Sempell Pressure Seal Gate Valves - Style A, Sempell-EN Manuals & Guides

SEMPELL PRESSURE SEAL GATE VALVES - STYLE A
Cast Gate ValVes, wedGe & Parallel slide ConfiGuration, welded ends
Installation and maintenance instructions
Handling requirements
A - Packed valves Crates: Lifting and handling of the packed
valves in crates will be carried out by a fork lift truck, bymeans of the appropriate fork hitches.
Cases: The lifting of packed valves in cases
should be carried out in the lifting points and at the center of gravity position which have been marked. The transportation of all packed material must be carried out safely and following the local safety regulations.
B - Unpacked valves
1. The lifting and the handling of these valves has to be carried out by using appropriate means and at respecting the carrying limits.
VALVE STORAGE
Preparation and preservation for Shipment
All valves are properly packed in order to protect the parts that are subject to deterioration during transportation and storage on site. In particular, the following precautions should be taken:
2. The weld ends surface shall be protected with suitable protective like Deoxaluminite. The end shall be closed with plywood or plastic disc fixed at the edge by strips.
3. All actuated valves must be carefully securely palleted or crated, in order to ensure that the parts of actuator (especially pneumatic piping or accessories) do not extend beyond the skid/crate.
4. The type of packing must be defined in the customer’s order and shall be appropriate to ensure safe transportation to final destination and eventual conservation before installation.
The handling must be carried out on pallets, protecting the machined surfaces to avoid any damage.
2. With valves of large dimensions, the sling and the hooking of the load must be carried out using the appropriate tools (brackets, hook, fasteners, ropes) and load balancing tools in order to prevent them from falling or moving during the lifting and handling.
Emerson.com/FinalControl
VCIOM-04586-EN 18/01© 2017 Emerson. All Rights Reserved.
SEMPELL PRESSURE SEAL GATE VALVES - STYLE A
Cast Gate ValVes, wedGe & Parallel slide ConfiGuration, welded ends
VALVE SLINGING
FIGURE NO. 1
Storage and preservation before installation
In case the valves have to be stored before installation, the storage has to be carried out in a controlled way, and has to be performed in accordance with the following criteria:
1. The valves have to be stocked in a closed, clean and dry storage room.
2. The wedge must be in the closed position, and the end faces must be protected with plastic or wooden discs fixed with straps. If possible, keep the original protection.
3. Periodical checks have to be carried out in the storage area to verify that the above mentioned conditions are maintained.
For actuated valves, in addition to the above, please refer to the warnings in the manual of the actuator.
NOTE
Storage in an open area for a limited period can be considered only in case the valves have appropriate packing (packed in cases lined with tarred paper, and contents well protected with barrier sacks). Do not place consignment packages directly on the ground. Do not expose consignment packages to the weather or directly to the sun. Check the packaging every two months.
CAUTION
For valve handling and/or lifting, the lifting equipment (fasteners, hooks, etc.) must be sized and selected while taking into account the valve weight indicated in the packing list and/or delivery note. Lifting and handling must be made only by qualified personnel. Do not use the lifting points located on the actuator, if any, to lift the valve. These lifting points are for the actuator only. Caution must be taken during the handling to avoid that this equipment passes over the workers or over any other place where a possible fall could cause damage. In any case, the local safety regulations must be respected.
INSTALLATION
Preparation before installation
1. Carefully remove the valve from the shipping package (box or pallet) avoiding any damage to the valve or, in case of automated valves, to the electric or pneumatic/ hydraulic actuator or instrumentation.
2. The valves are shipped with the ends protected by caps and coated with a thin layer of protective grease. Before installation, remove the caps of the ends and the protective grease by cleaning them completely with a solvent liquid. Clean the inside of the valve using an air line. Ensure that there are no solid objects such as pieces of wood, plastic or packing materials within the valve or on the valve seat.
3. Confirm that the materials of construction listed on the valve nameplates (service and temperature) are appropriate for the service intended and are as specified.
4. Define the preferred mounting orientation with respect to the system pressure. If any (see arrow on the body), identify the upstream side (high pressure) and downstream side (low pressure).
WARNING
Verify that the direction of the flow in the line corresponds to the arrow indicated on the valve body. Valves without the arrow are bi-directional. See the actuator user manual for the actuator preparation.
2
SEMPELL PRESSURE SEAL GATE VALVES - STYLE A
Cast Gate ValVes, wedGe & Parallel slide ConfiGuration, welded ends
IMPORTANT
After the valves installation and before the
90° max.
FIGURE NO. 2
INSTALLATION POSITIONS RECOMMENDED
WARNING
Before welding, check that valve is completely opened.
Installation instructions
Gate valves are normally installed in horizontal pipe with vertical stem. These valves can also be installed in vertical or horizontal pipe with stem other than vertical, but this may require special construction depending on valve size, service condition, material and type of operator. For a correct operation, we recommend that the valve shall be installed and oriented following the indications of Fig. 2. This can help minimize any problem associated with solid particles present in the fluid that otherwise could deposit in the lower part of the body and be obstacle to the wedge complete closure. Install the valve with the wedges in closed position unless otherwise stated. Thus, the sealing surfaces will not be damaged during installation. Particular care should be taken with those valves equipped with ‘fail-open’ actuators. For operating temperatures above 200°C (392°F) thermal insulation of the valve body is recommended. Handling and lifting of the valves during installation MUST be performed following the same criteria and instructions described in previous points ‘Valve handling’ and ‘Storage and Preservation before Installation’.
Buttweld valves
1. Open the valve.
2. Place the valve, check the alignment with the pipe and weld in accordance with the welding standard procedures as stated by the Engineering Society.
line testing, it is recommended to perform an accurate cleaning of the lines to eliminate dirt and any foreign objects that could seriously jeopardize the tightness between seat/disc and the correct operation of the valve. It is therefore recommended to leave the valve in the open position.
Valve verification before start up
1. Tighten the packing just enough to prevent stem leakage. Over-tightening will decrease packing life and increase operating torque. The bolt torque figures for the packing bolts can be calculated as indicated in Table I. In the case that leaking from the packing occurs during the start up, proceed as follows:
- Tighten the nuts to the indicated torque
(see table), operate the valve and re-tight the nuts to the indicated torque.
- Repeat the operation until the leakage
stops.
2. Check the operation of the valve by stroking it to ‘full open’ and ‘full close’.
3. In case of electric actuated valves, see paragraph for instructions on the adjustment of the actuator.
IMPORTANT
If piping system is pressurized with water for testing, and in case the piping system has been shut down after testing for a long time, the following recommendations should be adopted. a. Use corrosion inhibitor with water to
pressurize the piping system
b. After testing, the piping system should be
depressurized and the test water completely drained.
Scheduled maintenance
1. Style A Series Gate Valves do not require special care to work properly.
The following instructions will help provide a
satisfactory and long life service.
2. Make sure to perform periodic valve verification as described in paragraph ' Adjustment of electric actuators'.
3. In case of actuated valves always follow the specific instructions given by the actuator’s manufacturer.
4. Never change the setting of torque and/or limit switches which have been carefully set during the final test at the manufacturing plant.
3
Loading...
+ 5 hidden pages