Senci SC2500 II, SC4000 II, SC3500 II, SC3250 II, SC6000 II Operator's Manual

...
Generator Operator’s
Manual
Official importer for:
Introduction..........................................1
Section 1 Safety Rules.......................1
Standards Index...........................................1
Section 2 General Information..........4
2.1 Unpacking...................................................4
2.2 Assembly.....................................................4
Section 3 Features and Controls........5
Section 4 Preparation
Before Operation................6
4.1 Adding Engine Oil.........................................6
4.2 Adding Fuel.................................................6
4.3 Grounding The Generator.............................6
Section 6 Maintenance....................10
6.1 Maintenance Schedule................................10
6.2 General Recommendations..........................10
6.2.1 Generator Maintenance...........................10
6.2.2 To Clean The Generator...........................10
6.2.3 Engine Maintenance................................10
6.2.4 Changing The Oil....................................11
6.2.5 Replacing The Spark Plug........................11
6.2.6 Spark Arrestor.........................................11
6.3 Service Air Filter..............................................11
6.4 Valve Clearance..............................................12
6.5 General..........................................................12
6.6 Other Storage Tips..........................................12
Section 7 Storage...........................12
Section 5 Operation..........................7
5.1 Starting The Engine......................................7
5.2 Connecting Electrical Loads...........................9
5.3 Stopping The Engine....................................9
5.4 Low Oil Level Shutdown System....................9
5.5 High Altitude...............................................9
Section 8 Parameter........................13
Section 9
Warranty
.........................14
1
INTRODUCTION
DANGER indicates-a-hazard which, if not
avoided, will result in death or serious injury.
Thank you for purchasing products from Senci. We appreciate your business. Our generator is driven by a compact air-cooled engine with high performance, which can supply electrical power to operate power tools on job sites, or to run home appliances during outage; or provide power to remote locations where utility power is unavailable.
This manual contains safety information to make you aware of hazards and risks associated with generator products and how to avoid them. It is important that you read and understand these instructions thoroughly before attempting to start or operate this equipment. Save this original instruction for future reference.
If any portion of this manual is not understood, please contact the nearest authorized dealer for starting, operating and servicing procedures. We also strongly recommend you to instruct any other users who may operate the generator in an emergency needed.
Every effort has been made to ensure that information in this manual is both accurate and current. However Senci Group reserves all rights to change, alter, or otherwise to improve the generator and this documentation at any time without prior notice.
WARNING indicates a hazard which, if not
avoided, could result in death or serious injury.
CAUTION indicates a hazard which, if not
avoided, could result in minor or moderate injury.
NOTICE covers some practices which may
be not related to personal injury. Safety Symbols and Meanings
Toxic Fumes Kickback Electrical Shock
Fire Explosion Operators Manual
Moving Parts Flying Objects Hot Surface
W
ARNING
A running engine gives off carbon
SECTION 1 ­SA
FETY RULES
Read this manual carefully and become familiar with your generator. Know its applications, its limitations and any hazards involved.
Throughout this brochure, on tags and decals affixed to the generator, DANGER, WARNING, CAUTION and NOTICE marks are used to alert personnel with special instructions about a particular operation that may be hazardous if performed incorrectly, or carelessly. Observe them carefully. Their definitions are as follows:
monoxide, an odorless, colorless, poison gas. Breathing carbon
monoxide could result in death, serious injury, headache, fatigue, dizziness, vomiting, confusion, seizures, nausea or fainting.
• Operate this product ONLY outdoors.
Install a battery operated carbon monoxide
alarm near the bedrooms.
• Keep exhaust gas away from entering a confined
area through windows, doors, ventilation intakes, or other openings.
• NEVER operate this product inside any
building, carport, porch, mobile equipment, marine applications, or enclosure, even if windows and doors are open.
2
WARNING Starter cord kickback (rapid
retraction) will pull hand and arm toward engine faster than you can let
go which could cause broken bones, fractures, bruises, or sprains resulting in serious injury.
When starting engine, pull cord slowly until resistance is felt and then pull rapidly to avoid kickback.
NEVER start or stop engine with electrical devices plugged in and turned on.
WARNING Fuel and its vapors are
extremely flammable and explosive which could cause
burns, fire or explosion resulting in death, serious injury and/or property damage.
WHEN ADDING OR DRAINING FUEL
Turn generator engine OFF and let it cool
at
least
2 minutes before removing fuel cap. Loosen
cap slowly to relieve pressure in tank.
Fill or drain fuel tank outdoors.
DO NOT overfill tank, Allow space for fuel
expansion.
If fuel spills, wait until it evaporates before starting engine.
Keep fuel away from sparks, open flames, pilot light, heat, and other ignition sources.
Check fuel lines, tank, cap and fittings frequently for cracks or leaks. Replace if necessary.
DO NOT light a cigarette or smoke.
WHEN STARTING EQUIPMENT
Ensure spark plug, muffler, fuel cap, and air cleaner are in place.
DO NOT crank engine with spark plug removed.
WHEN OPERATING EQUIPMENT
DO NOT operate this product inside any building, carport, porch, mobile equipment, marine applications, or enclosure.
DO NOT tip engine or equipment at angle which cause fuel to spill.
DO NOT stop engine by moving choke control to “OFF” position.
WHEN TRANSPORTING, OR REPAIRING EQUIPMENT
Transport/move/repair with fuel tank EMPTY or with fuel valve OFF.
DO NOT tip engine or equipment at angle which cause fuel to spill.
Disconnect spark plug wire.
WHEN STORING FUEL OR EQUIPMENT WITH FUEL IN TANK
Store away from furnaces, stoves, water heaters, clothes dryers, or other appliances that have light or other ignition source because they could ignite fuel vapors.
WARNING Generator voltage could cause
electrical shock or burn resulting in death or serious injury.
Use approved transfer equipment to prevent back feed by isolating generator from electric utility workers.
When using generator for backup power, notify utility company.
Use a ground fault circuit interrupter in any damp or highly conductive area, such as metal decking or steel work.
DO NOT touch bare wires or receptacles.
DO NOT use generator with electrical cords
which are worn, frayed, bare or otherwise damaged.
DO NOT operate generator in the rain or wet weather.
DO NOT handle generator or electrical cords while standing in water, while barefoot, or while hands or feet are wet.
DO NOT allow unqualified persons or children to operate or service generator.
WARNING Exhaust heat/gases could ignite
combustibles, structures or damage fuel tank causing a fire, resulting in death, serious injury
and/or property damage. Contact with muff
ler
area
could cause burns resulting in serious injury.
DO NOT touch hot parts and AVOID hot exhaust gases.
Allow equipment to cool before touching.
Keep at least 5 feet (1.5m) of clearance on all
sides of generator including overhead.
3
CAUTION Excessively high operating
speeds could result in minor injury and/or generator damage. Excessively low speeds impose a heavy load.
DO NOT tamper with governor spring, links or other parts to increase engine speeds. Generator supplies correct rated frequency and voltage when running at governed speed.
WARNING Unintentional sparking could
cause fire or electric shock resulting in death or serious injury.
WHEN ADJUSTING OR MAKING REPAIRS TO YOUR GENERATOR
Disconnect the spark plug wire from the spark plug and place the wire where it cannot contact spark plug.
WHEN TESTING FOR ENGINE SPARK
Use approved spark plug tester.
DO NOT check for spark with spark removed.
WARNING Starter and other rotating parts could entangle hands, hair, clothing, or accessories resulting in serious injury.
NEVER operate generator without protective housing or covers.
DO NOT wear loose clothing, jewelry or anything that could be caught in the starter or other rotating parts.
Tie up long hair and remove jewelry.
DO NOT modify generator in any way.
NOTICE Exceeding generators wattage/ amperage capacity could damage generator and/or electrical devices connected to it.
DO NOT exceed the generator’s wattage/ amperage capacity. See Dont Overload Generator in the Operation section.
Start generator and let engine stabilize before connecting electrical loads.
Turn electrical loads OFF and disconnect from generator before stopping generator.
NOTICE Improper treatment of generator
could damage it and shorten its life.
• Use generator only for intended uses.
• If you have questions about intended use, ask
dealer or contact local service center.
• Operate generator only on level surfaces.
• DO NOT expose generator to excessive
moisture, dust, dirt, or corrosive vapor.
• DO NOT insert any object through cooling slots.
• If connected devices overheat, to turn them off and disconnect them from generator.
-or electrical output is lost.
-or equipment sparks, smokes, or emits flames.
-or unit vibrates excessively. to turn them off and disconnect them from generator.
4
SECTION 2 GENERAL INFORMATION
2.1 UNPACKING
Set the carton on a rigid flat surface.
Remove everything from carton except
generator.
Open carton completely by cutting each corner from top to bottom.
Leave generator on carton to install wheel kit.
2.1.1 PACKING CONTENTS
1-Owners Manual 2-Wheels 1-Handle Assembly 2-Wheel Axle 1-Hardware Bag (including 1-Spark Plug Socket; 1-Extension Housing)
The above contents in this manual are for reference only and do not represent for any specific model.
3. Refer to following Figure to install the handle assembly as shown.
Insert the handle bracket onto the generator frame and secure with two M8 bolts and two M8 flange nuts.
Align the handle assembly holes with the handle bracket holes and secure with one M8 bolt and one M8 flange nut.
2.2 ASSEMBLY
The generator requires some assembly prior to using it.
2.2.1 ASSEMBLING THE ACCESSORY KIT
The wheels are designed to the unit to greatly improve the portability of the generator.
NOTE The wheels are Not intended for
over-the-road use.
1. Refer to Figures to install wheels as shown.
Slide the axle through the frame brackets.
Slide on the hub,wheel and flat washer,then insert
the cotter pin through the wheel axle hole.
Bend the cotter pin tabs outward to lock the pin in place.
2. The wheel bumpers as
shown.
Insert an M6 bolt through the rubber bumper and
insert an M8 bolt through the bottom of the
bumper
bracket. Secure the bolt
with an M8
flange nut.
Install an M8 bolt through the generator frame and through top of the bumper bracket. Secure the bolt with an M8 flange nut.
handle
bolt
handle grip
locknut support
rubber pad
flange bolt
5
SECTION 3 FEATURES AND CONTROLS
Read this Operator’s Manual and safety rules before operating your generator.
Compare the illustrations with your generator, to familiarize yourself with the locations of various controls and adjustments. Save this manual for future reference.
9
1
8
7
3
11
4
5
14
15
13
17
6
16
2
10
12
1 ENGINE SWITCH
10
AIR CLEANER
2
MUFFLER
11
FUEL VALVE
3 AC CIRCUIT BREAKER
12
4 OIL DRAIN PLUG
13
5 OIL FILL CAP/DIPSTICK
14
6 SPARK PLUG
15
7 BATTERY
16
CHOKE LEVER FUEL GAUGE FUEL TANK CAP FUEL TANK RECOIL STARTER
8 GROUND TERMINAL 9 230 VOLT AC,3-HOLE LOCKING RECEPTACLE
17
230 VOLT AC RECEPTACLE
NOTICE
Pictures and drawings used in this manual are for reference only and do not represent any specific model.
6
SECTION 4 PREPARATION BEFORE OPERATION
4.1 ADDING ENGINE OIL
Please add properly oil before starting the generator.Use a special additives. Select
the oil’s Viscosity grade accordingly to the expected operating temperature(also see chart).
Above 40 F。, use S。AE 30
• Use regular UNLEAD gasoline with the
generator engine. Do not use any fuel with more than 10% added ethanol, and never use E85 fuel.
Do not mix oil with gasoline.
Install fuel cap and wipe up any spilled
gasoline.
Between 10 F to 40 F, please use 10W-30.
CAUTION Do not overfill the fuel tank.
Below 10
F,use synthetic 5W-30.
S A E 3 0
1 0 W - 3
0
Allow space for fuel expansion.
IF the fuel tank is overfilled, fuel can overflow onto a HOT engine and cause FIRE or EXPLOSION. If fuel spills, wait until it evaporates before starting engine. Check fuel lines, tank, cap and fittings frequently for cracks
S y n
t h e t i c 5 W - 3 0
or leaks. Replace if necessary.
Fuel gauge
Fuel tank cap
Max cap mark (red)
NOTICE Improper treatment of generator could damage it and shorten its life. DO NOT attempt crank or start the engine before it has been properly serviced with the recommended oil. This could result in an engine failure.
Place generator on a flat, level surface.
Clean area around oil fill and remove oil fill cap
and remove oil cap and dipstick. Wipe dipstick clean.
Slowly fill oil into engine through the oil filter
Full
Fuel gauge
Empty
Max oil level
until it reaches the full mark on the dipstick. Stop filling occasionally to check oil level. Be careful do not over fill.
Install oil fill cap and fasten the cap properly.
Check engine oil level before starting each time
thereafter.
4.2 ADDING FUEL
DANGER Never fill tank indoors. Never fill
fuel tank when engine is running
or hot. Turn generator engine OFF and allow engine to cool entirely before filling fuel tank. Avoid spilling gasoline on HOT engine. Keep fuel away from sparks, open flames, pilot lights, heat, and other ignition sources. DO NOT light a cigarette or smoke when filling the fuel tank. Fuel is highly FLAMMABLE and its vapors are EXPLOSIVE.
IMPORTANT: It is important to prevent gum deposits from forming in fuel system parts such as the carburetor, fuel hose or tank during storage. Alcohol-blended fuels (called gasohol), ethanol or methanol) can attract moisture, which leads to separation and formation of acids during storage. Acidic gas can damage the fuel system should be emptied before storage for 30 days or longer. See
the “Storage” section. Never use engine or
carburetor cleaner products in the fuel tank as permanent damage may occur.
4.3 GROUNDING THE GENERATOR
The national Electrical Code requires that the frame and external electrically conductive part of this generator be properly connected to an approved earth ground.
7
Amps
0 in
W
attage
Reference Guide
Tool or Appliance
Running*
(Rated)
Watts
Additional
Starting
(Surge)
Watts
Essentials
Light Bulb - 75
watt
75
Furnace Fan Blower - 1/2 HP
800
2350
Sump Pump - 1/3 HP
800
1300
Refrigerator/Freezer
700
2200
Water Well
Pump - 1/2 HP
1000
2100
Heating/Cooling
Window AC - 10,000
BTU
1200
3600
Humidifier - 13 Gal
175
Central
AC - 24,000
BTU
3800
11400
Kitchen
Microwave
Oven - 1000 Watt
1000
Coffee Maker
1000
Electric
Stove
- 8”
Elemen
2100
Toaster
850
Family
Room
DVD/CD
Player
100
VCR 100
Stereo Receiver
450
Color
Television - 27 in
500
Personal
Computer
w/17
in
monitor
800
Other
Security
System
500
AM/FM
Clock Radio
100
Garage
Door
Opener - 1/2 HP
875
2350
Electric
Water Heater
4700
11700
DIY/Job
Site
Quartz Halogen Work
Light
1000
Airless
Sprayer - 1/3 HP
600
1200
Reciprocating
Saw
960
Electric Drill -
1/2 HP, 5.
600
900
Circular
Saw - 7-1/4 in
1400
2300
Miter
Saw - 10 in
1800
1800
Table Planer - 6 in
1800
1800
Table Saw/Radial
Arm Saw -
2000
2000
Air
Compressor - 1 HP
1600
4500
ON
OFF
Start
Proper grounding of the generator will help prevent electrical shock in the event of ground fault condition in the generator or in connected electrical devices. Proper grounding also helps dissipate static electricity, which often builds up in ungrounded devices.
WATTAGE REFERENCE GUIDE
SECTION 5 OPERATION
5.1 STARTING THE ENGINE
WARNING Never start or stop engine with
electrical devices plugged into the receptacles and devices turned on.
Unplug all electrical loads from the unit’s receptacles before starting the engine. Make sure the unit is in a level position.
On/OFF Switch
Engine Fuel Switch
Choker Lever
Recoil Starter
Turn the engine switch to “On” position.
Turn fuel switch to “On” position.
8
ON
OFF
Start
M
ove engine choke lever to the OFF position.
RUN
CHOKE
For Recoil start, firmly grasp the recoil handle and pull slowly until increased resistance is felt. Pull rapidly up and away.
Recoil
Starter
For electric start, turn and hold key in start switch to “start” position until generator starts.To prolong the life of starter components, DO NOT hold key in “start” position for more than 15 seconds, and pause for at least 1 minute between starting attempts.
When engine starts, move choke lever to 1/2­CHO
KE position till engine runs smoothly and
then
fully into ON position. If engine flalters,
move
choke back to 1/2- CHOKE position
till
engine running smoothly and then fully into ON
positi
on again.
NOTICE If battery is unavailable,use manual
starting instructions.
NOTICE If engine is choking and running roughly, move choke lever to the OFF position and repeat starting instructions.
WARNING Starter cord kickback (rapid
retraction) will pull hand and arm toward engine faster than you can let go which could cause broken bones, fractures, bruises, or sprains resulting in serious injury. When starting engine, pull cord slowly until resistance is felt and then pull rapidly to avoid kickback. Never start or stop engine with electrical devices plugged in and turned on.
NOTICE If engine fails to start after 3 pulls, or if unit shut down during operation, make sure unit is on a level surface and check for proper oil level in crankcase. This unit may be equipped with a low oil protection device. If so, oil must be checked at proper level for engine to start and run.
WARNING Exhaust heat/ gases
could
ignite
combustible, structures or damage
fuel tank causing a fire, resulting in death, serious injury and/or property damage. Contact with muffler area could cause burn resulting in serious injury. DO NOT touch hot part and AVOID hot exhaust gases. Allow equipment to cool before touching. Keep at least 5 feet (152 cm) of clearance on all sides of generator including overhead. Contact the original equipment manufacturer, retailer , or dealer to obtain a spark arrester designed for the exhaust system installed on this engine. Replacement parts must be the same and installed in the same position as the original parts.
9
IMPORTANT Do not overload the generator. Also,do not overload individual panel receptacles. These outlets are protected against overload with push-to-reset-type circuit breakers. If amperage rating of any circuit breaker is exceeded, that breaker opens and electrical output to that receptacle is lost.
5.2 CONNECTING ELECTRICAL LOADS
Let engine runs stable and warm up for a few
minutes after starting.
Plug in and turn on the electrical loads.
Add up the rated watts (or amps) of all loads t
o be connected at one time. This total should not be greater than (a) the rated wattage/amperage capacity of the generator or (b) circuit breaker rating of the receptacle supplying the power.
NOTICE Start generator and let engine stabilize before connecting electrical loads. Connect electrical loads in OFF position then turn ON for operation. Turn electrical loads OFF and disconnect from generator before stopping generator.
NOTICE Exceeding generators wattage/ amperage capacity could damage generator and/or electrical devices connected to it. DO NOT exceed the generator’s wattage/amperage capacity.
Overloading a generator in excess of its rated
wattage capacity can result in damage to the generator and to connected electrical devices. Observe the following to prevent overloading the unit:
Add up the total wattage of all electrical devices to be connected at one time. This total should NOT be greater than the generator’s wattage capacity. The rated wattage of lights can be taken from light bulbs. The rated wattage of tools, appliances and motors can usually be found on a data label
or decal affixed to the devices. If the appliance, tool or motor does not give wattage, multiply volts times ampere rating to determine watts (volts× amps = watts).
Some electric motors, such as induction types, require about three times more watts of power for starting than for running. This surge of power
lasts only a few seconds when starting such motors. Make sure to allow for high starting wattage when selecting electrical devices to connect to the generator:
Figure the watts needed to start the largest motor.
Add to that figure the running watts of all other connected loads.
The wattage reference guide is provided to assist in determining how many items the generator can operate at one time.
5.3 STOPPING THE ENGINE
Shut off all loads then unplug the electrical loads from generator panel receptacles. Never start or stop the engine with electrical devices plugged in and turned on. Let engine run at no-load for several minutes to stabilize the internal temperatures of engine and generator. Move ON/OFF switch to OFF position. Close fuel valve.
5.4 LOW OIL LEVEL SHUTDOWN SYSTEM
The engine is equipped with a low oil
level sensor that shuts down the engine automatically when the oil level drops below a specified level. If the engine shuts down by itself and the fuel tank has enough gasoline, check engine oil level.
5.5 HIGH ALTITUDE
At altitudes over 5,000 feet (1524 meters), a minimum 85 octane / 85 (89 RON) gasoline is acceptable. To remain emissions compliant, high altitude adjustment is required. Operation without this adjustment will cause decreased performance, increased fuel consumption, and increased emissions. See an authorized dealer for high altitude adjustment information.
Operation of the engine at altitudes below 2,500 feet (762 meters) with the high altitude kit is not recommended.
1
First 5 Hours
• Change engine oil
Every 8 Hours or Daily
Clean debris
Check engine oil level
Every 25 Hours or Yearly
Clean engine air filte1r
Every 50 Hours or Yearly
• Change engine oi1l
Yearly
Replace engine air filte1r
Service fuel valve
Service spark plug
Check muffler and spark arrester
Clean cooling system
1
SECTION 6 MAINTENANCE
6.1 MAINTENANCE SCHEDULE
Follow the calendar intervals shown below. More frequent service is required when operating in adverse conditions.
6.2.1 GENERATOR MAINTENANCE
Generator maintenance consists of keeping the unit clean and dry. Operate and store the unit in a clean dry environment where it will not be exposed to excessive dust, dirt, moisture or any corrosive vapors. Cooling air slots in the generator must not become clogged with snow, leaves, or any other foreign material. Check the cleanliness of the generator frequently and clean when dust, dirt, oil, moisture or other foreign substances are visible on its exterior surface.
CAUTION Never insert any object or tool
through the air cooling slots, even if the engine is not running.
6.2 GENERAL RECOMMENDATIONS
The warranty of the generator does not cover items that have been subjected to operator abuse or negligence. To receive full value from the warranty, the operator must maintain the generator as instructed in this manual.
Some adjustments will need to be made periodically to properly maintain the generator.
All adjustments in the Maintenance section of this manual should be made at least once each season. Follow the requirements in the “Maintenance Schedule”.
NOTE Once a year replace the spark plug and replace the air filter. A new spark plug and clean air filter assure proper fuel-air mixture and help the engine run better and last longer.
NOTE DO NOT use a garden hose to clean generator. Water can enter the engine fuel system and cause problems. In addition, if water enters the generator though cooling air slots, some water will be retained in voids and crevices of the rotor and stator winding insulation. Water and dirt buildup on the generator internal windings will eventually decrease the insulation resistance of these windings.
6.2.2 TO CLEAN THE GENERATOR
Use a damp cloth to wipe exterior surfaces.
A soft, bristle brush may be used to remove
dirt, oil etc.
A vacuum cleaner may be used to pick up loose dirt and debris.
Low pressure air (not to exceed 25 psi) may be used to blow away dirt. Check cooling air slots and openings on the generator. These openings must be kept clean and unobstructed.
6.2.3 ENGINE MAINTENANCE
DANGER When working on the generator,
always disconnect spark plug wire from spark plug and keep wire away from spark plug.
1
Soak Squeeze Engine oil Squeeze
6.2.4 CHANGING THE OIL
Change the oil after the first five hours of operation, then every 20 hours thereafter. If running this unit under dirty or dusty conditions, or in extremely hot weather, change the oil more often.
Dipstick
Sealing ring
Max level
Drain plug
6.2.6 SPARK ARRESTOR
Shut off generator and allow the engine and muffler to cool down completely before servicing spark arrestor (located on the back of the muffler).
Remove the clamp and spark arrestor screen.
Clean the spark arrestor screen with a small
wire brush.
Replace the spark arrestor if it is damaged.
• Install the Spark arrestor reversely.
CAUTION Hot oil may cause burns.
Allow engine to cool before draining oil. Avoid prolonged or repeated skin exposure to used oil. Thoroughly wash exposed areas with soap.
Follow below instructions to change the oil
while the engine is cooling down:
• Clean area around oil drain plug.
• Remove oil drain plug from engine to drain oil
completely into a suitable container.
When oil has completely drained, install oil drain plug and fasten securely.
• Fill engine with recommended oil. (See “Before Starting the Generator” for oil recommendations).
Wipe up any spilled oil.
• Dispose used oil at a proper collection center.
6.3 SERVICE AIR FILTER
The engine will not run properly and may be damaged if using a dirty air filter. Replace the air filter once a year. Clean or replace more often if operating under dusty conditions.
Remove air filter cover.
Wash in soapy water. Squeeze filter dry in clean
cloth (DO NOT TWIST).
Clean air filter cover before re-installing it.
May drop a bit of engine oil to avoid ice blocked
during winter season.
6.2.5 REPLACING THE SPARK PLUG
Use spark plug F6TC, BPR4ES or Champioin RN14YC.Replace the plug once each year. This will help the engine start easier and run better.
Stop the engine and pull off the spark plug wire.
Clean the area around the spark plug and
remove it from the cylinder head.
Set the spark plug’s gap to 0.70-0.80 mm
(0.028-0.031 in.). Install the correctly gapped spark plug into the cylinder head and torque to 15 ft/lbs.
Bolt Cover of air cleaner
Cartridge of air cleaner
1
6.4 VALVE CLEARANCE
After the first 50 hours of operation, check the valve clearance in the engine and adjust if necessary.
Important: If feeling uncomfortable about doing
this procedure or the proper tools are not available, please take the generator to the nearest service center to have the valve clearance adjusted. This is a very important step to ensure longest life for the engine.
6.5 GENERAL
The generator should be started at least once every seven days and be allowed to run at least 30 minutes. If this cannot be done and the unit
must
be
stored for more than 30 days, use the following
information as a guide to prepare it for storage.
DANGER NEVER store engine with fuel in tank indoors or in enclosed, poorly ventilated areas where fumes may reach an open flame, spark or pilot light as on a furnace, water heater, clothes dryer or other gas appliance.
SECTION 7 STORAGE
It is important to avoid gum deposits from forming in essential fuel system parts such as the carburetor, fuel hose or tank during storage. Also, experience indicates that alcohol-blended fuels (called gasohol, ethanol or methanol) can attract moisture, which leads to separation and formation of acids storage. Acidic gas can damage the fuel system of an engine while in storage. To avoid engine problems, the fuel system should be emptied before storage of 30 days or longer, as follows:
Remove all gasoline from the fuel tank.
Start and run engine until engine stops from
lack of fuel.
While engine is still warm, drain oil from crankcase. Refill with recommended grade.
Remove spark plugs and pour about 1/2 ounce (15 ml) of engine oil the cylinders. Cover spark plug hole with rag. Pull the recoil starter a couple times to lubricate the piston rings and cylinder bore.
Drain
screw
CAUTION Avoid spray from spark plug
holes when cranking engine.
DANGER Drain fuel into approved container outdoors, away from open flame. Be sure engine is cool. Do not smoke.
6.6 OTHER STORAGE TIPS
Do not store gasoline from one season to another.
Replace the gasoline can if it starts to rust. Rust and/or dirt in the gasoline will cause problems with the carburetor and fuel system.
If possible, store the unit indoors and cover it to give protection from dust and dirt. BE SURE TO EMPTY THE FUEL TANK.
If it is not practical to empty the fuel tank and the unit is to be stored for some time, use a commercially available fuel stabilizer added to the gasoline to increase the life of the gasoline.
Cover the unit with a suitable protective cover that does not retain moisture.
Install and tighten spark plugs. Do not connect spark plug wires.
Clean the generator outer surfaces. Check that cooling air slots and openings on generator are open and unobstructed.
Store the unit in clean, dry place.
DANGER NEVER cover the generator while
engine and exhaust area are warm.
1
SECTION 8 PARAMETER
Specification
Model
Engine
6.5HP
7HP
7HP
7.5HP
13HP
Displacement
196cc
208cc
208cc
223cc
389cc
Rated frequency
60Hz/50Hz
60Hz/50Hz
60Hz/50Hz
60Hz/50Hz
60Hz/50Hz
Rated voltage
120V/230V
120V/240V/230V
120V/240V/230V
120V/240V/230V
120V/240V/230V
Rated power
2.2KW/2.0KW
2.8KW/2.5KW
3.2KW/2.8KW
3.8KW/3.3KW
4.5KW/4.2KW
Max power
2.5KW/2.2KW
3.2KW/2.8KW
3.5KW/3.1KW
4.1KW/3.8KW
5.0KW/4.5KW
Fuel tank capacity
15L
15L
15L
15L
25L
Full load continuum
running time
9.5H
9.5H
9.5H
9.5H
8.5H
1/2 load continuum
running time
12.5H
12.5H
13.5H
13.5H
13.5H
Model
Engine
13HP
14HP
14HP
16HP
16HP
Displacement
389cc
420cc
420cc
459cc
459cc
Rated frequency
60Hz/50Hz
60Hz/50Hz
60Hz/50Hz
60Hz/50Hz
60Hz/50Hz
Rated voltage
120V/240V/230V
120V/240V/230V
120V/240V/230V
120V/240V/230V
120V/240V/230V
Rated power
5.5KW/5.0KW
6.5KW/6.0KW
7.0KW/6.5KW
7.5KW/7.0KW
8.0KW/7.5KW
Max power
6.0KW/5.5KW
7.0KW/6.5KW
8.0KW/7.0KW
8.5KW/8.0KW
9.0KW/8.5KW
Fuel tank capacity
25L
25L
25L
25L
25L
Full load continuum
running time
8.5H
8.5H
8.5H
8.0H
8.0H
1/2 load continuum
running time
13.5H
13.0H
13.0H
12.5H
12.5H
1
SECTION 9 WARRANTY
SENCI GENERATOR OWNER WARRANTY POLICY
THANK YOU FOR CHOOSING SENCI GENERATOR!
OUR WARRANTY
SENCI will, at its option, free of charge, repair or
replace any part(s) which, upon examination, inspection and testing by
SENCI
or an
SENCI
Authorized Warranty Service Dealer, that is defective in material or workmanship or both. Transportation charges on product submitted for repair or replacement under this warranty must be borne by purchaser. Retain your proof-of­purchase receipt. If you do not provide proof of the initial purchase date, the manufacturer’s shipping date of the product will be used to determine the warranty period starting.
WARRANTY PERIOD
Any new SENCI generator purchased for non-commercial use from an authorized SENCI generator dealer will be warranted against defects in material or workmanship for a period of one year, from date of purchase, subject to exclusions noted herein. Commercial and rental applications are warranted for six months.SENCI customer service will keep on supplying spare parts per
installation. Similarly, the warranty is void if the manufacturing date or the serial number on the portable generator has been removed or the equipment has been altered or modified. During the warranty period, the Authorized Service Dealer, at its option, will repair or replace any part that, upon examination, is found to be defective under normal use and service. This warranty will not cover the following repairs and equipment:
REGULAR WEARING: Outdoor Power Equipment, as with all mechanical devices, need periodic part(s) service and replacement
to
perform
as designed. This warranty will not cover repair when normal use has exhausted the life time of a part(s) or engine.
INSTALLATION AND MAINTENANCE: This warranty does not cover the generators or its parts what have been subjected to improper or unauthorized assemblied, alterated, modified, or damaged due to misusing, negligence, accident, overloading, overspeeding, improper maintenance, repair or storage so as, in our judgment, to adversely affect its performance and reliability. This warranty also does not cover regular maintenance and parts such as air filters,
adjustments, fuel system cleaning and obstruction (due to chemical, dirt, carbon, lime, and so forth).
request after warranty period with cost charge.
OTHER EXCLUSIONS: This warranty excludes
“Consumer Use" means residential household using by a retail consumer. “Commercial Use" means all other uses, including used for commercial, industrial or business or rental purposes. Once equipment has experienced commercial use, it shall thereafter be considered as commercial use for purposes of this warrant
ABOUT YOUR WARRANTY
We welcome warranty repair and apologize to you for being inconvenienced. Any Authorized Service Dealer may perform warranty repairs. Most warranty repairs are handled routinely, but sometimes requests for warranty service may not be appropriate. For example, warranty service would not apply if equipment damage occurred because of misuse, lack of routine maintenance, shipping, handling, warehousing or improper wearing parts such as o-rings, filters, etc., or
malfunctions resulting from accidents, abuse, modifications, alterations, or improper
servicing
or freezing or chemical deterioration; Damaged related to rodent and/or insect infestation. Accessory parts such as starting batteries, generator adapter cord sets and storage covers are excluded from the product warranty.
This warranty
excludes used, reconditioned, and demonstration equipment, equipment used for prime power in place of utility power, equipment used in life support applications, and failures due to other force majeure events beyond the manufacturers control, such as collision, theft, vandalism, riot or wars, nuclear holocaust, fire, freezing, lightning, earth-quake, windstorm, hail, volcanic eruption, water or flood, tornado or hurricane.
Loading...