Sensorex CS8000TC Product Instruction Sheet

PRODUCT INSTRUCTION SHEET
CS8000TC - Cooling Tower Conductivity Sensor
and Flow Cell Installation
Introduction
Your CS8000TC conductivity sensor system installs easily by following the steps below:
1) Glue (FC875/S)or thread (FC875/T) into your cooling tower water loop.
2) Install CS8000TC into the tee by aligning the notch of the CS800TC with the FC875 tab as shown in FIG 1.
3) Slide nut of FC875 tee over CS8000TC and tighten as shown in FIG 2.
4) Attach S855 cable to the top of CS8000TC sensor by align­ing the black tab of the CS8000TC sensor with the slot of the S855 cable. Press in and then tighten nut as shown in FIG3.
Electrical Connections
Follow wiring connections from your conductivity transmitter of controller.
Wiring from S855 Cable is as follows: Wire Color Function Red Conductivity Black Conductivity Green Temperature White Temperature
Calibration
Follow calibration instructions in your conductivity transmitter or controller manual. Suggested calibration is at least 2 points. One point is in air (0uS) and the other is typically >75% of the selected range. See www.sensorex.com for a wide range of conductivity standard solutions.
FIG. 1
notch
SILICONE O-RING GREASE
tab
FIG. 2
Sensor Repair
Do not attempt to repair any part of the sensor. If the sensor's cable is damaged, consult the factory for details.
Sensor Storage
If long-term storage of probes is required, rinse off the sensor in clean water and dry off completely before storing.
Parts covered by this product instruction sheet include: CS8000TC/, FC875/S, FC875/T, S855
Page 1 of 2
Form: InstrCS8000TC-X [Rev: 2014-03-27]
©2011 Sensorex Corporation
PRODUCT INSTRUCTION SHEET
CS8000TC - Cooling Tower Conductivity Sensor
and Flow Cell Installation
SPECIFICATIONS
Sensor Materials Sensor Body: CPVC Measuring Surface: Graphite O-ring: EPDM ®
Flow Cell Materials Flow cell and nut: CPVC O-ring: Viton ®
Cable Materials Body of cable: PPS Cable Jacket: PVC, Black
Temp/Pressure Max: 60 deg C(140 deg F)/100 psig
Wiring Black, Red = Conductivity
White & Green = Temperature
FIG. 3
S855 cable assembly
Page 2 of 2
Form: InstrCS8000TC-X [Rev: 2014-03-27]
©2011 Sensorex Corporation