Sense KFT-2410R Instruction Manual

The KFT-2410R supply was designed for industrial installations where operation is continuous and requires reliable components. Built with the most modern techniques of switching with high performance and small footprint supplys, and excellent stabilization and regulation.
Supply Fixing:
1° Place only the supply upper bracket on the rail . (Fig.03)
2 º Lower the supply until it fully engages on the rail. (Fig. 04).
3º We recommend installing stops so that the supply does not slide on the rail. (Fig 05).
Horizontal mounting:
We recommend mounting in a horizontal position in order to ensure improved air circulation and that the panel is provided with a ventilation system to prevent overheating of the internal components. Note: We recommend also leaving a gap of at least 20mm
from one supply to another, in order to improve the cooling.
Electric Installation:
The supply has 9 terminals according to the table below:
Terminal Description
1 and 2
Positive output 24 Vdc
3 and 4
Negative output 24Vdc
5 and 6 Alarm
7 and 9 AC input
8
Ground
Wire Preparation:
Do the ends of the wires according to the drawing below: Be careful when removing the protective cover not to make small cuts in the wires, as this may cause short circuit.
Note: The minimum wire size for an output current of 10A must be 1mm2.
Procedures:
Remove the protective cover, insert the terminals and crimp them. If you want to tin the ends for better grip.
Terminals:
To avoid problems of poor contacts and shorting advise using pre-insulated terminals crimped on the wires.
AC input:
The KFT-2410R power supply has an automatic selection circuit for 110 or 220Vac (full range), which prevents damage to the supply with the improper selection / connection of the equipment.
Voltage Power Current
110 Vac 187 VA 1,7 A
220 Vac 220 VA 1 A
Note: The values shown in the table above are for the condition of maximum load (10A) in the supply.
AC Input Protection:
We recommend using the electrical circuit that supplies the unit by a protection circuit breaker or fuse.
Supply Terminals:
• Loosen the terminal screw using a switch with a diameter of 3 to 3,5mm.
• Insert the wire with the terminal already applied, from the bottom of the terminal.
• Tighten the terminal screw, and repeat for the other terminals.
• Verify that actually wires are securely attached by pulling them lightly.
Output Voltage:
The unit has a stabilized output voltage regardless of the current drawn. The direct current output, positive (1 or 2) and negative (3 or
4) terminals of the unit provides 24VDC with capacity for up to 10A. We recommend its use for automation circuits supply such as: electronic sensors PLC input or output cards. electronic modules auxiliary relays Current loops
• Industrial networks Profibus DP and DeviceNet standards
Signalling Led:
The supply has on its front a two-color LED whose function is described in the table below:
Led Status Function
Green on Normal operation Green off stand by Red on Short-circuit or overload
Note: The standby condition (sleep) occurs when the supply is working in parallel with each other and with lower output voltage than other supplys, and this condition does not provide (splits) current to the load.
Rua Tuiuti, 1237 - CEP: 03081-000 - São Paulo
Tel.: 11 2145-0444 - Fax.: 11 2145-0404
vendas@sense.com.br - www.sense.com.br
INSTRUCTIONS MANUAL
Switching Power Supply
KFT-2410R/110-220Vac
Tab. 8
Fig.7
1 2 3 4 5 6
7 8 9
Fig. 1
Pic. 2
Alicate ZA3Alicate ZA3
Pic. 10
Pic. 11
+ +
- -
55
FF
110 ou 220Vca
F F
N N
4040
55
Pic. 9
Fig. 3
Fig. 4
Fig. 6
FONTE DE ALIMENTAÇÃOFONTE DE ALIMENTAÇÃO
LEDLED
FF
FF
NN
CORRENTE ALTERNADACORRENTE ALTERNADA
110 ou 220Vca110 ou 220Vca
EMEM
ENTRADAENTRADA
CORRENTE CONTINUACORRENTE CONTINUA
SAÍDASAÍDA
--
++
24Vcc24Vcc
--
++
ALARMEALARME
Fig. 5
EA3000830- Rev. Bi - 09/15
21 .baT
Pic. 13
Fig. 14
Fig. 15
Fig. 16
Tab. 17
Output Ripple:
It is possible that a small ripple and a small output noise is noticed and may even audio noise characteristic occur, do not represent a malfunction to the supply.
Protection Against Short-Circuit:
The protection circuit is the oscillating type of automatic recovery, ie, when the protection operates the output de-energizes itself, and the supply back to operate automatically once the overload is removed. The short protection circuit acts as a power limiter, where the output voltage is reduced due to the overload current, as shown in the chart below:
Restoring After Overload:
If the supply is not supplying energy without , overload, must proceed: Remove the overload or decrease font loads. Disconnect and reconnect the AC power supply.
• If power not restored withdraw all charges deenergizing the 24 Vdc output and reconnect the AC input.
Output Voltage Adjustment:
If the supply is far from its loading center , the output voltage can be raised slightly by correcting the excessive voltage drop that may exist at the end of the line. To do so you must check the maximum allowable voltage for all devices connected to the line. The tension adjustment is made via a one pot back on the front of the fountain below the LED status. The potentiometer allows you to adjust the output voltage of 22V to 28V. Turn the trimpot counter-clockwise to decrease tension and counterclockwise to increase it.
Minimum Load:
So that the supply function properly, it is needed a minimum load of 1A, otherwise there will be a little instability in the supply due to narrowing of the PWM pulse, which DOES NOT cause problems, so it is possible that the supply function without charge, without risk to the user, but its output voltage regulation and can not be within the values established by having the supply indicates a nonexistent failure.
Minimum Load Resistor:
In the figure below minimum load resistor is installed in parallel with the load so that the total supply current is not less than 1A.
Resistor Calculation:
The load resistor should be calculated with the addition of
current drawn by the load current for minimum, as:
R
Ic a=-
=-= =
24124
1 072403
80
arg , ,
W
P Ic a x W= - = - = =24 1 24 1 07 24 03 7 2. ( arg ) . ( , ) , ,
For I load < 1A.
Redundance:
The supply is redundant type. Two or more supplies may be connected in parallel. Thus, even if a defect in one supply, the power supply will not be interrupted.
Alarm:
• The supply has an alarm relay, which is especially suitable for applications where dual power supplies, to indicate that one supply is not operating. The contact used to indicate remotely that one supply stops working.
Conditions that make the alarm contact open: Lack of AC current at the input.
• defect in the internal circuitry of the energy transformation.
Note: when the supply is in stand-by contact remains closed.
Load Division:
In applications with redundant power supplies, we recommend that supplies divide the load current, so that if one fails the other only increase the current supplied without prejudice to the load. The division need not be equally distributed by supplies recommend only adjust the output voltage so that the green LED output lights up, indicating that the supply is supplying current. For the current division is accurate, it is necessary to very precisely adjust the output voltage to the same voltage supply, but still can occur due to differences in wiring impedance.
Adjustment Procedure for Redundance:
• Taking as an example the design 22, disconnect the positive output of each source.
Place a voltmeter accurate to 2 decimal places in the output of the power and turn the potentiometer clockwise to increase pressure or counterclockwise to decrease.
• Look adjust the two supplies with the same output voltage.
Adjustment Procedure for Isolated Supplies:
In the case of single supplies acting on the pot by raising or lowering the output voltage by monitoring the voltage that effectively reaches the load, compensating for voltage losses in the cabling.
Incorrect Installation:
Attention! The improper installation or use can influence the
supply functioning, or even permanently damage the unit.
Safety Warnings:
Before working with the supply carefully read the instructions: Before placing the supply in operation must be ensured:
• The connection of supply and output are consistent with the connection diagram.
• Wires are securely attached to the terminals.
• That the cables are connected to the output load with correct polarity.
• That the load does not exceed 10A.
• You have enough for the perfect functioning of the cooling supply.
• Note that the wires have proper gauge for the current transmitted.
Attention!
Never open the power while in operation, because the unit contains components that store energy. Improper handling of these can cause serious injury to the operator.
Caution!
Even after de-energized, the supply accumulates electricity. Therefore we do not recommend open supply because very strong electric shocks to risk death can occur in the handling.
KFT-2410R Care:
Be careful when connecting the terminals as contact wires with metal housing may cause electric shock-threatening.
Mechanical Dimensions:
Fig. 18
24
20
16
12
8
4
0
2 4 6 8 10 10,5 11
V
A
21
Pic. 19
Vca
Fonte 1
Fonte 2
Vcc
F 1
F 2
CARGA
+
-
+
-
Pic. 22
Fig. 20
Pic. 21
Pic. 24
1
2
8
1
30
10
6
S
e n
s o
r
e s
e
I n
s t
r u
m
e n
t
o s
EA3000830- Rev. Bi - 09/15
Fig. 23
Loading...