Read and understand this Instruction Manual before installing,
operating or servicing ELDS 1000 / 2000 Series OPGD systems
Installations
Version 1.06 Iss 4 ECR111 Senscient ELDS™
SAFETY
Ensure that you read and understand these instructions BEFORE operating the equipment.
Please pay particular attention to the safety Warnings / Special Conditions of Safe Use.
WARNINGS / SPECIAL CONDITIONS OF SAFE USE
1. The Senscient ELDS™ 1000 / 2000 Series gas detectors are Baseefa ATEX certified
for use in Hazardous (Explosive) Atmospheres.
2. For installations in Europe (ATEX Certified) install in accordance with EN60079-14.
3. Elsewhere, the appropriate local or national regulations should be used.
4. ELDS™ 1000 / 2000 Series gas detectors must be properly earthed / grounded to
protect against electrical shock and minimise electrical interference. Internal and
external equipotential bonding facilities are provided for this purpose. For electrical
installation design considerations refer to Section 3.3.
5. Operators must be fully aware of the action to be taken if the gas concentration
exceeds an alarm level.
6. ELDS 1000 / 2000 Series gas detectors cannot be repaired or serviced by customers.
If units require repair or service they must be safely removed from any hazardous
location / area in which they are installed, and returned to Senscient. Other than the
rear cover providing access to the terminals for connection purposes the units are not
intended to be opened in service. Return to manufacturer for service or r epair.
7. Test gases may be toxic and/or combustible. Refer to Material Safety Sheets for
appropriate warnings.
8. Do not drill holes in any housing as this will invalidate the explosion protection.
9. In order to maintain electrical safety, units must not be operated in atmospheres with
more than 21% v/v oxygen.
10. Ensure that the bolts which secure the front flameproof enclosure are fully tightened.
The securing bolts are stainless steel M5 X 16mm socket head cap screws grade A4-
70. To ensure replacement suitability contact Senscient or their approved
agent/distributor.
11. Do not open the enclosure in the presence of an explosive atmosphere. Keep cover
tight when energised
12. The apparatus is certified for use in Hazardous Areas at atmospheric pressures not
exceeding 1.1 bar (16 psi).
13. Install only in environments with ambient temperature ranges of -40°C to +60°C.
14 For Europe (ATEX), apparatus incorporates an integral threaded cable entry (M25 x
1.5). Terminate cable only with a suitable equipment certified ATEX cable gland (not a
component). To maintain water and dust ingress protection seal threads with suitable
non-hardening sealant as described in EN 60079-14.
Note: See control drawing for product specification allowing selection of cable g lands.
15. For all installations use cable / conductors rated for service at temperatures >= 85°C
1
Version 1.06 Iss 4 ECR111 Senscient ELDS™
SAFETY
16. At all times during transit, installation and commissioning protect lens from accidental
direct mechanical impact. Use Senscient OEM supplied packaging during transit.
17. The transmitter and receiver units must be mounted horizontally and protected from
impact i.e. do not mount at floor le vel or in area s where moving veh icles, person nel or
loads may be of concern regarding impact.
CAUTIONS
1. Use only approved parts and accessories with the Senscient ELDS™ 1000 / 2000
Series gas detectors.
2. To maintain safety standards, commissioning and regular maintenance of ELDS™
1000 / 2000 Series gas detectors should be performed by qualified personnel.
3. Transit cases for the alignment telescope and gassing cell are manufactured from nonantistatic materials, and may, under certain circumstances become an electrostatic
risk. It is the users responsibility to take adequate precautions during transportation
and use if taken into hazardous areas.
IMPORTANT NOTICES
1. Senscient Inc. can take no responsibility for installation and/or use of its equipment if
this is not done in accordance with the appropriate issue and/or amendment of the
manual.
2. The user of this manual should ensure that it is appropriate in all details to the exact
equipment to be installed and/or operated. If in doubt, the user should contact
Senscient Inc. for advice.
3. Effect of explosive atmosphere on materials.
The Senscient ELDS™ 1000 / 2000 Series is manufactured from materials which
exhibit good resistance to corrosive substances and solvents. The Ex d enclosures are
made from 316L stainless steel (or aluminium, onshore only) and the explosion
protected windows are made from robust and chemically inert glass. Senscient are not
aware of any significant effects of explosive atmospheres upon these materials.
Contact Senscient or one of their agents for specific queries.
4. The final and long term effectiveness of any Open Path Gas Detector depends heavily
upon the user, who must be responsible for its proper application, installation and
regular maintenance.
Senscient Inc. reserves the right to change or revise the information supplied in this
document without notice and without obligation to notify any person or organisation of such
revision or change.
2
Version 1.06 Iss 4 ECR111 Senscient ELDS™
SAFETY
If further details are required that d o not appear in this ma nual, contact S enscient or one of
their agents. Senscient Ltd. will supply this manual in other languages of the European
Union (countries covered by the ATEX directive) upon request.
HELP US TO HELP YOU
Every effort has been made to ensure the accuracy in the contents of our documents.
However, Senscient can assume no responsibility for any errors or omissions in our
documents or their consequences.
Senscient would greatly appreciate being informed of any errors or omissions that may be
found in our documents. To this end we request that if you believe there are any errors or
omissions, please send us an e-mail at info@senscient.com describing the error or
omission, so that we may take the appropri ate action.
The Senscient ELDS™ 1000 / 2000 Series is a range of open path, flammable and / or toxic
gas detectors that is currently available in two versions*.
Senscient ELDS™ Series 1000 CH
Senscient ELDS™ Series 2000 CH
- Methane Detector
4
+ H2S - Simultaneous Methane & Hydrogen
4
Sulfide Detector
The Senscient ELDS™ Series 1000 CH
detector consists of a Transmitter unit that sends
4
an infrared laser beam to a separate Receiver unit that can be installed on a line-of-sight at
a distance of up to 200m. The ELDS 1000 Series CH4 detector can be located where there
is a risk that a leak of flammable methane gas may occur, to provide a rapid, early warning
of such a hazard. The ELDS™ 2000 version is similar, except that there are two coinciding
infrared laser beams, one for the detection of methane and the other for the detection of
hydrogen sulfide.
All ELDS
TM
gas detectors operate on the principle of absorption of infrared laser light.
Gases absorb light at specific wavelengths depending on their molecular composition.
Hydrocarbon gases such as methane and propane absorb in the infrared region of the
spectrum. If a cloud of target gas is present, the specific wavelength(s) of the infrared laser
light output by the ELDS
Fingerprint
TM
onto the signal reaching the Receiver that is proportional to the amount of gas
TM
Transmitter is absorbed by the gas, introducing a Harmonic
in the beam.
The Senscient ELDS™ Transmitter unit produces the precisely controlled infrared laser light
required to detect the target gases; whilst the Receiver unit contains an infrared detector
and advanced signal processing electronics which look for the Harmonic Fingerprint
TM
produced by the presence of target gas in the beam path. Each unit is housed in a robust
316L stainless steel or aluminium housing. The Receiver includes two 4 - 20mA analogue
outputs which are used to signal the quantity of each target gas measured in the beam path,
for example 0-1LEL.m CH4 and 0-250ppm.m H
S for the Series 2000 detector. These
2
outputs provide a linear relationship with the measured gas concentration.
Note that this product does not measure point concentration of the target gas(es), rather it
measures the integrated concentration over the whole length of the measurement path
between the transmitter and receiver units. This means that some account of the likely scale
of any gas cloud being monitored must be considered when attempting to interpret the
actual concentration of gas that might be present and must adjust any subsequent alarm
levels appropriately. The following figures illustrate this.
7
Version 1.06 Iss 4 ECR111 Senscient ELDS™
INTRODUCTION
Each of these different gas clouds will produce the same ELDS reading of 1.0 LEL.m,
however only the 1
flammable concentration within it.
st
example where the gas cloud is very small actually has a potentially
*Versions of the ELDS 1000 / 2000 Series for other gases and in different
configurations will be made available in the near future.
NOTE: THE INFRARED LASER BEAMS ARE INVISIBLE AND COMPLETELY EYESAFE.
Senscient ELDS™ is designed for use in the most demanding environments/applications
and provides a sensitive, fast and reliable response. The sophisticated ELDS
TM
open-path
technology provides immunity to sunlight and minimises the effects of environmental factors
such as rain, fog, ice, snow and condensation.
The Transmitter and Receiver units incorporate heated optics designed to minimise the
build up of humidity, condensation, snow or ice on the glass lens-windows that could
obscure the optics in extreme conditions.
Both the Transmitter and the Receiver are microprocessor controlled with advanced selfdiagnostics and fault finding facilities.
Local communication between an operator /technician and the gas detector system is made
via SITE (Senscient Installation & Test Environment) running on a laptop or an iRoc PDA,
using a communication link to either the transmitter or receiver. SITE provides the user with
a menu-style interface to select and invoke commands for commissioning and configuring
the system, and for viewing the system state and measurements.
8
Version 1.06 Iss 4 ECR111 Senscient ELDS™
INTRODUCTION
This manual consists of the following parts:
Chapter 1 INTRODUCTION
Chapter 2 SYSTEM DESCRIPTION
Chapter 3 INSTALLATION DESIGN & ENGINEERING
Chapter 4 INSTALLATION & COMMISSIONING
Chapter 5 FUNCTIONAL TESTING
Chapter 6 MAINTENANCE
Chapter 7 PROBLEM SOLVING
Chapter 8 SPECIFICATIONS
Chapter 9 CERTIFICATION
Appendix A Handheld Interrogator
Appendix B Glossary
Appendix C Accessories & Spare Parts
Information notices
The types of information notices used throughout this handbook are as follows:
WARNING
Indicates hazardous or unsafe practice which could result in severe injury or death to
personnel.
Caution: Indicates hazardous or unsafe practice which could result in minor injury to
If more information beyond the scope of this technical handbook is required please contact
Senscient.
9
Version 1.06 Iss 4 ECR111 Senscient ELDS™
SYSTEM DESCRIPTION
2 SYSTEM DESCRIPTION
2.1 Introduction
Each Senscient ELDS™ 1000 / 2000 Series gas detector consists of two units, a
Transmitter and a Receiver. This separate Transmitter / Receiver configuration provides the
most reliable basis for open path gas detection. There are no transceiver units or retropanels utilised in the Senscient ELDS™.
Mounting Bracket
Sun Shade
Alignment Adjustment
(horizontal and
vertical)
Tx and Rx Units
Monitored Path
There are several operating ranges of Senscient ELDS™ gas detector, e.g.:
Series 1000 CH
Refer to Senscient for additional ranges and gases.
When designing an installation for Senscient ELDS™ 1000 / 2000 Series it is important that
the correct range of the gas detector for each path to be monitored is selected and
specified.
Note:In order to avoid the problems associated with gas detectors b eing used beyond
their specified ranges or when incorrectly aligned, a procedure within the
Senscient Installation & Test Environment (SITE) checks for correct gas detector
10
Version 1.06 Iss 4 ECR111 Senscient ELDS™
SYSTEM DESCRIPTION
type, operating range and signal levels before allowing the ELDS OPGD to
activate.
The Transmitter and Receiver are each mounted upon robust, adjustable mounting
brackets. The design of the mounting and alignment arrangement for the Senscient ELDS™
1000 / 2000 Series is highly accommodating, making it simpler to realise a good installation
in a variety of locations and environments. Installation details are given in section 3.
2.2 Transmitter
The Senscient ELDS™ Transmitter produces up to two controlled-divergence beams of
infrared laser light from solid-state laser diodes. The outputs from the laser diodes are
partially collimated using a faceted lens, the facets of which introduce the controlleddivergence that is necessary to reduce system alignment sensitivity. The Transmitter
operates continuously
NOTE: THE INFRARED BEAM IS INVISIBLE AND EYE-SAFE.
245mm
220mm 300mm
The Transmitter contains a small retained sample of the target gas(es) to be detected by the
system, and uses this retained sample as a reference to maintain its laser diode(s) in
Harmonic Fingerprint
TM
lock. By continuously maintaining Harmonic Fingerprint lock it is
possible to be certain that whenever target gas(es) enter the system’s beam path this will
introduce a Harmonic Fingerprint onto the signal which will be seen and measured by the
Receiver. The retained target gas sample also enables the Transmitter to know precisely
how to simulate the presence of target gas in the beam by means of adding Harmonic
Fingerprint components to the drive signal applied to the laser diode(s). This is the basis of
the SimuGas on-demand functional test technology incorporated in Senscient’s ELDS
OPGDs.
The transmitter also incorporates links which can be used to communicate with a laptop or
i.Roc PDA. Using SITE and these communication links, a laptop or i.Roc PDA can be
employed to perform alignment checks, commissioning, configuration, functional testing,
diagnostic procedures and SimuGas
TM
tests.
The Transmitter window is heated to minimise condensation, frosting and the build up of
snow.
11
Version 1.06 Iss 4 ECR111 Senscient ELDS™
SYSTEM DESCRIPTION
Three connections to the Transmitter are required, +24V, 0V and GND (for electrical safety).
2.3 Receiver
The Senscient ELDS™ Receiver collects infrared laser light from the Transmitter and
determines the size of any Ha rmonic Fingerprint
TM
components that have been introduced
onto this signal to establish the quantity of any target gases present in the beam path
The Receiver collects and concentrates infrared laser light from the Transmitter onto a
single, infrared detector using an aspheric condensing lens-window. The detector output is
amplified and processed by a sophisticated electronic signal processing system which
effectively removes any ambient light and extracts Harmonic Fingerprint
TM
information
related to the quantity of target gas in the beam path. The detector amplification chain
incorporates an advanced Automatic Gain Control (AGC) system that enables it to
compensate for the wide range of signal levels that can be received due to effects arising
from rain, fog, snow, dirt etc. This enables the ELDS 1000 / 2000 Series to continue
operating reliably in the harshest conditions that are likely to be encountered at Oil & Gas
installations around the world.
245mm
300mm 220mm
The solid state, InGaAs photodiode detectors used in the Senscient ELDS™ 1000 / 2000
Series provide an exceptional dynamic range and superb temperature and long term
stability. These properties contribute significantly to the solar immunity and stability of the
Senscient ELDS™ 1000 / 2000 Series.
The primary output(s) of the Receiver are up to two 4 - 20mA loop outputs which can be
configured for source, sink or two-wire isolated operation. The outputs are factory calibrated
to provide the appropriate full scale range for the measured species and model variant. The
output is typically calibrated in units of LEL.m or ppm.m (See section 10 for the explanation
of LEL.m and other terms).
The receiver also incorporates links which can be used to communicate with a laptop or
i.Roc PDA. Using SITE and these communication links, a laptop or i.Roc PDA can be
employed to perform alignment checks, commissioning, configuration, functional testing,
diagnostic procedures and SimuGas
The Receiver window is heated to minimise condensation, frosting and the build-up of snow.
TM
tests.
12
Version 1.06 Iss 4 ECR111 Senscient ELDS™
SYSTEM DESCRIPTION
Between four and eight connections to the Receiver are required, depending upon the
number and configuration of the 4-20mA outputs used. These connections are required to
provide +24V, 0V, 4-20mA(1), 4-20mA(2) and GND (for electrical safety).
The ELDS system does not have any gas alarm set functions. The 4-20mA signal outputs
from the receiver are non-latching. If the ELDS system is intended to indicate a potentially
flammable gas concentration then any auxiliary equipment (e.g. control room plc, control
unit or monitoring apparatus etc.) shall have an alarm set point that is latching, requiring a
deliberate action to reset. If two or more set or alarm functions are provided the lower may
be non-latching.
2.4 Adjustable Mounting Bracket
The adjustable mounting brackets for the ELDS 1000 / 2000 Series are:
Purpose-built for the Transmitter and Receiver.
Provide coarse and fine adjustment for quick, simple system alignment
Rigid, stable and robust.
Made from 316L stainless steel or aluminium (with aluminium units).
The coarse horizontal adjustment facility enables a transmitter or receiver to be quickly
pointed in the approximate direction of its counterpart and provides a full 360º of rotation.
The fine horizontal adjustment facility enables a transmitter or receiver to be precisely
aligned and locked-off with respect to its counterpart, and has an adjustment range of 25º.
The fine vertical adjustment facility enables a transmitter or receiver to be precisely aligned
and locked-off with respect to its counterpart and has an adjustment range of 25º.
Alignment details are given in Section 3
Clamp nut
Mounting bracket
adjusting screw (2 off)
Adjustment clamp lock
screw
Mounting Lug (on unit
body)
Pivot block adjusting
screw (2 off)
Clamp nut
13
Version 1.06 Iss 4 ECR111 Senscient ELDS™
SYSTEM DESCRIPTION
2.5 Sunshade
The sunshade is a standard-fit item provided to ensure that units stay as cool as possible,
wherever they are installed and operated, thereby maximizing the service life of the
electronics inside. The sunshade is adjustable in order to facilitate use of the alignment
telescope and provide easier access to the electrical connections inside the terminal
compartment.
Sunshade
Retaining Screw
The sunshade is fixed by a single retaining screw as illustrated. Loosen this in order to allow
adjustment of the position of the sunshade. Tighten the retaining screw to ensure that the
sunshade remains in the desired position.
14
Version 1.06 Iss 4 ECR111 Senscient ELDS™
SYSTEM DESCRIPTION
2.6 Cross Duct Mounting Plate
Cross Duct ELDS systems are designed to be mounted on opposite sides of flat, parallelwalled ducts using the Mounting Plate provided for this purpose and shown below.
Note
It is the installers / end users responsibility to ensure that the duct hazardous (classified)
location and / or hazardous area is in compliance with ELDS certification (see Section 9 for
ELDS certification details).
Additionally, the duct environment shall not exceed the following:
Pressure: 80kPa (0.8Ba r) to 110kPa (1.1Bar)
Temperature: -40ºC to +60ºC
Oxygen Content: less than 21%v/v
15
Version 1.06 Iss 4 ECR111 Senscient ELDS™
INSTALLATION DESIGN & ENGINEERING
3 INSTALLATION DESIGN & ENGINEERING
3.1 Introduction
WARNING
The applicable National Code of Practice regarding selection, installation and maintenance
of electrical apparatus for use in Hazardous Areas/Zones must be complied with at all times
The Senscient ELDS™ 1000 / 2000 Series has been designed engineered and customer
tested to be the most robust, reliable Open-Path Gas Detector (OPGD) available to date.
The design and ELDS
makes it far more resistant to the adverse effects of the operating environment and nonideal installation engineering than previous generations of OPGDs.
With careful consideration of the intended operating environment and the installation design,
the installer/operator can maximise the reliability, availability and performance achieved with
ELDS™ OPGDs.
TM
technology employed in the Senscient ELDS™ 1000 / 2000 Series
Before designing or specifying an installation for Senscient ELDS™, it is strongly
recommended that the installation design authority reads and understands this chapter, and
considers how the information and recommendations provided can be applied to their
installation(s).
If a design authority has any queries concerning their installation design, they should
contact Senscient or their local agents.
Senscient is committed to ensuring that customers achieve reliable operation of their
Senscient ELDS™ OPGDs. For this reason, Senscient ELDS™ OPGDs should only be
installed by fully trained personnel (trained by Senscient or a Senscient authorised trainer).
This training will provide the installer with a clear understanding of the Sensci ent ELDS™
OPGD product and the associated accessories and tools. It will also provide familiarity with
the installation, alignment and commissioning procedures, plus installation assessment
skills to identify potential problem areas.
For each installation, it is recommended that the installer should check the installation and
operating environment against the Check List presented in Section 4.4.
NOTE: THE INFRARED LASER BEAMS ARE INVISIBLE AND EYE SAFE.
3.2 Siting and Mounting
3.2.1 General
When designing an installation for a Senscient ELDS™ OPGD it is important to give
consideration to where it is to be located, what potential sources of problems may be
encountered in this location and how the unit is to be mounted and supported and protected
from accidental impacts.
16
Version 1.06 Iss 4 ECR111 Senscient ELDS™
INSTALLATION DESIGN & ENGINEERING
3.2.2 Location for Best Coverage
Guidance on the positioning of gas detectors to provide the best detection coverage is
contained in national Codes of Practice. It is recommended that the installation designer
consults these Codes of Practice. Senscient would advise that the best current methodology
for siting all types of fixed gas detectors is based upon the expert use of gas dispersion
modelling, performed for the particular area(s) of plant or facility where potential gas leak
hazards exist. There are a number of organisations with the gas dispersion modelling tools
and expertise necessary to perform this work. In general, for OPGDs the following positions
usually provide the best results:
Running parallel to the physical perimeter of an area of plant or facility
containing potential gas leak hazards.
Forming a continuous ‘ring-fence’ surrounding an area of plant or facility
containing potential gas leak hazards.
At sufficient distance from any potential leak sources for dispersion to
produce a gas cloud of a size that will reliably be intercepted by the beampaths of the OPGDs employed.
Between potential leak sources and any known or likely sources of ignition.
For natural gas: beam-path parallel to the ground / floor and above the height
of most of the valves and flanges in the vicinity.
For toxic gases: beam-path parallel to the ground / floor at ‘breathing height’ (~
1.4m – 1.7m).
For gas mixtures significantly denser than air: beam-path parallel to the
ground / floor and below all potential leak sources*.
For gas mixtures significantly lighter than air: beam-path parallel to the ground
/ floor and above all potential leak sources*.
*NOTE: In mo st instances the hazardous gases leaking from a plant or facility aremixtures
of a number of gases with different chemical and physical properties. In a gas mixture the
constituent gases will retain most of their chemical properties, but the physical properties of
the gas mixture will be the proportionate sum of the physical properties of the constituent
gases.
For sour natural gas, the above principle means that this gas mixture will be both toxic and
flammable; whilst the density of this mixture will tend to be dictated by its high methane
content.
Only accurate modelling will determine the precise physical properties of a leak of sour
natural gas, but typically this mixture’s density will be similar to, or slightly lower than that of
air. Only leaks of very cold natural gas or of neat hydrogen sulfide are likely to be slightly
denser than air.
Dispersion modelling provides little support for the practice of placing hydrogen sulfide
detectors close to the ground. In the majority of instances leaks of sour natural gas or
hydrogen sulfide will not sink; whilst the toxicity hazard is greatest at the height where such
gas can be breathed in.
17
Version 1.06 Iss 4 ECR111 Senscient ELDS™
INSTALLATION DESIGN & ENGINEERING
Location to Maximise Reliability and Availability
Care in choosing the location of ELDS™ OPGDs can contribute significantly to the overall
reliability and availability.
When locating units, attempt to avoid areas where they may be adversely affected by the
following:
Vibration - Angular vibration of the structure to which ELDS™ OPGD units are attached
should be kept to less than +/- 0.5. Where possible, avoid locations where high levels of
vibration will be directly induced into the mounting structure. If close proximity to significant
sources of vibration is unavoidable, take steps to reduce coupling of this vibration and
maximise the rigidity of the mounting structure.
Intense Heat - ELDS™ OPGDs are certified and specified for operation in environments up
to +60C. If sources of intense heat (flarestacks, intense sunlight, etc.) are present, the
effect of these will be reduced by the fitted sunshade. If the sunshade proves insufficient in
an extremely hot installation then further shielding should be provided.
Sources of Heavy Contamination - Avoid locations where high levels of contaminants will
persistently be blown onto the unit’s lens-windows. Potential sources of heavy
contamination include generator/turbine exhausts, flare-stacks, drilling equipment, process
vents/chimneys etc. If sources of heavy contamination cannot be avoided, consider fitting
extra shielding and/or providing good access for more routine cleaning.
Snow and Ice in Ambients Below -20
melt snow or ice on the lens-windows in ambient temperatures down to approximately
-20C. Below this temperature, snow or ice blown onto the lens-window will not be melted
until the ambient temperature rises. If long-term, outdoor operation in very cold climates is
intended, it is recommended that extra shielding/covers are employed to prevent snow/ice
from being blown onto the windows and building up.
Deluge and Flooding - Senscient ELDS™ OPGDs are rated IP66/67 and as such will not
be damaged by occasional deluge or flooding. However, during such instances the unit will
completely lose its IR signal and will enter the BEAM -BLOCK/FAULT state. Also, when the
deluge/flooding subsides, there is the possibility that contaminants will be left on the
windows. Therefore, it is recommended that ELDS™ OPGD units be located away from
areas particularly prone to deluge or flooding.
Areas Prone to Subsidence and Settling - Where possible, it is recommended that
ELDS™ OPGD units are not mounted on structures located where problems with
subsidence, settling or thawing of permafrost are known to cause significant movement. If
such locations cannot be avoided, the foundations of the mounting structure should be
engineered to minimise any angular movements.
C - The heated optics on ELDS™ OPGD units will
Areas Prone to Earthquakes - In locations prone to earthquakes, there is a chance that
during or after an earthquake, the units of an ELDS™ OPGD will become misaligned with
respect to each other. Provided that the ELDS™ OPGD units do not suffer from direct
mechanical impact damage during an earthquake, they should remain undamaged by such
events. Anti-vibration mounts are unlikely to be of any benefit and are not recommended.
After an earthquake it is recommended that ELDS™ OPGDs are visited and their alignment
be checked.
18
Version 1.06 Iss 4 ECR111 Senscient ELDS™
INSTALLATION DESIGN & ENGINEERING
Accidental Impact - Mount transmitter and receiver horizontally to protect from impact.
Locations where there is a likelihood of equipment, personnel or moving objects accidentally
knocking ELDS™ OPGD units out of alignment should be avoided. If such locations cannot
be avoided, measures including improved mechanical protection and warning notices
should be considered.
Intense Electromagnetic Fields - Senscient ELDS™ OPGDs comply with FM63 25 an d a re
designed to comply with EN50270, and as such are well protected from interference by
electromagnetic fields. However, locations in close proximity to radio/radar transmitters,
heavy electrical plant and high voltage power cables may experience field strengths in
excess of those specified in EN50270. Where possible, such locations should be avoided or
units should be installed as far as possible from the source of the electromagnetic field.
Measures including additional screening, filtering and transient suppression may also be of
benefit in such locations.
3.2.3 Beam Path
The Transmitter and Receiver unit lens-windows should directly face each other across the
area to be protected and, depending on the range of the Transmitter in use, should be the
following distance apart:
Senscient ELDS™ Detector Series Type Path length between units
The beam path and immediate surrounds should be kept free of obstructions that might
hinder the free movement of air in the protected area or block the infrared beam. A clear
beam path of 20cm diameter or greater is recommended. In particular, for optimum
availability, avoid areas affected by the following.
a. Steam vents and plumes
b. Smoke stacks and chimneys
c. Walkways and personnel areas
d. Splash and spray, e.g. from moving equipment, cooling towers, etc.
e. Parking, loading, cranes, vehicle temporary stops, e.g. bus stops, road junctions, etc.
f. Vegetation, e.g. shrubs, bushes, branches, etc. - if currently clear, movement due to
weather and future growth or planting must be considered
Note: Where c. and d. cannot be avoided, consider indicating the beam by marking the
walkway or road with paint.
19
Version 1.06 Iss 4 ECR111 Senscient ELDS™
INSTALLATION DESIGN & ENGINEERING
Beam
clearance arc -
radius more
than 10cm
Telescope clearance arc
radius - more than 30cm
Notes:
1. In order to fit the alignment telescope, used during the alignment process, a clear
accessible arc of at least 30cm radius is required close to the unit as shown.
2. A clear beam path of at least 10cm radius or greater is recommended.
20
Version 1.06 Iss 4 ECR111 Senscient ELDS™
INSTALLATION DESIGN & ENGINEERING
3.2.4 Supporting Structure
The Transmitter and Receiver units should be fixed to a stable supporting structure using
the mounting brackets supplied.
Note: The maximum movement of the supporting structure under all anticipated
operating conditions must be
If either unit is unable to be mounted on an existing structure, and the required height above
the ground is no more than 3m, then the supporting structure shown is recommended:
0.5º.
100mm to 150mm (4” to 6”) dia.
steel pipe, nominal 6mm wall
thickness 4” to 6”
up to
3m
500mm
minimum
500mm
minimum
500mm
minimum
Concrete foundation
Note: The pipe can be filled with concrete to provide extra stability if necessary
21
Version 1.06 Iss 4 ECR111 Senscient ELDS™
INSTALLATION DESIGN & ENGINEERING
3.2.5 Wall Mounting
The mounting bracket can be directly attached to a suitable wall or similar structure as is
illustrated below:
3.2.6 Orientation
Senscient ELDS™ OPGDs are solar immune and therefore there is no need to take account
of the sun’s movement when considering orientation.
When positioning the units do not install them with the optical axis at an angle greater than
45º to the horizontal. This is to avoid dirt/water build-up on the lens-windows.
22
Version 1.06 Iss 4 ECR111 Senscient ELDS™
INSTALLATION DESIGN & ENGINEERING
3.2.7 Siting and Mounting Cross Duct ELDS Systems
Cross Duct ELDS systems are specifically designed and engineered for installation with
their beam-path running across the duct, perpendicular to the direction of flow through the
duct. In order to facilitate installation in this manner, the walls of the duct at the location
where the Cross Duct ELDS system is to be installed must be flat and parallel to each other.
Provided that this requirement is met it is then a simple matter of mounting each half of the
Cross Duct ELDS system directly opposite its counterpart. Self-adhesive templates (011389-D) are provided to assist with the location and drilling of suitable holes in the duct wall.
NOTE: The most important requirement for successful installation of a Cross Duct
ELDS system is that the optical centre lines, as indicated by the cross-hairs on the
self-adhesive templates are directly opposite each other on the duct wall.
All ranges of the Senscient ELDS™ 1000 / 2000 Series comply with the electrical and EMC
requirements of EN50270. In order to maintain compliance with the applicable standards it
is essential that the electrical installation of ELDS™ 1000 / 2000 Series systems is
engineered accordingly.
Electrical installation standards and practices vary between countries, companies and
applications. It is the responsibility of the installation design authority to determine the
applicable standards and practices, and to ensure compliance with them.
When designing electrical installations for ELDS™ 1000 / 2000 Series systems, it is
recommended that the installation design authority takes into account the following:
a. In order to comply with the applicable electrical installation standards and practices,
the metal cases of units must be connected to earth / ground. Care should be taken
in the design and engineering of this earth / ground connection to ensure that any
electrical noise or voltage introduced onto a unit’s case is no greater than the levels
specified in EN50270.
b. The case earth / ground bonding arrangement must ensure that the maximum
transient voltage between a unit’s case and any field cable conductor is less than
1000V. Voltages in excess of this may cause permanent damage to the unit.
c. The entire length of the field cabling connected to each unit should be fully shielded /
screened. This shield / screen should be connected to a low noise (clean) earth /
ground, preferably at a single point.
d. The shields / screens of the field cabling should not be connected such that earth /
ground loops are produced, or in a manner that will result in the shields / screens
carrying large currents from heavy plant or equipment.
e. Where the shield / screen of field cabling enters the terminal compartment of an
ELDS 1000 / 2000 Series unit, this shield / screen should not be connected to the
unit’s earth / ground terminal and should be preve nted from maki ng any contac t with
the unit’s case. The unit’s case will be connected to a local earth / ground which will
typically be noisy, and this noise should not be allowed to get onto the field cable’s
shield / screen.
f. Any electrical interference induced onto the 4-20mA loop conductors by the
installation must be kept below the levels necessary to comply with the general
requirements of EN50270. In practice, this means that peak noise currents induced
on the current loop should be no greater than 0.2 5mA.
g. The use of ‘two wire 4-20mA' isolated configurations effectively eliminates the
problems associated with field devices being at different potentials to those in the
control room and reduces susceptibility to noise and interference pick-up on a 420mA loop. Isolated ‘two wire 4-20mA’ configurations are therefore recommended for
applications where there is a long distance between the field device and the control
room (e.g. > 750m) or where there are particularly strong sources of electrical noise
and interference (e.g. heavy electrical plant) in the vicinity.
24
Version 1.06 Iss 4 ECR111 Senscient ELDS™
INSTALLATION DESIGN & ENGINEERING
h. When a single wire is used as the primary 4-20mA signal carrying conductor, the
current loop is completed by either the 0V or the +24V conductor running to the unit.
In such ‘single wire 4-20mA' configurations, any noise on the 0V or +24V rail is
effectively introduced onto one side of the current sensing resistor in the 4-20mA
loop. It is therefore beneficial to limit the level of noise and interference present on
the system’s 0V and +24V supply rails.
i. The level of noise on the 0V and +24V supply rails of a system can be reduced by
choosing high quality power supplies that are rated for the continuous supply of the
system’s maximum calculated power requirement, and that have effective filtering on
their outputs. Installation designers should avoid low cost, switched-mode power
supplies with minimal output filtering because they are noisy, unreliable and become
increasingly noisy as the cheap capacitors inside them degrade.
j. The 24V supply providing power to field devices should be free from large transients
and fluctuations.
k. The earth / ground at industrial facilities is typically very noisy, and therefore the level
of noise on the 0V and +24V rails can be reduced by the use of power supplies that
are isolated from earth / ground.
l. The use of a single, screened cable for each field device ensures maximum
screening and minimum crosstalk. This should be the preferred cabling arrangement
for field devices forming part of a gas detection system.
m. Cabling arrangements which use a single multicore cable for connecting a large
number of field devices compromise screening and increase the potential for
crosstalk. Such arrangements should be avoided wherever possible.
n. The 4-20mA outputs of gas detectors are typically updated no more than a few times
a second; whilst the electrical interference and noise introduced onto the cabling
carrying a 4-20mA signal back to the control room can include components with
frequencies ranging from 50Hz to 2GHz. In order to reduce false alarms due to
electrical interference and noise it is therefore extremely beneficial for the 4-20mA
inputs of gas detection control systems to be able to ignore high frequency
components. This can be achieved by analogue filtering / conditioning of the 4-20mA
input, or by appropriate processing of the digitized 4-20mA signal, or by a
combination of the two. The installation designer is advised that failure to address
this issue can result in an unacceptably high rate of false alarms in many industrial
environme nts and applications.
o. All electrical equipment directly connected to a gas detection system should comply
with applicable EMC standards such as EN50081, EN50270 & IEC 61000.
p. Radio, radar and satellite communication equipment is normally licensed to emit RF
radiation at power levels greatly in excess of those allowed by EN50081, EN50270 &
IEC 61000. Field devices should not be installed in close proximity to the antennae of
radio, radar or satellite communication equipment; whilst additional filtering /
screening measures may be required for reliable operation of field devices within 10
to 20 metres of such antennae.
q. The conductors carrying power to ELDS 1000 / 2000 Series units should have
sufficient cross sectional area to ensure that the minimum supply voltage reaching
25
Version 1.06 Iss 4 ECR111 Senscient ELDS™
INSTALLATION DESIGN & ENGINEERING
units is 18V when they are drawing their maximum specified power. Refer to section
3.3.5 for information to assist with the selection of suitable cable.
r. The power consumption of each half of an ELDS 1000 / 2000 Series system is
around 10W, which is sufficient to create a significant voltage drop due to the current
flowing through the resistance of the field cabling. Where installation designers intend
to ‘daisy chain’ the supply of power to an ELDS 1000 / 2000 Series system by
running the +24V and 0V connections to one half of a system and from there to the
other half, caution is advised. The voltage drop to the first half of the system will be
the product of the total system current and the cable resistance to that point; whilst
the voltage reaching the second half of the system will be still lower, further
increasing the current drawn by this half of the system. A ‘daisy chain’ arrangement
should be acceptable for systems installed within a few hundred metres of the control
room, but for greater distances the installation designer will need to calculate the
voltage drops and necessary cable resistances very carefully. Rather than use the
same pair of conductors to carry +24V and 0V to the system it may prove better to
use a separate pair of conductors to carry +24V and 0V to each half of the system.
s. All ELDS 1000 / 2000 Series units incorporate a power-up current limiting circuit. This
circuit ensures that even during power-up, the current drawn by a unit never exceeds
the maximum current that would be drawn by the unit when operating from the
minimum supply voltage (18V). See 3.3.5.
t. All ELDS 1000 / 2000 Series units incorporate a brown-out survival reservoir. Under
normal operating conditions this reservoir should be sufficient to enable the unit to
continue operating without being reset by a +24V power brown-out of up to 10mS
duration. The installation designer should therefore endeavour to ensure that any
battery back-up or similar system should detect a brown-out and restore the +24V
power rail within 5mS.
u. Whilst signalling readings using a 4-20mA current loop is considerably more robust
than signalling readings using a voltage (which will normally drop between the field
device and the control room) it is not completely immune to cable losses. Where long
cable runs are employed between the field device and the control room it is possible
for current to leak away through the insulation, reducing the current reaching the
control room and therefore the apparent gas reading. (This can be misinterpreted as
negative drift or warnings / faults being signalled.) Current leakage is not usually a
problem in high quality cables manufactured from durable, resistant materials, but it
can be a problem in lesser quality cables, especially after such cables have seen
several years of service. The installation designer is advised to ensure that all of the
insulation, protection and screening materials used in the construction of the cables
employed will resist the effects of chemical attack, corrosion, mechanical wear and
solar radiation that the cable is likely to experience over its anticipated service life.
(Bear in mind that if the outer insulation perishes, water will get through to any
armour and screening below, which will tend to corrode fairly rapidly. Once this has
happened, you have field conductors running in a solution of metallic corrosion
products surrounded by an earthed conductor. This arrangement is ideal for bleeding
current away from a 4-20mA loop, especially in wet conditions.)
v. Where a low noise instrument (clean) earth is employed, this instrument earth should
only be connected to safety earth (usually dirty) at a single point on the site /
26
Version 1.06 Iss 4 ECR111 Senscient ELDS™
INSTALLATION DESIGN & ENGINEERING
installation. The location and arrangement of this connection should be carefully
engineered to minimise the introduction of noise onto the instrument earth.
w. The terminal compartment of each ELDS 1000 / 2000 Series unit incorporates a
single cable entry on the underside of the unit. This arrangement minimizes the
potential for water ingress th rough the cable entry and should di scourage use of the
terminal compartment for purposes for which it is not well suited. If the installation
designer wishes to ‘daisy chain’ units or marshal the connections to several field
devices, a separate junction box should be employed.
x. For compliance with ATEX requirements, the Ex d (flameproof) terminal compartment
of ELDS 1000 / 2000 Series units can be entered by cables fitted with any suitable
equipment certified ATEX cable gland (not a component).
Note: For further details of installation requirements see ATEX Control Drawings in
Section 9.2
The Transmitter and Receiver units of the ELDS 1000 / 2000 Series OPGD both feature an
integral terminal compartment which is to be used for making all electrical connections to
the units. The terminal compartment is an explosionproof design, and in order to comply
with the applicable hazardous area protection standards, must be entered by a cable or
conduit fitted with a suitable explosionproof cable gland or conduit entry.
Prior to opening the terminal compartment it is recommended to slide forward the sunshade
and remove the M6 X 12 screw together with the anti-tamper device using an M6 Allen key
(supplied). Retain all components, and refit when installation is complete. Access to the
electrical connections inside the terminal compartment can then be gained by unscrewing
the threaded rear cover. A 12mm Allen key wrench (supplied) can be used to loosen the
rear cover.
27
Version 1.06 Iss 4 ECR111 Senscient ELDS™
INSTALLATION DESIGN & ENGINEERING
3.3.3 Receiver Electrical Connections
The terminal compartment of the Receiver of an ELDS 1000 / 2000 Series OPGD contains
a 12-way terminal block, by means of which most electrical connections to the unit can be
made. The terminal block is capable of accepting wires of up to 2.5mm
bootlace ferrules. The terminal numbers, connection labels and proper functions of the
connections available via the Receiver terminal block are detaile d in the table below:-
2
or compatible
Terminal
No.
1 +24V Positive connection to system power supply.
2 0V Negative or zero volt connection to system power supply.
3 LOCAL +24V Local connection to +24V to configure 4-20 (1) as source.
4 4-20 (1) SNK Sink + connection for 4-20 (1)
5 4-20 (1) SRC Source - connection for 4-20 (1)
6 LOCAL 0V Local connection to 0V to configure 4-20 (1) as sink.
7 LOCAL +24V Local connection to +24V to configure 4-20 (2) as source.
8 4-20 (2) SNK Sink + connection for 4-20 (2)
9 4-20 (2) SRC Source - connection for 4-20 (2)
10 LOCAL 0V Local connection to 0V to configure 4-20 (1) as sink.
11 RS485 (A) Connection to RS485 (A) Modbus output.
12 RS485 (B) Connection to RS485 (B) Modbus output.
Note: Conductors and insulation should be rated for operation at temperatures >= 85°C
Connection
Label
Function
28
Version 1.06 Iss 4 ECR111 Senscient ELDS™
INSTALLATION DESIGN & ENGINEERING
Wiring Diagram for ELDS 1000 Receiver with Isolated 4-20mA Output
29
Version 1.06 Iss 4 ECR111 Senscient ELDS™
INSTALLATION DESIGN & ENGINEERING
Wiring Diagram for ELDS 1000 Receiver with Current Source @ 4-20 (1)
30
Version 1.06 Iss 4 ECR111 Senscient ELDS™
INSTALLATION DESIGN & ENGINEERING
Wiring Diagram for ELDS 1000 Receiver with Current Sink @ 4-20 (1)
31
Version 1.06 Iss 4 ECR111 Senscient ELDS™
INSTALLATION DESIGN & ENGINEERING
Wiring Diagram for ELDS 2000 Receiver with Isolated 4-20 (1) & 4-20 (2)
32
Version 1.06 Iss 4 ECR111 Senscient ELDS™
INSTALLATION DESIGN & ENGINEERING
Wiring Diagram for ELDS 2000 Receiver with Current Sources @ 4-20 (1) & 4-20 (2)
33
Version 1.06 Iss 4 ECR111 Senscient ELDS™
INSTALLATION DESIGN & ENGINEERING
Wiring Diagram for ELDS 2000 Receiver with Current Sinks @ 4-20 (1) & 4-20 (2)
34
Version 1.06 Iss 4 ECR111 Senscient ELDS™
INSTALLATION DESIGN & ENGINEERING
3.3.4 Transmitter Electrical Connections
The terminal compartment of the Transmitter of an ELDS 1000 / 2000 Series OPGD
contains an 8-way terminal block, by means of which most electrical connections to the unit
can be made. The terminal block is capable of accepting wires of up to 2.5mm
compatible bootlace ferrules. The terminal numbers, connection labels and proper functions
of the connections available via the Transmitter terminal block are detailed in the table
below:-
2
or
Terminal
No.
1 +24V Positive connection to system power supply.
2 0V Negative or zero volt connection to system power supply.
3 LOCAL +24V Local connection to +24V to configure 4-20 (1) as source.
4 4-20 (1) SNK Sink + connection for 4-20 (1)
5 4-20 (1) SRC Source - connection for 4-20 (1)
6 LOCAL 0V Local connection to 0V to configure 4-20 (1) as sink.
7 RS485 (A) Connection to RS485 (A) Modbus output.
8 RS485 (B) Connection to RS485 (B) Modbus output.
Note: Conductors and insulation should be rated for operation at temperatures >= 85°C
Connection
Label
Function
35
Version 1.06 Iss 4 ECR111 Senscient ELDS™
INSTALLATION DESIGN & ENGINEERING
Wiring Diagram for ELDS 1000 / 2000 Series Transmitter
36
Version 1.06 Iss 4 ECR111 Senscient ELDS™
INSTALLATION DESIGN & ENGINEERING
3.3.5 Power Supply Connections & Wiring
The Senscient ELDS™ gas detector is designed to be operated from a nominal 24V DC
supply. For correct operation, the supply voltage reaching the terminals must be within the
range 18V to 32V.
The unit maximum power consumption and cable lengths are as follows:
Component Maximum Power
Consumption, W
Maximum Cable
Length, m with 1.5mm
Conductors (12Ω/km)
Maximum Cable Length,
2
m with 2.5mm
Conductors (7.6Ω/km)
2
Receiver 10W 450 710
Transmitter 12W 375 590
Note: Control room supply voltage assumed to be +24V.
2
Terminal sizes: Transmitter 0.5mm
Receiver 0.5mm
- 2.5mm2 (20AWG - 14AWG)
2
– 2.5mm2 (20AWG - 14AWG)
37
Version 1.06 Iss 4 ECR111 Senscient ELDS™
INSTALLATION & COMMISSIONING
4 INSTALLATION & COMMISSIONING
4.1 Unpacking an ELDS 1000 / 2000 Series System
Each ELDS 1000 / 2000 Series system is shipped inside custom-designed packaging
intended to provide substantial protection of the units during shipment and handling. Before
unpacking the two boxes that contain a complete ELDS OPGD system, inspect the
packaging for any external signs of damage.
1) Carefully unpack the equipment, observing any instructions that may be printed on or
contained within the packaging.
2) The first step is to remove the m ounting bra cket and small box con taining Al len keys
and documentation etc.
Note: The unit is constrained within the packaging by rotatable retaining parts as
illustrated below, simply rotate these in order to allow the Transmitter or Receiver
to be removed.
Rotate retainers prior to
attempting to remove unit
3) Check the contents for damage and against the packing note for deficiencies.
In the event of damage or loss in transit, notify the carrier and Senscient or your local
agent immediately.
4) Ensure that the installer/end user of the equipment receives the technical
documentation (operating instructions, manuals, etc.) contained in the packaging.
38
Version 1.06 Iss 4 ECR111 Senscient ELDS™
A
y
INSTALLATION & COMMISSIONING
NOTE: A complete shipment of an ELDS 1000 / 2000 Series OPGD system
consists of the following items.
1 x ELDS™ Transmitter Assembly
1 x ELDS™ Receiver
ssembl
`
39
Version 1.06 Iss 4 ECR111 Senscient ELDS™
INSTALLATION & COMMISSIONING
2 x Mounting Brackets
40
Version 1.06 Iss 4 ECR111 Senscient ELDS™
INSTALLATION & COMMISSIONING
4.2 Installation Procedure
4.1.1 General
The Senscient ELDS™ 1000 / 2000 Series OPGD is designed to allow installation and
alignment to be performed by a single, trained technician.
The installation procedure is split into mechanical installation and electrical installation.
Each unit needs to be mounted to a supporting structure before making the electrical
connections.
4.1.2 Mechanical Installation
The mechanical installation procedure applies to both the Receiver and the Transmitter.
1) Check that the gas detector equipment supplied is compatible with the required
application (i.e. correct gas and operating range for ap plication).
2) Ensure that the Hazardous Area Certification of the equipment supplied is correct for
the Hazardous Zone where the equipment is to be installed.
3) Check tha t the locations selected for siting the equipment are suitable - see Section
3.2
4) For each unit (Tx and Rx) fix the mounting bracket using one of the procedures
described in the following sections.
4.1.2.1 Wall Mounting
Schematic of Bracket Base-plate showing Slot Positions for Bolts / U Bolt Fixings
41
Version 1.06 Iss 4 ECR111 Senscient ELDS™
INSTALLATION & COMMISSIONING
Attach the mounting bracket to the wall or similar vertical surface using suitable fixing bolts
as illustrated below. The choice of fixing will depend on the nature of the surface and should
take regard of the weight of the unit (~13kg).
4.1.2.2 Pole Mounting
Attach the mounting bracket to the pole using suitable fixings. It is suggested that U bolts
are used as illustrated below; however other techniques may also be considered provided
the unit is securely attached to the pole and is prevented from slipping or rotating around
the pole.
42
Version 1.06 Iss 4 ECR111 Senscient ELDS™
INSTALLATION & COMMISSIONING
4.1.2.3 Mounting a Transmitter or Receiver
Mount a Transmitter or Receiver unit onto the bracket as illustrated below. The retaining nut
should be tightened to 45Nm (wrench tight) to ensure that the unit is secure.
43
Version 1.06 Iss 4 ECR111 Senscient ELDS™
INSTALLATION & COMMISSIONING
4.1.2.4 Mounting a Cross Duct Transmitter or Receiver
Attach the self-adhesive mounting templates to the duct wall in the position identified for
mounting of the Cross Duct ELDS system. Using the templates, drill and cut the necessary
mounting holes in the opposite sides of the duct.
NOTE: The most important requirement for successful installation of a Cross Duct
ELDS system is that the optical centre lines, as indicated by the cross-hairs on the
self-adhesive templates are opposite each other on the duct wall.
Cross Duct ELDS Mounting Template 01-01-1089-D
44
Version 1.06 Iss 4 ECR111 Senscient ELDS™
INSTALLATION & COMMISSIONING
Bolt Mounting Plates on each side of the duct.
Bolt a Transmitter or Receiver unit to the corresponding Mounting Plate.
45
Version 1.06 Iss 4 ECR111 Senscient ELDS™
INSTALLATION & COMMISSIONING
4.1.3 Electrical Installation
Perform electrical installation in accordance with the applicable Codes of Practice or
Guidelines for the installation of electrical apparatus in Hazardous Areas/Zones.
CAUTION: Before electrical installation ISOLATE or switch OFF all associated power
supplies and ensure that they remain ISOLATED or OFF during the electrical
installation.
The electrical installation process should include the following steps:
1) Removal of the red plastic bungs from the terminal compartment cable entry.
2) Feeding of field cabling or wires through the cable entry into the terminal compartment.
3) Screwing a suitable explosionproof M25 cable gland into the terminal compartment entry
and making this off.
4) Connecting the wires required for the field connections to the unit to the appropriate
terminals of the terminal block. (See Section 3.3)
5) Connecting the unit’s case to safety earth / ground (equipotential bonding) using one of
the internal or external earthing points provided.
6) Verification of correct connectivity back to the control room / gas detection monitoring
system.
Note: Detailed information and recommendations relating to the design and engineering of
the electrical installation of ELDS OPGDs is presented in Sections 3.3.1-3.3.5.
4.2 Alignment
In order to maximize operational reliability and availability, Senscient recommends that the
alignment and commissioning of ELDS™ 1000 / 2000 Series OPGDs should be performed
by personnel trained by Senscient or authorised trainers.
Alignment and commissioning of ELDS OPGDs can be performed by a single technician
using the alignment telescope and the Senscient Installation & Test Environment (SITE)
running on a laptop or iRoc PDA.
WARNING
Do not attempt to view the sun through the optical telescope.
4.2.1 Initial Pointing
The mounting bracket of ELDS OPGDs is designed to enable Transmitter and Receiver
units to be initially pointed in the direction of their counterpart without use of the alignment
telescope or the precision adjustment mechanisms. Loosening the M12 nut and M6 locking
screw on the adjustment block allows the unit hanging below to be quickly pointed in the
direction of its counterpart.
Once each unit is pointing in the direction of its counterpart, the M6 locking screw should be
tightened, followed by the M12 nut. Further adjustments will then only be possible by use of
the precision adjustment mechanisms.
46
Version 1.06 Iss 4 ECR111 Senscient ELDS™
INSTALLATION & COMMISSIONING
Adjustment Block
M12 Clamping Nut
M6 Locking Screw
47
Version 1.06 Iss 4 ECR111 Senscient ELDS™
INSTALLATION & COMMISSIONING
4.2.2 Final Alignment Using Telescope
Final alignment of ELDS OPGDs can be performed by a single technician using the
following equipment:-
1. Ideally, final alignment should be performed on a clear, dry day.
2. Get familiar with the workings of the adjustable parts of the mounting bracket before
proceeding with the alignment procedure, see section****.
3. To ensure precise field alignment, the alignment telescope makes use of the same
mounting datum that was used when the unit was aligned in the factory.
4. The telescope incorporates eye relief adjustment for comfortable viewing. The
eyepiece should be rotated to focus the image.
5. Keep the telescope and prism optics clean.
6. Do NOT try to adjust the cross-hairs using the telescope's elevation and windage
adjusters. These were precisely set in the factory and CANNOT be adjusted to this
precision in field conditions.
7. If the telescope is damaged or misaligned it will need to be returned to the factory for
repair and/or realignment.
4.2.2.1 Attaching the Alignment Telescope
The primary objective when attaching the alignment telescope to a unit to be aligned is to
get the alignment telescope’s datum sitting correctly on the unit’s alignment datum.
The alignment telescope’s datum is the flat, circular ring inside the three centration fingers
on the bottom of the alignment telescope mounting mechanism.
48
Version 1.06 Iss 4 ECR111 Senscient ELDS™
INSTALLATION & COMMISSIONING
The unit’s alignment datum is the flat, circular ring on the front of each unit’s telescope
mounting ring.
When the alignment telescope is correctly mounted, its datum is sitting flat against the unit’s
alignment datum.
The simplest procedure for correctly attaching the alignment telescope is as follows:-
1) Hold the alignment telescope in one hand, with the three centration fingers ready to
locate on the edge of the telescope mounting ring.
49
Version 1.06 Iss 4 ECR111 Senscient ELDS™
INSTALLATION & COMMISSIONING
2) With the centration fingers touching the edge of the telescope mounting ring, firmly push
the back surface of the gripping mechanism forwards towards the unit.
3) Push the back surface of the gripping mechanism forward until all three (3) gripping
fingers have clicked into the gripping recess on the telescope mounting ring.
50
Version 1.06 Iss 4 ECR111 Senscient ELDS™
INSTALLATION & COMMISSIONING
51
Version 1.06 Iss 4 ECR111 Senscient ELDS™
INSTALLATION & COMMISSIONING
4) When all three (3) gripping fingers have clipped into the gripping recess on the telescope
mounting ring, carefully release the alignment telescope, allowing it to be pulled against the
unit’s mounting datum by the gripping mechanism.
5) Double check that the alignment telescope is correctly mounted by checking that all three
(3) gripping fingers are clicked into the gripping recess and that the alignment telescope’s
mounting datum appears to be in contact with th e unit’s alignmen t datu m all the way aroun d
the mounting ring.
52
Version 1.06 Iss 4 ECR111 Senscient ELDS™
INSTALLATION & COMMISSIONING
6) Once the alignment telescope is correctly mounted on the unit’s alignment datum, gently
rotate the telescope such that the eye-piece is in a convenient position for vie wing.
7) With the eye-piece in a convenient position for viewing and the alignment datum’s in
contact, the alignment telescope is ready for use.
53
Version 1.06 Iss 4 ECR111 Senscient ELDS™
INSTALLATION & COMMISSIONING
4.2.2.2 Final Alignment Procedure
Final alignment of Transmitter or Receiver units can be performed using just the alignment
telescope and the precision adjustment mechanisms built into the mounting brackets.
The primary objective of the final alignment procedure is to align each unit such that the
crosshairs on the alignment telescope is in the centre of the lens-window of the opposing
unit as illustrated below:-
Notes:
1) Unlike NDIR OPGDs, Senscient ELDS 1000 / 2000 Series OPGDs are not critically
sensitive t o al i g nment.
2) A small improvement in alignment can be achieved by performing alignment adjustments
whilst monitoring the received signal levels using SITE running on a laptop or iRoc.
However, for ELDS 1000 / 2000 Series OPGDs these small improvements are not
important or necessary. ELDS OPGD systems aligned by the correct use of the
alignment telescope will perform to full specification with out further alignment tuning
Correct Final Alignment
54
Version 1.06 Iss 4 ECR111 Senscient ELDS™
INSTALLATION & COMMISSIONING
3) In order to use the alignment telescope correctly, it is necessary to view the image
produced by the telescope correctly. This requires the user to position one of their eyes
on the axis of the alignment telescope. When the eye is on axis, the user will see a
symmetrical, circular image f ield. See below:-
4) To see the full field-of-view of the alignment telescope, the user should position their eye
approximately 3 inches away from the eye-piece (See below). The alignment telescope
features an eye-relief adjustment which can be adjusted to make it easier for different
individuals to focus on the telescope’s image.
Eye on-axis
55
Version 1.06 Iss 4 ECR111 Senscient ELDS™
INSTALLATION & COMMISSIONING
5) If the user’s eye is not on the axis of the alignment telescope, an elliptical image field will
be seen, as below. For correct use of the alignment telescope, the user must keep their
eye on-axis, which will result in them seeing a sym metrical, circular image field.
Eye off-axis
56
Version 1.06 Iss 4 ECR111 Senscient ELDS™
INSTALLATION & COMMISSIONING
4.2.2.3 Making Alignment Adjustments
The Receiver and Transmitter units of ELDS OPGDs ar e mounted on brackets that allow
precision alignment adjustments in the horizontal and vertical directions.
Precise adjustments of horizontal and vertical alignment can be made using the opposed
pairs of M6 adjustment screws on the mounting bracket assembly. A pair of M6 Allen keys
is provided with each unit to enable the adjustment screws to be rotated.
Adjusting screws for
horizontal alignment
Adjusting screws for
vertical alignment
Tips:
1) Achieving a good alignment is best performed iteratively. Make alignment adjustments in
one axis to bring the cross-hairs nearer to the centre of the lens-window, and then make
some adjustments on the other axis. Expect to go back and forth between the horizontal
and vertical axes a few of times before achieving a good final alignment result.
Tips: continue on following pages.
57
Version 1.06 Iss 4 ECR111 Senscient ELDS™
INSTALLATION & COMMISSIONING
2) Initially, it is likely that the alignment will be quite a long way from ideal. When it is
necessary to make relatively large alignment adjustments it is best to ident ify which
direction needs to be moved in, and to loosen off the adjustment screw that would oppose
such a movement. This enables the aligner to drive the adjustm ent in the desired direction
without the resistance of the opposing adjustment screw.
58
Version 1.06 Iss 4 ECR111 Senscient ELDS™
INSTALLATION & COMMISSIONING
3) If the alignment is a long way from ideal, it might be difficult to see the opposing unit
through the alignment telescope. If this is the case, reduce the magnification of the
alignment telescope using the magnification adjustment, which will allow a larger field to be
seen. Once the opposing unit is more central, the magnification can be increased again to
enable the opposing unit to be seen more clearly.
CAUTION: Do NOT try to adjust the cross-hairs using the alignment telescope's
elevation and windage adjusters. These have been factory set.
Unauthorised adjustments of alignment telescopes will lead to systems
being incorrectly aligned. Return an alignment telescope to Senscient if
a problem with its alignment is suspected.
59
Version 1.06 Iss 4 ECR111 Senscient ELDS™
INSTALLATION & COMMISSIONING
4) When the aligner is getting close to achieving a good alignment, they should screw in
both pairs of adjustment screws such that the tips of these screws are in contact with their
points of action. Final, precision alignment adjustments should be made against the
resistance that arises from the screw tips being in contact with their points of action.
60
Version 1.06 Iss 4 ECR111 Senscient ELDS™
INSTALLATION & COMMISSIONING
6) When the aligner is happy that a good, final alignment has been achieved, the alignment
should be locked-off, by simultaneou sly rotating the opposed pair of adjustment screws in
the opposite direction against each other. Performed correctly, this locking-off step should
not affect the adjustment but should ensure that both adjustment screws are tight and that
there is no play in the alignment of the unit.
Correct Final Alignment
Locking-Off
61
Version 1.06 Iss 4 ECR111 Senscient ELDS™
INSTALLATION & COMMISSIONING
4.3 Cross Duct – Alignment Requirements
The Cross Duct ELDS system is designed to be installed and ‘aligned’ by simply mounting
each half of the system opposite its counterpart on the other side of the duct. Provided that
the duct walls where the Cross Duct ELDS system is installed are nominally parallel and the
walls are sufficiently rigid that they do not deform significantly when the Cross Duct ELDS
system is mounted upon them, no alignment is required.
In order to enable this simplified installation process, the Transmitter and Receiver units of a
Cross Duct ELDS system have a wide field-of-view (>= 6), enabling these units to
accommodate the out-of-parallel angular errors typically associated with duct walls. All that
is necessary is that the optical centre-lines of each half of the system should be opposite
each other to within 25mm when mounted on the duct wall. This modest requirement can
be met by employing normal constructional methods and tools such that the cross-hairs on
the Mounting Plate templates are positioned opposite each other when they are used to
guide the drilling and cutting of the required mounting holes.
4.4 Commissioning
The commissioning process can be performed by a single, trained technician using the
Senscient Installation and Test Environment (SITE) running on a laptop or an iRoc PDA.
The commissioning procedure requires that each receiver is ‘paired’ with the appropriate
transmitter unit. Calibration data for each unit is held within each transmitter unit and is
copied to the paired receiver as part of the installation process. For this reason it is
necessary to commission the transmitter unit before attempting to commission the
receiver for each system. If multiple systems are to be installed it is possible to install all
the transmitters prior to the receivers; alternatively each system (transmitter/receiver) can
be commissioned in turn.
The necessary steps to commission a system are as follows:-
62
Version 1.06 Iss 4 ECR111 Senscient ELDS™
INSTALLATION & COMMISSIONING
4.4.1 Configuring SITE - Adding Users
1) Start the SITE software, the initial screen will invite the user to log-in to the program as
the adminis trator.
2) The appropriate password is “S3nsci3nt” (Senscient with each “e” replaced by “3”, note
the case sensitivity also). Enter this password and then press the “OK” button, the main
SITE screen is then displayed. This contains a series of buttons as illustrated below.
63
Version 1.06 Iss 4 ECR111 Senscient ELDS™
INSTALLATION & COMMISSIONING
3) Select the “Admin” button, this generates the following dialogue screen
4) To add a new user, simply fill in the fields for Operator ID Number, Username and the
optional Password (leave this blank to allow access to SITE without password protection).
Once the appropriate details have been entered press the “Add Operator” button, the new
entry will then appear in the list of operators in the list-box as illustrated above.
5) Once the required entries have been made close the “adminform” dialogue box by using
the form close button
(top right).
4.4.2 Commissioning a System - Transmitter
1) Open the transmitter’s terminal compartment and connect the RS485 A & B leads from
the laptop to the corresponding terminals on the transmitter’s terminal block (Positions 7
RS485(A) - Purple lead and 8 RS485(B) - Black lead). Ensure that the transmitter is
powered before proceeding.
64
Version 1.06 Iss 4 ECR111 Senscient ELDS™
INSTALLATION & COMMISSIONING
Purple - A
2) Start the SITE software, a login screen will be presented, enter the appropriate user
name and password and press OK.
3) From the various button options available select “Commission Unit” as i llustrated.
Select this Button to
commence installation
Black - B
4) The first screen presented illustrates the connection of the computer to the transmitter
unit as described above, once the appropriate connections have been made and the unit is
65
Version 1.06 Iss 4 ECR111 Senscient ELDS™
INSTALLATION & COMMISSIONING
powered press the “Next” button, SITE will then present the following screen while it
interrogates the unit connected.
5) After a short delay SITE will report the type of unit found as illustrated below.
6) Press “Next” to proceed. The following screen is then presented.
66
Version 1.06 Iss 4 ECR111 Senscient ELDS™
INSTALLATION & COMMISSIONING
7) Senscient uses the unit serial number as the default Tag. If this is acceptable then select
“Leave Default”, otherwise select “Add Tag”. In this case the following dialogue is
presented; edit/change the displayed Tag as required then select “Next” to continue. Note
that either a real keyboard or the on-screen virtual keyboard may be used to change the
Tag data.
8) A confirmation that the new Tag has been saved will be presented, following this an
opportunity to check the operation of the 4-20mA output of the unit is offered.
67
Version 1.06 Iss 4 ECR111 Senscient ELDS™
INSTALLATION & COMMISSIONING
9) Select “Next” to proceed past this advisory screen.
10) For transmitter units there is no current requirement to check the operation of the 4-
20mA output (which is available for future feature expansion), so select “Skip” to proceed
past this option without undertaking any tests. The following screen is then displayed, tick
the option to confirm that the 4-20mA operation is confirmed and then press “Next” to
proceed.
68
Version 1.06 Iss 4 ECR111 Senscient ELDS™
INSTALLATION & COMMISSIONING
11) The opportunity to change/select the behaviour of the 4-20mA drive is then presented.
Again for transmitter units it is not necessary to consider any configuration of this so select
“Leave Defaults” to proceed.
12) SITE will then complete the commission ing of the unit and save various data relating to
the transmitter and the appropriate calibration for it, the following screen indicates the
successful commissioning of the transmitter.
69
Version 1.06 Iss 4 ECR111 Senscient ELDS™
INSTALLATION & COMMISSIONING
13) Select “Next”, the following screen is then presented.
14) Select “Next” to this screen to complete the process, SITE then returns to the main
selection screen.
Disconnect the RS485 A and B leads from the transmitter’s terminal block.
Carefully replace the terminal compartment lid and screw it down firmly.
Caution: Both the explosion proof protection and the ingress protection of the ELDS OPGD
system rely upon the terminal compartment lid being screwed down full y. The lid should be
tight and the o-ring compressed when the lid is properly screwed down.
Once the terminal compartment lid is properly screwed down, attach and lock-off the antitamper fixture.
70
Version 1.06 Iss 4 ECR111 Senscient ELDS™
INSTALLATION & COMMISSIONING
The transmitter installation is now completed.
4.4.3 Commissioning a System - Receiver
1) Open the receiver’s terminal compartment and connect the RS485 A & B leads from the
laptop to the corresponding terminals on the receiver’s terminal block (Positions 11
(RS485(A) - Purple & 12 (RS485(B) - Black). Ensure that the receiver is powered prior to
proceeding with SITE.
Purple - A
2) Enter SITE and the software will check for a connected unit. Screen as below:-
Black - B
71
Version 1.06 Iss 4 ECR111 Senscient ELDS™
INSTALLATION & COMMISSIONING
3) If the receiver unit is already powered up, it should be detected and the following screen
will appear. If the receiver unit is not correctly connected or not powered up, rectify the
problem and wait for the receiver to be detected.
Note: It can take up to 60 seconds from power up for a receiver unit to begin
communicating with SITE.
4) Having reached the above screen successfully, click on Next to continue the
commissioning process.
5) It is now necessary to select a transmitter unit to “pair” the receiver with. The following
screen is presented which allows the appropriate transmitter to be selected.
72
Version 1.06 Iss 4 ECR111 Senscient ELDS™
INSTALLATION & COMMISSIONING
6) SITE will normally select the last transmitter that was installed as the default option. If this
is not correct then select the appropriate unit from the drop-down list. Note that units are
identified by the Tag number so it is important that the installer is aware of the appropriate
Tag number that was entered on the unit which the receiver is to be paired with.
7) Once the appropriate unit is selected press “Next” to continue. SITE will then transfer the
calibration data for the selected transmitter to the receiver unit and confirms this with the
following screen.
8) SITE will display the screen below, requesting the operator to enter the range in metres
between the transmitter and receiver. This value will be used by SITE to confirm that the
signal reaching the receiver from the transmitter is as expec t ed.
9) The range can be adjusted by clicking on the up and down arrows to the right of the box
displaying the range. When the correct range has been set, click on Next.
73
Version 1.06 Iss 4 ECR111 Senscient ELDS™
INSTALLATION & COMMISSIONING
10) Assuming that the transmitter and receiver units have been satisfactorily aligned with
respect to each other and there is nothing obscuring the beam-path, SITE will display the
following screen, indicating that the signals are okay.
11) Move onto the next step in the commissioning process by clicking Next.
12) If SITE displays the following screen then the signals reaching the receiver from the
transmitter are lower than expected. This could either be due to poor alignment of the
transmitter or receiver, or due to obscuration of the beam-path.
74
Version 1.06 Iss 4 ECR111 Senscient ELDS™
INSTALLATION & COMMISSIONING
13) IF the Signal Low screen is displayed: Check that the lens-windows of both the
transmitter and receiver are clean, and that there is nothing obscuring the beam-path
between the transmitter.
14) If the check at 13) does not identify any problem, use the alignment telescope to doublecheck that there is nothing obscuring the beam-path.
15) Finally, using the alignment telescope, double-check the alignment of the transmitter
and receiver with respect to each other. (See Section 4.2 for Alignment instructions.)
16) If SITE displays the screen below then there is no signal reaching the receiver from the
transmitter. There could be a number of reasons for this:-
Beam Blocked – There is something in the beam-path which is completely blocking
the beam-path between the transmitter and the receiver.
No TX Power – The transmitter is not receiving the +24V (nominal) power supply
voltage that it requires to operate.
System Not Aligned – The transmitter or receiver have not been aligned with respect
to each other, or are so far from correct alignment that no signal is reaching or being
seen by the receiver.
TX Fault – There is a fault condition preventing the transmitter from producing the
expected output.
75
Version 1.06 Iss 4 ECR111 Senscient ELDS™
INSTALLATION & COMMISSIONING
17) In order to continue with the commissioning process, the cause of the ‘No Signal’
problem must be identified and corrected. Perform checks to establish which of the reasons
listed at 16) is causing the problem experienced and where possible correct this problem.
18) Once the SITE software displays the green ‘Signals OK’ screen you are ready to
proceed to the next step in the commissioning process.
19) Upon the successful completion of the signal levels test, SITE will move on to the
zeroing process.
20) If the system has not been zeroed before, SITE will display the following screen.
76
Version 1.06 Iss 4 ECR111 Senscient ELDS™
INSTALLATION & COMMISSIONING
21) Verify that there is no target gas in the system’s beam-path, and once this has been
verified click Next to zero the system.
Caution: Zeroing a system with target gas in the beam-path will result in a positive offset on
the unit’s zero position. This offset will introduce errors in the gas readings output by the
system and may give rise to the spurious diagnosis of Fault or Warning conditions. Only
zero a system when you are confident that there is either zero target gas or a negligibly
small quantity of target gas in the beam-path.
22) If the system has been zeroed before, SITE will display the following screen.
77
Version 1.06 Iss 4 ECR111 Senscient ELDS™
INSTALLATION & COMMISSIONING
23) If you do not want to re-zero the unit, click “Leave Zero Data” and then click Next to
move on.
24) If you elect to re-zero the unit then, the following screen will be displayed.
25) SITE will display the above screen throughout the zeroing process, which will normally
take around 30 seconds.
26) Subsequent to satisfactory completion of the zeroing process, SITE will display the
following screen.
78
Version 1.06 Iss 4 ECR111 Senscient ELDS™
INSTALLATION & COMMISSIONING
27) If you are happy that the zeroing process was performed satisfactorily, click Next to
save the zeros in the system.
28) If any of the events below occurred during the zeroing process, the zero might not be
correct. In order to ensure that a good zero is performed, click Previous to return SITE to
the zeroing s c r ee n:-
A release of target gas took place in or near the system.
An object or person moved into or through the beam-path.
A gas challenge cell or gassing cell was mistakenly inserted into the beam-path.
29) Once SITE has successfully saved the zero data on the system, the following screen
will be displayed.
79
Version 1.06 Iss 4 ECR111 Senscient ELDS™
INSTALLATION & COMMISSIONING
30) Click Next to move onto the next step in the commissioning process.
31) SITE will now ask you if you would like to enter a tag number for the unit. This is
recommended as it will give the unit a recognisable ID when subsequently communicating
with the unit using Bluetooth, or downloading event history logs. The tag number should
ideally correspond to the position / location of the unit on the site or within the safety system
to which it is connected.
32) Select “Add Tag” if you want to enter a tag number and SITE will display the tag number
entry screen.
80
Version 1.06 Iss 4 ECR111 Senscient ELDS™
INSTALLATION & COMMISSIONING
33) Select “Leave Default” if you do not want to enter a tag number. In this case the
Senscient serial number of the unit will be left as the default tag number, then click Next to
move on to the next step in the commissioning process.
34) Using either the touchscreen keyboard displayed by SITE below or a real keyboard,
enter the tag number for the unit.
35) When you are happy with the tag number, click Next and this will be stored inside the
unit.
36) SITE will now display the following screen, recommending that the 4-20mA output and
loop be checked.
81
Version 1.06 Iss 4 ECR111 Senscient ELDS™
INSTALLATION & COMMISSIONING
37) When you are ready to check the 4-20mA output and loop, click Next.
38) SITE will now give you the opti on o f per fo rming 4-2 0 mA lo op tests wi th a fo rced 4-20 mA
output.
39) If you want to force a specific test current out on the 4-20mA output to test the loop and
/ or the control system’s response, click “Force 4-20mA”.
40) If you do not want to force a specific current out on the 4-20mA output, click “Skip”, in
this case the output current for loop testing will be 4mA.
82
Version 1.06 Iss 4 ECR111 Senscient ELDS™
INSTALLATION & COMMISSIONING
41) If SITE is displaying the screen below, use the up and down arrows to the side of the
current setting box to set the current to be output by the receiver unit and when you are
happy with the value click the Set 4-20mA button followed by Next.
42) With the receiver attempting to output the 4-20mA check current on the 4-20mA loop,
check that the current flowing through the loop is as expected. This can either be done
using a multimeter inserted into the loop or by checking the current or gas reading being
displayed for this loop by the control system. Note that both circuits (for a dual gas receiver)
will be generating the selected current and both should be checked.
43) Once the operation of the outputs has been tested select “Next” to proceed.
83
Version 1.06 Iss 4 ECR111 Senscient ELDS™
INSTALLATION & COMMISSIONING
44) SITE wants to make sure that you have checked the 4-20mA output and lo op before it
allows the system to be fully commissioned. To this end, SITE requires you to click the
check box next to the 4-20mA Circuits Checked statement - before you can proceed any
further. Only click the check box if you have successfully checked the 4-20mA output and
loop.
45) SITE next displays the screen illustrated below to allow the behaviour of the 4-20mA
loops to be configured.
84
Version 1.06 Iss 4 ECR111 Senscient ELDS™
INSTALLATION & COMMISSIONING
46) The behaviours that can be configured are Inhibit current, Fault current, Beam Block
current, the Time between detecting a beam blocked state and raising the associated
warning, the Time between loosing optical signal and detecting/declaring a beam blocked
state, the Low Signal state current, the Time between detecting low signal and entering the
low signal state and the over-range current. Each of these parameters has default values
associated and screens are presented in turn to allow the defaults to be adjusted as
required. At the end of this process a summary screen is presented as follo ws:
47) Note that in this example all the values are left at the factory defaults. Note that the
“Beam Block to Fault” time is -1 hours by default, this value disables this feature (i.e. BeamBlock does not generate a Fault condition and is just signalled as a warning.).
48) Once the correct parameters are established press “Save Config” to update the unit, if
any values remain incorrect the select “Change Config” to allow further changes to be
made.
49) Following “Save Config” a confirmation screen is presented declaring that the values are
updated
85
Version 1.06 Iss 4 ECR111 Senscient ELDS™
INSTALLATION & COMMISSIONING
50) Select “Next” to proceed.
51) SITE will then write a commissioning log, this takes a few seconds to implement and
completes with the following screen
52) Select “Next” to proceed, the following screen is then displayed.
86
Version 1.06 Iss 4 ECR111 Senscient ELDS™
INSTALLATION & COMMISSIONING
53) Disconnect the RS485 A and B leads from the receiver’s terminal block.
54) Carefully replace the terminal compartment lid and screw it down firmly.
Caution: Both the explosionproof protection and the ingress protection of the ELDS OPGD
system rely upon the terminal compartment lid being screwed down full y. The lid should be
tight and the o-ring compressed when the lid is properly screwed down.
55) Once the terminal compartment lid is properly screwed down, attach and lock-off the
anti-tamper fixture.
87
Version 1.06 Iss 4 ECR111 Senscient ELDS™
INSTALLATION & COMMISSIONING
4.5 Installation Checklist
The following information is for the guidance of personnel carrying out installation checks /
tests on Senscient ELDS™ OPGDs. In general it should be noted that:
Installation of ELDS™ 1000 / 2000 Series OPGDs should be performed by personnel
trained by Senscient or authorised trainers.
Detailed information concerning installation, alignment and commissioning is provided in
this Instruction Manual.
Senscient ELDS™ is explosion protected by a certified, explosionproof enclosure. Carefully
read the safety warnings, cautions and certification details in this manual. Ensure that they
have been complied with, before and during the installation.
The following is a check list with notes to assist the installer:-
Site/Facility
Check that the unit is being installed at the correct site / facility, e.g.
Hibernia Platform, North Atlantic
Is this the correct site / facility?
Operating Range
Check the di stance (preferably in metres), between the Transmitter and the Re ceiver.
Is the unit being installed suitable for this operating range?
Detector Location
Check the location / position of the unit, e.g.
West Walkway, Compressor Skid
Is this the correct location / position for the unit?
Tag No
Check the Tag No, or equivalent, that has been allocated to the ELDS™ Receiver and
Transmitter units. Do the Tag No.’s and details for the units all tie up?
Mod State
Check the Mod State of the units as indicated on their certification labels.
Certification
Check the ce rtification of the units, e.g.
Is the Hazardous Area Certification of the unit correct for the Hazardous Area/Zone where it
is being installed?
Mount Rigidity
Check that the units have been mounted securely to the supporting structure. Check that
the supporting structure is sufficiently rigid to maintain alignment in the anticipated operating
conditions. A maximum angular movement of 1º is allowable.
Baseefa ATEX (Europe),
88
Version 1.06 Iss 4 ECR111 Senscient ELDS™
INSTALLATION & COMMISSIONING
As an approximate guideline, a sufficiently rigid mount/supporting structure will only move a
few millimetres (not more than 6mm) when leaning body weight against it.
When pushed hard and released, the mount/supporting structure should return quickly to its
original position and should not wobble or sway. If the mount/ support is unacceptable, take
steps to have the mount / supporting structure improved.
Vibration
Check the installation and its close surrounds for potential or existing sources of excessive
vibration. Such sources could include heavy plant/machinery, turbines, generators etc.
If there is the possibility that such vibration sources could be or already are causing
unacceptable movement, investigate how the effects of this vibration can be mitigated.
Excess Heat
Check the installation and its surrounds for potential sources of excessive heat. The unit is
specified for ambients up to +60°C. Potential sources of excessive heat include flare-stacks,
generator/turbine exhausts and steam vents. If there is the possibility that such heat
sources are causing unacceptable temperatures to be reached, investigate how the effects
of these sources can be reduced.
Supply Voltage
Check that the supply voltage applied to the unit is within the specified 18V to 32V range
and is stable.
Earthing
Inspect the earth / ground connections to the units.
RFI/EMC
Assess the installation, cabling and its close surrounds for known or potential sources of
excessive RFI/Electromagnetic Interference. Such sources could include radio/radar
transmission antennae, high voltage switch-gear, large electrical generators/motors etc.
Contaminants
Assess the installation and its surrounds for sources of contaminants that could build up on
the unit’s windows. Such contaminants could include oil mist, heavy sea spray, drilling mud,
dirty exhaust fumes, wave splash etc.
If there is a realistic possibility that such contaminants could eventually completely obscure
the optics, consider how the rate of build-up could be reduced or whether scheduled
cleaning might be required.
Beam Obstruction/Blocks
Ideally, a clear path of at least 20cm diameter should be provided between the Transmitter
and the Receiver. Assess the installation and the beam path for potential sources of beam
blockage. These could include personnel walking in the beam, parking vehicles, moving
machinery/plant, growing vegetation etc.
Functional Test
After completing the installation procedure, perform a functional test upon the unit either
using a gas challenge cell, a gassing cell or SimuGas.
89
Version 1.06 Iss 4 ECR111 Senscient ELDS™
INSTALLATION & COMMISSIONING
4 - 20mA Loop Integrity
Test the 4 - 20mA loop integrity by forcing the unit to output a known current and monitoring
this at the control room or with a multimeter inserted into the loop. Update the appropriate
box.
Fault/Warning Log
Check the Fault / Warning Log. In order for the unit to complete installation satisfactorily, the
ACTIVE FAULTS log must be CLEAR. Use SITE running on a laptop or iRoc interrogator to
diagnose and remedy all ACTIVE FAULT conditions.
Wherever possible, it is recommended to CLEAR any ACTIVE WARNINGS, since these
may lead to faults in the future.
90
Version 1.06 Iss 4 ECR111 Senscient ELDS™
FUNCTIONAL TESTING
5 FUNCTIONAL TESTING
5.1 Introduction
Senscient’s ELDS 1000 / 2000 Series OPGDs feature the most advanced gas detector
functional testing technology currently available, enabling the correct function of OPGDs to
be tested with far greater ease and frequency than has previously been possible. The key
functional testing technology incorporated in Senscient’s ELDS OPGDs is called
SimuGas
beam-path.
The flexibility afforded by SimuGas
testing of ELDS OPGDs in a number of different ways, including SimuGas Auto, SimuGas
Inhibited and SimuGas Live, which approaches are described in the following sections.
In addition to the use of SimuGas, it is also possible to test the function of ELDS OPGDs
using methodologies that physically introduce target gas into the monitored beam-path. For
these purposes, Senscient provides a Gassing Cell that can be used in conjunction with
ELDS OPGDs.
TM
and is an on-command, electronic simulation of a quantity of target gas in the
TM
technology makes it possible to perform functional
5.2 SimuGasTM Explained
5.2.1 Harmonic FingerprintsTM
In an ELDS Transmitter the drive current applied to the laser diode(s) comprises two
components, a DC bias co mponent which sets the mean operating wavelength of the laser
diode(s), and a pure sinusoidal component which modulates the wavelength of the laser
diode(s). Continuous registration of the wavelength(s) of the Transmitter’s laser diode(s) is
achieved by passing a small fraction of the laser diode output(s) through a retained sample
of target gas(es) inside the Transmitter, and measuring the resulting signals from a
reference detector (See below).
Transmitter: Gas Reference Channel
91
Version 1.06 Iss 4 ECR111 Senscient ELDS™
FUNCTIONAL TESTING
Using the signal reaching the reference detector through the retained gas sample, the
transmitter’s microcontroller is capable of determining the precise bias and wavelength
modulation components that need to be applied to the laser diode(s) in order to ensure that
absorption of the laser diode’s optical radiation by target gas always produces a Harmonic
FingerprintTM.
A Harmonic Fingerprint
absorption, in which the relative amplitudes and phases of the components are known and
specific to the target gas absorption line that is being scanned by the ELDS Transmitter.
When the laser diode drive conditions in an ELDS transmitter are maintained such that
target gas absorption always produces a Harmonic Fingerprint, the transmitter is said to be
maintaining Harmonic Fingerprint Lock.
TM
is a set of harmonic components introduced by target gas
Harmonic Fingerprint for a H
Under conditions of Harmonic Fingerprint Lock, the size of any Harmonic Fingerprint
measured is proportional to the amount of target gas in the beam-path. In an ELDS OPGD
system, the Receiver detects and measures the size of any Harmonic Fingerprints in the
signal reaching it from the Transmitter, and uses this to determine the quantity of target gas
in the monitored beam-path.
As described in Section 5.2.1, the transmitter in an ELDS-based OPGD is continuously
using the signal from its reference detector channel to maintain Harmonic Fingerprint Lock.
The transmitter’s microprocessor controls the electronic synthesis of the drive waveforms
that are applied to the laser diode(s) such that the laser diode(s) remain precisely locked to
the chosen target gas absorption line(s), and by so doing ensures that the sizes of each
Harmonic Fingerprint component produced by target gas absorpti on are precisely known.
Because the transmitter in an ELDS OPGD is electronically synthesising the drive
waveforms that are applied to its laser diode(s) and knows the sizes of the Harmonic
Fingerprint components produced by target gas, it is possible for a transmitter to
electronically synthesise laser diode drive waveforms which include Harmonic Fingerprint
components corresponding to a quantity of target gas.
When the laser diodes in an ELDS transmitter are driven by waveforms including Harmonic
Fingerprint components corresponding to a quantity of target gas, their optical outputs
include the Harmonic Fingerprint components - just as if they had been introduced by
genuine optical absorption by the target gas.
This means that an ELDS transmitter can electronically simulate the presence of a
quantity of target gas in the monitored beam-path. Senscient refers to this type of
electronically simulated gas as SimuGas
When the receiver of an ELDS OPGD receives signals from the transmitter which include
SimuGas
TM
components, it cannot tell the difference between electronically synthesised
Harmonic Fingerprint components and those produced by genuine absorption by target gas.
Consequently, the receiver processes the received signal and calculates the amount of
target gas believed to be present in the beam-path - based upon the sizes of the Harmonic
Fingerprint components.
Comparing the gas quantity calculated by the receiver to the quantity of SimuGas simulated
by the transmitter provides a powerful means of verifying the correct function of an ELDS
OPGD. Because of the flexibility afforded by the SimuGas
perform functional testing of ELDS OPGDs in a number of different ways. The different
functional test methodologies made possible by the use of SimuGas
Auto, SimuGas Inhibited and SimuGas Live, and are described in the following sections.
SimuGas
TM
OPGD functionality testing offers considerable advantages over conventional
OPGD testing methodologies, including the following:-
There is no need for operators to generate, handle or apply hazardous gases to
detectors in the field.
There is no need for operators to gain direct physical access to detectors in order
to test them. Commands to perform SimuGas tests can be sent remotely from
wherever it is convenient, and the results of tests ca n be monitored remotely too.
Because SimuGas is simple, quick and convenient it makes it possible to
functionally test gas detectors much more frequently, improving the safety
integrity of a fixed gas detection system.
If desired, the functional testing of gas detectors can be completely automated
(SimuGas Auto).
The operation and maintenance costs for a fixed gas detection system are
considerably reduced.
TM
.
93
TM
technology it is possible to
TM
include SimuGas
Version 1.06 Iss 4 ECR111 Senscient ELDS™
FUNCTIONAL TESTING
5.3 SimuGas
The simplest way for users to realise the considerable safety integrity benefits provided by
SimuGas
configured, the transmitter will perform a SimuGas test with a known level every 24 hours;
whilst the receiver will check that each test produces acceptable results. In the event that a
SimuGas Auto test does not produce acceptable results, the receiver is configured to signal
a Warning or Fault to the control system, providing an early warning about a potential
problem with the ELDS OPGD affected.
Compared to conventional OPGD testing methodologies or operator-initiated SimuGas
tests, SimuGas Auto has the following advantages:-
When configured for SimuGas Auto, an ELDS OPGD system performs the following
actions:-
TM
technology is to configure ELDS OPGDs to perform SimuGas Auto. When so
Testing is performed without the gas detector being visited by operators.
Testing is performed every 24 hours, providing far earlier diagnosis of any problem
than tests relying upon operators visiting gas detectors.
Requires no additional cabling, software or control system infrastructure. SimuGas
Auto can be employed successfully using the same wiring and control systems that
were used with earlier generations of gas detectors.
1) Every 24hours, at a user-set time the transmitter commences the procedure for a
SimuGas Auto test.
TM
Auto
2) The transmitter warns the receiver that it is about to perform a SimuGas Auto test.
3) The receiver freezes the gas reading signalled on its 4-20mA output(s) at the
value(s) immediately preceding the SimuGas Auto test.
4) The transmitter drives it laser diode(s) such that its output includes a pre-defined
quantity of SimuGas, and holds this SimuGas level for 30 seconds duration.
5) The receiver measures the size of the Harmonic Fingerprint components introduced
by the SimuGas test and calculates the quantity of gas that this corresponds to.
6) At the end of the SimuGas test, the receiver un-freezes its 4-20mA output(s),
enabling a return to the live signalling of the quantity of gas in the monitored beampath.
7) The receiver compares the quantity of gas calculated to be in the monitored beampath during the recent SimuGas test with the quantity of gas known to be simulated
during SimuGas Auto tests.
8) The receiver assesses whether the results of the SimuGas Auto test were
satisfactory, and if satisfactory continues operating as normal.
9) If the results of the SimuGas Auto test were not satisfactory, the receiver updates its
status and outputs the configured Fault or Warning signal on its 4-20mA output(s)
94
Version 1.06 Iss 4 ECR111 Senscient ELDS™
FUNCTIONAL TESTING
5.4 SimuGasTM Inhibited
A SimuGas Inhibited test enables a Simu-Gas functional test to be performed without the
receiver signalling a gas reading on its 4-20mA output(s). The purpose of the receiver not
signalling the gas reading during this test is to avoid unwanted initiation of executive actions
by the safety system, such as shut-downs or audible alarms.
A SimuGas Inhibited test can be commanded by using SITE software on a laptop or iRoc
handheld that is in communication with a transmitter. Following receipt of a valid SimuGas
Inhibited command and an acceptable gas level, the transmitter will calculate the laser drive
waveforms necessary to simulate the instructed gas level, and drive its laser diodes with
these waveforms for 30 seconds, subsequently returning to the ‘gas-free’ drive waveforms.
During the SimuGas Inhibited test the receiver will calculate the gas level present in the
monitored path as normal, and will remember these levels. Immediately following the test,
the receiver will calculate the average gas level present during the last 20 seconds of the
test and store this reading for later retrieval and assessment using SITE software on a
laptop or iRoc handheld communicating with the receiver.
The results of a SimuGas Inhibited test may be determined by comparison of the gas
reading(s) stored in the receiver with the gas level(s) that the transmitter was instructed to
simulate during the test. Assuming that there were no target gases present in the beampath during the SimuGas Inhibited test, the reading stored by the receiver should be within
+/-10%FSD of the level that the transmitter was instructed to simulate.
Example
For a 0-1LEL.m CH4 system, simulating 0.5LEL.m, the reading stored by the receiver
should be:-
0.5LEL.m +/- 0.1LEL.m
Or between
0.4LEL.m & 0.6LEL.m
Note:
1) In the event that a SimuGas Inhibited test is performed whilst there is real target gas in
the beam-path, the amount of gas seen by the receiver will be the combination of the
SimuGas level and the real gas level. Since real gas levels tend to fluctuate rapidly, this
could cause problems correctly interpreting the results of a SimuGas Inhibited test.
2) Due to the problem noted at 1) it is preferable to perform SimuGas tests when there is no
real gas in the monitored beam-path. This can be established by checking the gas readings
from the receiver before performing a SimuGas test. If the gas readings are stable at zero,
SimuGas testing results will be simpler to interpret.
95
Version 1.06 Iss 4 ECR111 Senscient ELDS™
FUNCTIONAL TESTING
5.5 SimuGasTM Live
A SimuGas Live test enables a Simu-Gas functional test to be performed with the receiver
signalling the quantities of gas calculated present in the monitored beam-path on its 4-20mA
output(s).
Caution: Unless the purpose of a SimuGas Live test is to confirm correct initiation of
executive actions by the connected safety system, before performing SimuGas Live tests
the user will have to take steps to ensure that live gas readings being signalled on the 420mA output(s) of ELDS OPGDs are inhibited further up in the system.
A SimuGas Live test can be commanded by using SITE software on a laptop or iRoc
handheld that is in communication with a transmitter. Following receipt of a valid SimuGas
Live command and an acceptable gas level, the transmitter will calculate the laser drive
waveforms necessary to simulate the instructed gas level, and drive its laser diodes with
these waveforms for 30 seconds, subsequently returning to the ‘gas-free’ drive waveforms.
During the SimuGas Live test the receiver will calculate the gas level(s) present in the
monitored beam-path as normal, and signal these over its 4-20mA outputs .
The results of a SimuGas Inhibited test may be determined by comparison of the gas
reading(s) signalled by the receiver during the test with the gas level(s) that the transmitter
was instructed to simulate. Assuming that there were no target gases present in the beampath during the SimuGas Live test, the reading stored by the receiver should be within +/10%FSD of the level that the transmitter was instructed to simulate.
Example
For a 0-1LEL.m CH4 system, simulating 0.5LEL.m, the reading stored by the receiver
should be:-
0.5LEL.m +/- 0.1LEL.m
Or between
0.4LEL.m & 0.6LEL.m
Note:
1) In the event that a SimuGas Live test is performed whilst there is real target gas in the
beam-path, the amount of gas seen by the receiver will be the combination of the SimuGas
level and the real gas level. Since real gas levels tend to fluctuate rapidly, this could cause
problems correctly interpreting the results of a SimuGas Live test.
2) Due to the problem noted at 1) it is preferable to perform SimuGas tests when there is no
real gas in the monitored beam-path. This can be established by checking the gas readings
from the receiver before performing a SimuGas test. If the gas readings are stable at zero,
SimuGas testing results will be simpler to interpret.
96
Version 1.06 Iss 4 ECR111 Senscient ELDS™
FUNCTIONAL TESTING
5.6 Testing with the Gassing Cell
Senscient’s ELDS OPGDs are supplied factory calibrated and cannot be re-calibrated in the
field because experience has shown that accurate OPGD calibration can only be achieved
in a controlled factory environment. Where customers must undertake calibration checks,
these can be performed using the Gassing Cell, but users are advised that such checks are
far more likely to be in error than the original factory calibration.
Caution: The use of conventional gas cells employing glass windows will lead to
erroneous results with Senscient ELDS™ products because of optical
interference fringes generated by cell windows. ONLY the Senscient
Gassing Cell should be used with ELDS OPGDs.
The Gassing Cell is designed to allow easy response checking using high concentration test
gases. The cell is suitable for both high level (LEL) response ranges such as CH
1LEL.m units or for lower concentration ranges applicable to toxic gases such as H
2
S.
0 -
4
The gassing cell is designed to fit to the front of a ELDS™ transmitter or receiver unit. It
may be helpful to move the sun shield to the furthest back position to allow better access to
the clamping bolts on the cell when fitting the part.
97
Version 1.06 Iss 4 ECR111 Senscient ELDS™
FUNCTIONAL TESTING
The integrated LEL.m concentration in the cell can be calculated using the following
formula:
Int(lel.m)
ELDS = Lcell * (Concv/v / LELv/v)
where:
Int(lel.m)
cell = Length of cell in metres (0.236 for the Senscient Cali bration Cell),
L
Conc
LEL
ELDS = Integrated LEL.m reading output by Senscient ELDS™,
v/v = Gas concentration in %v/v and
v/v = Lower Explosion Limit of the gas in %v/v.
The integrated ppm.m concentration in the cell can be calculated from the following formula:
Int(ppm.m)
ELDS = Lcell * Concppm
where:
Int(ppm.m)
ppm = Gas concentration in ppm by volume.
Conc
ELDS = Integrated ppm.m reading output by Senscient ELDS™,
The test gas concentration must be selected to generate a reading from the unit that is
between 0.5× and 1× full scale.
98
Version 1.06 Iss 4 ECR111 Senscient ELDS™
FUNCTIONAL TESTING
WARNING
Take the necessary precautions to ensure safety when dealing with flammable or toxic
gases
The Gassing Cell utilises thin film windows which are relatively fragile. Avoid touching these
during use and also ensure that no over-pressure is applied to the cell during the filling
process to prevent damage to the windows
To get the very best accuracy when using the gassing cell:
1) Mount the empty Gassing Cell on the ELDS™ OPGD receiver unit.
2) Zero the ELDS™ OPGD with the empty Gassing Cell in place.
3) Apply the test gas to the Gassing Cell and allow sufficient time to fully flush the cell
through, without pressurising it and check that the reading output by the ELDS™
OPGD has completely stabilised.
Note: A maximum flow-rate of 1 litre/min is recommended for the Gassing Cell. The cell
must be purged for at least 5 minutes at this flow-rate to ensure the correct
burden will be presented to the unit
4) Check the ELDS™ OPGD output is as expected.
5) Remove the Gassing Cell.
6) Re-zero the ELDS™ OPGD.
Note:In common with all optical gas sensors the ELDS™ OPGD respond s to the total
quantity of gas in the beam. When attempting to check calibration accuracy using
a Gassing Cell the quantity of gas in the beam will be affected by atmospheric
pressure and ambient temperature. Suitable allowance for these factors must be
made when assessing the response of the system. Errors of the order of +/-5% of
reading should be expecte d; whilst errors as la rge as +/-10% of readin g can and
will occur at times.
99
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.