SENSING LABS SL TOR-LAB-41NS Datasheet

SMART BUILDING
Ref : TOR-LAB-41NS
INDOOR
EVENT AND
ALARM MONITORING
SENLAB™ D IS A SMART WIRELESS DEVICE, FEATURING THE
LoRaWAN™ CONNECTIVITY PROTOCOL, EQUIPPED WITH AN INTEGRATED
DIGITAL INPUT SENSOR FOR ON/OFF OR OPEN/CLOSE STATE DETECTION.
17 years*
(replaceable battery)
15km*
Local or Public
Network compliant
*Depending on the operating conditions
Designed to monitor the status of relays, transistors, and switches and detect
abnormalities, Senlab D IP30 offers a highly-congurable information reporting
algorithm, notably for triggering alarms, counting, and more. It is ideal for your
IP30 (Indoor use)
Monitor engines and machines state
Manage alert and event system
Physical
specications
RF
specications
EC Conformity :
Compliant with Directive
2014/53/UE (RED)
This Senlab offers best in class features such as :
Battery Life time up to 17 years
Rich data content
Radio performances
Advanced set of functionalities
Dimensions 50 X 91,5 X 25 mm
Weight 60 gr
Operating temperature 0°C to +55°C
RF sensitivity -137dBm
RF power +14dBm (25mW)
Radio band 868 MHz
EMC
Radio EN 300 220-2 v3.1.1
Magnetic eld exposure EN 62479
Safety EN 60950-1, EN 60950-22
Final draft EN 301 489-3 v2.1.1
Draft EN 301 489-1 v2.2.0
www.sensing-labs.com
25 mm
TECHNICAL FEATURES FOCUS
DIMENSIONAL DRAWING
91,5 mm
50 mm
Plug & Play installation
Product fixing with double
sided tape or screw mounting
Screw terminal for on/off
sensor cable connection
Activation with magnet
(LED feedback)
High congurability of event detection and transmission
Event notification of open/
close or on/off digital state
State detection duration
configurable
Immediate transmission or
after N events or after maximum
duration
Reconfiguration possible
over the air
Network conguration
LoRaWAN parameters
(OTAA or ABP activation mode,
initial datarate,...)
Encryption keys customizable
by client
Standard LoRaWAN retries
support
Radio collisions avoidance
by pseudo-randomization
of transmissions
Advanced transmission
reliability mechanisms (recovery
of lost messages, ...)
BATTERY LIFE DURATION ESTIMATION
This following matrix provides the estimated battery lifetime depending on the average spreading factor used by the Senlab and the transmission period.
Battery life (years) 10 min 15 min 30 min 1 h 2 h 4 h 6 h 8 h 12 h 24 h
SF7 12,8 14,0 15,3 16,1 16,5 16,8 16,8 16,9 16,9 16,9
SF8 10,9 12,4 14,3 15,5 16,2 16,6 16,7 16,8 16,9 16,9
SF9
SF10
SF11
SF12
8,4 10,1 12,7 14,5 15,6 16,3 16,5 16,6 16,7 16,9
5,8 7,5 10,4 12,9 14,7 15,7 16,1 16,3 16,5 16,8
3,7 5,0 7,8 10,7 13,1 14,8 15,5 15,8 16,2 16,6
2,2 3,1 5,3 8,1 11,0 13,3 14,4 14,9 15,6 16,2
A single event per frame. For guidance and information purposes only.