Flame Detector
User Manual
General
Description
The flame detector is designed for use where open flaming fires may be expected. It responds to the light emitted from flames during combustion. The detector discriminates between flames and other light sources by responding only to particular optical wavelengths and flame flicker frequencies. This enables the detector to avoided false alarms due to such factors as flicking sunlight.
Electrical Considerations
The flame detector can be connected in many different electrical configurations depending on the application. The detector requires a 24Vdc (14Vmin. to 30Vmax.) supply to operate. The detector can be connected as a two-wire loop powered device increasing its supply current to signal that a flame has been detected. See Fig 8. The supply connections to the detector are polarity sensitive. Also available are volt free contacts from two internal relays RL1 (Fire) and RL2 (Fault or pre-alarm). Using the relay contacts connected in a four-wire configuration the detector status can be signalled back to control equipment. See Fig 9. Removing the detector front cover provides accesses the detector terminals and configuration DIL switch. See Fig.4.
Alarm Response Modes The detector is normally configured to latch into an alarm state when a flame is detected. The supply to the detector has to be broken in order to reset the detector. The configuration DIL switch within the detector can be set to place the detector into a non-latching mode. The detector can then also produce proportional analogue current alarm signals i.e. 8-28mA or 4-20mA. In non-latching mode the detector only produces an alarm signal when a flame is in view resetting itself to normal when the flame has gone.
Application for Flame Detectors
Flame detectors are used when detection is required to be:
Unaffected by convection currents, draughts or wind
Tolerant of fumes, vapours, dust and mist
Responsive to a flame more than 25m away
Fast reacting
The detector is capable of detecting the optical radiation emitted by burning material even non­carbonaceous materials. e.g. Hy
drogen
Numerous other potential fire sources can be detected such as
Liquids Solids Gases
Aviation Fuels (kerosene) Coal
Ethanol
● Cotton ● Fluorine
Methylated Spirits Grain & Feeds
n-Heptane
Paraffin
Paper Natural Gas
Refuse Off Gas
Petrol (gasoline) Wood
Butane
Hydrogen
Propane
Typical applications examples are:
Agriculture
Aircraft hangars Engine rooms
Atria
Automotive industry
Coal handling plant Pharmaceutical
Power plants
Generator rooms Textiles
Metal fabrication Transformer stations
- spray booths ● Paper manufacture Waste handling
- parts manufacture ● Petrochemical Woodw
orking
Applications and Locations to Avoid:
ambient temperatures above 55°C large IR sources – heaters, burners, flares
close proximity
to RF sources
exposure to severe rain and ice sunlight falling directly
obstructions to field of view
on the detector optics
large amounts of flickering reflections spot lighting directly on the detector optics
Quantities Required and Positioning of Detectors
The number of detectors required and their position depends on:
The flame detector is designed to have a class 1 performance as defined in BS EN54-10:2002 on the high sensitivity methylated spirit (clear) fire of 0.25m² at a distance of up to 25m within 30 seconds. The detector can be set to have to a lower sensitivity Class 3 performance is defined as detecting the same size fires as for class 1 but at a distance of only
the anticipated size of the flame
the distance of the flame from the detector
the angle of view of the flame detector
setting. That is the ability
12m.
to detect an n-heptane (yellow) fire of 0.1m² or
setting equivalent to class 3 performance.
Functional Testing
When 24Vdc power is applied to the detector the green
supply on indicator LED will illuminate. The fault relay RL2, if selected with the DIL switch, will energise and the contact between terminals 7 and 8 will close. If 24Vdc is applied to terminals 3 and 4 or terminal 3 is linked to terminal w
ill perform a self-test. It does this by
1 the detector
causing internal optical test sources to simulate the behaviour of flames and the detector will alarm.
6913
F1
6912
FLAME SENSOR TEST UNIT
F3
F2
2
1
ABC
5
4
GHI
JKL
7
PQRS8TUV
0
*
SUPPLY
SIGNAL
F4
3
DEF
6
MNO
9
WXYZ
#
Fig 12 Portable Flame Detector Test Unit
Service & Repairs
Servicing of the fire protection system should be car
ried out by competent persons familiar with this type of system, or as recommended by the local regulations in force.
Alternatively a portable flame sensor test unit is available to generate simulated behaviour and test the detector a few in front of the detector. See Fig 12. Finally, provided it is safe to do so, carry out a flame test using a flickering flame such as a portable Bunsen burner. See Fig 13. A still non-flickering flame w response
Fig 13 Portable Bunsen Burner
from the detector.
ill not produce a
Only the manufacturer or equivalent authorised body
may
carry out repairs to the flame detectors. In practical terms this means that flame detector may be repaired only at the manufacturers factory.
flame
metres
source,
2
11
R
Control Unit / Interface
(Supplied by others)
Flame Detector
Fire Relay
Fault Relay
1
+
2
-
5 6 7 8
Two pair cable, also see note 1
Refer to note 2
24Vdc Normal
(Break supply to rese
+
if detector set to latch)
-
+
Zone
-
Flame Detector
Fire Relay
Fault Relay
1
+
2
-
5 6 7 8
EOL
Refer to note 3
NOTE 2 R = To indicate fire to control unit or interface. E.g.: - 470R
NOTE 3 EOL = End of line device required by some control units. This is required to monitor the cable to the detectors and prevent fault indications on the control unit.
Fig 9 4 Wire Connection Diagram
The circuit shown above enables the flame detectors to interface with most type of fire alarm control systems. The fire relay RL1 is used to switch the required alarm load ‘R’ to generate a fire alarm signal. An end of line device ‘EOL’ mounted in the last detector provides the system with the ability to monitor the detector fault relay RL2 and the integrity of the interconnecting cables.
Installation
It is important that the detectors are installed in such a way that all terminals and connections are protected to at least IP20 with the detector cover fitted. The earth bonding terminals are provided for
convenience where continuity of a cable sheath or similar if required. Adjustable mounting brackets and weather shields are available as shown below.
In fact, the flame detector will detect fires at distances of up to 40 metres, but the flame size at such distances needs to be proportionally greater in order to be sure of reliable detection. Thus the yellow flickering flame that can be detected at 25m, provided that its size is not less than
0.1m², will have to be 0.4m² in order to be detected at 40metres. In a rectangular room the distance from the flame detector to the fire is calculated by the formula:
Maximum distance = √ L² + W² + H²
In the example shown in fig 1 the room in which the flame detector is to be installed measures 20m x 10m x 5m; the maximum distance from the detector to the flame will therefore be;
Height
Width
Fig 1 Calculation of distance from detector to flame
Field of View
The flame detector has a field of view of approximately 90°, as shown in the diagram below.
Fig 2 Conical field of view of the flame detector
F I R E
I R
S E N
S O R
Maximum distance = √ 20² + 10² + 5² = 22.9m
Length
F
I R E
I R
S E N
S O
R
90° Cone
Fig 10 Stainless Steel Adjustable Mount Fig 11 Stainless Steel Weather Shield
10
3
0.4m² flame seen at 40m
0.1m² flame seen at 25m
-75°
-90°
Fig 3 Detector Field of View Plot
The flame detector should be positioned at the perimeter of the room, pointing directly at the anticipated flame or at the centre of the area to be protected. If the detector cannot ‘see’ the whole of the area to be protected, one or more additional detectors may be required.
The flame detector is not affected by normal light sources but should be positioned so that sunlight does not fall directly onto the viewing window.
-45°
-60°
Centre line of detector
-15°
-30°
15°
0 25m
Detector
30°
45°
60°
75°
90°
40m
Detector Window Contamination
It is important to keep the detector window clean and checks should be carried out at regular intervals – determine locally according to the type and degree of contamination encountered – to ensure optimal performance of the flame detector. Although the IR detectors can detect flames when the window is contaminated, there may be a reduction of sensitivity as shown in Table 1.
Contamination
Water spray 75%
Steam 75%
Smoke 75%
Oil film 86%
Salt water film 86%
Dry salt deposits 86%
Table 1 IR Detector window contamination
UV/IR detectors are more susceptible to window contamination and must be kept clean.
Typical percentage of normal response
Connection Information
Flame Detector
Fig 8 Basic 2 Wire Connection Diagram
The simplest method of connecting the flame detector is in a 2-wire configuration as shown above. With a 24Vdc supply the current (i) drawn by a detector/detectors can be monitored to determine the detector status. The DIL switches within the detector can be set to produce different current values (i) to suit control systems.
Detector Supply Current
i @ 24Vdc
Normal
Quiescent
Current
3mA 9mA 0 0 0 0 Lowest power configuration, RL1 only
4mA 20mA 0 0 1 0 For 4-20mA systems, no relays
8mA 14mA 1 1 1 0 Lowest power configuration & relays
8mA 20mA 1 1 0 1 For 4-20mA systems & relays
8mA 28mA 1 1 1 1 Fire control panels
Table 4 Detector Supply & Alarm Currents
If the detector supply current falls below the normal quiescent current consumption then a fault is present. This could be simply an open circuit cable fault or a fault within the detector possibly due to the detector being taken over its rated temperature. Detectors can be connected in parallel increasing the overall quiescent current required. The alarm current signal will remain the same with the additional quiescent current drawn from other detectors.
1
+
2
-
Alarm
(Fire)
Current
Single pair cable, also see note 1
DIL Switch Setting
2
1
3
4
Control Unit
(Supplied by others)
i
NOTE 1 Screened cable should be used with one end of the screen connected to earth. Also care should be taken not to run the detector cable next to power cables.
Comment
24Vdc Normal
+
(Break supply to reset
if detector set to latch)
-
4
9
p
p
Theory of Operation
The detector responds to low-frequency (1 to 15 Hz.) flickering IR radiation emitted from flames during combustion. IR flame flicker techniques enable the sensor to operate through a layer of oil, dust, water vapour, or ice. Most IR flame sensors respond to 4.3µm light emitted by hydrocarbon flames. By responding to 1.0 to 2.7µm light emitted by every fire all flickering flames can be detected. Gas fires not visible to the naked eye e.g. hydrogen may also be detected.
Signal Processing
The detector views the flame at particular optical wavelengths. The more differing optical wavelength signals available the better the detector is at discriminating between flames and false optical sources. So although IR², IR³ and UV/IR² detectors can detect similar sized flames at the same distances, the UV/IR² detector will
Flame Optics
If the detector has interpreted the optical signals as a fire then it produces the required output responses. This will be in the form of supply current changes and the illumination of the red fire LED. The fire relay will also change state if required.
Fig 7 Block Diagram of the Detector Signal Processing
The dual (IR²) and triple (IR³) IR photoelectric detectors, responding to neighbouring IR wavelengths, enable it to discriminate between flames and spurious sources of IR radiation. The combination of filters and signal processing allows the sensor to be used with little risk of false alarms in difficult situations characterised by factors such as flickering sunlight.
give the greatest optical false signal immunity as it has the most diverse selection of optical wavelengths. The detector processes the optical signal information to determine if a flame is in view. This is achieved by comparing the signals with known flame characteristics stored within the detector.
Flame Detector
Terminals
Signal
Processing
Input/Output
Interface
The detector is constantly checking itself to ensure it is performing correctly. If a fault occurs the detector supply current will reduce, the fault relay will de-energise and the green supply LED will no longer illuminate constantly.
Detector Interior
FLAME DETECTOR
TO EN 54-10
6903
1 2 3 4 5 6 7 8
0
1
3
1
Fig 4 Detector with Front Cover removed
SENSITIVITY
LOW CLASS 3
HIGH CLASS 1
7 8
42
5 6
IR Optics - IR optical flame sensors
& filters
Supply ON (Green) - Steady if detector
functioning correctly
Fire (Red) - Indicates a FIRE detected
Test (Yellow) - Indicates detector in test
mode
UV Optics (Option) - UV optical flame sensor
if fitted
DIL Switch - Select detector functions
Connection Terminals
Electrical Connections
The flame detector has eight connection terminals as show in Fig 5. Removing the front cover of the flame detector accesses the connections. The cable is passed through the gland holes in the base of the detector.
Closes if flames
Normally closed
(N/C) when
owered
+IN -IN
+24Vdc Supply
ut
In
+R -R
FLAME
(N/O)
Test Input
Fig 5 Electrical Connection Terminals
Relay RL1
FAULT
(N/C)
Relay RL2
8
5
Connection Terminal Descriptions
Terminal No.
1 +IN Power Supply +V. +IN is the power supply input to the flame detector
2 -IN Power Supply 0V. –IN is the return path for the detector supply current.
3 +R Remote Detector Test Input +V. No connection to +R is necessary if
4 -R Remote Detector Test Input 0V. No connection to -R is necessary if the
5
6
7
8
Table 2 Connection Terminal Descriptions
Mnemonic Function
RL1
RL2
and is normally 24Vdc with respect to terminal 2. The current consumption of detector can be monitored to determine the detector status (Fault, Normal, Pre-alarm, Fire). If the detector is in latching mode then this supply line must be broken in order to reset the detector. A thermal fuse within the detector will blow and break the +IN connection if the detector operating temperature is exceeded.
-IN is also internally connected to terminal 4.
the detector optical and circuit test feature is not required. If 24Vdc is applied to terminals 3 and 4 the detector internal optical test sources will activate to simulate a flame. The detector yellow test LED will flicker to indicate an optical test is progress. The detector will then alarm indicating that the test was successful.
detector optical and circuit test feature is not required.
-R is internally connected to terminal 2.
Flame Relay RL1. This volt free contact is normally open (N/O) and only closes when a flame has been detected. If the detector is in latching mode (see DIL switch settings) the contact will remain closed once a flame has been detected. Only when the detector supply +IN is broken will the detector reset and the contact open once again. The contact can be changed to a normally closed (N/C) state by moving the link on JP1 in the rear of the detector. Maximum relay contact ratings: Power=3W, Current=0.25Amp, Voltage=30Vdc. Resistive loads only.
Fault or Pre-alarm Relay RL2. This volt free contact is normally closed (N/C) if the detector has no faults and the supply voltage between terminals +IN and –IN is the correct value. If the detector mode is changed (see DIL switch settings) this relay can be de-energised to reduce the detector current consumption. Alternatively RL2 can be set to provide a pre-alarm fire signal. The normal contact state can be changed state by moving the link on JP2 in the rear of the detector. Maximum relay contact ratings: Power=3W, Current=0.25Amp, Voltage=30Vdc. Resistive loads only.
Selectable Detector Functions
(DIL Switch Settings)
Fig 6 DIL Switch with Detector Front Cover Removed (Normal factory settings shown)
Selectable Functions DIL Switch Settings
Relay RL2 Function: 1 2
RL2 off (No fault relay) – For lowest detector current consumption. 0 0
RL2 off, or UV pre-alarm, flame or electrical sparks detected. 1 0
RL2 detector fault relay (Energised if detector powered and no faults) 1 ~ 1
Detector Supply Current (Detector Status): [-/ = see Output Mode below] 3 4
Low current mode, 3mA / 9mA (RL1 Only), 8mA / 14mA (RL1 & RL2) 0 0
Two-wire current signalling only. No relays operating. 4-20mA, 4/20mA 1 0
Two-wire current signalling 8-20mA, 8/20mA and both relays operating. 0 1
Two-wire current signalling 8/28mA and both relays operating. 1 ~ 1
Output Mode: 5
(-) Proportional analogue supply current. Non-latching fire alarm signalling. (-) 0
(/) Step change, supply current. Latching fire alarm signalling. (/) ~ 1
Response Time: 6 7
Faster response times reduce the optical interference immunity. Very Fast 1s 1 1
Sensitivity: See EN 54-10 8
Factory settings ~
Table 3 DIL Switch Settings
DIL Switch
0 1
SENSITIVITY
Low Class 3 High Class 1
12345678
RL2 energised on IR pre-alarm 0 1
Slowest 8s 0 0 Medium 4s 1 ~ 0
Fast 2s 0 1
Low Class 3 0
High Class 1 ~ 1
6