Selcon PRG-SE-C, PRG-SE-C-O2 Technical Sheet

Page 1
PROGRAMMER FOR START, FLAME SUPERVISION
AND SAFE STOP OF BURNER
PRODUCT: PRG-SE-C
Costumer Service 55 11 3019-1616

- O2 TECHNICAL SHEET 1/11
For further details see technical bulletin
APPLICATION
Programmer PRG-SE-C-O2 equipment recommended for start, flame supervision and safe stop for any type of burner for up to two stages of flame, in commercial applications or industrial and fuels gas or light liquids, with a cycle of use do not continuum (on/off burner Period in less than 24 hours).
For use in closed combustion camera, the user should provide safe system of pre-purge before each sequence of start, or require the programmer PRG-SE-C-O2 with purge timer coupled,
since that the times offered are appropriate for application. Entry for flame sensor for ionization. See electrode sensors for ionization, line SEL-HT-I (standard) or SEL-HT-E (electrode mounted on a drawing or sample of the client).
This product meets the requirements of the standard NBR 12313 of ABNT-review
Sept./2000.
TECHNICAL DATA
⇒⇒⇒⇒
Watch dog micro process – safe failure.
⇒⇒⇒⇒
Supply/frequency: 90 a 250Vca - 50/60 Hz ± 3% or 24Vcc (-10 +20%).
NOTE: To supply network CA, consisting of phase/neutral, should consider the
possible need for its reversal (terminals 9 and 10), for flame sensor circuit not
lose sensitivity and therefore the capacity to detect signal of flame. See below
diagram for the connections AC and DC.
⇒⇒⇒⇒
Consumption of energy: 5 VA
⇒⇒⇒⇒
Protection against tension outbreaks
⇒⇒⇒⇒
Protection fuses retardate the internal circuitry (0,25A) and for the control outputs (6,3A)
⇒⇒⇒⇒
Temperature of work: 0 at 60 ºC
⇒⇒⇒⇒
Storage ambient temperature: -5° a 65 °C
⇒⇒⇒⇒
Maximum relative humidity of environment in operation: 90% (40 ± 2°C) – NBR 5291
⇒⇒⇒⇒
Flame Sensor : Ionization.
⇒⇒⇒⇒
Minimum current flame for supply of 90 at 250Vca: 2 microampers dc (uA).
⇒⇒⇒⇒
Minimum current flame for supply in 24 Vcc: 7 uA microampers dc (uA).
NOTE: The cable of flame sensor must be installed separately from other cables that
are part of the command set of the burner. The best type of cable recommended for
this purpose is used for ignition.
⇒⇒⇒⇒
Protection against short circuit failure sensor ionization for mass.
⇒⇒⇒⇒
Blocking with local signaling (type LED) and remote (contact of relay N.A.)
⇒⇒⇒⇒
With verification of premature flame or false flame signal, before starting the burner.
⇒⇒⇒⇒
Purge Time: 10 or 20 seconds (see field code for request)
⇒⇒⇒⇒
Maximum time for confirmation of contact closure of the PS of combustion air: 5 sec.
SELCON
Automação Industrial
SELCON S
CNPJ 56.935.877/0001-29
Street Américo Samarone, 502 • CEP 04284-000 • Moinho Velho • São Paulo • SP • Tel/Fax: (55 11) 3019-1616
http://www.selcon.com.br
Selcon Ltda., keeps the right to modify this technical sheet
when never it is necessary
ISTEMAS ELETRÔNICOS DE CONTROLE LTDA
February/10
.
Representative or Distributor:
1/11
Page 2
PROGRAMMER FOR START, FLAME SUPERVISION
AND SAFE STOP OF BURNER
PRODUCT: PRG-SE-C
Costumer Service 55 11 3019-1616
⇒⇒⇒⇒
Time of ignition: 6 sec.
⇒⇒⇒⇒
Time to confirm the signal of flame: < 1 sec.
⇒⇒⇒⇒
Time of answer to the flame flaw: < 4 seg.
⇒⇒⇒⇒
BARGRAF of LED’s:
Signaling
Signaling
Signaling
Signaling
Signaling
Signaling
Signaling 7
(BLINK, BLINK)
Signaling
1 – ¨PUR
2 – ¨IGN
3 –
4 – ¨N3
5 – ¨N2
6 – ¨N1
8 – ¨ANT¨ 

- O2 TECHNICAL SHEET 2/11
For further details see technical bulletin
¨
 BURNER IN PURGE
¨
 BURNER IN IGNITION
¨
N4
¨
 LEVEL OF FLAME
¨
 LEVEL OF FLAME
¨
 LEVEL OF FLAME
¨
 LEVEL OF FLAME
– ¨FCH
¨
FAILURE OF IGNITION / FLAME FAILURE (fixed access)
DEFECT SENSOR - SHORT CIRCUIT FOR OF MASS
- available only for the model fed on 24Vdc
FAILURE FOR FLAME PREMATURE OR FALSE
Signaling
Signaling
NOTE: The flame sign will be greater the higher the level "N" indicated
⇒⇒⇒⇒
Maximum current per output in 250 Vac (resistive):
••••
VE
••••
TI
••••
V1
••••
V2
••••
AL
⇒⇒⇒⇒
Electric connections: through socket of fast extraction polarized, type terminal rule,
to receive the external cables.
⇒⇒⇒⇒
Expected electrical life of output contacts:> 100,000 operations.
⇒⇒⇒⇒
Expected mechanical life of output contacts:> 10,000,000 operations.
⇒⇒⇒⇒
Reset local and remote after 3(three) sec. waiting for security to enable the reset system.
⇒⇒⇒⇒
Auto Test of key air flow or pressure switch: (NA) before start the fan, and (NC) continuously after the start of the fan.
⇒⇒⇒⇒
Degree of environmental protection: IP 54 (except connector of fast extraction - IP 50)
⇒⇒⇒⇒
Cabinet: Plastic box gray color
⇒⇒⇒⇒
Mounting: External or internal on flat surface in protected environment.
9 – ¨PSA
10 – ¨PSF¨ 
(ventilator): 2 A
(transformer of ignition): 2 A
(low fire or pilot): 2 A
(high fire): 2 A
(alarm): 2 A
¨
 FAILURE PS AIR COMBUSTION OPENED
FAILURE PS AIR COMBUSTION CLOSED
SELCON
Automação Industrial
SELCON S
CNPJ 56.935.877/0001-29
Street Américo Samarone, 502 • CEP 04284-000 • Moinho Velho • São Paulo • SP • Tel/Fax: (55 11) 3019-1616
http://www.selcon.com.br
Selcon Ltda., keeps the right to modify this technical sheet
when never it is necessary
ISTEMAS ELETRÔNICOS DE CONTROLE LTDA
February/10
.
Representative or Distributor:
2/11
Page 3
PROGRAMMER FOR START, FLAME SUPERVISION
97
35
AND SAFE STOP OF BURNER
PRODUCT: PRG-SE-C
Costumer Service 55 11 3019-1616
⇒⇒⇒⇒
Fixation: 3 screws on plane surface.
⇒⇒⇒⇒
Weight : 300 grams
⇒⇒⇒⇒
Warranty: 12 months (see the guarantee)

- O2 TECHNICAL SHEET 3/11
For further details see technical bulletin
Dimensional drawing (mm) - version for supply AC-90 to 250V
PART IDA
RR
SELC ON LTDA .
Indús tria Brasile ira
PROD UTO:
Alime ntação:
90-25 0VCA~50/ 60Hz
109
PRG-SECAMPO
TI
CHAM A
ALARM ES
AL V1 V2 VE PS R L2
1
PUR
2
IGN
3
N4
4
N3
5
N2
6
N1
7
FCH
8
ANT
9
PSA
10
PSF
654321 7 8 9 1 0
V
I
E100
R
14 15 16
11 12 13
~
95
14
FIGURE 1
Main ruler of terminals (10 terminals) and additional (optional 3 +3 terminals) - AC 90 to 250V
1
2
3
4
5
6
7
8
9
10
SELCON
Automação Industrial
SELCON S
CNPJ 56.935.877/0001-29
Street Américo Samarone, 502 • CEP 04284-000 • Moinho Velho • São Paulo • SP • Tel/Fax: (55 11) 3019-1616
ISTEMAS ELETRÔNICOS DE CONTROLE LTDA
http://www.selcon.com.br
Selcon Ltda., keeps the right to modify this technical sheet
when never it is necessary
February/10
FIGURE 2
.
Representative or Distributor:
3/11
Page 4
PROGRAMMER FOR START, FLAME SUPERVISION
AND SAFE STOP OF BURNER
PRODUCT: PRG-SE-C
Costumer Service 55 11 3019-1616

- O2 TECHNICAL SHEET 4/11
For further details see technical bulletin
Scheme of electric connections CA - version for supply CA - 90 to 250V:
1 2 3 4
F (6,3A)
5 6 7 8 9
10
AL V1 V2 VE
ICC> 2uAdc
PRG-SE-C -O2
R
654321 7 8 9 10
V
+
PS R L2 L1(N)
_
uA
_
~
14 15 16
11 12 13
SELCON
Automação Industrial
ACS-TE - 1-CTI
G
SELCON S
CNPJ 56.935.877/0001-29
Street Américo Samarone, 502 • CEP 04284-000 • Moinho Velho • São Paulo • SP • Tel/Fax: (55 11) 3019-1616
http://www.selcon.com.br
Selcon Ltda., keeps the right to modify this technical sheet
when never it is necessary
ISTEMAS ELETRÔNICOS DE CONTROLE LTDA
February/10
I
FIGURE 3
.
Representative or Distributor:
4/11
Page 5
PROGRAMMER FOR START, FLAME SUPERVISION
AND SAFE STOP OF BURNER
PRODUCT: PRG-SE-C
Costumer Service 55 11 3019-1616
Dimensional drawing (mm) - version for supply DC in 24Vcc:
99.5

- O2 TECHNICAL SHEET 5/11
For further details see technical bulletin
PART IDA
R
SELCON L TDA.
Indústria Brasileira
PROD UTO:
PRG-SECAMPO
TI AL V1 V2
CHAM A
ALARM ES
4321 9 10
9735
1
PUR
2
IGN
3
N4
4
N3
5
N2
6
N1
7
FCH
8
ANT
9
PSA
10
PSF
Alime ntação:
24 Vcc
65 7 8
VE I PS RV24v
E115
R
95
-
+
4.5
FIGURE 4
Scheme of electric connections - version for supply DC in 24Vcc:
1
F (6,3A)
2 3 4 5 6 7 8 9
10
PRG-SE-C 1-O2
R
654321 7 8 9 10
V
+
uA
_
I
AL V1 V2 VE PS R
_ _
ICC> 7uA<250uADC
ACS-TE-05-C5
TI
G
FIGURE 5
-
24v
+
SELCON
Automação Industrial
SELCON S
CNPJ 56.935.877/0001-29
Street Américo Samarone, 502 • CEP 04284-000 • Moinho Velho • São Paulo • SP • Tel/Fax: (55 11) 3019-1616
http://www.selcon.com.br
ISTEMAS ELETRÔNICOS DE CONTROLE LTDA
Selcon Ltda., keeps the right to modify this technical sheet
when never it is necessary
February/10
.
Representative or Distributor:
5/11
Page 6
PROGRAMMER FOR START, FLAME SUPERVISION
AND SAFE STOP OF BURNER
PRODUCT: PRG-SE-C
Costumer Service 55 11 3019-1616
LEGEND

- O2 TECHNICAL SHEET 6/11
For further details see technical bulletin
L1 / L2 (N): Power Input 90 to 250Vac or 24Vdc (see code for request).
Ps: Pressure switches for minimum gas (permission of start).
Rearme: Reset local
R: Reset remote
VE: Fan
PS: Key of flow of air / key of pressure of combustion air and/or exhaustion
TI: Transformer of ignition:
••••
We recommend using the model ACS-TE--C5 or ACS-TE -1-C6.
For other transformers of Ignition, consult Selcon Ltda.
G: Electrode ignitor – line SEL-HT
I: Sensor electrode of flame for ionization – line SEL-HT
V1: Pilot valve (1º stage / pilot / fire low)
V2: Main valve (2º stage / main / fire high)
AL: Alarm of flame premature or false; failure of ignition; failure of flame in regime;
circuit short short of the flame sensor.
Q: Burner-pilot and main; low fire and high or of 2 stages.
SELCON
Automação Industrial
SELCON S
CNPJ 56.935.877/0001-29
Street Américo Samarone, 502 • CEP 04284-000 • Moinho Velho • São Paulo • SP • Tel/Fax: (55 11) 3019-1616
http://www.selcon.com.br
Selcon Ltda., keeps the right to modify this technical sheet
when never it is necessary
ISTEMAS ELETRÔNICOS DE CONTROLE LTDA
February/10
.
Representative or Distributor:
6/11
Page 7
PROGRAMMER FOR START, FLAME SUPERVISION
AND SAFE STOP OF BURNER
PRODUCT: PRG-SE-C
Costumer Service 55 11 3019-1616
Diagram of times

- O2 TECHNICAL SHEET 7/11
For further details see technical bulletin
TIMES
t1 Wait to start sequence 1 sec. t2 Wait for stabilization of the key signal of air flow 5 sec. t3 Purge 0, 10 or 20 sec. t4 Pre-ignition 2 sec. t5 Ignition 6 sec. t6 Stabilization pilot flame or 1st stage. 8 sec.
Operation starting with the formation of normal flame
t0
~
L1-L2(N)
t1
PS
t2
TERMINALS FOR ELECTRICAL CONNECTIONS
9/10
7
SELCON
Automação Industrial
VE
V
t3
TI
V1
V2
I
AL
R
FIGURE 6
SELCON S
CNPJ 56.935.877/0001-29
Street Américo Samarone, 502 • CEP 04284-000 • Moinho Velho • São Paulo • SP • Tel/Fax: (55 11) 3019-1616
http://www.selcon.com.br
Selcon Ltda., keeps the right to modify this technical sheet
when never it is necessary
ISTEMAS ELETRÔNICOS DE CONTROLE LTDA
February/10
5
t4
1
t5
3
t6
4
6
2
8
.
Representative or Distributor:
7/11
Page 8
PROGRAMMER FOR START, FLAME SUPERVISION
t0
AND SAFE STOP OF BURNER
PRODUCT: PRG-SE-C
Costumer Service 55 11 3019-1616
Operation starting with the presence of premature flame / false signal

~
L1-L2(N)
PS
VE
V
TI
V1
V2
I
AL
R
- O2 TECHNICAL SHEET 8/11
For further details see technical bulletin
TERMINALS FOR
t0
ELECTRICAL CONNECTIONS
9/10
7
5
1
3
4
6
2
8
Operation of start with ignition failure
t0
~
V
L1-L2(N)
PS
VE
TI
V1
V2
I
AL
R
t1
t2
FIGURE 7
t3
t4
t5
FIGURE 8
TERMINALS FOR ELECTRICAL CONNECTIONS
9/10
7
5
1
3
4
6
2
8
t0
SELCON
Automação Industrial
SELCON S
CNPJ 56.935.877/0001-29
Street Américo Samarone, 502 • CEP 04284-000 • Moinho Velho • São Paulo • SP • Tel/Fax: (55 11) 3019-1616
http://www.selcon.com.br
ISTEMAS ELETRÔNICOS DE CONTROLE LTDA
Selcon Ltda., keeps the right to modify this technical sheet
when never it is necessary
February/10
.
Representative or Distributor:
8/11
Page 9
PROGRAMMER FOR START, FLAME SUPERVISION
t0
t0
AND SAFE STOP OF BURNER
PRODUCT: PRG-SE-C
Costumer Service 55 11 3019-1616
Operation of start with pre-existent flaw of the key of flow of air

~
L1-L2(N)
PS
VE
V
TI
V1
V2
I
AL
R
- O2 TECHNICAL SHEET 9/11
For further details see technical bulletin
TERMINALS FOR
t0
ELECTRICAL CONNECTIONS
9/10
7
5
1
3
4
6
2
8
FIGURE 9
Operation of start with flaw of the key of flow of air after entering in regime.
t0
~
V
L1-L2(N)
PS
VE
TI
V1
V2
t1
t2
t3
t4
t5
t6
TERMINALS FOR
ELECTRICAL
CONNECTIONS
9/10
7
5
1
3
4
I
AL
R
6
2
8
FIGURE 10
SELCON
Automação Industrial
SELCON S
CNPJ 56.935.877/0001-29
Street Américo Samarone, 502 • CEP 04284-000 • Moinho Velho • São Paulo • SP • Tel/Fax: (55 11) 3019-1616
http://www.selcon.com.br
ISTEMAS ELETRÔNICOS DE CONTROLE LTDA
Selcon Ltda., keeps the right to modify this technical sheet
when never it is necessary
February/10
.
Representative or Distributor:
9/11
Page 10
PROGRAMMER FOR START, FLAME SUPERVISION
AND SAFE STOP OF BURNER
PRODUCT: PRG-SE-C
Costumer Service 55 11 3019-1616
Operation of normal start with lack and subsequent electric power return.
t0
~
V
L1-L2(N)
PS
VE
TI
V1
V2
I
AL
R
t1

- O2 TECHNICAL SHEET 10/11
For further details see technical bulletin
t0
t1
t2t2
t4t3
t5
t6
RETURN OF ENERGY / NORMAL OPERATION
t4t3
t5
FIGURE 11
Equipment lock with momentary lack of energy
t0
~
L1-L2(N)
TERMINALS FOR ELECTRICAL CONNECTIONS
t6
TERMINALS FOR ELECTRICAL CONNECTIONS
PS
VE
V
TI
V1
V2
I
AL
R
SELCON
Automação Industrial
SELCON S
CNPJ 56.935.877/0001-29
Street Américo Samarone, 502 • CEP 04284-000 • Moinho Velho • São Paulo • SP • Tel/Fax: (55 11) 3019-1616
http://www.selcon.com.br
ISTEMAS ELETRÔNICOS DE CONTROLE LTDA
Selcon Ltda., keeps the right to modify this technical sheet
when never it is necessary
February/10
FIGURE 12
.
Representative or Distributor:
10/11
Page 11
PROGRAMMER FOR START, FLAME SUPERVISION
-
AND SAFE STOP OF BURNER
PRODUCT: PRG-SE-C
Costumer Service 55 11 3019-1616
CODE OF REQUEST
PRG-SE -

PRG-SE-C
TIME OF
PURGE
- O2 TECHNICAL SHEET 11/11
For further details see technical bulletin

-O2
C-
SETUP
FAN + KEY OF
AIR FLOW
O-
OPTION
SUPPLY
 (d1)
d1 = 0 => 0 sec.
OR
d1 = 1 => 10 sec.
OR
d1 = 2 => 20 sec.
Obs.: The sensor and other accessories must be specified separately, according to a specific code.
• B
EWARE
⇒⇒⇒⇒ Use the programmers and/or relays detectors exclusively with flame sensors manufactured by the Selcon.
OTHER PRODUCTS AND ACCESSORIES:
⇒⇒⇒⇒
Flame relays : CHM-SE, CHM-P, CHM-M, CHM-M-IIIMe (with base) and CHM-F
⇒⇒⇒⇒
Relay tester tightness of shutoff valves: CHM-T
⇒⇒⇒⇒
Programmers ignition and flame monitoring: PRG-SE, PRG-E, PRG-Ie, PRG-Ie-IIIMe (with base), PRG-I, PRG-M and PRG-M-M-IIIMe (with base)
⇒⇒⇒⇒
Optical flame sensors: SEL-SV.
⇒⇒⇒⇒
Sensors flame ionization electrodes and igniters: SEL-HT (standard) and SEL-HT-E (sensors and electrodes mounted on a drawing or sample of client-special).
⇒⇒⇒⇒
Signal transmitter of flame ACS-TX (up to 500 meters between sensor and relay or
programmer).
⇒⇒⇒⇒
Signal converter flame 4 -20 mA: ACS-CV
⇒⇒⇒⇒
Transformers Ignition : ACS-TE (for supply on VAC or VDC)
⇒⇒⇒⇒
Panel ignition timer: ACS-IT
⇒⇒⇒⇒
Ignitor portable: ACS-IP (operates with batteries)
⇒⇒⇒⇒
Panel ignition (operates with batteries): ACS-PN-E
⇒⇒⇒⇒
Panel ignition and flame monitoring: PRG-Ie/O3
⇒⇒⇒⇒
Different cables: ACS - CB (ignition / sensing / communication / control)
⇒⇒⇒⇒
Connector and shield to touch for cable of ignition: ACS-CP
⇒⇒⇒⇒
Junction of articulation : ACS-CN
⇒⇒⇒⇒
Panel ignition and monitoring: ACS-PN (under consultation)
⇒⇒⇒⇒
Services of reform of pilot burners: under consultation
⇒⇒⇒⇒
LINE OF SUPERVISORS PRODUCTION DATA
:
 (d2)
d2 = 1 => without
OR
d2 = 2 => with
 (d3)
d3 =
0
=>
90 a 250 Vac­50/60 Hz
OR
d4= 2 => 2 stages
d3 = 1 => 24Vcc
SELCON
Automação Industrial
SELCON S
CNPJ 56.935.877/0001-29
Street Américo Samarone, 502 • CEP 04284-000 • Moinho Velho • São Paulo • SP • Tel/Fax: (55 11) 3019-1616
http://www.selcon.com.br
Selcon Ltda., keeps the right to modify this technical sheet
when never it is necessary
ISTEMAS ELETRÔNICOS DE CONTROLE LTDA
February/10
.
Representative or Distributor:
11/11
Loading...