Sensit HXG-3 Instruction Manual

SENSIT® HXG-3
Combustible Gas Detector
INSTRUCTION MANUAL
7-11 UL V4
Approved UL913, For Class 1, Division 1, Groups C & D hazardous locations when used with alkaline batteries.
C
L
A
S
S
I
F
I
E
D
Read and understand instructions before use.
S
E
N
S
I
T
H
X
G
-
3
®
A
P
O
W
E
R
C
S
A
V
E
B
M
E
N
U
Warning:
To prevent ignition of flammable or combustible atmospheres, disconnect power before servicing.
Sensit® is a registered trademark of J And N
Ex-Ox-Tox Gasdetectie
Westerdreef 5V 2152 CS Nieuw-Vennep
Telefoon: 0252 620885 E-mail: info@exoxtox.nl Website: www.exoxtox.nl
CONTENTS
Page # 1. Accessories and Parts
2. General Description
2. Specifications
3. Product Features
5. Sensor Type
5. Battery Installation
6. Adjustable Features - Factory Only
7. Operation and Use
10. Calibration Check
11. Menu
16. Calibration
18. Warranty and Repair Policy
ACCESSORIES AND PARTS
1
Standard Accessories (included) Carrying Case 872-00001 Wrist Strap 360-00040 Filter Cap 365-00045 Instruction Manual 750-00023 Alkaline Batteries 310-00004
Optional Accessories and Parts
Extension Adapter 870-00012 Printer 870-00004 PC Interface with Software 870-00008
Calibration Kit – Methane 881-00015 Calibration Kit – Pentane 881-00077 LEL Sensor 375-2611-01
This safety symbol is used to indicate a potentially hazardous situation which, if not avoided, may result in minor or moderate injury.
CAUTION
NOTICE
2
The Sensit® HXG-3 is designed to detect combustible gases. All Sensit® HXG-3 instruments incorporate an advanced low power semiconductor sensor to measure combustible gases in LEL (Lower Explosive Limit) range. All measurements are in 0.1% LEL incre­ments. The ppm display is simultaneously shown in 1 or 10ppm increments (resolution). An automatically backlit display shows all gas concentrations being measured. LEDs located on the front of the instrument indicate preset visual warnings of increased gas concentration. Audible and visual alarms warn the operator of hazardous condi­tions being sensed. The preset alarms are indicated by a red flashing LED, display indicator and alarm sound. The combustible gas alarm is preset from 50% LEL (2.5% methane or 0.75% pentane).
The Sensit® HXG-3 instrument is approved by Underwriters Labo-
ratories to UL913, for Class 1, Division 1, Groups C & D hazardous locations when used with Duracell™ MN1400BK or equivalent al­kaline batteries.
GENERAL DESCRIPTION
SPECIFICA TIONS
SENSOR SPECIFICATIONS
TYPE RESOLUTION RANGE ACCURACY
Leak 1ppm or 10ppm 0-50,000ppm ±10%
LEL 0.1% 0-100% ±10%
PRODUCT SPECIFICATIONS
Size: 1 1.5” x 3” x 2.32” (292 x 76 x 69 mm) Weight: 1.2 lbs. Operational Temp: 0 to 120° F Storage Temp: -20° to 132° F Battery Life-Alkaline: approximately 25 hrs. continuous
PRODUCT FEATURES continued from p age 3
The tick can be easily heard with the speaker located in the back of the instrument.
The Infrared Communication window is located on the right side to allow the Sensit® HXG-3 instrument to download: Calibra- tion data; Communicate with Smart-Cal Calibration S tation; PCi­2s Computer Interface; Readings the operator has elected to save to the instrument’s on-board memory .
A flexible gooseneck is used to assist in locating the source of gas leaks and remote sampling.
A two line display continuously updates the operator of all avail­able gas concentrations and alarms simultaneously as well as indicates battery power. Below the display is a series of LEDs that are preset to indicate combustible gas concentrations. Dur­ing an alarm condition the red LED on the right side will flash and an audible warning will sound.
There are 3 operational button pads on the front of all Sensit® HXG-3 instruments.
• POWER/MUTE BUTTON (A): Operate the POWER and MUTE feature and exit menu items.
• MENU BUTTON (B): Use to enter , change and select menu items.
• SA VE/ZERO BUTTON (C): Use save data feature, zero sensor, scroll and change menu items.
4
S
E
N
S
I
T
H
X
G
-
3
®
A
P
O
W
E
R
C
S
A
V
E
B
M
E
N
U
3
Sensit® HXG-3 instruments are constructed of durable ABS plastic to withstand the rigors of field use.
Incorporated in the hand grip area is the battery compartment. All Sensit® HXG-3 instruments require 3 “C” type alkaline bat- teries. Duracell MN 1400 batteries provide approximately 25 hours of continuous use. A thumbwheel is located on the right side of the instrument to activate the audible tick sound that helps in locating the source of a gas leak. This tick is generated by using specialized circuitry in combination with the LEL sen­sor located at the end of the gooseneck assembly .
PRODUCT FEA TURES
BACKLIT 2 LINE DISPLAY
SPEAKER (ON BACK)
WARNING LED’S
16” FLEXIBLE GOOSENECK
IR COMMUNICATION (DOWNLOADING)
SOLID STATE SENSOR
PUSH PA D BUTTONS
BATTERY COMPARTMENT
(Continued on page 4)
THUMBWHEEL FOR TICK ADJUSTMENT
ADJUST ABLE FEATURES (FACTOR Y ONL Y)
6
Session Saves 1 -1 00 6 Alarm-LEL 0-100% 50% PPM Display Option 1ppm or 10ppm 10p pm Cal Due Interval 30, 45, 60,
90, 180, 360 30 days Show Session Log* 1- 10 0 6 Warm-up Time 10-30 sec. 30 sec. Purge Time 1-60 sec. 0 sec.
* Can be disabled
MENU ITEMS RANGE DEFAULT
If you do not use your right hand to hold the bottom of the bat­tery compartment the batteries can come out. Observe the po­larity markings on the inside of the battery holder. Improper in­stallation will cause the instrument not to operate. Replace the battery sleeve and allow the locking tab to snap into position.
NOTE: Improper battery installation will disable the instru­ment.
Check to be sure the handle is secure to the instrument body by gently pulling the handle away . The handle will remain firmly in place if a proper connection is made.
BA TTERY INST ALLA TION/REPLACEMENTContinued from pg 5
5
Combustible Gas Sensor
All Sensit® HXG-3 instruments incorporate a highly sensitive semiconductor type sensor. The function and accuracy of the sensor are monitored and controlled by specialized circuitry and a microprocessor. This sensor is capable of measuring concen­trations of 10ppm of methane (natural) gas up to 100% LEL.
SENSOR TYPE
BA TTERY INST ALLA TION/REPLACEMENT CAUTION: Always change batteries in an environment
free of combustible gases. Battery replacement is necessary when the display reads BA T
LOW, an audible alarm sounds and the green ready LED flashes.
When the instrument remains in BAT LOW, a countdown will appear starting at 300 seconds (5 minutes) which is the maxi­mum time remaining to shutdown.
Remove the battery sleeve cover by depressing the locking tab on the front of the handle with a coin or flat object and pulling the handle away from the top or display area of the instrument.
Place 3 approved batteries into the battery holder. For best re­sults hold the battery compartment so that it lays in your right hand. With your left hand install the battery that goes toward the front first, the battery that is in contact with the rear spring sec­ond and finally insert the third battery in the center by forcing the second battery such that the spring compresses and allows the batteries to go into place.
(Continued on page 6)
7
(Continued on page 8)
CAUTION: Always start any Sensit® HXG-3 in a gas free environment to insure a proper zero.
1. Push and hold the power button (A) until the display illumi-
nates.
2. If the display fails to illuminate or BA T LOW is shown on the display replace the batteries. There is room in the carrying case to keep an extra set of alkaline batteries.
3. During successful start-up the instrument will display: a.Product name and model version b.System check c. Date and time d.Gas Ty pe e.CAL P AST DUE when calibration is overdue f. Warm-up countdown g.AUTOZERO indicating the zeroing of the sensor h.Working display
NOTE: If a sensor is completely inoperable or improperly zeroed at start up, the display will show ERROR LEL followed by FAIL.
OPERATION AND USE
8
(continued on page 9)
OPERA TION AND USE continued from page 7
4. Model 3.30 displays LEL% only . Model 3.35 displays LEL%
and ppm. All LEL readings have a resolution of 0.1% LEL or 50ppm methane. All ppm readings have a resolution of 1ppm or 10ppm and are displayed simultaneously with the LEL display .
5. It may be necessary to manually zero the instrument based on company practices and environmental conditions.
CAUTION: Zeroing should be done in a gas free envi­ronment only.
6. When testing high areas or overhead lines the use of the
optional extension adapter will allow a broom handle or painters stick to extend the instrument to the area where sensing must be accomplished. This slides onto the battery sleeve and is held in place by the locking nut assembly.
7. When a gas is sensed the display will update. Additionally , a series of LEDs on the front of the instrument will illuminate when the preset concentrations of the calibration gas are reached. If an alarm condition exists, based on a preset alarm point, the red (HAZ 3) LED will flash and the alarm will sound.
The preset levels of the LED warning lights are:
Amber LED/Low 5 - 9.9% LEL methane Red LED/Haz1 10.0 - 24.9% LEL Red LED/Haz2 25.0 - 49.9% LEL Red LED/Haz3 50.0 - 100% LEL
(Continued on page 10)
9
OPERA TION AND USE continued from page 8 Caution: These instruments have cross sensitivities to
a variety of gases.
8. During an alarm condition (factory default at 50% LEL) the
display will flash, LED HAZ 3 will flash and an audible alarm will sound indicating a potentially unsafe environment. To disable the audible alarm press and release the mute button (A). To enable the alarm press and release it again.
9. To assist in locating the source of small combustible gas
leaks or surveying areas outdoors or indoors, rotate the thumbwheel located on the right side of the instrument until a steady ticking sound is heard. Note: There is no warm-up for this feature as it uses the LEL sensor that is already operating. Move the sensor toward the area suspected of leakage. As the sensor moves closer to a leak source the tick will increase.When the tick becomes a steady tone rotate the thumbwheel in a clockwise direction while keeping the sensor in the same posi­tion. This will slow down the tick and allow the operator to find a higher concentration using the same procedure.If the tick goes away you have moved away from the leak or there is no more gas present. For best results always use the leak detector prior to using any liquid leak detection fluids as these sensors will detect their presence.
10. At any time the operator may save the readings on the dis-
play by pressing the SA VE/ZERO button (C). This will save all readings for download at a later time.
10
OPERA TION AND USE continued from page 9
The memory is factory set to store 6 events. This can be ad­justed from 1-15 at the factory. The most recent save is first during download.
11. Following Federal, State, Municipal and/or Company proce­dures move to the areas where gas readings are suspected or must be tested. During sampling the respective readings may change. Audible and visual alarms will activate when the preset limits are reached.
12. When being used in dark areas an automatic backlight will illuminate the display .
13. T o turn instrument off, push and hold the power button (A) for 5-6 seconds until POWER DOWN appears on the display .
To verify the accuracy of any Sensit® HXG-3, it must be ex­posed to a known concentration of test gas. Any sensor that does not meet the specifications listed in this manual may re­quire calibration or replacement. A calibration check does not update the calibration due date. Full calibration is required to update these times.
A calibration past due message will illuminate during warm-up if calibration has not been performed per your company specified interval. Anytime it is suspected the Sensit® HXG-3 is not work- ing properly , check calibration.
CALIBRA TION CHECK
12
(continued on page 13)
MENU continued from page 11
(C) to scroll to another PRINT MENU function. Pressing the POWER/MUTE button (A) will reenter the USER MENU. Use the SAVE/ZERO button (C) at this time to scroll to another menu function. Pressing the POWER/MUTE button (A) will re­turn the instrument to the working display .
CALIBRATION (see page 16 for complete instructions)
From the working display access the user menu by pressing and holding the MENU button (B) until the top line of the display reads USER MENU. Press and release the SA VE/ZERO but- ton (C) until the bottom line displays CALIBRATION.
POWER OFF
From the working display access the menu by pressing and hold­ing the MENU button (B) until the top line of the display reads USER MENU. Press and release the SA VE/ZERO button (C) until the bottom line displays POWER OFF. Press the MENU button (B). Use the SAVE/ZERO button (C) to increase the number of minutes of run time and the MENU button (B) to reduce them. Setting the timer to 0 will cause the unit to always remain on. After adjusting the number, press and release the left button (A) to save the adjustment. Use the SAVE/ZERO button (C) at this time to scroll to another menu function. Pressing the POWER/MUTE but­ton (A) will return the instrument to the working display .
SET CLOCK
From the working display access the user menu by pressing and holding the MENU button (B) until the top line of the display reads USER MENU. Press and release the SA VE/ZERO button (C) until the bottom line displays SET CLOCK. Press the MENU button (B). The day will flash upon entering the SET CLOCK
MENU
11
(Continued on page 12)
The Sensit® HXG-3 has several features in the user menu. These include:
PRINT MENU: SESSION LOG - print data that was saved. CAL LOG - print last 4 successful calibrations. SMART CAL - access to Smart-Cal Calibration S tation. CALIBRATION: Calibrate LEL and access Smart-Cal Calibration St ation.
POWER OFF: Set the automatic shut off timer in minutes. SET CLOCK: Set date and time. SHOW CAL LOG: Display last calibration. SHOW SES LOG: Display saved gas reading data with date
and time. BUMP TEST: Perform automatic test for response to minimum of 80% of calibrated gas value within 30 seconds.
SMART-CAL: Access automatic calibration st ation. GAS TYPE: Select natural/methane or pentane as primary gas
to be sensed.
PRINT MENU
From the working display access the user menu by pressing and holding the MENU button (B) until the top line of the display reads USER MENU. The bottom line will read PRINT MENU. Press the MENU button (B) to access the print menu options. Use the SA VE/ZERO button (C) to select the CAL LOG or SES- SION LOG. At this time prepare the printer . Aim the IR window on the right side of the instrument to the IR receptor on the printer. Position the instrument 6-12” from the IR receptor and press the MENU button (B). Downloading will begin immediately . When the dis­play no longer reads PRINTING... use the SA VE/ZERO button
13
(Continued on page 14)
MENU continued from page 12 option. The SA VE/ZERO button (C) advances to the next item
are based on US time and date settings using a 24 hour clock. After adjusting all numbers press and release the POWER/ MUTE button (A) to save the adjustment. Use the SA VE/ZERO button (C) at this time to scroll to another menu function in the USER MENU. Pressing the POWER/MUTE button (A) will re­turn the instrument to the working display .
SHOW CAL LOG
From the working display access the user menu by pressing and holding the MENU button (B) until the top line of the display reads USER MENU. Press and release the SA VE/ZERO button (C) until the bottom line displays SHOW CAL LOG. Press the MENU button (B) and the display will show the last gas cali­brated and calibration date. Pressing any button will return the display to the user menu. Pressing the POWER/MUTE button (A) will return the instrument to the working display.
SHOW SES LOG
From the working display access the user menu by pressing and holding the MENU button (B) until the top line of the display reads USER MENU. Press and release the SA VE/ZERO button (C) until the bottom line displays SHOW SES LOG. Press the MENU button (B). Use the SA VE/ZERO button (C) to scroll to the saved session you wish to review. SESSION 1 is the most recent data saved. Pressing the MENU button (B) will display the date and time of that session. Pressing the MENU button (B) again will display the gas reading. Press the POWER/MUTE
14
(Continued on page 15)
MENU continued from page 13 (B) again will display the gas reading. Press the POWER/MUTE
button (A) to return to SESSION(#) and pressing the SAVE/ ZERO button (C) will allow you to scroll all previously saved SESSIONS. Pressing the POWER/MUTE button (A) 2 times will return you to the USER MENU. Pressing the POWER/MUTE button (A) once more returns you to the working display. The number of stored session log saves is factory set at 6. It can store up to 100 by changing a factory setting (contact SENSIT TECHNOLOGIES for instructions).
BUMP TEST
From the working display access the menu by pressing and hold­ing the MENU button (B) until the top line of the display reads USER MENU. Press and release the SAVE/ZERO button (C) until the bottom line displays BUMP TEST. Prepare 50% LEL methane (or pentane) calibration gas for application to the instrument.
Apply calibration gas to the instrument sensor. Press the MENU button (B). The reading must read 80% of calibrated value within 30 seconds. The reading is on the left side and the timer is on the right side of the display .
If the instrument passes, the display will read BUMP TEST PASSES, a beep will sound and the unit display will automati­cally return to the user menu. If the instrument fails, the display will read BUMP TEST F AILED and a beep will sound. Repeated bump test failure indicates possible need for instrument repair. Contact J And N for instructions.
At the end of any bump test press the POWER/MUTE button (A) to return to the working display .
15
MENU continued from page 14 SMART-CAL (methane calibration only)
From the working display access the menu by pressing and holding the MENU button (B) until the top line of the display reads USER MENU. Press and release the SA VE/ZERO button (C) until the bottom line displays SMART CAL. Place the instrument into the cradle provided on the left side of the Smart­Cal Calibration Station. Att ach the tubing from the station to the instrument sensor. Press the MENU button (B). The display will show SMART CAL Communicating. Select the test from the Smart-Call Station to be performed. At the end of the test the instrument will beep 3 times and display PASS or FAIL. Retry the test if necessary by pressing the proper button on the Smart-Cal St ation again. Press and release the POWER/MUTE button (A) to return the working display . Remove the tubing and return instrument to service or send instrument to the proper place for repair per company procedures.
SHORTCUT TO ACCESS SMAR T-CAL: Place the instrument into the cradle provided on the left side of the Smart-Cal calibra­tion Station. Attach the tubing from the station to the instru­ment sensor. While in the working display press the POWER/ MUTE button (A) for 2-3 seconds and release. The display will show SMART CAL Communicating. Perform all tests as de­scribed in the SMART CAL section.
GAS TYPE
From the working display access the user menu by pressing and holding the MENU button (B) until the top line of the display
(Continued on page 16)
GAS TYPE continued from page 15
16
(continued on page 17)
reads USER MENU. Press and release the SAVE/ZERO BUTTON (C) until the bottom line displays GAS TYPE. Press the MENU BUTTON (B). Press Button (B) or Button (C) to change between PEN (Pentane) or NA T (Natural or Methane) as primary gas to be sensed. Press Button (A) to confirm selection is made.
CALIBRA TION
Calibration is the process of setting the readings of the instru­ment to equal the value of certified calibration gases.
NOTE: Using calibration kits other than recommended by SENSIT TECHNOLOGIES may cause inaccurate readings. Repairs are required if any sensor fails to calibrate. Con­sult SENSIT TECHNOLOGIES for details.
NOTE: When calibrating, the numbers shown on the dis­play represent the numbers seen by the microprocessor and should not be confused with actual gas readings.
Combustible Gas Calibration Procedure (50%LEL Methane or 50%LEL Pentane)
The calibration gas used for this procedure should match the Gas Type selected for your instrument. Refer to Gas Type in the Menu section of this manual. Instruments set to methane will calibrate with 50% LEL methane/air while those set to pentane will calibrate with 50% LEL pentane/air .
Prior to calibration allow the instrument to operate for 5 minutes in a gas free environment. Manually zero the instrument by
17
CALIBRATION continued from page 16
press and holding the (C) button until the display shows AUTOZERO. Prepare the corresponding calibration gas (methane or pentane), regulator and adapter .
From the working display access the USER MENU by pressing and holding the (B) button until the top line of the display reads USER MENU. Press and release the (C) button and the bottom line should read CALIBRA TION. Press and release the (B) button, the top line will read CALIBRA TION and the bottom line will read LEL 50%.
Apply the appropriate calibration gas for your instruments set-up and press the (B) button to start the automated calibration process.
If calibration is successful, the display will flash DATA SAVED before automatically returning to the calibration menu. Pressing the (A) button repeatedly will return the instrument to the working display . Remember to disconnect and shut off the gas supply .
If calibration is unsuccessful, the display will flash BAD CAL before returning to the calibration menu. In the event of a BAD CAL, remove the instrument from service and contact SENSIT T echnologies for assistance.
NOTE: Calibration will be based on the last successful calibration. The calibration due date will not be updated until successful calibration has occurred.
Any instrument that does not calibrate
requires service. Contact SENSIT TECHNOLOGIES for details.
WARRANTY AND REP AIR POLICY
Your Sensit® HXG-3 is warranted to be free from defects in materials and workmanship for a period of two years after pur­chase (excluding sensor, calibration and batteries). If within the warranty period, your instrument should become inoperative from such defects, the unit will be repaired or replaced at our option. This warranty covers normal use and does not cover damage which occurs in shipment or failure which results from alteration, tampering, accident, misuse, abuse, neglect or improper main­tenance. Proof of purchase may be required before warranty is rendered. Units out of warranty will be repaired for a service charge. Internal repair or maintenance must be completed by a SENSIT TECHNOLOGIES authorized technician. Violation will void warranty . Units must be returned postpaid, insured and to the attention of the Service Dept. for warranty or repair .
This warranty gives you specific legal rights and you may have other rights which vary from state to state.
18