording
of readings. The number of readings will be recorded on the dashboard
but the readings will not be stored.
Power Off the Radio Ohmstik
Press and hold the Function Button on the Display Unit until the LCD goes blank
or Press and hold the Function Button on the Radio Ohmstik until the LED goes off.
Either of these actions will power off itself and the accompanied device. The Radio
Ohmstik will power off by itself if left inactive for 20 minutes.
Page 9
Troubleshooting and Error Messages:
“No Contact”
The Radio Ohmstik reads current but not µs:
This indicates that either one of the two voltage sensors is not making contact. Use
the rough edges of the probes to clean the corrosion from the conductor and retake the measurement. Make certain that both voltage sensors are making contact.
“Poor Contact”
This means either there is Poor Contact between the two voltage contacts:
Provide fi ve seconds to measure, while the Radio Ohmstik is held stationary with
both voltage probes securely on the line.
“Reading Ohms”
The following message indicates that the current measurement was completed
before the resistance measurement could be completed:
Provide fi ve seconds to measure, while the Radio Ohmstik is held stationary with
both voltage probes securely on the line.
“Unable To Measure”
The Radio Ohmstik uses logic to know when it is on a conductor by looking for a
stable load:
Hold the Radio Ohmstik fi rmly on the line for at least fi ve seconds. The Ohmstik
samples the line three times every 100 milliseconds. If it cannot fi nd three
consecutive reads that are similar within fi ve seconds it will display “Unable To
Measure”.
Page 10
“Exceeds 1400 Amps”
The Radio Ohmstik limits the maximum current to 1400 Amps;
Exceeds Limits indicates that the current limit has exceeded 1400 Amps.
Page 11
Application: Deterioration Infl uences
Time is not an “aging factor” for fi ttings. Deterioration is due to increases in resistance
of the connection. The increased resistance is produced, in part, by peaks of load and
fault current that can heat the interface, even if only temporarily, or for a few cycles
(also in part by oxidation of the interfaces during thermal expansion and cooling, and
by corrosion accelerated by moisture and chemicals in very small quantities that get
in between the strands). Every splice has at least one “uphill” side for water, etc. to
run. The reasons we hear that fewer “dead-ends” fail may be that most of them are
pointed “downhill”.
All of these infl uences accelerate the deterioration of fi ttings that are not installed
properly. Cleaning and roughening the conductor was always important in making
a “good fi tting”, and with today’s shorter, harder alloy tube fi ttings, we have found
it critically important, even with the new conductor. Proper dispersion of an inhibitor
will help keep the interfaces from oxidizing. All major manufacturers have frequently
found a missing, or inadequately dispersed, inhibitor when examining failed fi ttings.
Proper die closure is very important, especially with the newer (last 20 years or so)
alloy tube “single die” type compression fi ttings. There is generally less conductor
inserted in the fi tting than in the older “hex die” type of fi tting, so it is less forgiving
of installation error. These consequences of installation lead to incremental increases
in resistance during the service life of the fi tting. Resistance measurements of newly
made alloy tube fi ttings indicate they are more likely to start service at the higher end
of the normal range than the lower end.
Lately, what has been learned about fi tting reliability indicates that there will be more
problems with unexpected failures than in the past. This comes at a time when just
the opposite is needed. Fittings need to be replaced on a planned basis, before failure
occurs.
Page 12
Ohmstik Evaluation Method
The Ohmstik Evaluation Method provides defi nitive and actionable early warnings of
a deteriorating fi tting. This method directly measures the resistance of the connection
with an Ohmstik. The resistance is the electrical condition of the splice. If the resistance
is outside the normal range, the connection is deteriorating. A connection with
resistance above the normal range is in a failure process, where the time to failure
depends on how high the resistance is. The appropriate planned actions for ranges of
resistance above normal are shown in Table One. The resistance ratio is calculated by
comparing the resistance of the fi tting over the resistance of the conductor.
All fi ttings or splices consist of two different connectors. All connectors consist
of three resistors in series; the resistance of the conductor, the connector and the
interface between the conductor and the connector (See fi gure 4.0).
Figure 1.0
The interface is the only resistor of the three that changes over time. The object of
the Ohmstik Evaluation Method is to measure as little of the conductor & connector
as possible, and all of the section that surrounds the interface.
A good way to make reliability judgments about a connector is to compare the
resistance of the connector assembly to the conductor. This ratio allows you to
compare measurements on connectors of various sizes.
1. In order to establish the baseline, or denominator, for the ratio of the subsequent
measurements, measure the resistance of a portion of the conductor that is equal in
length to the interface portion of the connector.
Figure 5.0
2. Measure the interface of one of the connectors.
Figure 5.1
3. Measure the interface of the second connector.
Figure 5.2
The ratio is calculated by making the conductor measurement as the denominator
and the Connector measurement as the numerator.
Ratio = Connector / Conductor
Page 13
The following table shows the suggested action for various ratios based on
maintaining the present load rating.
Resistance ratio Condition of fi ttingAction
0.3 to 1.0Normal Connection Serviceable
New connections are expected to
be in the 0.3 to 0.8 range
1.01 to 1.2Serviceable; poor
Shows deterioration; Overloads
& faults may deteriorate the connection
1.21 to 1.5Serviceable; poor
Serviceable, shows deterioration;
Overloads & faults may deteriorate
the connection
1.51 to 2.0Serviceable; very poor
High loads, overloads, or faults may
deteriorate the connection
2.01 to 3.0Bad; deterioration rate is
increasing
High loads, overloads, or faults may
fail the connection; High tensions
from cold weather or wind may
initiate failure under normal loading
> 3.0Failing
Normal loads, overloads, or faults
may fail the connection; High
tensions from cold weather or wind
are likely to initiate failure under
normal loading
Table 1.0: Actions required based on resistance ratios (Rfi tting / Rconductor)
None
Re-inspect in one year, or
after next fault
Fault
Schedule replacement in
less than three months
Schedule replacement
very soon
Replace as soon as
possible
Note: This information was developed from fi eld measurements, manufacturer
data, lab tests, failure analysis and understanding of deterioration mechanisms.
This guideline may be modifi ed as fi eld & test data accumulates.
Page 14
Standard Probes and Ac ces so ries
7-081 XT Standard Fused Probe, for 8-182 Transmitter
7-081 Standard Fused Probe, for 8-184 Transmitter
The probe is de signed for use in close prox im i ty to ad ja cent phases or ground structures
(see Cau tions on page one). In the event of mak ing a phase to phase or phase to
ground con nec tion, the Fused Probe will break the connection.
Fused Probe Confi guration with Contactor Attachment
Fused Probe Confi guration with the Straight Rod and Contactor Attachment
Fused Probe Confi guration with the Bent Rod and Curved Rod
Page 15
7-081 ADJ Adjustable Probe Kit
The Adjustable probe is designed for any measurement where the distance to be
measured is less than 12 inches. This probe wil adjust from 4 to 13 inches.
The Universal Adapter allows the user to adjust the Ohmstik Transmitter at com pound
an gles. This is a useful adapt er when working from the ground on com plex ap pa ra tus.
Page 16
Battery Replacement
The Radio Ohmstik system is powered by two 9V batteries, one in the Radio Ohmstik and one in the Display. The expected battery life for both units is 6 to 8 hours at
68
° F or 20° C. The expected life declines in colder environments. At 32°F or 0°C it is
reduced 3 to 4 hours.
Note: It is recommended that fresh batteries be installed prior to operation each day
and always replace both batteries.
To replace the battery, remove the four screws on the battery cover at the rear of the
unit. Carefully insert a screwdriver blade in the notch and pry the cover out, being
careful not to damage the cover seal. Pull the battery out of the compartment and
separate the battery from the battery connector. To avoid breaking the battery leads
do not pull on the battery only. Install a fresh battery and reinsert the battery in its
compartment. Do not pinch the wires between the battery and compartment; put
wires in slot above the battery. Reinstall the cover by gently pressing it into place while
pulling out on the edges of the compartment, and reinstall the four cover screws. Take
care to avoid over tightening the screws. Always reuse the screws provided and do not
damage or lose the O-ring seal on each screw.
Cleaning
The Radio Ohmstik can be cleaned by wiping with a small amount of alcohol.
Transporting
There are no special consideration for transporting this device.
Page 17
Sensorlink Corporation Warranty
SensorLink warrants each instrument it man u fac tures to be free from defects in materials
and workmanship under normal use and service for the period of one year after date
of shipment. Within this period, SensorLink agrees to repair or replace, at SensorLink’s
option, any instrument that fails to perform as spec i fi ed. This Warranty shall not apply
to any instrument that has been:
1 Repaired, worked on, or altered, including removal of the front panel, by persons
un au tho rized by SensorLink in such a manner as to injure, in SensorLink’s sole
judgment, the per for mance, sta bil i ty, or reliability of the instrument;
2 Sub ject ed to misuse, negligence, or accident; or
3 Connected, installed, adjusted, or used otherwise than in ac cor dance with the
instructions furnished by SensorLink.
This Warranty is in lieu of any other warranty, expressed or im plied. SensorLink reserves
the right to make any changes in the design or construction of its in stru ments at any
time, without incurring any obligation to make any change what ev er in units previously
de liv ered.
If a failure occurs, contact the manufacturer for a Return Au tho ri za tion and
instructions for return shipment. This warranty con sti tutes the full understanding of
the man u fac tur er and buyer, and no terms, conditions, understanding, or agree ment
purporting to modify or vary the terms hereof shall be binding unless here af ter made
in writing and signed by an authorized offi cial of SensorLink Corporation.
Page 18
Quality Assurance Certifi cation
Radio Ohmstik
Transmitter Models 8-182 and 8-184
Display Unit Model 8-180
SensorLink certifi es that its calibration measurements are traceable to the National
Institute of Standards and Technology (NIST), to the extent allowed by the Institute's
calibration facility, and to the calibration facilities of other International Standards
Organization members.
This document certifi es the following Radio Ohmstik was tested at the Sensorlink High
Voltage Lab o ra to ry, Ferndale, WA, USA to the ap pro pri ate standard and comply with
the re quire ments of that stan dard.
Transmitter; Model Number: _______________________________
Serial Number _______________________________
Display Unit; Model Number: __________________________________
Serial Number _______________________________
I hereby certify that the Radio Ohmstik listed above has passed all tests de fi ned in the
Sensorlink Corporation standard. I also certify that I have reviewed the standard and
test pro ce dure and that they are suffi cient in determining compliance with the stan dard.